Plastics piping systems for soil and waste discharge (low and high temperature) within the building structure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications for pipes, fittings and the system

This document specifies the requirements for solid wall pipes with smooth internal and external surfaces, extruded from the same formulation throughout the wall, fittings and the system of unplasticized poly(vinyl chloride) (PVC-U) piping systems intended for soil and waste discharge applications (low and high temperature):
-   inside buildings (application area code "B");
-   for both inside buildings and buried in ground within the building structure (application area code "BD").
NOTE 1   The intended use is reflected in the marking of products by "B" or "BD".
NOTE 2   Multilayer pipes with different formulations throughout the wall and foamed core pipes are covered by EN 1453-1 [1].
NOTE 3   For use buried in ground within the building structure are intended only those components (marked with "BD") with nominal outside diameters equal to or greater than 75 mm.
NOTE 4   EN 476 [2] specifies the general requirements for components used in discharge pipes, drains and sewers for gravity systems. Pipes and fittings conforming to this standard fully meet these requirements.
This document is also applicable to PVC-U pipes, fittings and the system intended for the following purposes:
-   ventilating part of the pipework in association with discharge applications;
-   rainwater pipework within the building structure.
This document also specifies the test parameters for the test method that are referred to.
This document covers a range of nominal sizes, a range of pipes and fittings series and gives recommendations concerning colours.
NOTE 5   It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national regulations and installation practices or codes.
For external above ground application additional requirements depending on the climate should be agreed between the manufacturer and the user.
NOTE 6   Pipes, fittings and other components conforming to any of the plastics product standards listed in Annex B can be used with pipes and fittings conforming to this document, provided they conform to the requirements for joint dimensions given in Clause 6 and to the requirements of Table 25.

Kunststoff-Rohrleitungssysteme zum Ableiten von Abwasser (niedriger und hoher Temperatur) innerhalb der Gebäudestruktur - Weichmacherfreies Polyvinylchlorid (PVC-U) - Teil 1: Anforderungen an Rohre, Formstücke und das Rohrleitungssystem

Dieses Dokument legt die Anforderungen an Vollwand-Rohre mit glatter Innen- und Außenfläche, die über die gesamte Wanddicke die gleiche Zusammensetzung aufweisen, Formstücke und das Rohrleitungssystem aus weichmacherfreiem Polyvinylchlorid (PVC-U) zum Ableiten von Abwasser (niedriger und hoher Temperatur) fest:
-   innerhalb von Gebäuden (Anwendungskennzeichen "B");
-   innerhalb von Gebäuden und erdverlegt innerhalb der Gebäudestruktur (Anwendungs-kennzeichen "BD").
ANMERKUNG 1   Der vorgesehene Verwendungszweck wird durch die Kennzeichnung der Erzeugnisse mit "B" bzw. "BD" angezeigt.
ANMERKUNG 2   Mehrschichtverbund-Rohre mit unterschiedlichen Zusammensetzungen innerhalb der Wanddicke und kerngeschäumte Rohre werden in EN 1453 1 [1] behandelt.
ANMERKUNG 3   Für erdverlegte Anwendungen innerhalb der Gebäudestruktur sind nur solche Rohrleitungsteile (gekennzeichnet mit "BD") mit einem Nenn-Außendurchmesser von mindestens 75 mm bestimmt.
ANMERKUNG 4   EN 476 [2] legt die allgemeinen Anforderungen an Bauteile für Abwasserleitungen und  kanäle zur Verwendung in Schwerkraftentwässerungssystemen fest. Rohre und Formstücke nach der vorliegenden Norm erfüllen diese Anforderungen vollständig.
Dieses Dokument gilt ebenfalls für Rohre, Formstücke und das Rohrleitungssystem aus PVC-U für die folgenden Verwendungszwecke:
-   Lüftungsleitungen in Verbindung mit Abwasseranwendungen;
-   Regenfallleitungen innerhalb der Gebäudestruktur.
Dieses Dokument legt auch die Prüfparameter für die Prüfverfahren fest, auf die verwiesen wird.
Dieses Dokument behandelt eine Reihe von Nennweiten, mehrere Rohr- und Formstückreihen sowie Empfehlungen für die Einfärbung.
ANMERKUNG 5   Die geeignete Auswahl aus diesen Aspekten unter Berücksichtigung der jeweils geltenden Anforderungen sowie aller maßgebenden nationalen Bestimmungen und Verlegeverfahren oder -vorschriften liegt in der Verantwortung des Kunden oder Auftraggebers.
Für Rohrleitungsteile, die oberirdisch außerhalb an Gebäuden befestigt werden, sollten zusätzliche Anforderungen in Abhängigkeit vom Klima zwischen Hersteller und Anwender vereinbart werden.
ANMERKUNG 6   Rohre, Formstücke und andere Rohrleitungsteile, die einer der in Anhang B aufgeführten Normen zu Kunststofferzeugnissen entsprechen, können mit Rohren und Formstücken nach dem vorliegenden Dokument verwendet werden, sofern sie die Anforderungen an die Maße von Verbindungen nach Abschnitt 6 und die Anforderungen nach Tabelle 25 erfüllen.

Systèmes de canalisations en plastique pour l'évacuation des eaux-vannes et des eaux usées (à basse et à haute température) à l'intérieur de la structure des bâtiments - Poly(chlorure de vinyle) non plastifié (PVC-U) - Partie 1 : Spécifications pour tubes, raccords et le système

Le présent document spécifie les exigences pour les tubes à paroi compacte avec des surfaces internes
et externes lisses, extrudées à partir de la même formulation dans toute l’épaisseur de la paroi, les
raccords et le système pour des systèmes de canalisations en poly(chlorure de vinyle) non plastifié
(PVC-U) destinés aux applications d’évacuation des eaux-vannes et des eaux usées (à basse et à haute
température) :
- à l'intérieur des bâtiments (code de zone d’application « B ») ;
- aussi bien à l'intérieur des bâtiments qu'en enterré dans la structure du bâtiment (code de zone
d’application « BD »).
NOTE 1 L’utilisation prévue est repérée au niveau du marquage des produits par « B » ou « BD ».
NOTE 2 L’application « B » couvre les utilisations en aérien à l'intérieur des bâtiments, ou fixés au mur à
l'extérieur des bâtiments.
NOTE 3 Les tubes multicouches avec des formulations différentes dans l’épaisseur de la paroi et les tubes à
âme alvéolaire sont couverts par l’EN 1453-1 [1].
NOTE 4 Seuls sont destinés à l'usage en enterré dans la structure du bâtiment, les composants (marqués
« BD ») avec un diamètre extérieur nominal égal ou supérieur à 75 mm.
NOTE 5 L’EN 476 [2] spécifie les exigences générales pour les composants utilisés dans les canalisations
d’évacuation, les branchements et les collecteurs pour des réseaux à écoulement libre. Les tubes et raccords
conformes à cette norme satisfont pleinement à ces exigences.
Le présent document est également applicable aux tubes en PVC-U, raccords et le système destinés aux
usages suivants :
- la partie de ventilation du réseau de canalisation en association avec des applications d’évacuation
des eaux-usées ;
- les canalisations pour les eaux pluviales à l'intérieur de la structure du bâtiment.
Le présent document spécifie également les paramètres d'essai pour les méthodes d'essai référencées.
Le présent document couvre une gamme de dimensions nominales, une gamme de séries de tubes et de
raccords et donne des recommandations concernant les couleurs.
NOTE 6 Il est de la responsabilité de l'acheteur ou du concepteur du réseau d'effectuer les sélections
appropriées à partir de ces données en tenant compte des exigences particulières, des éventuelles règles
nationales et des pratiques ou codes de pose concernés.
NOTE 7 Les tubes, les raccords et autres composants conformes à l'une des normes de produits plastiques
listées dans l'Annexe B peuvent être utilisés avec des tubes et des raccords conformes au présent document dans
la mesure où ils répondent aux exigences pour les dimensions d'assemblage données dans l'Article 7 et aux
exigences du Tableau 26.

Cevni sistemi iz polimernih materialov za nizko- in visokotemperaturne odvodne sisteme v zgradbah - Nemehčan polivinilklorid (PVC-U) - 1. del: Zahteve za cevi, fitinge in sistem

General Information

Status
Published
Public Enquiry End Date
19-Oct-2019
Publication Date
16-Dec-2020
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
11-Dec-2020
Due Date
15-Feb-2021
Completion Date
17-Dec-2020

Relations

Buy Standard

Standard
EN 1329-1:2021
English language
46 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 1329-1:2019
English language
47 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 1329-1:2021
01-januar-2021
Nadomešča:
SIST EN 1329-1:2014+A1:2018
Cevni sistemi iz polimernih materialov za nizko- in visokotemperaturne odvodne
sisteme v zgradbah - Nemehčan polivinilklorid (PVC-U) - 1. del: Zahteve za cevi,
fitinge in sistem
Plastics piping systems for soil and waste discharge (low and high temperature) within
the building structure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications
for pipes, fittings and the system
Kunststoff-Rohrleitungssysteme zum Ableiten von Abwasser (niedriger und hoher
Temperatur) innerhalb der Gebäudestruktur - Weichmacherfreies Polyvinylchlorid (PVC-
U) - Teil 1: Anforderungen an Rohre, Formstücke und das Rohrleitungssystem
Systèmes de canalisations en plastique pour l'évacuation des eaux-vannes et des eaux
usées (à basse et à haute température) à l'intérieur de la structure des bâtiments - Poly
(chlorure de vinyle) non plastifié (PVC-U) - Partie 1 : Spécifications pour tubes, raccords
et le système
Ta slovenski standard je istoveten z: EN 1329-1:2020
ICS:
23.040.20 Cevi iz polimernih materialov Plastics pipes
91.140.80 Drenažni sistemi Drainage systems
SIST EN 1329-1:2021 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 1329-1:2021

---------------------- Page: 2 ----------------------
SIST EN 1329-1:2021


EN 1329-1
EUROPEAN STANDARD

NORME EUROPÉENNE

December 2020
EUROPÄISCHE NORM
ICS 23.040.20; 91.140.80 Supersedes EN 1329-1:2014+A1:2018
English Version

Plastics piping systems for soil and waste discharge (low
and high temperature) within the building structure -
Unplasticized poly(vinyl chloride) (PVC-U) - Part 1:
Specifications for pipes, fittings and the system
Systèmes de canalisations en plastique pour Kunststoff-Rohrleitungssysteme zum Ableiten von
l'évacuation des eaux-vannes et des eaux usées (à Abwasser (niedriger und hoher Temperatur) innerhalb
basse et à haute température) à l'intérieur de la der Gebäudestruktur - Weichmacherfreies
structure des bâtiments - Poly(chlorure de vinyle) non Polyvinylchlorid (PVC-U) - Teil 1: Anforderungen an
plastifié (PVC-U) - Partie 1 : Spécifications pour tubes, Rohre, Formstücke und das Rohrleitungssystem
raccords et le système
This European Standard was approved by CEN on 2 November 2020.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.





EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1329-1:2020 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 7
4 Symbols and abbreviations . 10
4.1 Symbols . 10
4.2 Abbreviations . 10
5 Material . 11
5.1 General . 11
5.2 Pipe material for BD application . 11
5.2.1 Use of mineral modifier . 11
5.2.2 Additional requirements . 11
5.3 Additional requirements for fitting material for BD application . 12
5.4 Fabricated fitting material . 13
5.5 Utilization of non-virgin material . 13
5.6 Sealing ring retaining means material . 13
6 General characteristics . 13
6.1 Appearance . 13
6.2 Colour . 13
6.3 External above ground application . 13
6.4 Reaction to fire . 13
7 Geometrical characteristics . 14
7.1 General . 14
7.2 Dimensions of pipes . 14
7.2.1 Outside diameter . 14
7.2.2 Out-of-roundness . 15
7.2.3 Length of pipes . 15
7.2.4 Chamfering . 16
7.2.5 Wall thickness . 16
7.2.6 Dimensions of sockets . 18
7.3 Dimensions of fittings . 18
7.3.1 General . 18
7.3.2 Outside diameters . 19
7.3.3 Design lengths (Z) . 19
7.3.4 Wall thicknesses . 19
7.4 Diameters and lengths of sockets and spigot . 23
7.4.1 Adhesive joint sockets and spigot . 23
7.4.2 Ring seal sockets and spigot . 25
7.4.3 One-piece expansion couplings for adhesive joint sockets and spigot . 28
7.5 Types of fittings . 29
8 Mechanical characteristics . 34
8.1 Mechanical characteristics of pipes. 34
8.1.1 Impact resistance . 34
8.1.2 Additional mechanical requirements . 36
2

---------------------- Page: 4 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
8.2 Mechanical characteristics of fittings . 36
9 Physical characteristics . 36
9.1 Physical characteristics of pipes . 36
9.2 Physical characteristics of fittings . 38
10 Performance requirements . 38
11 Sealing rings . 39
12 Adhesives . 40
13 Marking . 40
13.1 General . 40
13.2 Minimum required marking of pipes . 40
13.3 Minimum required marking of fittings . 41
13.4 Additional marking . 42
Annex A (normative) Utilization of non-virgin material . 43
A.1 General . 43
A.2 Own reprocessed material . 43
A.3 External reprocessed and/or recycled materials with agreed specifications . 43
Annex B (informative) Product standards . 45
Bibliography . 46

3

---------------------- Page: 5 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
European foreword
This document (EN 1329-1:2020) has been prepared by Technical Committee CEN/TC 155 “Plastics
piping systems and ducting systems”, the secretariat of which is held by NEN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by June 2021, and conflicting national standards shall be
withdrawn at the latest by June 2021.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1329-1:2014+A1:2018.
The main changes compared to the previous version EN 1329-1:2014+A1:2018:
— review of non-virgin material use and alignment with recently revised EN 1401-1;
— addition of subclause 6.4 Reaction to fire;
— updating in accordance with the latest template;
— updating of normative references.
EN 1329 consists of the following parts, under the general title Plastics piping systems for soil and waste
discharge (low and high temperature) within the building structure — Unplasticized poly(vinyl chloride)
(PVC-U) :
— Part 1: Specifications for pipes, fittings and the system;
— Part 2: Guidance for the assessment of conformity (technical specification).
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
4

---------------------- Page: 6 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
1 Scope
This document specifies the requirements for solid wall pipes with smooth internal and external
surfaces, extruded from the same formulation throughout the wall, fittings and the system of
unplasticized poly(vinyl chloride) (PVC-U) piping systems intended for soil and waste discharge
applications (low and high temperature):
— inside buildings (application area code “B”);
— for both inside buildings and buried in ground within the building structure (application area code
“BD”).
NOTE 1 The intended use is reflected in the marking of products by “B” or “BD”.
NOTE 2 Application "B" covers uses above ground inside the building, or outside buildings fixed onto the wall.
NOTE 3 Multilayer pipes with different formulations throughout the wall and foamed core pipes are covered by
EN 1453-1 [1].
NOTE 4 For use buried in ground within the building structure are intended only those components (marked
with “BD”) with nominal outside diameters equal to or greater than 75 mm.
NOTE 5 EN 476 [2] specifies the general requirements for components used in discharge pipes, drains and
sewers for gravity systems. Pipes and fittings conforming to this standard fully meet these requirements.
This document is also applicable to PVC-U pipes, fittings and the system intended for the following
purposes:
— ventilating part of the pipework in association with discharge applications;
— rainwater pipework within the building structure.
This document also specifies the test parameters for the test methods that are referred to.
This document covers a range of nominal sizes, a range of pipes and fittings series and gives
recommendations concerning colours.
NOTE 6 It is the responsibility of the purchaser or specifier to make the appropriate selections from these
aspects, taking into account their particular requirements and any relevant national regulations and installation
practices or codes.
NOTE 7 Pipes, fittings and other components conforming to any of the plastics product standards listed in
Annex B can be used with pipes and fittings conforming to this document, provided they conform to the
requirements for joint dimensions given in Clause 7 and to the requirements of Table 26.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 681-1, Elastomeric seals — Materials requirements for pipe joint seals used in water and drainage
applications — Part 1: Vulcanized rubber
EN 681-2, Elastomeric Seals — Materials requirements for pipe joint seals used in water and drainage
applications — Part 2: Thermoplastic elastomers
5

---------------------- Page: 7 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
EN 1401-1, Plastics piping systems for non-pressure underground drainage and sewerage — Unplasticized
poly(vinyl chloride) (PVC-U) — Part 1: Specifications for pipes, fittings and the system
EN 14680, Adhesives for non-pressure thermoplastics piping systems — Specifications
EN 14814, Adhesives for thermoplastic piping systems for fluids under pressure — Specifications
EN ISO 472, Plastics — Vocabulary (ISO 472)
EN ISO 580, Plastics piping and ducting systems — Injection-moulded thermoplastics fittings — Methods
for visually assessing the effects of heating (ISO 580)
EN ISO 1043-1, Plastics — Symbols and abbreviated terms — Part 1: Basic polymers and their special
characteristics (ISO 1043-1)
EN ISO 1158, Plastics — Vinyl chloride homopolymers and copolymers — Determination of chlorine
content (ISO 1158)
EN ISO 1167-1:2006, Thermoplastics pipes, fittings and assemblies for the conveyance of fluids —
Determination of the resistance to internal pressure — Part 1: General method (ISO 1167-1:2006)
EN ISO 1167-2:2006, Thermoplastics pipes, fittings and assemblies for the conveyance of fluids —
Determination of the resistance to internal pressure — Part 2: Preparation of pipe test pieces
(ISO 1167-2:2006)
EN ISO 1183-1, Plastics — Methods for determining the density of non-cellular plastics — Part 1:
Immersion method, liquid pycnometer method and titration method (ISO 1183-1)
EN ISO 2505, Thermoplastics pipes — Longitudinal reversion — Test method and parameters (ISO 2505)
EN ISO 2507-1, Thermoplastics pipes and fittings — Vicat softening temperature — Part 1: General test
method (ISO 2507-1)
EN ISO 3126, Plastics piping systems — Plastics components — Determination of dimensions (ISO 3126)
EN ISO 3127, Thermoplastics pipes — Determination of resistance to external blows — Round-the-clock
method (ISO 3127)
EN ISO 3451-5, Plastics — Determination of ash — Part 5: Poly(vinyl chloride) (ISO 3451-5)
EN ISO 6259-1, Thermoplastics pipes — Determination of tensile properties — Part 1: General test
method (ISO 6259-1)
EN ISO 9852, Unplasticized poly(vinyl chloride) (PVC-U) pipes — Dichloromethane resistance at specified
temperature (DCMT) — Test method (ISO 9852)
EN ISO 11173, Thermoplastics pipes — Determination of resistance to external blows — Staircase method
(ISO 11173)
EN ISO 13254, Thermoplastics piping systems for non-pressure applications — Test method for
watertightness (ISO 13254)
EN ISO 13255, Thermoplastics piping systems for soil and waste discharge inside buildings — Test method
for airtightness of joints (ISO 13255)
6

---------------------- Page: 8 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
EN ISO 13257:2018, Thermoplastics piping systems for non-pressure applications — Test method for
resistance to elevated temperature cycling (ISO 13257:2018)
EN ISO 13259, Thermoplastics piping systems for underground non-pressure applications — Test method
for leaktightness of elastomeric sealing ring type joints (ISO 13259)
ISO 6259-2, Thermoplastics pipes — Determination of tensile properties — Part 2: Pipes made of
unplasticized poly(vinyl chloride) (PVC-U), oriented unplasticized poly(vinyl chloride) (PVC-O), chlorinated
poly (vinyl chloride) (PVC-C) and high-impact poly (vinyl chloride) (PVC-HI)
ISO 18373-1, Rigid PVC pipes — Differential scanning calorimetry (DSC) method — Part 1: Measurement
of the processing temperature
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN ISO 472 and EN ISO 1043-1
and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
application area code
code used in the marking of pipes and fittings to indicate the application area(s) for which they are
intended, as follows:
— B: application area code for components intended for use above ground inside the building, or for
components outside buildings fixed onto the wall;
— D: application code for the area under and within 1 m from the building where the pipes and
fittings are buried in ground and are connected to the underground drainage and sewerage system
Note 1 to entry: In D application areas the existence of external forces from the surroundings in addition to the
hot water discharge is usual.
Note 2 to entry: Components intended for use for both code B and code D application areas are marked BD.
Note 3 to entry: Other application area codes U and UD not covered by this standard are defined elsewhere, e.g.
in EN 1401-1.
3.2
nominal size
DN
numerical designation of the size of a component, other than a component designated by thread size,
which is approximately equal to the manufacturing dimension
Note 1 to entry: It is expressed in millimetres, mm.
3.3
nominal size, outside diameter related
DN/OD
nominal size, related to the outside diameter
7

---------------------- Page: 9 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
3.4
nominal outside diameter
d
n
specified outside diameter, assigned to a nominal size DN/OD
Note 1 to entry: It is expressed in millimetres, mm.
3.5
outside diameter
d
e
value of the measurement of the outside diameter through its cross section at any point of a pipe or
spigot of a fitting, rounded to the next greater 0,1 mm
3.6
mean outside diameter
d
em
value of the measurement of the outer circumference of a pipe or spigot of a fitting in any cross section,
divided by π (≈ 3,142), rounded to the next greater 0,1 mm
3.7
inside diameter
d
s
value of the measurement of the inside diameter through its cross section at any point of a socket,
rounded to the next greater 0,1 mm
3.8
mean inside diameter of socket
d
sm
arithmetical mean of a number of measurements of the inside diameter of a socket in the same cross
section
3.9
out-of-roundness
ovality
difference between the measured maximum and the measured minimum outside diameter in the same
cross section of a component
3.10
wall thickness
e
value of measurement of the wall thickness at any point around the circumference of a component
3.11
mean wall thickness
e
m
arithmetical mean of a number of measurements of the wall thickness, regularly spaced around the
circumference and in the same cross section of a component, including the measured minimum and the
measured maximum values of the wall thickness in that cross section
3.12
standard dimension ratio
SDR
numerical designation of a pipe series, which is a convenient round number, approximately equal to the
ratio of the nominal outside diameter of а pipe to its nominal wall thickness
8

---------------------- Page: 10 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
[SOURCE: ISO 4065:2018, 3.5, modified — No symbol is introduced in the definition and Note 1 to entry
is not included here]
3.13
ring stiffness class
SN
numerical designation of the ring stiffness of the pipe or fitting which is a convenient round number,
indicating the minimum required ring stiffness of the pipe or stiffness of the fitting
3.14
assembled fittings
fittings which are made from several injection moulded parts to be assembled together by screwing or
clipping
Note 1 to entry: Such fittings can incorporate rubber membranes or joints.
3.15
fabricated fittings
fittings produced from pipe and/or from injection-moulded fittings by thermoforming, adhesive joint or
welding
Note 1 to entry: Fabricated fittings need an additional fabrication step.
3.16
solid wall pipe
pipe with smooth internal and external surface with the same formulation throughout the wall
Note 1 to entry: Pipes having more than one layer are considered as solid wall pipes, provided they are all made
from the same formulation.
3.17
virgin material
material in the form such as granules or powder that has not been subjected to use or processing other
than that required for its manufacture
Note 1 to entry: Virgin material is a material to which no own and/or external reprocessed or recycled material
has been added.
Note 2 to entry: It is understood that the addition of additives such as stabilizers and pigments is still resulting
into a virgin material.
3.18
non-virgin material
all material which is not defined as virgin material
Note 1 to entry: It covers own reprocessed material, external reprocessed materials and recycled materials.
3.18.1
own reprocessed material
material prepared from rejected unused pipes, gutters, fittings and ancillaries, including trimmings
from the production, that will be reprocessed in a manufacturer's plant after having been previously
processed by the same manufacturer by a process such as moulding or extrusion, and for which the
complete formulation is known
9

---------------------- Page: 11 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
3.18.2
external reprocessed material
material prepared from unused thermoplastics products regardless of where those products were
manufactured
Note 1 to entry: External reprocessed material is often called post-industrial recyclate.
3.18.3
recycled material
material prepared from used thermoplastic products which have been cleaned and crushed or ground
Note 1 to entry: Recycled material is often called post-consumer recyclate.
3.19
agreed specification
specification of the relevant material characteristics agreed between the supplier of the non-virgin
material and the pipes and/or fittings manufacturer
4 Symbols and abbreviations
4.1 Symbols
For the purposes of this document, the following symbols apply.
A length of engagement
α nominal angle of fitting
C depth of sealing zone
e minimum wall thickness
min
e wall thickness of socket
2
e wall thickness at the groove
3
L length of spigot
1
L length of adhesive joint socket
2
l effective length of pipe
R radius of swept fittings
X stop width
Z design length of fitting

4.2 Abbreviations
For the purposes of this document, the following abbreviations apply.
PVC-U unplasticised poly(vinyl chloride)
TIR true impact rate
10

---------------------- Page: 12 ----------------------
SIST EN 1329-1:2021
EN 1329-1:2020 (E)
5 Material
5.1 General
The formulation shall be a mixture of PVC to which are added additives and if applicable non-virgin
material that shall allow the final product to comply with the requirements of this document.
Non-virgin material (either supplied externally or own reprocessed or a mixture of both) may be used
in the conditions given in 5.5.
The formulation (including non-virgin materials if applicable) shall comply with the requirements given
in Table 1 and, if applicable in 5.2 for pipes and 5.3 for fittings.
Table 1 — Requirements applicable for the formulation
Characteristics Requirements Test method
a b c
PVC content for pipes ≥ 80 % by mass Calculation or EN ISO 1158  or
c
EN ISO 3451-5, Metho
...

SLOVENSKI STANDARD
oSIST prEN 1329-1:2019
01-oktober-2019
Cevni sistemi iz polimernih materialov za nizko- in visokotemperaturne odvodne
sisteme v zgradbah - Nemehčan polivinilklorid (PVC-U) - 1. del: Zahteve za cevi,
fitinge in sistem
Plastics piping systems for soil and waste discharge (low and high temperature) within
the building structure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications
for pipes, fittings and the system
Kunststoff-Rohrleitungssysteme zum Ableiten von Abwasser (niedriger und hoher
Temperatur) innerhalb der Gebäudestruktur - Weichmacherfreies Polyvinylchlorid (PVC-
U) - Teil 1: Anforderungen an Rohre, Formstücke und das Rohrleitungssystem
Systèmes de canalisations en plastique pour l'évacuation des eaux-vannes et des eaux
usées (à basse et à haute température) à l'intérieur de la structure des bâtiments - Poly
(chlorure de vinyle) non plastifié (PVC-U) - Partie 1 : Spécifications pour tubes, raccords
et le système
Ta slovenski standard je istoveten z: prEN 1329-1
ICS:
23.040.20 Cevi iz polimernih materialov Plastics pipes
91.140.80 Drenažni sistemi Drainage systems
oSIST prEN 1329-1:2019 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 1329-1:2019

---------------------- Page: 2 ----------------------
oSIST prEN 1329-1:2019


DRAFT
EUROPEAN STANDARD
prEN 1329-1
NORME EUROPÉENNE

EUROPÄISCHE NORM

August 2019
ICS 23.040.20; 91.140.80 Will supersede EN 1329-1:2014+A1:2018
English Version

Plastics piping systems for soil and waste discharge (low
and high temperature) within the building structure -
Unplasticized poly(vinyl chloride) (PVC-U) - Part 1:
Specifications for pipes, fittings and the systems
Systèmes de canalisations en plastique pour Kunststoff-Rohrleitungssysteme zum Ableiten von
l'évacuation des eaux-vannes et des eaux usées (à Abwasser (niedriger und hoher Temperatur) innerhalb
basse et à haute température) à l'intérieur de la der Gebäudestruktur - Weichmacherfreies
structure des bâtiments - Poly(chlorure de vinyle) non Polyvinylchlorid (PVC-U) - Teil 1: Anforderungen an
plastifié (PVC-U) - Partie 1 : Spécifications pour tubes, Rohre, Formstücke und das Rohrleitungssystem
raccords et le système
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 155.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1329-1:2019 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 7
4 Symbols and abbreviations . 10
4.1 Symbols . 10
4.2 Abbreviations . 10
5 Material . 10
5.1 General . 10
5.2 Pipe material for BD application . 11
5.2.1 Use of mineral modifier . 11
5.2.2 Additional requirements . 11
5.3 Additional requirements for fitting material for BD application . 12
5.4 Fabricated fitting material . 13
5.5 Utilization of non-virgin material . 13
5.6 Sealing ring retaining means material . 13
6 General characteristics . 13
6.1 Appearance . 13
6.2 Colour . 13
7 Geometrical characteristics . 13
7.1 General . 13
7.2 Dimensions of pipes . 14
7.2.1 Outside diameter . 14
7.2.2 Out-of-roundness . 15
7.2.3 Length of pipes . 15
7.2.4 Chamfering . 16
7.2.5 Wall thickness . 16
7.2.6 Dimensions of sockets . 18
7.3 Dimensions of fittings . 18
7.3.1 General . 18
7.3.2 Outside diameters . 19
7.3.3 Design lengths . 19
7.3.4 Wall thicknesses . 19
7.4 Diameters and lengths of sockets and spigot . 23
7.4.1 Adhesive joint sockets and spigot . 23
7.4.2 Ring seal sockets and spigot . 25
7.4.3 One-piece expansion couplings for adhesive joint sockets and spigot . 28
7.5 Types of fittings . 29
8 Mechanical characteristics . 35
8.1 Mechanical characteristics of pipes. 35
8.1.1 Impact resistance . 35
8.1.2 Additional mechanical requirements . 36
8.2 Mechanical characteristics of fittings . 37
2

---------------------- Page: 4 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
9 Physical characteristics . 37
9.1 Physical characteristics of pipes . 37
9.2 Physical characteristics of fittings . 39
10 Performance requirements . 39
11 Sealing rings . 40
12 Adhesives . 41
13 Marking . 41
13.1 General . 41
13.2 Minimum required marking of pipes . 41
13.3 Minimum required marking of fittings . 42
13.4 Additional marking . 43
Annex A (normative) Utilization of non-virgin material . 44
A.1 General . 44
A.2 Own reprocessed material . 44
A.3 External reprocessed and/or recycled materials with agreed specifications . 44
Annex B (informative) Product standards . 46
Bibliography . 47

3

---------------------- Page: 5 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
European foreword
This document (prEN 1329-1:2019) has been prepared by Technical Committee CEN/TC 155 “Plastics
piping systems and ducting systems”, the secretariat of which is held by NEN.
This document will supersede EN 1329-1:2014+A1:2018.
The main changes compared to the previous edition are:
— review of non-virgin material use and alignment with recently revised EN 1401-1;
— updating in accordance with the latest template;
— updating of normative references.
EN 1329 consists of the following parts, under the general title Plastics piping systems for soil and waste
discharge (low and high temperature) within the building structure — Unplasticized poly(vinyl chloride)
(PVC-U) :
— Part 1: Specifications for pipes, fittings and the system;
— Part 2: Guidance for the assessment of conformity (technical specification).
4

---------------------- Page: 6 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
1 Scope
This document specifies the requirements for solid wall pipes with smooth internal and external
surfaces, extruded from the same formulation throughout the wall, fittings and the system of
unplasticized poly(vinyl chloride) (PVC-U) piping systems intended for soil and waste discharge
applications (low and high temperature):
— inside buildings (application area code “B”);
— for both inside buildings and buried in ground within the building structure (application area code
“BD”).
NOTE 1 The intended use is reflected in the marking of products by “B” or “BD”.
NOTE 2 Multilayer pipes with different formulations throughout the wall and foamed core pipes are covered by
EN 1453-1 [1].
NOTE 3 For use buried in ground within the building structure are intended only those components (marked
with “BD”) with nominal outside diameters equal to or greater than 75 mm.
NOTE 4 EN 476 [2] specifies the general requirements for components used in discharge pipes, drains and
sewers for gravity systems. Pipes and fittings conforming to this standard fully meet these requirements.
This document is also applicable to PVC-U pipes, fittings and the system intended for the following
purposes:
— ventilating part of the pipework in association with discharge applications;
— rainwater pipework within the building structure.
This document also specifies the test parameters for the test method that are referred to.
This document covers a range of nominal sizes, a range of pipes and fittings series and gives
recommendations concerning colours.
NOTE 5 It is the responsibility of the purchaser or specifier to make the appropriate selections from these
aspects, taking into account their particular requirements and any relevant national regulations and installation
practices or codes.
For external above ground application additional requirements depending on the climate should be
agreed between the manufacturer and the user.
NOTE 6 Pipes, fittings and other components conforming to any of the plastics product standards listed in
Annex B can be used with pipes and fittings conforming to this document, provided they conform to the
requirements for joint dimensions given in Clause 6 and to the requirements of Table 25.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 681-1, Elastomeric seals — Materials requirements for pipe joint seals used in water and drainage
applications — Part 1: Vulcanized rubber
EN 681-2, Elastomeric Seals — Materials requirements for pipe joint seals used in water and drainage
applications — Part 2: Thermoplastic elastomers
5

---------------------- Page: 7 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
EN 1401-1, Plastics piping systems for non-pressure underground drainage and sewerage — Unplasticized
poly(vinyl chloride) (PVC-U) — Part 1: Specifications for pipes, fittings and the system
EN 1905, Plastics piping systems — Unplasticized poly(vinyl chloride) (PVC-U) pipes, fittings and material
— Method for assessment of the PVC content based on total chlorine content
EN 14680, Adhesives for non-pressure thermoplastics piping systems — Specifications
EN 14814, Adhesives for thermoplastic piping systems for fluids under pressure — Specifications
EN ISO 472, Plastics — Vocabulary (ISO 472)
EN ISO 580, Plastics piping and ducting systems — Injection-moulded thermoplastics fittings — Methods
for visually assessing the effects of heating (ISO 580)
EN ISO 1043-1, Plastics — Symbols and abbreviated terms — Part 1: Basic polymers and their special
characteristics (ISO 1043-1)
EN ISO 1167-1:2006, Thermoplastics pipes, fittings and assemblies for the conveyance of fluids —
Determination of the resistance to internal pressure — Part 1: General method (ISO 1167-1:2006)
EN ISO 1167-2:2006, Thermoplastics pipes, fittings and assemblies for the conveyance of fluids —
Determination of the resistance to internal pressure — Part 2: Preparation of pipe test pieces
(ISO 1167-2:2006)
EN ISO 1183-1, Plastics — Methods for determining the density of non-cellular plastics — Part 1:
Immersion method, liquid pyknometer method and titration method (ISO 1183-1)
EN ISO 2505, Thermoplastics pipes — Longitudinal reversion — Test method and parameters (ISO 2505)
EN ISO 2507-1, Thermoplastics pipes and fittings — Vicat softening temperature — Part 1: General test
method (ISO 2507-1)
EN ISO 3126, Plastics piping systems — Plastics components — Determination of dimensions (ISO 3126)
EN ISO 3127, Thermoplastics pipes — Determination of resistance to external blows — Round-the-clock
method (ISO 3127)
EN ISO 3451-5, Plastics — Determination of ash — Part 5: Poly(vinyl chloride) (ISO 3451-5)
EN ISO 6259-1, Thermoplastics pipes — Determination of tensile properties — Part 1: General test
method (ISO 6259-1)
EN ISO 9852, Unplasticized poly(vinyl chloride) (PVC-U) pipes — Dichloromethane resistance at specified
temperature (DCMT) — Test method (ISO 9852)
EN ISO 11173, Thermoplastics pipes — Determination of resistance to external blows — Staircase method
(ISO 11173)
EN ISO 13254, Thermoplastics piping systems for non-pressure applications — Test method for
watertightness (ISO 13254)
EN ISO 13255, Thermoplastics piping systems for soil and waste discharge inside buildings — Test method
for airtightness of joints (ISO 13255)
6

---------------------- Page: 8 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
EN ISO 13257:2018, Thermoplastics piping systems for non-pressure applications — Test method for
resistance to elevated temperature cycling (ISO 13257:2018)
EN ISO 13259, Thermoplastics piping systems for underground non-pressure applications — Test method
for leaktightness of elastomeric sealing ring type joints (ISO 13259)
ISO 6259-2, Thermoplastics pipes — Determination of tensile properties — Part 2: Pipes made of
unplasticized poly(vinyl chloride) (PVC-U), chlorinated poly (vinyl chloride) (PVC-C) and high-impact poly
(vinyl chloride) (PVC-HI)
ISO 18373-1, Rigid PVC pipes — Differential scanning calorimetry (DSC) method — Part 1: Measurement
of the processing temperature
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN ISO 472 and EN ISO 1043-1
and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
application area code
code used in the marking of pipes and fittings to indicate the application area(s) for which they are
intended, as follows:
— B: application area code for components intended for use above ground inside the building, or for
components outside buildings fixed onto the wall;
— D: application code for the area under and within 1 m from the building where the pipes and
fittings are buried in ground and are connected to the underground drainage and sewerage system
Note 1 to entry: In D application areas the existence of external forces from the surroundings in addition to the
hot water discharge is usual.
Note 2 to entry: Components intended for use for both code B and code D application areas are marked BD.
Note 3 to entry: Other application area codes U and UD not covered by this standard are defined elsewhere, e.g.
in EN 1401-1.
3.2
nominal size
DN
numerical designation of the size of a component, other than a component designated by thread size,
which is approximately equal to the manufacturing dimension
Note 1 to entry: It is expressed in millimetres, mm.
3.3
nominal size, outside diameter related
DN/OD
nominal size, related to the outside diameter
7

---------------------- Page: 9 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
3.4
nominal outside diameter
d
n
specified outside diameter, assigned to a nominal size DN/OD
Note 1 to entry: It is expressed in millimetres, mm.
3.5
outside diameter
d
e
value of the measurement of the outside diameter through its cross section at any point of a pipe or
spigot of a fitting, rounded to the next greater 0,1 mm
3.6
mean outside diameter
d
em
value of the measurement of the outer circumference of a pipe or spigot of a fitting in any cross section,
divided by π (≈ 3,142), rounded to the next greater 0,1 mm
3.7
inside diameter
d
s
value of the measurement of the inside diameter through its cross section at any point of a socket,
rounded to the next greater 0,1 mm
3.8
mean inside diameter of a socket
d
sm
arithmetical mean of a number of measurements of the inside diameter of a socket in the same cross
section
3.9
out-of-roundness
ovality
difference between the measured maximum and the measured minimum outside diameter in the same
cross section of a component
3.10
wall thickness
e
value of measurement of the wall thickness at any point around the circumference of a component
3.11
mean wall thickness
e
m
arithmetical mean of a number of measurements of the wall thickness, regularly spaced around the
circumference and in the same cross section of a component, including the measured minimum and the
measured maximum values of the wall thickness in that cross section
3.12
standard dimension ratio
SDR
numerical designation of a pipe series, which is a convenient round number, approximately equal to the
of а pipe to its nominal wall thickness e
ratio of the nominal outside diameter dn n
8

---------------------- Page: 10 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
3.13
ring stiffness class
SN
numerical designation of the ring stiffness of the pipe or fitting which is a convenient round number,
indicating the minimum required ring stiffness of the pipe or stiffness of the fitting
3.14
assembled fittings
fittings which are made from several injection moulded parts to be assembled together by screwing or
clipping
Note 1 to entry: Such fittings can incorporate rubber membranes or joints.
3.15
fabricated fittings
fittings produced from pipe and/or from injection-moulded fittings by thermoforming, solvent-
cementing or welding
Note 1 to entry: Fabricated fittings need an additional fabrication step.
3.16
solid wall pipe and fitting
pipe or fitting with smooth internal and external surface with the same formulation throughout the wall
Note 1 to entry: Pipes having more than one layer are considered as solid wall pipes, provided they are all made
from the same formulation.
3.17
virgin material
material in the form such as granules or powder that has not been subjected to use or processing other
than that required for its manufacture
Note 1 to entry: Virgin material is a material to which no own and/or external reprocessed or recycled material
has been added.
Note 2 to entry: It is understood that the addition of additives such as stabilizers and pigments is still resulting
into a virgin material.
3.18
non-virgin material
all material which is not defined as virgin material
Note 1 to entry: It covers own reprocessed material, external reprocessed materials and recycled materials.
3.18.1
own reprocessed material
material prepared from rejected unused pipes, gutters, fittings and ancillaries, including trimmings
from the production, that will be reprocessed in a manufacturer's plant after having been previously
processed by the same manufacturer by a process such as moulding or extrusion, and for which the
complete formulation is known
3.18.2
external reprocessed material
material prepared from unused thermoplastics products regardless of where those products were
manufactured
9

---------------------- Page: 11 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
Note 1 to entry: External reprocessed material is often called post-industrial recyclate.
3.18.3
recycled material
material from used thermoplastic products which have been cleaned and crushed or ground
Note 1 to entry: Recycled material is often called post-consumer recyclate.
3.19
agreed specification
specification of the relevant material characteristics agreed between the supplier of the non-virgin
material and the pipes and/or fittings manufacturer
4 Symbols and abbreviations
For the purposes of this document, the following symbols and abbreviations apply.
4.1 Symbols
A length of engagement
α nominal angle of a fitting
C depth of sealing zone
e minimum wall thickness
min
e wall thickness of a socket
2
e wall thickness in the groove area
3
L length of spigot
1
L length of adhesive joint socket
2
l effective length of a pipe
R radius of swept fittings
X stop width
Z design length of a fitting
4.2 Abbreviations
PVC-U unplasticised poly(vinyl chloride)
TIR true impact rate
5 Material
5.1 General
The formulation shall be a mixture of PVC to which are added additives and if applicable non-virgin
material that shall allow the final product to comply with the requirements of this document.
Non-virgin material (either supplied externally or own reprocessed or a mixture of both) may be used
in the conditions given in 5.5.
The formulation (including non-virgin materials if applicable) shall comply with the requirements given
in Table 1 and, if applicable in 5.2 for pipes and 5.3 for fittings.
10

---------------------- Page: 12 ----------------------
oSIST prEN 1329-1:2019
prEN 1329-1:2019 (E)
Table 1 — Requirements applicable for the formulation
Characteristics Requirements Test method
a b
PVC content for pipes ≥ 80 % by mass Calculation or EN 1905 or
b
EN ISO 3451-5, Method A
PVC content for injection-moulded fittings ≥ 85 % by mass
a
A further reduction of the PVC content is permitted according to 5.2.1.
b
The measurement of filler content by ash rest is an alternative to the measurement of PVC content and is
recommended when external reprocessed and/or recycled material is used.

5.2 Pipe material for BD application
5.2.1 Use of mineral modifier
For pipes ≥ 110 mm and intended for BD application, a further reduction of the PVC content to ≥ 75 %
by mass is permitted provided the PVC is substituted by coated or uncoated CaCO conforming to the
3
following:
a) The composition of the CaCO , before coating if any, shall conform to the following:
3
1) content of CaCO ≥ 96 % by mass;
3
2) content of MgCO ≤ 4 % by mass;
3
3) content of CaCO and MgCO in total ≥ 98 % by mass.
3 3
b) The physical properties of the material shall conform to the following:
4) mean particle size D50 ≤ 2,5 μm;
5) top cut D98 ≤ 20 μm.
5.2.2 Additional requirements
The material of pipes intended to be used in application area BD shall comply wi
...