This European Standard covers d.c. metal-enclosed and non-metallic enclosed switchgear
assemblies used in indoor stationary installations of traction systems, with nominal voltage
not exceeding 3 000 V.
It is intended that individual items of equipment, for example circuit breakers, housed in the
assembly are designed, manufactured and individually tested (simulating the enclosure when
necessary) in accordance with their respective parts of EN 50123 or, when appropriate, with
another applicable standard.
NOTE 1 The requirements covered in this European Standard are those concerning the assembly as such, its
enclosure and the mutual influence of the equipment enclosed.
NOTE 2 EMC requirements are covered by EN 50121-5 and additional requirements concerning dependability
(RAMS) are covered by EN 50126.
Bahnanwendungen - Ortsfeste Anlagen - Gleichstrom-Schalteinrichtungen -- Teil 6: Gleichstrom-Schaltanlagen
Applications ferroviaires - Installations fixes - Appareillage à courant continu -- Partie 6: Ensembles d'appareillage
Železniške naprave - Stabilne naprave električne vleke - Stikalne naprave za enosmerni tok - 6. del: Oprema stikalnih naprav za enosmerni tok
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 50123-6:2003/oprAA:2013
01-maj-2013
äHOH]QLãNHQDSUDYH6WDELOQHQDSUDYHHOHNWULþQHYOHNH6WLNDOQHQDSUDYH]D
HQRVPHUQLWRNGHO2SUHPDVWLNDOQLKQDSUDY]DHQRVPHUQLWRN
Railway applications - Fixed installations - D.C. switchgear -- Part 6: D.C. switchgear
assemblies
Bahnanwendungen - Ortsfeste Anlagen - Gleichstrom-Schalteinrichtungen -- Teil 6:
Gleichstrom-Schaltanlagen
Applications ferroviaires - Installations fixes - Appareillage à courant continu -- Partie 6:
Ensembles d'appareillage
Ta slovenski standard je istoveten z: EN 50123-6:2003/prAA:2013
ICS:
29.130.99 Druge stikalne in krmilne Other switchgear and
naprave controlgear
29.280 (OHNWULþQDYOHþQDRSUHPD Electric traction equipment
SIST EN 50123-6:2003/oprAA:2013 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 50123-6:2003/oprAA:2013
---------------------- Page: 2 ----------------------
SIST EN 50123-6:2003/oprAA:2013
DRAFT
EUROPEAN STANDARD
EN 50123-6
prAA
NORME EUROPÉENNE
March 2013
EUROPÄISCHE NORM
ICS 29.130.99; 29.280
English version
Railway applications -
Fixed installations -
D.C. switchgear -
Part 6: D.C. switchgear assemblies
Applications ferroviaires - Bahnanwendungen -
Installations fixes - Ortsfeste Anlagen -
Appareillage à courant continu - Gleichstrom-Schalteinrichtungen -
Partie 6: Ensembles d'appareillage Teil 6: Gleichstrom-Schaltanlagen
This draft amendment prAA, if approved, will modify the European Standard EN 50123-6:2003; it is submitted to
CENELEC members for CENELEC enquiry.
Deadline for CENELEC: 2013-08-09.
It has been drawn up by CLC/SC 9XC.
If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this amendment the status of a national standard without any
alteration.
This draft amendment was established by CENELEC in three official versions (English, French, German). A version in
any other language made by translation under the responsibility of a CENELEC member into its own language and
notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they
are aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change
without notice and shall not be referred to as a European Standard.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Project: 23568 Ref. No. EN 50123-6:2003/prAA:2013 E
---------------------- Page: 3 ----------------------
SIST EN 50123-6:2003/oprAA:2013
EN 50123-6:2003/prAA:2013
1 Contents Page
2 Foreword. 3
3 2 Normative references . 4
4 3 Definitions . 4
5 8 Tests. 4
6 8.2 List of the applicable tests . 4
7 8.3 Performance of tests . 4
8
8.3.9 Internal arc test . 4
9 Annex B (normative) Method for testing under conditions of arcing due to an internal fault . 5
10 B.1 Purpose of the test . 5
11 B.2 Characteristics – Rated short-circuit current under internal arcing conditions (I ). 5
Narc
12 B.3 Test arrangements . 5
13 B.3.1 Test specimen . 5
14 B.3.2 Test circuit . 6
15 B.3.3 Voltage . 6
16 B.3.4 Duration of the test . 7
17 B.4 Test procedure . 7
18 B.4.1 Supply circuit . 7
19 B.4.2 Arc initiation . 7
20 B.4.3 Indicators . 8
21 B.4.4 Repetition of the test . 8
22 B.5 Assessment of the test . 9
23 B.6 Test report . 9
24 Bibliography . 14
25
26
2
---------------------- Page: 4 ----------------------
SIST EN 50123-6:2003/oprAA:2013
EN 50123-6:2003/prAA:2013
27 Foreword
28 This document [EN 50123-6:2003/prAA:2013] has been prepared by CLC/SC 9XC "Electric supply and
29 earthing systems for public transport equipment and ancillary apparatus (Fixed installations)".
30 This document is currently submitted to the Enquiry.
31 This amendment was elaborated to provide guidance to the requirement of 6.6.3, Internal arcing, that gas or
32 vapour escaping under pressure does not endanger operating staff.
3
---------------------- Page: 5 ----------------------
SIST EN 50123-6:2003/oprAA:2013
EN 50123-6:2003/prAA:2013
33 2 Normative references
34 Add the following references:
35 EN 50123-1:2003, Railway applications – Fixed installations – D.C. switchgear – Part 1: General
36 EN 50123-7-1:2003, Railway applications – Fixed installations – D.C. switchgear – Part 7-1: Measurement,
37 control and protection devices for specific use in d.c. traction systems – Application guide
38 3 Definitions
39 Replace Clause 3 by the following:
40 3 Terms and definitions
41 For the purposes of this document, the terms and definitions given in EN 50123-1:2003 and the following
42 apply.
43 3.1
44 internal arc
45 arcing within a switchgear assembly arising from a fault between active parts and/or between active parts and
46 other conductive parts
47 3.2
48 rated short-circuit current under internal arcing conditions (I )
Narc
49 current, during the test duration/150 ms, indicating the maximum allowable value of sustained short-circuit
50 current at the terminals of the incoming unit for which the requirements of this test specification are fulfilled
51 Note 1 to entry: The value is the maximum value of the prospective sustained short-circuit current.
52 3.3
53 compartment under test
54 compartment of a switchgear assembly which is subject to an internal arc test
55 8 Tests
56 8.2 List of the applicable tests
57 Add the following at the end of Table 2:
Internal arc test Type, optional 8.3.9
58
59 8.3 Performance of tests
60 Add the following after 8.3.8:
61 8.3.9 Internal arc test
62 The internal arc test is an optional type test. The test shall be performed according to the procedure specified
63 in Annex B. The criteria for successful passing are given in B.5.
4
---------------------- Page: 6 ----------------------
SIST EN 50123-6:2003/oprAA:2013
EN 50123-6:2003/prAA:2013
64 Add the following after Annex A:
65 Annex B
66 (normative)
67
68 Method for testing under conditions of arcing due to an internal fault
69 B.1 Purpose of the test
70 Annex B applies to metal-enclosed d.c. switchgear assemblies - hereafter called ASSEMBLIES - used in
71 indoor stationary installations.
72 The test procedure described below is intended
73 to assess the ability of the ASSEMBLY to limit the risk of personal injury,
74 to verify the effectiveness of the design in protecting persons,
75 in case of an internal arc.
76 The testing conditions take into account that ASSEMBLIES are installed in areas restricted to authorised
77 personnel.
78 NOTE This is equivalent to accessibility class A of EN 62271-200:2012.
79 B.2 Characteristics – Rated short-circuit current under internal arcing
80 conditions (I )
Narc
81 Value of the rated short-circuit current shall be equal to the rated earth fault current I . The peak of the
Ncwe
82 short-circuit current value is conventionally assumed to be 1,42 times the prospective sustained short-circuit
83 current (fault of negligible impedance).
84 NOTE The current level during internal arcing depends on the earthing of the switchboard frame (see
85 EN 50123-7-1:2003, 6.5.7). High fault currents can be expected where the switchboard frame is
86 – directly connected to the return circuit as shown in EN 50123-7-1:2003, 6.5.7, Figure 4b, or
87 – connected to substation earth as shown in EN 50123-7-1:2003, 6.5.7, Figure 4a, and a fast acting,
88 – voltage limiting device is installed between substation earth and the return circuit.
89 Lower fault currents can be expected where the bedding resistance of the track and the earth resistance limit the fault
90 current
91 B.3 Test arrangements
92 B.3.1 Test specimen
93 The test shall be carried out on representative samples. In case of an ASSEMBLY with a continuous main
94 busbar, consisting of extensible (modular) standalone units, the test specimen shall consist of minimum three
95 units connected together as in service.
5
---------------------- Page: 7 ----------------------
SIST EN 50123-6:2003/oprAA:2013
EN 50123-6:2003/prAA:2013
96 The following points shall be observed.
97 The test shall be carried out on a test specimen not previously subjected to an arcing test or on a
98 specimen cleaned and prepared accordingly. The specimen and the equipment in it may be repaired or
99 replaced before each test.
100 NOTE Degradation of insulation due to carbonisation or moderate erosion of metal parts is not necessarily
101 considered to render a unit unsuitable for a further test.
102 The test specimen shall be placed in an open area and shall be fixed by its designed means.
103 Vertical indicators shall be installed all around.
104 A ceiling s
...
SLOVENSKI STANDARD
SIST EN 50123-6:2003/A1:2015
01-april-2015
äHOH]QLãNHQDSUDYH6WDELOQHQDSUDYHHOHNWULþQHYOHNH6WLNDOQHQDSUDYH]D
HQRVPHUQLWRNGHO2SUHPDVWLNDOQLKQDSUDY]DHQRVPHUQLWRN
Railway applications - Fixed installations - D.C. switchgear -- Part 6: D.C. switchgear
assemblies
Bahnanwendungen - Ortsfeste Anlagen - Gleichstrom-Schalteinrichtungen -- Teil 6:
Gleichstrom-Schaltanlagen
Applications ferroviaires - Installations fixes - Appareillage à courant continu -- Partie 6:
Ensembles d'appareillage
Ta slovenski standard je istoveten z: EN 50123-6:2003/A1:2014
ICS:
29.130.99 Druge stikalne in krmilne Other switchgear and
naprave controlgear
29.280 (OHNWULþQDYOHþQDRSUHPD Electric traction equipment
SIST EN 50123-6:2003/A1:2015 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 50123-6:2003/A1:2015
---------------------- Page: 2 ----------------------
SIST EN 50123-6:2003/A1:2015
EUROPEAN STANDARD
EN 50123-6:2003/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
December 2014
ICS 29.130.99; 29.280
English Version
Railway applications - Fixed installations - D.C. switchgear - Part
6: D.C. switchgear assemblies
Applications ferroviaires - Installations fixes - Appareillage à Bahnanwendungen - Ortsfeste Anlagen - Gleichstrom-
courant continu - Partie 6: Ensembles d'appareillage Schalteinrichtungen - Teil 6: Gleichstrom-Schaltanlagen
This amendment A1 modifies the European Standard EN 50123-6:2003; it was approved by CENELEC on 2014-11-17. CENELEC
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the
status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status
as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 50123-6:2003/A1:2014 E
---------------------- Page: 3 ----------------------
SIST EN 50123-6:2003/A1:2015
EN 50123-6:2003/A1:2014 - 2 -
Contents Page
Foreword. 3
2 Normative references . 4
3 Definitions . 4
8 Tests. 4
8.2 List of the applicable tests . 4
8.3 Performance of tests . 4
8.3.9 Internal arc test . 4
Annex B (normative) Method for testing under conditions of arcing due to an internal fault . 5
B.1 Purpose of the test . 5
B.2 Characteristics – Rated short-circuit current under internal arcing conditions (I ). 5
Narc
B.3 Test arrangements . 6
B.3.1 Test specimen . 6
B.3.2 Test circuit . 7
B.3.3 Voltage . 7
B.3.4 Duration of the test . 7
B.4 Test procedure . 7
B.4.1 Supply circuit . 7
B.4.2 Arc initiation . 7
B.4.3 Indicators . 8
B.4.4 Repetition of the test . 9
B.5 Assessment of the test . 9
B.6 Test report . 10
Bibliography . 14
---------------------- Page: 4 ----------------------
SIST EN 50123-6:2003/A1:2015
- 3 - EN 50123-6:2003/A1:2014
Foreword
This document (EN 50123-6:2003/A1:2014) has been prepared by CLC/SC 9XC "Electric supply and earthing
systems for public transport equipment and ancillary apparatus (Fixed installations)".
The following dates are fixed:
• latest date by which this document has to be (dop) 2015-11-17
implemented at national level by publication of
an identical national standard or by
endorsement
(dow) 2017-11-17
• latest date by which the national standards
conflicting with this document have to
be withdrawn
This amendment was elaborated to provide guidance to the requirement of 6.6.3, Internal arcing, that gas or
vapour escaping under pressure does not endanger operating staff.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights.
---------------------- Page: 5 ----------------------
SIST EN 50123-6:2003/A1:2015
EN 50123-6:2003/A1:2014 - 4 -
2 Normative references
Add the following reference:
EN 50123-1:2003, Railway applications – Fixed installations – D.C. switchgear – Part 1: General
3 Definitions
Replace Clause 3 by the following:
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 50123-1:2003 and the following
apply.
3.1
internal arc
arcing within a switchgear assembly arising from a fault between active parts and/or between active parts and
other conductive parts
3.2
rated short-circuit current under internal arcing conditions (I )
Narc
current, during the test duration/150 ms, indicating the maximum allowable value of sustained short-circuit
current at the terminals of the incoming unit for which the requirements of this test specification are fulfilled
Note 1 to entry: The value is the maximum value of the prospective sustained short-circuit current.
3.3
compartment under test
compartment of a switchgear assembly which is subject to an internal arc test
8 Tests
8.2 List of the applicable tests
Add the following at the end of Table 2:
Internal arc test Type, optional 8.3.9
8.3 Performance of tests
Add the following after 8.3.8:
8.3.9 Internal arc test
The internal arc test is an optional type test. The test shall be performed according to the procedure specified
in Annex B. The criteria for successful passing are given in B.5.
---------------------- Page: 6 ----------------------
SIST EN 50123-6:2003/A1:2015
- 5 - EN 50123-6:2003/A1:2014
Add the following after Annex A:
Annex B
(normative)
Method for testing under conditions of arcing due to an internal fault
B.1 Purpose of the test
Annex B applies to metal-enclosed d.c. switchgear assemblies - hereafter called ASSEMBLIES - used in
indoor stationary installations.
The test procedure described below is intended
to assess the ability of the ASSEMBLY to limit the risk of personal injury,
to verify the effectiveness of the design in protecting persons,
in case of an internal arc.
The testing conditions take into account that ASSEMBLIES are installed in areas restricted to authorized
personnel.
NOTE This is equivalent to accessibility class A of EN 62271-200:2012.
B.2 Characteristics – Rated short-circuit current under internal arcing
conditions (I )
Narc
Value of the rated short-circuit current current under internal arcing conditions I shall be equal to the rated
Narc
earth fault current I . The peak of the short-circuit current value is conventionally assumed to be 1,42 times
Ncwe
the prospective sustained short-circuit current (fault of negligible impedance).
NOTE The current level during internal arcing depends on the earthing of the switchboard frame (see
EN 50123-7-1:2003, 6.5.7). High fault currents can be expected where the switchboard frame is
– directly connected to the return circuit as shown in EN 50123-7-1:2003, 6.5.7, Figure 4b, or
– connected to substation earth as shown in EN 50123-7-1:2003, 6.5.7, Figure 4a, and a voltage limiting device is
installed between substation earth and the return circuit.
Lower fault currents can be expected where the bedding resistance of the track and the earth resistance limit the fault
current.
---------------------- Page: 7 ----------------------
SIST EN 50123-6:2003/A1:2015
EN 50123-6:2003/A1:2014 - 6 -
B.3 Test arrangements
B.3.1 Test specimen
The test shall be carried out on representative samples. In case of an ASSEMBLY with a continuous main
busbar, consisting of extensible (modular) standalone units, the test specimen shall consist of minimum two
units connected together as in service.
The following points shall be observed.
The test shall be carried out on a test specimen not previously subjected to an arcing test or on a
specimen cleaned and prepared accordingly. The specimen and the equipment in it may be repaired or
replaced before each test.
NOTE Degradation of insulation due to carbonisation or moderate erosion of metal parts is not necessarily
considered to render a unit unsuitable for a further test.
The test specimen shall be placed in an open area and shall be fixed by its designed means.
Vertical indicators shall be installed all around.
A ceiling shall be loca
...