kSIST FprEN 54-26:2026
(Main)Fire detection and fire alarm systems - Part 26: Carbon monoxide detectors - Point detectors
- Abstract
This document specifies product characteristics, test methods and performance criteria for point detectors using carbon monoxide sensing (CO fire detectors) for use in fire detection and fire alarm systems for buildings and civil engineering works.
- Status
- Not Published
- Public Enquiry End Date
- 27-Feb-2025
- Technical Committee
- POZ - Požarna varnost
- Current Stage
- 5020 - Formal vote (FV) (Adopted Project)
- Start Date
- 04-Sep-2026
- Due Date
- 23-Oct-2026
- Completion Date
- 07-Sep-2026
kSIST FprEN 54-26:2026 is a CEN standard for fire detection and fire alarm systems. It specifies product characteristics, test methods and performance criteria for point detectors using carbon monoxide sensing (CO fire detectors) for buildings and civil engineering works.
The document is aimed at detectors used indoors, where CO sensing can be suitable for smouldering fires and where smoke detectors may be more prone to unwanted alarms. It also makes clear that CO fire detectors are not a direct replacement for smoke detectors and should be selected using a risk assessment.
What does kSIST FprEN 54-26:2026 specify?
kSIST FprEN 54-26:2026 specifies how point CO fire detectors are checked for sensitivity, reliability and resistance to environmental and electrical influences. It also sets out marking and supplied-data requirements so a detector can be identified, installed and maintained correctly.
The standard is organized into five clauses and ten annexes:
- Clause 1 gives the scope.
- Clause 2 lists normative references.
- Clause 3 gives terms and definitions.
- Clause 4 sets requirements and assessments.
- Clause 5 covers marking, labelling and supplied data.
| Annex | What it covers |
|---|---|
| Annex A | Gas test chamber for response value and cross-sensitivity |
| Annex B | CO and smoke measuring instruments |
| Annex C | Fire test room |
| Annex D | Smouldering (pyrolysis) wood fire (TF2) |
| Annex E | Glowing smouldering cotton fire (TF3) |
| Annex F | Information on gas test chamber construction |
| Annex G | Establishing exposure levels of chemical agents |
| Annex H | Apparatus for impact test |
| Annex I | Test procedures and assessment for response to slowly developing fires |
| Annex J | Test schedule |
| Annex K | Significance of edition changes |
What are the key requirements of kSIST FprEN 54-26:2026?
kSIST FprEN 54-26:2026 combines functional checks with environmental, mechanical and EMC tests. In practice, this means a manufacturer or test laboratory has to show not only that the detector alarms at the right CO level, but also that it keeps working after temperature, humidity, shock, vibration and interference exposure.
Test setup and response measurement
- Clause 4.1 fixes the test conditions: standard atmospheric conditions, normal mounting, specified tolerances and a controlled way to measure the CO response value. The detector is tested in its normal orientation and with the manufacturer’s supply and monitoring equipment, so the result reflects real use.
- Clause 4.1.5 defines the CO response value as the CO concentration at the detector when it gives an alarm. That value is the core performance result used throughout the standard, so it is the number labs compare before and after conditioning.
- Clause 4.1.6 covers combined products that also fall under another EN 54 part. It tells the test house when a conditioning can be done once and when it must be repeated, which avoids mixing results from different product functions.
Functional behaviour
- Clause 4.2 requires an integral, distinguishable red alarm indicator that can be reset by an external signal. This matters because users and service staff need to identify which detector has alarmed.
- Clause 4.5 requires detectors with ancillary device connections to keep operating correctly if those connections open or short circuit. Clause 4.6 requires detachable detectors to signal removal of the head from the base as a fault at a remote monitoring system.
- Clauses 4.7 and 4.8 control adjustment features. Manufacturer settings must not be changed except by special means, and any on-site response adjustment must also require a code, special tool or removal from the base, unless non-compliance is clearly marked.
- Clause 4.9 sets software expectations for software-controlled detectors. The software must be modular, protect against invalid data and deadlock, and keep program and preset data in non-volatile memory.
Sensitivity and consistency
- Clause 4.3 checks rate-sensitive CO response. If the detector uses rate-sensitive behaviour, it still must not alarm on a small step change in CO over background levels. This prevents a design feature from creating avoidable false alarms.
- Clause 4.4 addresses slowly developing fires and drift compensation. If compensation is used, it must not reduce sensitivity to slow CO growth too much, so ageing compensation does not hide a real fire.
- Clauses 4.10 to 4.12 check repeatability, supply variation and reproducibility. These clauses look at the spread of CO response values from repeated tests, across supply limits and across multiple specimens, so buyers can judge whether the product is stable from unit to unit and under normal supply changes.
- Clause 4.13 verifies fire sensitivity with four specimens in a standard fire test room using TF2 and TF3. All four specimens must alarm in each fire before the end-of-test condition, so the detector is shown to respond to the smouldering fire types the standard is built around.
Environmental, mechanical and EMC resistance
- Clauses 4.14 to 4.21 cover long-term stability, dry heat, cold, damp heat and low humidity. These tests check that the detector still behaves correctly after prolonged exposure to realistic indoor climates.
- Clauses 4.22 to 4.25 cover shock, impact and sinusoidal vibration. These are operational and endurance checks, so the detector should survive handling and building-related mechanical stress without changing alarm or fault status.
- Clauses 4.26 to 4.28 cover high CO exposure, chemical agents and SO2 corrosion. These tests show whether the detector remains serviceable after exposure to fire gas, pollutants and corrosive atmospheres.
- Clause 4.29 covers immunity against electromagnetic interferences. The detector is exposed to the EMC disturbances listed there, which matters because false alarms or loss of indication can be caused by electrical noise.
What terms does kSIST FprEN 54-26:2026 define?
kSIST FprEN 54-26:2026 uses a small set of defined terms that are central to the test method.
- Carbon monoxide (CO) - the gas the detector senses to detect fire conditions.
- CO response value - the CO concentration near the specimen when it gives an alarm during the defined test.
- Rate-sensitive - describes a detector whose behaviour depends on how fast CO concentration changes.
- TF2 - the smouldering (pyrolysis) wood fire used in the fire sensitivity test.
- TF3 - the glowing smouldering cotton fire used in the fire sensitivity test.
- MIC - measuring ionization chamber, used in the fire test room measurements.
- EMC - electromagnetic compatibility, relevant to the immunity tests in Clause 4.29.
Who uses kSIST FprEN 54-26:2026?
kSIST FprEN 54-26:2026 is used by detector manufacturers, test laboratories, certification bodies and technical assessors. Manufacturers use it to design and document CO fire detectors, while labs use it for type testing, fire testing and environmental conditioning.
It is also useful to buyers, specifiers and installers who need to confirm that a detector is intended for indoor fire detection and alarm systems in buildings and civil engineering works. In practice, it helps them compare detectors on the basis of the same performance and marking requirements.
What changed in kSIST FprEN 54-26:2026 from the previous edition?
kSIST FprEN 54-26:2026 supersedes EN 54-26:2015. The changes stated in the document are:
- removal of the directional dependence test;
- removal of the Air Movement test;
- modified mounting orientation and CO response value measurement for fire tests;
- reduced peak acceleration in the Shock (operational) test;
- conditioning at 500 µl/l CO in the Exposure to high level of carbon monoxide (operational) test;
- revised Annex A and Annex F so a diffusion test chamber can be used in addition to the recirculating chamber;
- updated normative references;
- added requirements for environmental testing of combined products;
- Annex J moved to the informative annexes;
- clarification that settings not compliant with the standard do not need to be claimed as compliant.
Which standards are used with kSIST FprEN 54-26:2026?
kSIST FprEN 54-26:2026 relies on several other standards for terms, test methods and instruments:
- EN 54-1:2021 - gives the general introduction to the EN 54 series and supports the terminology framework.
- EN 54-7:2018 - provides the TF2 and TF3 fire tests and the obscuration meter and MIC characteristics used in the fire room.
- EN 50130-4:2011+A1:2014 - gives the EMC immunity test procedures.
- EN 60068-1:2014 - defines standard atmospheric conditions for testing.
- EN 60068-2-1:2007 - covers cold testing.
- EN 60068-2-2:2007 - covers dry heat testing.
- EN 60068-2-6:2008 - covers sinusoidal vibration testing.
- EN 60068-2-27:2009 - covers shock testing.
- EN 60068-2-30:2005 - covers damp heat, cyclic testing.
- EN 60068-2-42:2003 - covers SO2 corrosion testing.
- EN 60068-2-78:2013 - covers damp heat, steady-state testing.
- ISO 209:2007 - specifies the aluminium alloy used for the impact-test hammer head.
What does the kSIST FprEN 54-26:2026 document contain?
kSIST FprEN 54-26:2026 contains detailed test setups, chamber specifications, fire-room layouts and assessment procedures that the overview does not repeat. Annex A and Annex F describe how the gas test chamber is built and verified for repeatable CO-response measurements, including both recirculating and diffusion chamber approaches.
Annex C gives the fire test room arrangement, while Annex D and Annex E define the fuel, ignition and validity criteria for TF2 and TF3. Annex H describes a possible impact-test apparatus, Annex I explains the reasoning behind slowly developing fire assessment, and Annex J gives a full test schedule with specimen counts for type testing.
Relations
- Effective Date
- 17-Jul-2024
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
kSIST FprEN 54-26:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire detection and fire alarm systems - Part 26: Carbon monoxide detectors - Point detectors". This standard covers: This document specifies product characteristics, test methods and performance criteria for point detectors using carbon monoxide sensing (CO fire detectors) for use in fire detection and fire alarm systems for buildings and civil engineering works.
This document specifies product characteristics, test methods and performance criteria for point detectors using carbon monoxide sensing (CO fire detectors) for use in fire detection and fire alarm systems for buildings and civil engineering works.
kSIST FprEN 54-26:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection; 13.320 - Alarm and warning systems. The ICS classification helps identify the subject area and facilitates finding related standards.
kSIST FprEN 54-26:2026 has the following relationships with other standards: It is inter standard links to SIST EN 54-26:2015. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
kSIST FprEN 54-26:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 CO response value
- 3.2 rate -sensitive
- 4 Requirements and assessments
- 4.1 General testing methods
- 4.2 Individual alarm indication
- 4.3 Rate sensitive CO response
- 4.4 Response to slowly developing fires
- 4.5 Connection of ancillary devices
- 4.6 Monitoring of detachable detectors
- 4.7 Manufacturer's adjustments
- 4.8 On-site adjustment of response behaviour
- 4.9 Software controlled detectors
- 4.10 Repeatability
- 4.11 Variation in supply parameters
- 4.12 Reproducibility
- 4.13 Fire sensitivity
- 4.14 Long term stability (operational)
- 4.15 Dry heat (operational)
- 4.16 Dry heat (endurance)
- 4.17 Cold (operational)
- 4.18 Damp heat, cyclic (operational)
- 4.19 Damp heat steady-state (operational)
- 4.20 Damp heat steady-state (endurance)
- 4.21 Low humidity, steady-state (operational)
- 4.22 Shock (operational)
- 4.23 Impact (operational)
- 4.24 Vibration, sinusoidal (operational)
- 4.25 Vibration, sinusoidal (endurance)
- 4.26 Exposure to high level of carbon monoxide (operational)
- 4.27 Exposure to chemical agents at environmental concentrations (operational)
- 4.28 Sulphur dioxide (SO ) corrosion (endurance)
- 4.29 Immunity against electromagnetic interferences (operational)
- 5 Marking, labelling and supplied data
- Annex A
- Annex B
- Annex C
- Annex D
- 1 S-value
- Annex E
- 1 S-value
- Annex F
- 4 CO inlet 16 humidity trap
- 3 CO measurement instrument 8 test gas inlet
- 1 CO measuring instrument 4 CO inlet
- Annex G
- Annex H
- Annex I
- Annex J
- Annex K
- 1 Scope 1 Scope n/a
- 3 Terms and definitions 3 Terms, definitions and abbreviations -
- 4.2 Individual alarm indication 4.2.1 Individual alarm indication A
- 4.3 Rate sensitive CO response A
- 4.4 Response to slowly developing fires 5.2.3 Response to slowly developing fires A
- 4.5 Connection of ancillary devices 4.3.1 Connection of ancillary devices A
- 4.6 Monitoring of detachable detectors 4.3.2 Monitoring of detachable detectors A
- 4.7 Manufacturer's adjustments 4.3.3 Manufacturer's adjustments A
- 4.9 Software controlled detectors 4.3.5 Software controlled detectors A
- 4.10 Repeatability 5.2.4 Repeatability A
- 4.11 Variation in supply parameters 5.4.1 Variation in supply parameters A
- 4.12 Reproducibility 5.2.6 Reproducibility A
- 4.13 Fire sensitivity 5.5.1 Fire sensitivity A
- 4.14 Long term stability (operational) 5.3.6 Long term stability A
- 4.15 Dry heat (operational) 5.6.1.1 Dry heat (operational) A
- 4.16 Dry heat (endurance) 5.6.1.2 Dry heat (endurance) A
- 4.17 Cold (operational) 5.6.1.3 Cold (operational) A
- 4.18 Damp heat, cyclic (operational) 5.6.2.1 Damp heat, cyclic (operational) A
- 4.19 Damp heat steady-state (operational) A
- 4.20 Damp heat steady-state (endurance) A
- 4.21 Low humidity, steady-state (operational) A
- 4.23 Impact (operational) 5.6.4.2 Impact (operational) A
- 4.24 Vibration, sinusoidal (operational) A
- 4.25 Vibration, sinusoidal (endurance) 5.6.4.4 Vibration, sinusoidal (endurance) A
- 4.27 Exposure to chemical agents at 5.6.6.2 Exposure to chemical agents at
- 4.29 Immunity against electromagnetic
- 5 Marking, labelling and packaging 8 Marking, labelling and packaging A
Introduction
Carbon monoxide (CO) is a product of the incomplete combustion of carbon-based materials. CO fire detectors can react promptly to smouldering fires involving carbonaceous materials because CO does not depend solely on convection, but also moves by diffusion. CO fire detectors might be better suited to applications where other fire detection techniques are prone to false alarms, i.e. due to dust, steam and cooking vapours.
The purpose of this document is to ensure that carbon monoxide (CO) fire detectors have adequate sensitivity and reliability for use in fire detection and fire alarm systems for residential commercial and industrial premises. In many fire situations CO is not produced in detectable quantities where pyrolysis of material rather than self-sustained combustion occurs (e.g. overheating cables) or in the early stages of rapidly burning flaming fires (e.g. liquid fuel fires). It is important that carbon monoxide fire detectors are only used where a risk assessment indicates that they are appropriate for detecting the types of fires that may occur. CO fire detectors should not be considered as a direct replacement for smoke detectors. CO fire detectors detect carbon monoxide gas rather than the smoke particulates detected by optical and ionization smoke detectors.
A number of different methods for sensing CO are suitable. However, most sensors will also be influenced by other gases and phenomena. Tests have therefore been included in the test schedule to assess crosssensitivity to substances normally present in the service environment that may affect the performance of the detector.
As CO detectors are specifically well suited for the detection of incipient fires rather than flaming fires this document only includes tests to verify performance in smouldering fires. For this purpose, test fires TF2 and TF3 from EN 54-7 have been included in the test schedule. An additional validity criterion has been added to each of these tests to make them suitable for evaluating CO fire detectors. CO detectors are intended to be installed indoors, and only indoor environmental test severities are specified in the test schedule.
The environmental tests specified in this standard cover normal general conditions. Other directives or regulations applicable to the CO fire detector or installation guidelines may require other environmental test methods or conditions (including test apparatus, procedure, and conditioning).
oSIST prEN 54-26:2025 prEN 54-26:2024 (E)
1 Scope
This document specifies product characteristics, test methods and performance criteria for point detectors using carbon monoxide sensing (CO fire detectors) for use in fire detection and fire alarm systems for buildings and civil engineering works.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 54-1:2021, Fire detection and fire alarm systems — Part 1: Introduction EN 54-7:2018, Fire detection and fire alarm systems — Part 7: Smoke detectors — Point smoke detectors that operate using scattered light, transmitted light or ionization EN 50130-4:2011+A1:2014, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems EN 60068-1:2014, Environmental testing — Part 1: General and guidance (IEC 60068-1:2013) EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Test A: Cold (IEC 60068-2-1:2007) EN 60068-2-2:2007, Environmental testing — Part 2-2: Tests — Test B: Dry heat (IEC 60068-2-2:2007) EN 60068-2-6:2008, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal) (IEC 60068-2-6:2007) EN 60068-2-27:2009, Environmental testing — Part 2-27: Tests — Test Ea and guidance: Shock (IEC 60068-2-27:2008) EN 60068-2-30:2005, Environmental testing — Part 2-30: Tests — Test Db: Damp heat, cyclic (12 h + 12h cycle) (IEC 60068-2-30:2005) EN 60068-2-42:2003, Environmental testing — Part 2-42: Tests — Test Kc: Sulphur dioxide test for contacts and connections (IEC 60068-2-42:2003) EN 60068-2-78:2013, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state (IEC 60068-2-78:2012) ISO 209:2007, Aluminium and aluminium alloys — Chemical composition
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1:2021 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https://www.iso.org/obp/ui/#home
- IEC Electropedia: available at https://www.electropedia.org/
oSIST prEN 54-26:2025 prEN 54-26:2024 (E)
3.1 CO response value
CO concentration in the proximity of the specimen at the moment that it generates an alarm signal, when tested as described in 4.1.5 Note 1 to entry: The response value may depend on signal processing in the detector and in the control and indicating equipment.
3.2 rate -sensitive
behaviour of a detector that depends on the rate of change of CO concentration
4 Requirements and assessments
4.1 General testing methods
4.1.1 Atmospheric conditions for tests
Unless otherwise stated in a test procedure, the testing shall be carried out after the test specimen has been allowed to stabilize in the standard atmospheric conditions for testing as described in EN 60068-1:2014 as follows:
- temperature: (15 to 35) °C;
- relative humidity: (25 to 75) %;
- air pressure: (86 to 106) kPa.
If variations in these parameters have a significant effect on a measurement, then such variations should be kept to a minimum during a series of measurements carried out as part of one test on one specimen. The ambient concentration of CO shall not exceed 3 µl/l.
4.1.2 Operating conditions for tests
If a test method requires a specimen to be operational, then the specimen shall be connected to suitable supply and monitoring equipment with characteristics as required by the manufacturer's data. Unless otherwise specified in the test method, the supply parameters applied to the specimen shall be set within the manufacturer's specified range(s) and shall remain substantially constant throughout the tests. The value chosen for each parameter shall normally be the nominal value, or the mean of the specified range. If a test procedure requires a specimen to be monitored to detect any alarm or fault signals, then connections shall be made to any necessary ancillary devices (e.g. through wiring to an end-of-line device for conventional detectors) to allow a fault signal to be recognized. The details of the supply and monitoring equipment and the alarm criteria used should be given in the test report.
4.1.3 Mounting arrangements
The specimen shall be mounted by its normal means of attachment and in its normal orientation in accordance with the manufacturer's instructions. If these instructions describe more than one method of mounting, or more than one acceptable orientation, then the method considered to be most unfavourable shall be chosen for each test.
oSIST prEN 54-26:2025 prEN 54-26:2024 (E)
4.1.4 Tolerances
Unless otherwise stated, the tolerances for the environmental test parameters shall be as given in the basic reference standards for the test (e.g. the relevant part of EN 60068). If a requirement or test procedure does not specify a tolerance or deviation limits, then deviation limits of ± 5 % shall be applied.
4.1.5 Measurement of CO response value
The specimen, for which the CO response value shall be measured, shall be installed in the gas test chamber, described in Annex A, in its normal operating position, by its normal means of attachment. The orientation of the specimen, relative to the direction of airflow or gas diffusion, shall be selected arbitrarily and recorded.
Before commencing each measurement, the gas test chamber shall be purged with clean air to ensure that the concentration of CO in the chamber is less than 1,5 µl/l. Unless otherwise specified in the test procedure, the air temperature in the gas test chamber shall be (23 ± 5) °C and shall not vary by more than 5 K for all the measurements. The specimen shall be connected to its supply and monitoring equipment as described in 4.1.2 and shall be allowed to stabilize for a period of at least 15 min, unless otherwise specified by the manufacturer. CO shall be introduced into the gas test chamber such that the rate of increase of CO concentration is between 1 μl/l per min and 6 μl/l per min, unless otherwise specified in the test procedure. For detectors with a rate sensitive behaviour, the manufacturer may specify a rate of increase within this range to ensure that the measured CO response value is representative of the static CO response value of the detector.
The same target rate of increase of CO concentration should be used for all measurements on a particular detector type. Above 20 µl/l during the ramp the measured CO concentration shall not vary by more than ± 2 µl/l from the target value.
The CO concentration at the moment that the specimen gives an alarm shall be recorded as S (μl/l). This shall be taken as the CO response value.
NOTE The typical range of response values is between 25 µl/l and 60 µl/l.
4.1.6 Environmental tests of combined products
Where the CO fire detector has an additional function which in the scope of another standard in the EN 54 series (e.g. a detector and sounder or a manual call point and transmission path/short-circuit isolator), the following points shall be considered for each environmental test when applied to the CO fire detector:
a) if the specific environmental test exists in both standards and the environmental conditions (including test apparatus, procedure, and conditioning, when applicable) are the same, then the conditioning shall be done only once. Tests before and after the conditioning shall be conducted according to both standards as well as monitoring of all relevant signals of both standards during the conditioning phase.
When special equipment to monitor and operate the specimen during/after conditioning is needed, the equipment of both standards can be used together or in combination when it is assured that it has no impact to the environmental conditions or the test and monitoring results. If this is not possible or in cases of doubt, the environmental tests shall be done twice, each test based on applying the standards separately and independently; b) if the specific environmental test exists in both the standards but the environmental conditions (including test apparatus, procedure, and conditioning, when applicable) are not the same, then the
oSIST prEN 54-26:2025 prEN 54-26:2024 (E) environmental tests shall be done twice, each test based on applying the standards separately and independently.
Measurements and monitoring signals as well as requirements shall be independent for each environmental test. If it is expected that the environmental conditions will harm the product in any way, a separate sample shall be used for each test; c) if the specific environmental test exists only in one standard, then the environmental test shall be done only once. Measurements and monitoring of signals, as well as any other requirement, shall be applied only according to the standard that specifies the environmental test. NOTE 1 Environmental tests are tests where the product is exposed to specific environmental conditions. Measurements before, during or after the conditioning are performed to assess the ability of the product to function correctly during or after the conditioning.
NOTE 2 The logic of the above specified procedure can also be applied in cases where the product is in the scope of three or more standards by comparing pairs of standards in turn. NOTE 3 Case c) implies that it is acceptable for an additional function to be susceptible to (or adversely affected) by the conditioning. However, careful attention is needed to the criteria for each environmental test as expressed in the standard being applied to ensure that the appropriate criteria is used.
4.2 Individual alarm indication
4.2.1 Objective
The CO fire detector is assessed to demonstrate the provision of an integral visual alarm indicator, by which the detector that released an alarm can be identified, until the alarm indicator is externally reset. For detachable detectors, the indicator may be integral with the base or the detector head.
4.2.2 Assessment method
One specimen shall be mounted in an ambient light intensity up to 500 lx at a distance of 6 m from the observer. The mounting surface shall be perpendicular to the line of view. When the detector is in alarm condition, it shall be indicated by a visual alarm indicator. The visibility of the indicator shall be confirmed, and the colour of the indicator shall be recorded. The alarm indication shall then be reset by an external signal.
Where other conditions of the detector can be visually indicated, it shall be confirmed and recorded that they are clearly distinguishable from the alarm indication, except when the detector is switched into a service mode.
4.2.3 Requirements
There shall be at least one distinguishable red alarm indicator, and the alarm indicator shall be resettable by an external signal.
4.3 Rate sensitive CO response
4.3.1 Objective
The CO response value of the detector may depend on the rate of change of CO concentration in the vicinity of the detector. Such behaviour may be incorporated in the detector design to improve the discrimination between ambient CO levels and those generated by a fire.
oSIST prEN 54-26:2025 prEN 54-26:2024 (E) The CO fire detector is assessed to demonstrate that if such rate sensitive behaviour is included then it shall not lead to a significant reduction in the detector’s sensitivity to fires, nor to a significant increase in the probability of false alarm.
4.3.2 Assessment method
The behaviour of the CO fire detector to rate sensitive CO response shall be assessed by analysis of the circuit/software, and/or by physical tests and simulations.
NOTE This approach is used as it is not practical to make tests with all possible rates of increase in CO concentration.
4.3.3 Requirements
The CO fire detector shall not signal an alarm condition when subjected to a step change in CO concentration of 10 µl/l, superimposed on a background level between 0 µl/l and 1,5 µl/l.
4.4 Response to slowly developing fires
4.4.1 Objective
The CO fire detector is assessed to demonstrate that if automatic offset compensation” is provided, for example to compensate for ageing of the CO sensor or the build-up of contaminants, then it shall not lead to a significant change in the detector's sensitivity to slowly developing fires.
4.4.2 Assessment method
An analysis of the circuit/software and/or physical or software simulations of the CO fire detector's response to slow increases in CO concentration shall be conducted to assess the provision for “drift compensation”.
NOTE 1 This approach is used as it is not practical to make tests with all possible rates of increase in CO concentration.
NOTE 2 Further information about the assessment is given in Annex I.
4.4.3 Requirements
If drift compensation is provided:
a) for any rate of increase in CO concentration R, which is greater than S/4 per hour (where S is the detector's initial uncompensated CO response value), the time for the detector to give an alarm or reach the compensated CO response value shall not exceed 1,6 × S/R by more than 100 s; b) The range of compensation shall be limited such that, throughout this range, the compensation does not cause the CO response value of the detector to change from its initial value by a factor greater than 1,6.
4.5 Connection of ancillary devices
4.5.1 Objective
The CO fire detector is assessed to demonstrate that where the detector provides for connections to ancillary devices (e.g. remote indicators, control relays), open- or short-circuit failures of these connections shall not prevent the correct operation of the detector.
oSIST prEN 54-26:2025 prEN 54-26:2024 (E)
4.5.2 Assessment method
One specimen shall be mounted as described in 4.1.3, shall be connected to supply and monitoring equipment as described in 4.1.2 and a simple functional test, i.e. providing a stimulus sufficient to generate an alarm condition shall be conducted while each connection to ancillary devices has open- or short-circuit failure.
4.5.3 Requirements
Where the detector provides for connections to ancillary devices the detector operates correctly with open or short circuit failures on any connection to ancillary devices.
4.6 Monitoring of detachable detectors
4.6.1 Objective
The CO fire detector is assessed to demonstrate the provision of means for a remote monitoring system (e.g. the control and indicating equipment) to detect the removal of the head from the base of the detector.
4.6.2 Assessment method
For detachable detectors, one specimen shall be mounted as described in 4.1.3, shall be connected to supply and monitoring equipment as described in 4.1.2 and a visual inspection shall be conducted while removing the head from the base.
4.6.3 Requirements
If the CO fire detector is detachable the removal of the detector head from the base is indicated as fault signal at a remote monitoring system.
4.7 Manufacturer's adjustments
4.7.1 Objective
The CO fire detector is assessed to demonstrate that it shall not be possible to change the manufacturer's settings except by special means.
4.7.2 Assessment method
A visual inspection of one specimen and its supporting data shall be conducted to assess the possibilities of changing the manufacturer’s settings.
4.7.3 Requirements
It shall not be possible to change the manufacturer's settings except by special means (e.g. the use of a special code or tool or by breaking or removing a seal).
4.8 On-site adjustment of response behaviour
4.8.1 Objective
The CO fire detector is assessed to demonstrate that if on site adjustment of response behaviour is provided it should not enable non-compliance with this standard unless this is clearly marked.
4.8.2 Assessment method
A visual inspection of one specimen and its supporting data shall be conducted in conjunction with the appropriate operation of the detector in order to assess the possibilities of on-site adjustment of the detector response behaviour.
oSIST prEN 54-26:2025 prEN 54-26:2024 (E)
4.8.3 Requirements
If there is provision for on-site adjustment of the response behaviour of the detector, then the response behaviour can only be adjusted by the use of a code or special tool or by removing the detector from its base or mounting.
NOTE On-site adjustment of the detector response behaviour can either be carried out at the detector or via the control and indicating equipment. A control and indicating equipment is considered a special tool.
4.9 Software controlled detectors
4.9.1 Objective
CO fire detectors which rely on software control are assessed to ensure the reliability of the software.
4.9.2 Assessment method
4.9.2.1 General
For CO fire detectors which rely on software control the manufacturer software documentation shall be visually assessed as in 4.9.2.2 and 4.9.2.3.
4.9.2.2 Design overview
The software documentation shall be in sufficient detail for the design to be inspected and shall include at least the following:
...