Abstract

The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input. The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines:
-The monitored and controlled AC inverter power system architectures.
-The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
-The XML files with tags and variables corresponding to the data in the tables.

Status
Published
Publication Date
12-Feb-2013
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
16-Jan-2013
Due Date
23-Mar-2013
Completion Date
13-Feb-2013

Buy Documents

Standard

es_20233610v010101m - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 10: AC inverter power system control and monitoring information model

English language (18 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

es_20233610v010101p - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 10: AC inverter power system control and monitoring information model

English language (18 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

SIST ES 202 336-10 V1.1.1:2013

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

SIST ES 202 336-10 V1.1.1:2013 is the SIST adoption of an ETSI standard for Environmental Engineering (EE) monitoring and control interfaces. It specifies the AC inverter power system control and monitoring information model for telecommunication equipment supply using 48 Vdc or 400 Vdc input. Engineers, integrators, and operators use it to define alarms, measurements, control points, and XML data exchange for remote supervision.

What does SIST ES 202 336-10 V1.1.1:2013 specify?

SIST ES 202 336-10 V1.1.1:2013 specifies how to monitor and control AC inverter power systems used in telecommunication networks. It focuses on the information model, the minimum exchanged data at the interface, and the XML representation of that data.

The scope keeps two related areas outside its boundary: inverters included in UPS and the back-up battery connected to the inverter power system. Those parts are handled by other ETSI documents, so this standard is aimed at the inverter subsystem itself.

AnnexWhat it covers
Annex AMandatory monitoring/supervision information and functions
Annex BNon-mandatory monitoring/supervision information and functions
Annex CMandatory XML structure and elements

The document is organized into scope, references, definitions and abbreviations, the AC inverter power system description, and three annexes that separate mandatory, optional, and XML-specific content.

What are the key requirements of SIST ES 202 336-10 V1.1.1:2013?

System boundaries and architecture

SIST ES 202 336-10 V1.1.1:2013 applies to AC inverter power systems for telecommunication equipment supply with 48 Vdc or 400 Vdc input. It covers single-phase and three-phase output systems, and it allows one XCU to supervise several power cabinets through a field bus.

In practice, that means the standard is written for distributed telecom power installations, not for general-purpose inverter products. The field bus itself is outside the scope, so the document focuses on the monitored data and control model, not the transport network.

Mandatory monitoring and control

Annex A gives the mandatory information that shall be provided. It includes device description, alarm, event, data, config, and control elements, and it expects the XCU to provide the information, or the DGU where there is no XCU.

The mandatory alarms and states cover loss or out-of-range DC input, loss or out-of-range output, inverter failure, overload or short circuit, frequency out of range, static bypass failure, synchronization error, module failure, protection trips, and forced cooling failure. In practice, this is the core fault and status set needed for remote supervision, alarm handling, and maintenance response.

Annex A also requires operational data such as input DC voltage and current, output AC voltage and current, output frequency, output active power, static bypass current, and internal temperature. It also includes log-related items, output low-voltage threshold, forced operating mode changes, and inverter module control, which supports troubleshooting and remote adjustment.

Optional information

Annex B adds non-mandatory monitoring and control items. These include battery nearly discharged, peak current limiter active, inverter temperature out of limit, manual bypass operation, room temperature, power capacity management, harmonic distortion, frequency synchronization range, output overload threshold, and inverter power device control.

This gives manufacturers and operators a richer model when they need deeper diagnostics, energy accounting, or more detailed supervision, while keeping Annex A as the minimum common set.

XML representation

Annex C standardizes the XML structure and elements for the AC inverter power system. It organizes the data in tables for description, alarm, event, data, data record, config, and control, and it allows child elements for inverter, static_bypass_switch, and protection_and_distribution.

That structure matters because it lets different systems exchange the same monitoring data in a predictable format. It also lets manufacturers add sub-equipment details while staying within the standard's folder-like XML layout.

What terms does SIST ES 202 336-10 V1.1.1:2013 define?

  • AC inverter power system - A device or system that converts DC voltage to AC voltage and keeps supplying power when commercial power drops outside acceptable limits.
  • Alarm - Information that signals an abnormal state and carries a severity indication.
  • Event - Information that signals a state change that is not an alarm, such as a battery test or a change in battery charge state.
  • Control Unit (CU) - An integrated unit in equipment that monitors and controls the equipment through sensors and actuators.
  • Data Gathering Unit (DGU) - A unit that collects serial, digital, and analog data and forwards or receives information via agreed protocols.
  • Static Bypass Switch (SBS) - A bypass function that monitors inverter and mains AC voltage and transfers the supply path when needed.
  • XCU - A CU enabled to communicate using the XML interface defined in this standard.

Who uses SIST ES 202 336-10 V1.1.1:2013?

SIST ES 202 336-10 V1.1.1:2013 is used by telecom power system designers, equipment manufacturers, integrators, and maintenance teams. It is relevant in telecommunications centres and Access Networks locations where inverter-based power support must be monitored remotely.

It also supports operators of Remote Management Application (RMA), Control Unit (CU), Data Gathering Unit (DGU), and XML-based supervision systems. These users need a common way to describe alarms, measurements, records, and control actions across different inverter installations.

Which standards are used with SIST ES 202 336-10 V1.1.1:2013?

  • ETSI ES 202 336-1 - Provides the generic interface framework and the meaning of element types used throughout the series.
  • ETSI ETS 300 132-1 - Defines the AC power supply interface used as the output reference for this inverter system.
  • ETSI ES 202 336-2 - Covers DC power system control and monitoring, including the back-up battery context.
  • ETSI ES 202 336-3 - Covers AC UPS power system control and monitoring, which is the excluded UPS case.
  • ETSI EN 300 132-2 - Provides the DC input interface referenced for 48 Vdc systems.
  • ETSI EN 300 132-3-1 - Provides the input interface referenced for up to 400 V solutions.
  • ETSI EN 302 099 - Gives powering guidance for access network equipment.
  • ISO/IEC 10164, ISO/IEC 8879, and IEEE 802.1 to 802.11 - Support the management, markup, and networking terms used in the document.

What does the SIST ES 202 336-10 V1.1.1:2013 document contain?

The document contains a figure showing the AC inverter power system connected to DC power supply systems with battery backup, plus text tables for mandatory and optional monitoring points. Annex A and Annex B organize alarms, data, config, and control items for both the system and individual inverter modules.

Annex C contains the XML structure for the site-level and AC inverter power system data model, including the main tables and allowed child elements. In practice, this is the part used to build software interfaces, map fields into XML, and exchange supervision data between equipment and management systems.

Buy Documents

Standard

es_20233610v010101m - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 10: AC inverter power system control and monitoring information model

English language (18 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

es_20233610v010101p - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 10: AC inverter power system control and monitoring information model

English language (18 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

SIST ES 202 336-10 V1.1.1:2013

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST ES 202 336-10 V1.1.1:2013 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE) - Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) - Part 10: AC inverter power system control and monitoring information model". This standard covers: The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input. The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines: -The monitored and controlled AC inverter power system architectures. -The minimum set of exchanged information required at the interface, described in "natural language" in text tables. -The XML files with tags and variables corresponding to the data in the tables.

The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input. The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines: -The monitored and controlled AC inverter power system architectures. -The minimum set of exchanged information required at the interface, described in "natural language" in text tables. -The XML files with tags and variables corresponding to the data in the tables.

SIST ES 202 336-10 V1.1.1:2013 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST ES 202 336-10 V1.1.1:2013 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 8 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 3.2 Abbreviations
  • 9 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 4 AC inverter power system
  • 10 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 11 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 12 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 13 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 14 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 15 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 16 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 17 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)
  • 18 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)

1 Scope

The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input.

The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines:

  • The monitored and controlled AC inverter power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the reference document (including any amendments) applies.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are necessary for the application of the present document. [1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI ETS 300 132-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 1: Operated by alternating current (ac) derived from direct current (dc) sources".

2.2 Informative references

The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolitan Area Network". [i.2] ISO/IEC 10164: "Information technology - Open Systems Interconnection - Systems Management:

Objects and attributes for access control".

[i.3] ISO/IEC 8879: "Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current (dc)". ETSI

6 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)

[i.5] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

[i.6] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.7] ETSI ES 202 336-2: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model". [i.8] ETSI ES 202 336-3: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards ETS 300 132-1 [2], EN 300 132-2 [i.4], EN 300 132-3 [i.5] for ac and dc interface and EN 302 099 [i.6] for access network equipment powering.

AC inverter power system: device or system that convert DC voltage to AC voltage and provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low voltage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents, tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

7 Final draft ETSI ES 202 336-10 V1.1.1 (2011-07)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected EXAMPLE: This may be a pop-up menu when the pointer is on a title button. ETSI

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 8 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 3.2 Abbreviations
  • 9 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 4 AC inverter power system
  • 10 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 11 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 12 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 13 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 14 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 15 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 16 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 17 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 18 ETSI ES 202 336-10 V1.1.1 (2011-09)

1 Scope

The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input.

The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines:

  • The monitored and controlled AC inverter power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the reference document (including any amendments) applies.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are necessary for the application of the present document. [1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI ETS 300 132-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 1: Operated by alternating current (ac) derived from direct current (dc) sources".

2.2 Informative references

The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolitan Area Network". [i.2] ISO/IEC 10164: "Information technology - Open Systems Interconnection - Systems Management:

Objects and attributes for access control".

[i.3] ISO/IEC 8879: "Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current (dc)". ETSI

6 ETSI ES 202 336-10 V1.1.1 (2011-09)

[i.5] ETSI EN 300 132-3-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 3-1: Operated by rectified current source, alternating current source or direct current (DC) source up to 400 V solution". [i.6] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.7] ETSI ES 202 336-2: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model". [i.8] ETSI ES 202 336-3: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards ETS 300 132-1 [2], EN 300 132-2 [i.4], EN 300 132-3-1 [i.5] for ac and dc interface and EN 302 099 [i.6] for access network equipment powering.

AC inverter power system: device or system that convert DC voltage to AC voltage and provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low voltage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents, tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

7 ETSI ES 202 336-10 V1.1.1 (2011-09)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected EXAMPLE: This may be a pop-up menu when the pointer is on a title button. ETSI

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 8 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 3.2 Abbreviations
  • 9 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 4 AC inverter power system
  • 10 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 11 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 12 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 13 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 14 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 15 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 16 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 17 ETSI ES 202 336-10 V1.1.1 (2011-09)
  • 18 ETSI ES 202 336-10 V1.1.1 (2011-09)

1 Scope

The present document applies to monitoring and control of AC inverter power systems for telecommunication equipment supply using 48 Vdc or 400 Vdc input.

The present document does not apply to inverters included in UPS which are covered in ES 202 336-3 [i.8]. The back-up battery connected to the inverter power system is outside the scope of the present document; they are covered in the standard dealing with the control and monitoring of DC system (ES 202 336-2 [i.7]). The present document defines:

  • The monitored and controlled AC inverter power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the reference document (including any amendments) applies.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are necessary for the application of the present document. [1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI ETS 300 132-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 1: Operated by alternating current (ac) derived from direct current (dc) sources".

2.2 Informative references

The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolitan Area Network". [i.2] ISO/IEC 10164: "Information technology - Open Systems Interconnection - Systems Management:

Objects and attributes for access control".

[i.3] ISO/IEC 8879: "Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current (dc)". ETSI

SIST ES 202 336-10 V1.1.1:2013

6 ETSI ES 202 336-10 V1.1.1 (2011-09)

[i.5] ETSI EN 300 132-3-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 3-1: Operated by rectified current source, alternating current source or direct current (DC) source up to 400 V solution". [i.6] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.7] ETSI ES 202 336-2: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model". [i.8] ETSI ES 202 336-3: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards ETS 300 132-1 [2], EN 300 132-2 [i.4], EN 300 132-3-1 [i.5] for ac and dc interface and EN 302 099 [i.6] for access network equipment powering.

AC inverter power system: device or system that convert DC voltage to AC voltage and provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low voltage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents, tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

SIST ES 202 336-10 V1.1.1:2013

7 ETSI ES 202 336-10 V1.1.1 (2011-09)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected EXAMPLE: This may be a pop-up menu when the pointer is on a title button. ETSI

SIST ES 202 336-10 V1.1.1:2013

...