SIST EN 14972-6:2023
(Main)Fixed firefighting systems - Water mist systems - Part 6: Test protocol for false floors and false ceilings for automatic nozzle systems
Fixed firefighting systems - Water mist systems - Part 6: Test protocol for false floors and false ceilings for automatic nozzle systems
This document specifies the evaluation of the firefighting performance of water mist systems for false ceilings and false floors with heights between 300 mm and 800 mm.
This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited volume.
This document is applicable for horizontal, solid, flat ceilings.
It is not possible to apply these tests to other applications than the ones specified within this fire test protocol.
Ortsfeste Brandbekämpfungsanlagen - Wassernebelsysteme - Teil 6: Prüfprotokoll für Zwischenböden und Zwischendecken für automatische Düsensysteme
Dieses Dokument legt die Beurteilung des Brandbekämpfungsverhaltens von Wassernebelsystemen für Zwischenböden und Zwischendecken mit Höhen zwischen 300 mm und 800 mm fest.
Dieses Brandversuchsprotokoll ist anwendbar für hängende oder stehende automatische Düsen zur Verwendung ohne Volumenbegrenzung.
Dieses Dokument ist anwendbar für waagerechte, massive, ebene Decken.
Es ist nicht möglich, diese Versuche auf andere als die in diesem Brandversuchsprotokoll festgelegten Anwendungen anzuwenden.
Installations fixes de lutte contre l'incendie - Systèmes à brouillard d'eau - Partie 6 : Protocole d'essai des systèmes à buses automatiques pour faux-planchers et faux-plafonds
Le présent document spécifie l'évaluation des performances de lutte contre l'incendie du système à brouillard d'eau pour les faux-plafonds et faux-planchers d'une hauteur comprise entre 300 mm et 800 mm.
Le présent protocole d'essai au feu est applicable aux buses automatiques de type pendant ou debout, à utiliser dans des volumes illimités.
Le présent document est applicable aux plafonds horizontaux, pleins et plans.
Il n'est pas possible de réaliser ces essais pour des applications autres que celles spécifiées dans le présent protocole d'essai au feu.
Vgrajeni gasilni sistemi - Sistemi s pršečo vodo - 6. del: Protokol preskušanja sistemov s samodejnimi šobami za privzdignjene pode in viseče strope
Ta dokument določa vrednotenje protipožarnega delovanja sistemov s pršečo vodo za viseče strope in privzdignjene pode, ki v višino merijo med 300 mm in 800 mm.
Ta protokol požarnega preskusa se uporablja za viseče ali pokončne samodejne šobe, ki se uporabljajo v neomejenem obsegu.
Ta dokument se uporablja samo za vodoravne, masivne in ravne strope.
Teh preskusov ni mogoče uporabiti za druge načine uporabe, temveč samo za načine uporabe, ki so določeni v tem protokolu požarnega preskusa.
V primeru pozitivnega rezultata preskusov se lahko sistem s pršečo vodo uporablja za zaščito pred naslednjimi tveganji:
Viseči stropi in privzdignjeni podi med 300 mm in 800 mm.
General Information
Overview
EN 14972-6:2023 is a CEN European Standard that defines a fire test protocol for evaluating the firefighting performance of water mist systems protecting false floors and false ceilings. Published May 2023, the document covers automatic pendent or upright nozzles used in unlimited volume and applies to horizontal, solid, flat ceilings with false-floor/ceiling cavity heights between 300 mm and 800 mm.
Key topics and technical requirements
- Scope: Test protocol for water mist automatic nozzle systems for false ceilings and false floors (300–800 mm cavity). Tests are not applicable to other configurations outside this protocol.
- System operation: Tests require the system to operate automatically without manual intervention; up to 5 nozzles retained after testing for verification.
- Test mock-up:
- Standardized mock-up: height 800 mm, width 400 mm, length = three times nozzle spacing.
- Non-combustible ceiling and floor plates; one side open; one side plywood wall (≈5 mm).
- Fuel package and ignition:
- Cable-based fire load (specified cable types and loading); cable trays of non-combustible, open ladder type.
- Ignition source: heptane pan (200 × 200 × 20 mm) filled with 120 ml heptane, positioned beneath lower cable tray.
- Reference sprinkler baseline:
- Ordinary Hazard 1 classification, water discharge density 5.75 l/min·m², protected area per sprinkler 12 m², sprinkler K-factor 80, temperature rating 68 °C, and arrangement of two sprinklers (max 3.5 m spacing).
- Test conditions:
- Tests conducted at manufacturer-specified maximum spacing and minimum discharge conditions.
- Water flow is shut off 10 minutes after activation of the first nozzle; remaining fire is then manually extinguished and damage recorded.
- Instrumentation & reporting: Requirements for temperature, pressure, timing instrumentation and detailed test reports, including system layout and unaltered test mock-up throughout the test series.
- Normative references: EN 14972-1 (design/installation), EN 12259-1 (sprinklers), EN 12845 (sprinkler system design), EN 13501-1 (fire classification).
Applications and users
EN 14972-6 is intended for:
- Water mist system manufacturers validating nozzle performance for false floor/ceiling applications
- Testing laboratories and fire test facilities performing standardized fire tests
- Fire safety engineers, specifiers and system designers who evaluate or select suppression systems for cavities and service voids
- Authorities having jurisdiction and building owners requiring validated fire protection for raised floors and suspended ceiling cavities
This standard helps demonstrate compliance and comparative performance of water mist automatic nozzle systems for small cavity protection scenarios.
Related standards
- EN 14972-1: Design, installation, inspection and maintenance (water mist systems)
- EN 12259-1: Sprinklers - components for sprinkler systems
- EN 12845: Automatic sprinkler system design and installation
- EN 13501-1: Fire classification of construction products
Keywords: EN 14972-6, water mist systems, false ceilings, false floors, automatic nozzles, test protocol, CEN standard, fire test, water mist fire suppression.
Frequently Asked Questions
SIST EN 14972-6:2023 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Fixed firefighting systems - Water mist systems - Part 6: Test protocol for false floors and false ceilings for automatic nozzle systems". This standard covers: This document specifies the evaluation of the firefighting performance of water mist systems for false ceilings and false floors with heights between 300 mm and 800 mm. This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited volume. This document is applicable for horizontal, solid, flat ceilings. It is not possible to apply these tests to other applications than the ones specified within this fire test protocol.
This document specifies the evaluation of the firefighting performance of water mist systems for false ceilings and false floors with heights between 300 mm and 800 mm. This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited volume. This document is applicable for horizontal, solid, flat ceilings. It is not possible to apply these tests to other applications than the ones specified within this fire test protocol.
SIST EN 14972-6:2023 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting; 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.
You can purchase SIST EN 14972-6:2023 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2023
Vgrajeni gasilni sistemi - Sistemi s pršečo vodo - 6. del: Protokol preskušanja
sistemov s samodejnimi šobami za privzdignjene pode in viseče strope
Fixed firefighting systems - Water mist systems - Part 6: Test protocol for false floors and
false ceilings for automatic nozzle systems
Ortsfeste Brandbekämpfungsanlagen - Wassernebelsysteme - Teil 6: Prüfprotokoll für
Zwischenböden und Zwischendecken für automatische Düsensysteme
Installations fixes de lutte contre l'incendie - Systèmes à brouillard d'eau - Partie 6 :
Protocole d'essai des systèmes à buses automatiques pour faux-planchers et faux-
plafonds
Ta slovenski standard je istoveten z: EN 14972-6:2023
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 14972-6
EUROPEAN STANDARD
NORME EUROPÉENNE
May 2023
EUROPÄISCHE NORM
ICS 13.220.20
English Version
Fixed firefighting systems - Water mist systems - Part 6:
Test protocol for false floors and false ceilings for
automatic nozzle systems
Installations fixes de lutte contre l'incendie - Systèmes Ortsfeste Brandbekämpfungsanlagen -
à brouillard d'eau - Partie 6 : Protocole d'essai des Wassernebelsysteme - Teil 6: Brandversuchsprotokoll
systèmes à buses automatiques pour faux-planchers et für Zwischenböden und Zwischendecken für
faux-plafonds automatische Düsensysteme
This European Standard was approved by CEN on 17 April 2023.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2023 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14972-6:2023 E
worldwide for CEN national Members.
Contents Page
European foreword . 3
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 General requirements . 5
5 Fuel packages . 6
5.1 General. 6
5.2 False ceiling / false floor mock-up requirements . 9
5.3 Cable trays . 9
5.4 Cables . 9
5.5 Conditioning of the fuel load . 10
5.6 Ignition source . 10
6 Test arrangement . 10
6.1 Reference sprinkler requirements . 10
6.1.1 General. 10
6.1.2 Reference sprinkler tests . 11
6.2 Water mist system requirements . 11
7 Test equipment requirements . 11
8 Instrumentation requirements . 12
8.1 General. 12
8.2 Temperature. 12
8.3 Pressure . 12
8.4 Time . 13
9 Test criteria . 13
9.1 General. 13
9.2 Fire tests . 13
9.3 Evaluation of test results . 14
10 Test report . 14
Bibliography . 15
European foreword
This document (EN 14972-6:2023) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by November 2023, and conflicting national standards shall
be withdrawn at the latest by November 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
The EN 14972 series, published under the general title Fixed firefighting systems — Water mist systems,
consists of the following parts. This list includes standards that are in preparation, and other standards
can be added. For the current status of published standards, refer to www.cencenelec.eu.
— Part 1: Design, installation, inspection and maintenance;
— Part 2: Test protocol for shopping areas for automatic nozzle systems;
— Part 3: Test protocol for office, school classrooms and hotel for automatic nozzle systems;
— Part 4: Test protocol for non-storage occupancies for automatic nozzle systems;
— Part 5: Test protocol for car garages for automatic nozzle systems;
— Part 6: Test protocol for false floors and false ceilings for automatic nozzle systems;
— Part 7: Test protocol for commercial low hazard occupancies for automatic nozzle systems;
— Part 8: Test protocol for machinery in enclosures exceeding 260 m for open nozzle systems;
— Part 9: Test protocol for machinery in enclosures not exceeding 260 m for open nozzle systems;
— Part 10: Test protocol for atrium protection with sidewall nozzles for open nozzle systems;
— Part 11: Test protocol for cable tunnels for open nozzle systems;
— Part 12: Test protocol for commercial deep fat cooking fryers for open nozzle systems;
— Part 13: Test protocol for wet benches and other similar processing equipment for open nozzle systems;
— Part 14: Test protocol for combustion turbines in enclosures exceeding 260 m for open nozzle systems;
— Part 15: Test protocol for combustion turbines in enclosures not exceeding 260 m for open nozzle
systems;
— Part 16: Test protocol for industrial oil cookers for open nozzle systems;
— Part 17: Test protocol for residential occupancies for automatic nozzle systems.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
1 Scope
This document specifies the evaluation of the firefighting performance of water mist systems for false
ceilings and false floors with heights between 300 mm and 800 mm.
This fire test protocol is applicable to pendent or upright automatic nozzles to be used in unlimited
volume.
This document is applicable for horizontal, solid, flat ceilings.
It is not possible to apply these tests to other applications than the ones specified within this fire test
protocol.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12259-1, Fixed firefighting systems - Components for sprinkler and water spray systems - Part 1:
Sprinklers
EN 12845, Fixed firefighting systems - Automatic sprinkler systems - Design, installation and maintenance
EN 13501-1:2018, Fire classification of construction products and building elements - Part 1: Classification
using data from reaction to fire tests
EN 14972-1:2020, Fixed firefighting systems - Water mist systems - Part 1: Design, installation, inspection
and maintenance
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 14972-1 apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/
4 General requirements
4.1 Up to a maximum of 5 nozzles used in the fire tests shall be kept for later verification.
4.2 The water mist system, operating without manual intervention, shall successfully complete all
described performance fire tests.
4.3 The fire load shall be taken from the conditioning area and arranged into the test area just before
conducting the test.
4.4 The water flow shall be shut-off 10 min after the activation of the first sprinkler/automatic nozzle.
Any remaining fire shall be manually extinguished and the fire damage shall be recorded.
4.5 Prior to the testing, a layout of the water mist system to be tested shall be submitted for test
preparation purposes. This layout shall include any components required for the testing as well as the
full dimensioning (e.g. length of pipes, distances of automatic nozzles/sprinklers, etc.).
4.6 System components, component locations, operating conditions and test mock-up details shall
remain unaltered throughout all of the fire tests for a given application.
4.7 All fire tests shall be conducted using the manufacturer instructions in regard to automatic nozzle
placement, spray flux, and operating pressure. Sprays shall not be intermittent.
4.8 The test protocol is only applicable to pendent or upright mounted automatic nozzles.
4.9 The water supply shall be capable of supplying a flow rate and pressure at the minimum operating
pressure and flow rate of the automatic nozzle as specified by the manufacturer. These parameters shall
be met based on the actual layout of the pipework installation as used in the test scenario.
4.10 The tests with the water mist system shall be conducted at maximum spacing and minimum
discharge conditions regarding water flow and pressure as specified by the manufacturer for this
application. The system shall be installed to achieve the maximum allowed time delay of water pressure
build-up of the system.
5 Fuel packages
5.1 General
The test assembly to be provided for the tests by the applicant shall comply with the following
specifications and figures.
The test scenario is based on a typical false ceiling layout comprising the appropriate fire load in terms
of cabling.
The test assembly shall include the following elements:
a) housing;
b) cable trays;
c) cables as fire load;
d) heptane pan (200
...
게시물 제목: SIST EN 14972-6:2023 - 고정 소화 시스템 - 수증기 분무 시스템 - 파트 6: 자동 노즐 시스템을 위한 가짜 바닥과 가짜 천장의 테스트 프로토콜 게시물 내용: 이 문서는 높이가 300mm에서 800mm인 가짜 천장과 가짜 바닥에 대한 수증기 분무 시스템의 소화 성능을 평가하는 것을 명시합니다. 이 화재 시험 프로토콜은 무제한 용량에 사용되는 붕규나거나 세로로 설치되는 자동 노즐에 적용됩니다. 이 문서는 수평, 고체, 평평한 천장에 적용됩니다. 이 화재 시험 프로토콜에 명시된 것 이외의 다른 응용 프로그램에는 이 테스트를 적용할 수 없습니다. 테스트 결과가 양호하면, 수증기 분무 시스템은 300mm에서 800mm까지의 가짜 천장과 가짜 바닥을 보호하기 위해 사용될 수 있습니다.
The article discusses the SIST EN 14972-6:2023 standard, which outlines the test protocol for evaluating the firefighting performance of water mist systems on false ceilings and false floors. The test protocol applies to pendent or upright automatic nozzles used in unlimited volume and is specifically designed for horizontal, solid, flat ceilings. It cannot be applied to other applications. If the tests yield positive results, the water mist system can be used to protect false ceilings and false floors between 300 mm and 800 mm in height.
記事のタイトル:SIST EN 14972-6:2023 - 固定消防システム - ウォーターミストシステム - パート6:自動ノズルシステムのための偽の床と偽の天井のテストプロトコル 記事の内容:この文書では、高さが300mmから800mmの偽の天井と偽の床に対するウォーターミストシステムの消防性能の評価方法を規定しています。 この火災試験のプロトコルは、無制限の容積で使用されるペンデント型または直立型自動ノズルに適用されます。 この文書は、水平な固体で平らな天井に適用されます。 この火災試験のプロトコルに規定されていない他の応用には、このテストを適用することはできません。 テスト結果が良好であれば、ウォーターミストシステムは、300mmから800mmの偽の天井と偽の床を保護するために使用することができます。








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...