kSIST prES 202 336-9 V1.1.1:2012
(Main)Environmental Engineering (EE) - Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) - Part 9: Alternative Power Systems
- Abstract
Establish a minimum set of information necessary for outdoor installations as is recognized that the full set of information request from part2 to part 8 are not applicable to outdoor installation on cabinet
- Status
- Not Published
- Technical Committee
- SPN - Services and Protocols for Networks
- Current Stage
- 5020 - Formal vote (FV) (Adopted Project)
- Start Date
- 18-Jul-2012
- Due Date
- 05-Sep-2012
- Completion Date
- 07-Sep-2012
Buy Documents
es_20233609v010101m - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 9: Alternative Power Systems
es_20233609v010101p - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 9: Alternative Power Systems
kSIST prES 202 336-9 V1.1.1:2012 is a SIST standard in the Environmental Engineering (EE) series for monitoring and control of alternative power systems used with telecommunication equipment. It specifies the minimum information that must be exchanged for systems such as solar, wind, fuel cell and external heat engine generator power systems. The document is aimed at equipment designers, integrators, operators and maintainers who need a common remote supervision interface for outdoor cabinet installations.
What does kSIST prES 202 336-9 V1.1.1:2012 specify?
kSIST prES 202 336-9 V1.1.1:2012 defines the minimum monitoring and control information for alternative power supply systems in telecommunication networks. It focuses on the information needed for outdoor cabinet installations, where the broader information set used in parts 2 to 8 is not applied in full.
The document is organized around the generic interface in part 1, then the alternative power system clause, followed by annexes that separate mandatory and optional information and the XML representation of that information.
| Annex | What it covers |
|---|---|
| A | Mandatory monitoring/supervision information and functions for solar, wind, fuel cell and external heat engine generator systems |
| B | Non-mandatory monitoring/supervision information and functions, including extra measurements and controls |
| C | Mandatory XML structure and elements for the four system types |
| D | XML examples for a solar power system |
| E | XML examples for a wind power system |
| F | XML examples for a fuel cell power system |
| G | XML examples for an external heat engine generator power system |
| H | XML examples for a solar converter |
| I | XML examples for a wind power rectifier |
| J | XML examples for a fuel cell |
| K | XML examples for an external heat engine generator rectifier |
| L | Bibliography |
What are the key requirements of kSIST prES 202 336-9 V1.1.1:2012?
Common architecture and interface model
kSIST prES 202 336-9 V1.1.1:2012 treats each alternative power system as a DC supply subsystem that feeds the telecommunication load through interface A. Clause 4 says the output is DC voltage aligned with the power supply interfaces in EN 300 132-2 or EN 300 132-3-1, or with the access-network powering arrangement in EN 302 099. In practice, this means the monitored points are tied to the DC output side, not to the internal energy source itself.
Clause 4 also says one XCU can monitor and control several power cabinets through a field bus, but the field bus is outside the scope of the document. That matters because the standard is about the information model and XML exchange, not the physical bus design.
System-specific content
Clause 4 splits the subject into four system types: solar power system, wind power system, fuel cell system and external heat engine generator power system. Each type has its own list of main elements and its own monitoring set.
- Solar systems cover solar converters, storage battery strings, DC bus protection and distribution, and an XCU.
- Wind systems cover wind rectifiers, wind machine control, storage battery strings, protection and distribution, an XCU and, for large systems, a warning light at the top of the mast.
- Fuel cell systems cover the fuel cell stack, fuel storage, converters, protection and distribution, and an XCU.
- External heat engine generator systems cover the engine, alternator and power circuit, fuel tank, cooling circuits, oil circuit, starting devices, auxiliary electrical circuits and an XCU.
In practice, this tells a designer which hardware blocks must be represented in the monitoring model for each energy source.
Mandatory information in Annex A
Annex A gives the mandatory monitoring and supervision information. For each of the four system types, the minimum set includes device description and critical alarms such as at least one converter, rectifier, fuel cell or generator failure, plus partial network failure. For the minimal set, Annex A shows no mandatory events and no mandatory data, which means the standard starts from fault reporting and identification rather than from a full measurement list.
Annex A also requires XCU alarm, event, test and command parameters where they exist, as well as XCU program download with default fallback to the previous release and default-value resetting to a safe value. In practice, this means a compliant system must support remote parameter handling and recovery functions, not just alarm reporting.
The annex notes that optional alarms requiring a parameter set make that parameter set mandatory in the control section for remote adjustment under login procedure. It also notes that if a CU is connected to a DGU over a field data bus, the DGU shall store data, and an XCU with XML interface over Ethernet TCP/IP shall store these data too.
Optional information in Annex B
Annex B adds non-mandatory information that should be provided for a common installation. It expands the supervision set with operating values such as DC bus voltage, total load current, total energy consumption, total power and capacity management ratio, plus source-specific measurements like wind speed and maximum wind speed or output current and output power.
Annex B also adds source-specific device-level items for converters, rectifiers and fuel cells, including alarms, events, data, configuration and control. In practice, this is the layer used for richer remote supervision, trending and maintenance analysis.
XML representation in Annex C
Annex C standardizes the XML structure for these data. The alternative power system appears as a child of a site energy_system element in the site DGU XML structure, and each system can also be generated as its own XML document for embedding into site.xml. Annex C also introduces the specific XML elements for the system types, such as solar-converter, wind-power-rectifier, fuel-cell and external heat engine generator-converter.
This matters because implementers need to place the monitored objects in the correct XML tree and use the right element names for interchange between XCU and DGU.
What terms does kSIST prES 202 336-9 V1.1.1:2012 define?
- alarm - Information that signals an abnormal state in hardware, software or environment, and it is meant to be understandable on its own with a severity marking.
- event - Information that signals a state change that is not an alarm, such as a battery test or a change in charge state, and it also carries severity.
- Control Unit (CU) - An integrated unit that monitors and controls equipment through sensors and actuators.
- Data Gathering Unit (DGU) - A functional unit that collects serial, digital and analog data, can send commands, and forwards information to or from the Local/Remote Management Application.
- XCU - A CU that is enabled to communicate through the XML interface defined in this document.
- XML - eXtensible Mark-up Language, used here as the structured data format for exchange between systems.
- battery string - A number of serially interconnected battery blocks or cells, used as one storage branch in the system.
Who uses kSIST prES 202 336-9 V1.1.1:2012?
kSIST prES 202 336-9 V1.1.1:2012 is used by telecom equipment manufacturers, cabinet integrators, network operators and remote monitoring software teams. They use it to define alarms, measurements, control actions and XML files for alternative power cabinets.
Quality managers and buyers can use it to check whether a proposed system exposes the expected monitoring points and control functions. Maintenance teams use it for remote fault handling, event clearing and supervision of power-source-specific parameters.
Which standards are used with kSIST prES 202 336-9 V1.1.1:2012?
| Standard | Role in this document |
|---|---|
| ETSI ES 202 336-1 | Provides the generic interface, common terms and the site XML structure used by this part |
| ETSI EN 300 132-2 | Defines the -48 V dc power supply interface referenced for the DC output side |
| ETSI EN 300 132-3-1 | Defines the dc source up to 400 V power supply interface referenced for the DC output side |
| ETSI ES 202 336-2 | Provides the DC power system control and monitoring information model used for DC power system elements |
| ETSI ES 202 336-11 | Provides the battery systems control and monitoring information model used for battery systems |
| ETSI EN 302 099 | Provides powering information for access network equipment |
| ETSI TR 102 532 | Gives background on the use of alternative energy sources in telecommunication installations |
| IEEE 802.1 to 802.11 | Source cited for Ethernet |
| ISO/IEC 8879 | SGML basis referenced for XML |
What does the kSIST prES 202 336-9 V1.1.1:2012 document contain?
The document contains clause 4 descriptions of four alternative power system types, each with the main equipment blocks and the kinds of measurements and controls used for supervision. It also contains Annex A and Annex B tables that separate mandatory and optional monitoring information for solar, wind, fuel cell and external heat engine generator systems.
Annex C gives the mandatory XML tree structures and the specific elements for each system type. Annexes D to K provide worked XML examples for descriptions, alarms, events, data, config and control elements, including device-level examples for solar converters, wind rectifiers, fuel cells and external heat engine generator converters.
The examples are useful for implementation work, because they show how the data items are expected to appear in XML files rather than only naming the items in prose. Annex L gives the bibliography.
Buy Documents
es_20233609v010101m - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 9: Alternative Power Systems
es_20233609v010101p - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 9: Alternative Power Systems
Get Certified
Connect with accredited certification bodies for this standard

ANCE
Mexican certification and testing association.

IMP NDT d.o.o.
Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

Inštitut za kovinske materiale in tehnologije
Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.
Sponsored listings
Frequently Asked Questions
kSIST prES 202 336-9 V1.1.1:2012 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE) - Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) - Part 9: Alternative Power Systems". This standard covers: Establish a minimum set of information necessary for outdoor installations as is recognized that the full set of information request from part2 to part 8 are not applicable to outdoor installation on cabinet
Establish a minimum set of information necessary for outdoor installations as is recognized that the full set of information request from part2 to part 8 are not applicable to outdoor installation on cabinet
kSIST prES 202 336-9 V1.1.1:2012 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.
kSIST prES 202 336-9 V1.1.1:2012 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 References
- 2.1 Normative references
- 2.2 Informative references
- 8 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 3 Definitions and abbreviations
- 3.1 Definitions
- 9 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 10 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 3.2 Abbreviations
- 11 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 4 Alternative power system
- 12 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 13 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 14 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 4.4 External heat engine generator power system
- 15 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 16 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 17 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 18 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 19 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 20 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 21 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 22 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 23 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 24 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 25 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 26 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 27 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 28 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 29 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 30 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 31 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 32 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 33 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 34 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 35 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 36 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 37 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 38 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 39 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 40 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 41 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 42 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 43 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 44 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 45 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 46 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 47 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 48 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 49 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 50 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 51 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- 52 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- Bibliography
- 53 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
1 Scope
The present document applies to monitoring and control of alternative power supply systems for telecommunication equipment. The alternative power systems may include solar power system, wind power system, fuel cell system, external heat engine generator system, etc.
This multi-part deliverable defines:
- The monitored and controlled alternative power supply system architectures.
- The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
- The XML files with tags and variables corresponding to the data in the tables.
2 References
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity.
2.1 Normative references
The following referenced documents are necessary for the application of the present document. [1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".
[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current (dc)". [3] ETSI EN 300 132-3-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V; Sub-part 1: Direct current source up to 400 V".
[4] ETSI ES 202 336-2: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model".
2.2 Informative references
The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area.
[i.1] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.2] ETSI TR 102 532: "Environmental Engineering (EE) The use of alternative energy sources in telecommunication installations".
ETSI
8 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
[i.3] ETSI ES 202 336-11: "Environmental engineering (EE) Monitoring and Control Interface for infrastructure equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks). Part 11: Battery systems control and monitoring information model".
[i.4] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolitan Area Network". [i.5] ISO/IEC 8879: "Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".
[i.6] ISO/IEC 10164: "Information technology - Open Systems Interconnection - Systems Management:
Objects and attributes for access control".
3 Definitions and abbreviations
3.1 Definitions
For the purposes of the present document, the following terms and definitions apply:
NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [2], EN 300 132-3-1 [3] for ac and dc interface and EN 302 099 [i.1] for access network equipment powering.
alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).
EXAMPLE: Rectifier failure, battery low voltage, etc.
alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to web documents. Tutorials, books, mailing lists for users, etc.
Data Gathering Unit (DGU): functional unit used for several functions:
- collect serial, digital, and analog data from several equipment;
- option to send (output) serial or digital commands;
- forward/receive information to/from the Local/Remote Management Application via agreed protocols; ETSI
9 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
- mediation between interfaces and protocols.
NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.
Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment Ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to 11 [i.4].
event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.5]) documents. XML is designed to describe data and focus on what data is. XML is discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.
eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.
infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations NOTE: Examples of the infrastructure equipment are cabinets, shelters, underground locations, etc. intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.
object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.
PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. ETSI
10 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
Representational State Transfer (REST): way to build an application for distributed system as www Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.6]. warning: low severity alarm web: common name for the Internet or Intranet windows: virtual area on the display that corresponds to a specific application World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.
XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C definition) XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD
3.2 Abbreviations
For the purposes of the present document, the following abbreviations apply:
AC Alternative Current ASCII American Standard Code for Information Interchange CU Control Unit of an equipment CUE Current Using Equipment DC Direct Current DGU Data Gathering Unit HTML Hypertext Transfer Make-up Language HTTP HyperText Transfer Protocol IP Internet Protocol LAN Local Array Network LMA Local Management Application LVD Low Voltage Disconnection M&C Monitoring and Control MCB Miniature Circuit Breaker MMC Maintenance Mobile Client MN Management Network MPPT Maximum Power Point Tracking PLC Programmable Logic Controller PV Photovoltaic RB Rectifier Battery RMA Remote Management Application SMN System Management Network SPD Surging Protection Device SU Service Unit TCP Transmission Control Protocol for IP TMN Telecommunications Management Network UPS Uninterruptible Power Supply URL Uniform Resource Locator XCU XML enabled CU ETSI
11 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
XML eXtensible Markup Language
4 Alternative power system
The alternative power system subset described in ES 202 336-1 [1] transforms alternative energy source into DC voltage on interface A defined in EN 300 132-2 [2] or EN 300 132-3-1 [3] for telecom center or defined for local or remote power supply of access network equipment in EN 302 099 [i.1]. The alternative power systems may includes solar-power system, wind-power system, fuel cell system external heat engine generator system, etc., referenced in TR 102 532 [i.2]. One single control unit XCU can monitor and control several power cabinets through field bus. Field bus is outside the scope of the present document. 4.1 solar power system This clause defines solar power systems. One example is depicted in figure 1.
Figure 1: Example of solar power system with storage battery The main elements of solar power systems are:
- One or more solar converters that convert DC voltage to DC voltage and control the battery charge in voltage and current. These DC/DC can have a Maximum Power Point Tracking function (MPPT).
- One or more storage battery strings.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, send alarms and provide system control functionality.
Several measurements are possible: converter states (normal/abnormal operation), converter input and output voltages and currents, temperature (battery, ambient), load currents, protective devices states, etc. In option solar energy measurement can be proposed.
ETSI
12 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
Several controls are possible to adjust converter voltage and current, to optimize the load between converters for energy saving and higher reliability.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.1 corresponds to mandatory data that shall be provided for a minimal solar power system. Table B.1 corresponds to non mandatory data that shall be provided for a common solar power system, and Table B.5 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.2 wind power system This clause defines wind power systems . One example is depicted in figure 2.
Figure 2: Example of a modular wind power system with storage battery The main elements of wind power systems are:
- One or more wind rectifiers that convert AC voltage to DC voltage, or control the battery charge in voltage and current. These AC/DC can have a function to track the maximum possible power at a given wind speed.
- Wind machine control (speed limitation including ballast load or mechanical brake, turbine orientation, pitch control, etc.).
- One or more storage battery strings.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, send alarms and provide system control functionality.
- Warning light at top of mast for large system.
ETSI
13 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
Several measurements are possible: rectifiers states (normal/abnormal operation), rectifiers input and output voltages and currents, temperature (battery, ambient), load currents, protective devices states. In option wind measurement can be proposed.
Several controls are possible to adjust rectifier voltage and current, to optimize the load between rectifiers for energy saving and higher reliability.
NOTE: The AC input form wind turbine to wind AC/DC rectifier varies both in frequency and voltage much more than AC grid.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.2 corresponds to mandatory data that shall be provided for a minimal wind power system. Table B.2 corresponds to non mandatory data that shall be provided for a common wind power system, and table B.6 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.3 fuel cell system This clause defines the fuel cell systems . One example is depicted in figure 3.
Figure 3: Example or fuel cell system The main elements of fuel cell systems are:
- Fuel cell stack and management (including a heater to avoid internal water temperature falling below 0 °C, fans, filters, compressors, automatic valves, control unit that can be common with the XCU, etc.).
- A fuel storage made with bottle of Hydrogen, or hydride storage, or methanol + reformer, etc.
- One or more converters that convert fuel cell DC voltage to required DC voltage.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature, fuel level etc., send alarms and provide system control functionality.
- Several measurements are possible: converter states, converter voltage and current, temperature, user load currents, etc.
Several controls are possible to adjust converter voltage and current, to optimize the load between converters for energy saving and higher reliability.
ETSI
14 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.3 corresponds to mandatory data that shall be provided for a minimal fuel cell system. Table B.3 corresponds to non mandatory data that shall be provided for a common fuel cell system, and table B.7 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.4 External heat engine generator power system
This clause defines the external heat engine generator power systems. One example is depicted in figure 4. NOTE: The external heat engine generator is a system based on a motor using heat from external combustion burner or solar concentrator.
Figure 4: Example of external heat engine generator power system The main elements of external heat engine generator systems are:
- Engine (speed control, temperature, safety circuitry).
- Alternator and power circuit (voltage, frequency, current).
- Fuel tank and supply to the engine.
- Water and air cooling circuit (fluid temperature, levels, circulation pumps, air, louvers, fans control).
- Oil circuit (pressure, levels, preheating).
- Starting devices system (battery voltage, starting speed, battery charger).
- Electrical auxiliary circuit (auxiliary protection devices, power contactors).
- A system monitoring and control unit (XCU) to monitor the generator, extend alarms and provide system control functionality.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.4 corresponds to mandatory data that shall be provided for a minimal external heat engine generator system. Table B.4 corresponds to non mandatory data that shall be provided for a common external heat engine generator system, and table B.8 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
ETSI
15 Final draft ETSI ES 202 336-9 V1.1.1 (2012-07)
Annex A (normative):
Summary of mandatory monitoring / supervision information and functions This annex gathers the information needed on the remote monitoring application for different types of power supplies. It specifies the mandatory requirements that shall be provided in all cases. NOTE: These tables do not specify the power equipment by itself. These tables refer to subsets or devices that are not necessarily present in each equipment configuration. As a matter of fact, one alarm and its class apply only in case of the presence of this subset or device.
...
Contents
- 1 Scope
- 2 References
- 2.1 Normative references
- 2.2 Informative references
- 8 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 3 Definitions and abbreviations
- 3.1 Definitions
- 9 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 3.2 Abbreviations
- 10 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 4 Alternative power system
- 11 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 12 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 13 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 4.4 External heat engine generator power system
- 14 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 15 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 16 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 17 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 18 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 19 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 20 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 21 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 22 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 23 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 24 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 25 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 26 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 27 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 28 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 29 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 30 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 31 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 32 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 33 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 34 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 35 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 36 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 37 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 38 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 39 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 40 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 41 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 42 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 43 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 44 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 45 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 46 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 47 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 48 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 49 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 50 ETSI ES 202 336-9 V1.1.1 (2012-09)
- 51 ETSI ES 202 336-9 V1.1.1 (2012-09)
- Bibliography
- 52 ETSI ES 202 336-9 V1.1.1 (2012-09)
1 Scope
The present document applies to monitoring and control of alternative power supply systems for telecommunication equipment. The alternative power systems may include solar power system, wind power system, fuel cell system, external heat engine generator system, etc.
This multi-part deliverable defines:
- The monitored and controlled alternative power supply system architectures.
- The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
- The XML files with tags and variables corresponding to the data in the tables.
2 References
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long term validity.
2.1 Normative references
The following referenced documents are necessary for the application of the present document. [1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".
[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 2: Operated by -48 V direct current (dc)". [3] ETSI EN 300 132-3-1: "Environmental Engineering (EE); Power supply interface at the input to telecommunications and datacom (ICT) equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V; Sub-part 1: Direct current source up to 400 V".
[4] ETSI ES 202 336-2: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model".
2.2 Informative references
The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area.
[i.1] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.2] ETSI TR 102 532: "Environmental Engineering (EE) The use of alternative energy sources in telecommunication installations".
ETSI
8 ETSI ES 202 336-9 V1.1.1 (2012-09)
[i.3] ETSI ES 202 336-11: "Environmental engineering (EE) Monitoring and Control Interface for infrastructure equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks). Part 11: Battery systems control and monitoring information model".
[i.4] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolitan Area Network". [i.5] ISO/IEC 8879: "Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".
3 Definitions and abbreviations
3.1 Definitions
For the purposes of the present document, the following terms and definitions apply:
NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [2], EN 300 132-3-1 [3] for ac and dc interface and EN 302 099 [i.1] for access network equipment powering.
alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).
EXAMPLE: Rectifier failure, battery low voltage, etc.
alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators Data Gathering Unit (DGU): functional unit used for several functions:
- collect serial, digital, and analog data from several equipment;
- option to send (output) serial or digital commands;
- forward/receive information to/from the Local/Remote Management Application via agreed protocols;
- mediation between interfaces and protocols.
NOTE: This function may be integrated as part of specific equipment. Dynamic Name Server (DNS): associates a single domain name to an IP address Ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to 11 [i.4].
event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". ETSI
9 ETSI ES 202 336-9 V1.1.1 (2012-09)
eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.5]) documents. XML is designed to describe data and focus on what data is. XML is discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.
infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations NOTE: Examples of the infrastructure equipment are cabinets, shelters, underground locations, etc. intranet: internal company network generally using Ethernet protocol and extended IP addresses menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.
object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.
pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. warning: low severity alarm web: common name for the Internet or Intranet World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.
XCU: CU enabled to communicate using XML interface as defined in the present document
3.2 Abbreviations
For the purposes of the present document, the following abbreviations apply:
AC Alternative Current CU Control Unit of an equipment DC Direct Current DGU Data Gathering Unit DNS Dynamic Name Server HTML Hypertext Transfer Make-up Language HTTP HyperText Transfer Protocol IP Internet Protocol LAN Local Array Network LVD Low Voltage Disconnection MPPT Maximum Power Point Tracking PV Photovoltaic SPD Surging Protection Device TCP Transmission Control Protocol for IP W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Mark-up Language ETSI
10 ETSI ES 202 336-9 V1.1.1 (2012-09)
4 Alternative power system
The alternative power system subset described in ES 202 336-1 [1] transforms alternative energy source into DC voltage on interface A defined in EN 300 132-2 [2] or EN 300 132-3-1 [3] for telecom center or defined for local or remote power supply of access network equipment in EN 302 099 [i.1]. The alternative power systems may includes solar-power system, wind-power system, fuel cell system external heat engine generator system, etc., referenced in TR 102 532 [i.2]. One single control unit XCU can monitor and control several power cabinets through field bus. Field bus is outside the scope of the present document. 4.1 solar power system This clause defines solar power systems. One example is depicted in figure 1.
Figure 1: Example of solar power system with storage battery The main elements of solar power systems are:
- One or more solar converters that convert DC voltage to DC voltage and control the battery charge in voltage and current. These DC/DC can have a Maximum Power Point Tracking function (MPPT).
- One or more storage battery strings.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, send alarms and provide system control functionality.
Several measurements are possible: converter states (normal/abnormal operation), converter input and output voltages and currents, temperature (battery, ambient), load currents, protective devices states, etc. In option solar energy measurement can be proposed.
Several controls are possible to adjust converter voltage and current, to optimize the load between converters for energy saving and higher reliability.
ETSI
11 ETSI ES 202 336-9 V1.1.1 (2012-09)
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.1 corresponds to mandatory data that shall be provided for a minimal solar power system. Table B.1 corresponds to non mandatory data that shall be provided for a common solar power system, and Table B.5 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.2 wind power system This clause defines wind power systems . One example is depicted in figure 2.
Figure 2: Example of a modular wind power system with storage battery The main elements of wind power systems are:
- One or more wind rectifiers that convert AC voltage to DC voltage, or control the battery charge in voltage and current. These AC/DC can have a function to track the maximum possible power at a given wind speed.
- Wind machine control (speed limitation including ballast load or mechanical brake, turbine orientation, pitch control, etc.).
- One or more storage battery strings.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, send alarms and provide system control functionality.
- Warning light at top of mast for large system.
Several measurements are possible: rectifiers states (normal/abnormal operation), rectifiers input and output voltages and currents, temperature (battery, ambient), load currents, protective devices states. ETSI
12 ETSI ES 202 336-9 V1.1.1 (2012-09)
In option wind measurement can be proposed.
Several controls are possible to adjust rectifier voltage and current, to optimize the load between rectifiers for energy saving and higher reliability.
NOTE: The AC input form wind turbine to wind AC/DC rectifier varies both in frequency and voltage much more than AC grid.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.2 corresponds to mandatory data that shall be provided for a minimal wind power system. Table B.2 corresponds to non mandatory data that shall be provided for a common wind power system, and table B.6 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.3 fuel cell system This clause defines the fuel cell systems . One example is depicted in figure 3.
Figure 3: Example or fuel cell system The main elements of fuel cell systems are:
- Fuel cell stack and management (including a heater to avoid internal water temperature falling below 0 °C, fans, filters, compressors, automatic valves, control unit that can be common with the XCU, etc.).
- A fuel storage made with bottle of Hydrogen, or hydride storage, or methanol + reformer, etc.
- One or more converters that convert fuel cell DC voltage to required DC voltage.
- Protection and distribution (DC bus, circuit breaker, …) to power different loads and discriminate faults.
- A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature, fuel level etc., send alarms and provide system control functionality.
- Several measurements are possible: converter states, converter voltage and current, temperature, user load currents, etc.
Several controls are possible to adjust converter voltage and current, to optimize the load between converters for energy saving and higher reliability.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
ETSI
13 ETSI ES 202 336-9 V1.1.1 (2012-09)
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.3 corresponds to mandatory data that shall be provided for a minimal fuel cell system. Table B.3 corresponds to non mandatory data that shall be provided for a common fuel cell system, and table B.7 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
4.4 External heat engine generator power system
This clause defines the external heat engine generator power systems. One example is depicted in figure 4. NOTE: The external heat engine generator is a system based on a motor using heat from external combustion burner or solar concentrator e.g. Robert Stirling or John Ericsson machine.
Figure 4: Example of external heat engine generator power system The main elements of external heat engine generator systems are:
- Engine (speed control, temperature, safety circuitry).
- Alternator and power circuit (voltage, frequency, current).
- Fuel tank and supply to the engine.
- Water and air cooling circuit (fluid temperature, levels, circulation pumps, air, louvers, fans control).
- Oil circuit (pressure, levels, preheating).
- Starting devices system (battery voltage, starting speed, battery charger).
- Electrical auxiliary circuit (auxiliary protection devices, power contactors).
- A system monitoring and control unit (XCU) to monitor the generator, extend alarms and provide system control functionality.
For element of DC power systems that are used in alternative power systems, the information table model of DC system control monitoring ES 202 336-2 [4] shall be used.
For battery systems, the information table model ES 202 336-11 [i.3] under preparation should be used. Table A.4 corresponds to mandatory data that shall be provided for a minimal external heat engine generator system. Table B.4 corresponds to non mandatory data that shall be provided for a common external heat engine generator system, and table B.8 includes data that should be provided in addition to mandatory one. Annex C standardizes XML coding structures for these data.
ETSI
14 ETSI ES 202 336-9 V1.1.1 (2012-09)
Annex A (normative):
Summary of mandatory monitoring / supervision information and functions This annex gathers the information needed on the remote monitoring application for different types of power systems. It specifies the mandatory requirements that shall be provided in all cases. NOTE 1: These tables do not specify the power equipment by itself. These tables refer to subsets or devices that are not necessarily present in each equipment configuration. As a matter of fact, one alarm and its class apply only in case of the presence of this subset or device.
When an optional alarm that requires a parameter set is present, the corresponding parameter set is mandatory in the control section in order to allow remote adjustment under appropriate login procedure. According to their types (Description, Alarm, Data, etc.), as defined in ES 202 336-1 [1] the information shall be provided by the Control Unit (XCU).
NOTE 2: If there is no XCU this data can be provided by the Data Gathering Unit (DGU). When a CU has a field data bus connected to the DGU, at least, the DGU shall store data (record measurements, log files).The XCU which has the XML interface over Ethernet TCP/IP, shall store these data. A.1 Table for solar power system Table A.1 Type Monitored information Explanation description Device description alarm One solar converter failure at least Partial network failure (high error rate, XCU-DGU link fault, etc) event None data None data record None config None All XCU alarm/event/test/command parameters (time-out, counter, thresholds, …) if any control XCU program download with default to previous release Default values resetting (safe value for XCU) NOTE: The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1].
ETSI
15 ETSI ES 202 336-9 V1.1.1 (2012-09)
A.2 Table for wind power system Table A.2 Type Monitored information Explanation description Device description One wind rectifier failure at least
Partial network failure (high error rate, XCU-DGU link fault, etc) event None data None data record None config None All XCU alarm/event/test/command parameters (time-out, counter, thresholds, …) if any control XCU program download with default to previous release Default values resetting (safe value for XCU) NOTE: The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1].
A.3 Table for fuel cell power system Table A.3 Type Monitored information Explanation description Device description One fuel cell failure at least
Partial network failure (high error rate, XCU-DGU link fault, etc.) event None data None data record None config None All XCU alarm/event/test/command parameters (time-out, counter, thresholds, etc.) if any control XCU program download with default to previous release Default values resetting (safe value for XCU) NOTE: The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1].
A.4 Table for external heat engine generator power system Table A.4 Type Monitored information Explanation description Device description alarm One external heat engine generator failure at least Partial network failure (high error rate, XCU-DGU link fault, etc) event None data None data record None config None All XCU alarm/event/test/command parameters (time-out, counter, thresholds, …) if any control XCU program download with default to previous release Default values resetting (safe value for XCU) NOTE: The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1].
ETSI
16 ETSI ES 202 336-9 V1.1.1 (2012-09)
Annex B (informative):
...