SIST ETS 300 019-1-8 E1:2006
(Main)Equipment Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations
- Abstract
The purpose of this sub-part of this standard is to define the classes of environmental conditions and their severities to which equipment may be exposed at specified locations below ground level. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. This sub-part applies to equipment installed for stationary use at underground locations during:
- normal operation;
- on site installation and lining up;
- repair, maintenance and restoration of functions failed.
- Status
- Published
- Publication Date
- 31-Jan-2006
- Withdrawal Date
- 30-Sep-2003
- Technical Committee
- RES - Radio equipment and systems
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 01-Feb-2006
- Due Date
- 01-Feb-2006
- Completion Date
- 01-Feb-2006
SIST ETS 300 019-1-8 E1:2006 is the Slovenian adoption of ETS 300 019-1-8 Edition 1 from ETSI. It classifies environmental conditions and severities for telecommunications equipment used at underground locations, with a focus on stationary equipment during operation, installation, maintenance, repair, and restoration.
What does SIST ETS 300 019-1-8 E1:2006 specify?
SIST ETS 300 019-1-8 E1:2006 specifies the environmental class for stationary use at underground locations and the severities associated with that class. It is written for places below ground level where equipment is normally protected from direct weather, but may still face humidity, dust, contamination, vibration, shock, and earthquake effects.
| Clause | What it covers |
|---|---|
| 1 | Scope |
| 2 | Normative references |
| 3 | Definitions and abbreviations |
| 4 | Environmental class |
| 5 | Environmental conditions |
Clause 4 defines Class 8.1: Partly weatherprotected underground locations. Clause 5 then sets out the environmental parameters for climate, biology, chemically active substances, mechanically active substances, mechanical conditions, and earthquake conditions.
What are the key requirements of SIST ETS 300 019-1-8 E1:2006?
SIST ETS 300 019-1-8 E1:2006 gives a single environmental class, but it is detailed enough to guide both site specification and test planning. The main practical point is to match equipment design and verification to the actual underground environment, rather than to a generic indoor or outdoor class.
Class 8.1 and where it applies
Clause 4 says Class 8.1 applies to partly weatherprotected underground locations. In practice, this means places such as footway boxes, manholes, and some tunnels where direct weather is reduced but not eliminated. The class also assumes low-significance vibration and shock, normal urban contamination, and possible short-term immersion in water under exceptional conditions.
Climate and biological exposure
Clause 5.1 lists the climatic parameters for Class 8.1, including temperature range, humidity, air pressure, temperature change, condensation, icing, and exposure to heat radiation. Clause 5.2 covers biological conditions such as mould, fungus, rodents, and other harmful animals, while excluding termites. For users, this means enclosure materials, sealing, ventilation, and internal layout must suit damp, variable underground conditions.
Chemical and particulate exposure
Clause 5.3 gives severities for airborne contaminants such as sea salts, road salts, sulphur dioxide, hydrogen sulphide, chlorine, hydrogen chloride, hydrogen fluoride, ammonia, ozone, and nitrogen oxide. It also notes that the special chemical class 3C3 may be selected for more severe chemical exposure. Clause 5.4 sets levels for sand and dust. In practice, this helps decide corrosion protection, filtering, gasketing, and whether a more severe chemical class is needed near industrial sources.
Mechanical and seismic effects
Clause 5.5 defines stationary vibration and non-stationary vibration including shock, and refers to shock response spectrum types L and II. Clause 5.6 explains seismic conditions using Response Spectrum (RS) and Zero Period Acceleration (ZPA), with values for strong to very strong earthquakes and rigid mounting structures. If the support structure is not rigid, the structure should be included in testing or the RS should be corrected.
What terms does SIST ETS 300 019-1-8 E1:2006 define?
- stationary use - Equipment is permanently placed at a site, with only short handling periods accepted for erection, maintenance, or repair.
- totally weatherprotected location - A location where direct weather influences are fully excluded.
- partly weatherprotected location - A location where direct weather influences are not completely excluded.
- Response Spectrum (RS) - A graph showing the maximum response of single degree-of-freedom oscillators to transient base motion, used to describe seismic motion at the mounting point.
- Zero Period Acceleration (ZPA) - The high-frequency asymptotic value of the response spectrum, representing the largest peak acceleration of the base motion.
Who uses SIST ETS 300 019-1-8 E1:2006?
SIST ETS 300 019-1-8 E1:2006 is used by telecommunications equipment designers, manufacturers, test laboratories, installers, maintenance teams, quality managers, and buyers who need to specify or verify equipment for underground sites. It is relevant where equipment is installed in manholes, footway boxes, tunnels, or similar locations below ground level. It also helps procurement and engineering teams agree on the environmental class before design, testing, or acceptance.
What changed in SIST ETS 300 019-1-8 E1:2006 from the previous edition?
SIST ETS 300 019-1-8 E1:2006 is the first edition of this sub-part as ETS 300 019-1-8. The foreword says it supersedes the application of class 3.2 in ETS 300 019-1-3 for stationary use at underground locations.
Which standards are used with SIST ETS 300 019-1-8 E1:2006?
- ETS 300 019-1-0 - gives the general overview of Part 1.
- ETS 300 019-1-3 - provides the class 3.2 application that this sub-part supersedes for underground locations.
- ETS 300 019-2 - covers the recommended test requirements for the environmental classes.
- IEC Publication 721-3-3: Stationary use at weatherprotected locations - supplies the class combinations referenced for Class 8.1.
- IEC Publication 68-2-27: Test Ea: Shock - supports the shock terminology and the maximax shock reference.
- IEC Publication 721-2-6: Earthquake vibration and shock - defines the seismic environment zone used for Class 8.1.
- IEC Publication 68-3-3: Guidance. Seismic test methods for equipment - supports the RS and ZPA approach and the selection of seismic severities.
What does the SIST ETS 300 019-1-8 E1:2006 document contain?
The document contains a climatogram for Class 8.1, a table of climatic parameters, a table of biological conditions, a table of chemically active substances, a table of mechanically active substances, and a table for vibration and shock conditions. It also includes a section on earthquake conditions that explains RS and ZPA and gives a response spectrum figure with coordinate data. These elements are used for environmental specification, equipment design, and test planning.
Get Certified
Connect with accredited certification bodies for this standard

ANCE
Mexican certification and testing association.
IMP NDT d.o.o.
Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.
Inštitut za kovinske materiale in tehnologije
Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.
Sponsored listings
Frequently Asked Questions
SIST ETS 300 019-1-8 E1:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Equipment Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations". This standard covers: The purpose of this sub-part of this standard is to define the classes of environmental conditions and their severities to which equipment may be exposed at specified locations below ground level. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. This sub-part applies to equipment installed for stationary use at underground locations during: - normal operation; - on site installation and lining up; - repair, maintenance and restoration of functions failed.
The purpose of this sub-part of this standard is to define the classes of environmental conditions and their severities to which equipment may be exposed at specified locations below ground level. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. This sub-part applies to equipment installed for stationary use at underground locations during: - normal operation; - on site installation and lining up; - repair, maintenance and restoration of functions failed.
SIST ETS 300 019-1-8 E1:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST ETS 300 019-1-8 E1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
01-februar-2006
Inženiring opreme (EE) – Okoljski pogoji in preskusi vplivov okolja na
telekomunikacijsko opremo – 1-8. del: : Klasifikacija okoljskih pogojev – Fiksna
uporaba na podzemnih lokacijah
Equipment Engineering (EE); Environmental conditions and environmental tests for
telecommunications equipment; Part 1-8: Classification of environmental conditions;
Stationary use at underground locations
Ta slovenski standard je istoveten z: ETS 300 019-1-8 Edition 1
ICS:
19.040 Preskušanje v zvezi z Environmental testing
okoljem
33.050.01 Telekomunikacijska Telecommunication terminal
terminalska oprema na equipment in general
splošno
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN ETS 300 019-1-8
TELECOMMUNICATION September 1997
STANDARD
Source: EE Reference: DE/EE-01019-1-8
ICS: 33.020
Key words: Environment, testing, underground
Equipment Engineering (EE);
Environmental conditions and environmental tests for
telecommunications equipment;
Part 1-8: Classification of environmental conditions
Stationary use at underground locations
ETSI
European Telecommunications Standards Institute
ETSI Secretariat
Postal address: F-06921 Sophia Antipolis CEDEX - FRANCE
Office address: 650 Route des Lucioles - Sophia Antipolis - Valbonne - FRANCE
X.400: c=fr, a=atlas, p=etsi, s=secretariat - Internet: secretariat@etsi.fr
Tel.: +33 4 92 94 42 00 - Fax: +33 4 93 65 47 16
Copyright Notification: No part may be reproduced except as authorized by written permission. The copyright and the
foregoing restriction extend to reproduction in all media.
© European Telecommunications Standards Institute 1997. All rights reserved.
Page 2
ETS 300 019-1-8: September 1997
Whilst every care has been taken in the preparation and publication of this document, errors in content,
typographical or otherwise, may occur. If you have comments concerning its accuracy, please write to
"ETSI Editing and Committee Support Dept." at the address shown on the title page.
Page 3
ETS 300 019-1-8: September 1997
Contents
Foreword .5
1 Scope .7
2 Normative references.7
3 Definitions and abbreviations .7
3.1 Definitions .7
3.2 Abbreviations .7
4 Environmental class .8
4.1 Class 8.1: Partly weatherprotected underground locations .8
5 Environmental conditions .10
5.1 Climatic conditions.10
5.2 Biological conditions .10
5.3 Chemically active substances.11
5.4 Mechanically active substances.11
5.5 Mechanical conditions.12
5.6 Earthquake conditions .12
History.15
Page 4
ETS 300 019-1-8: September 1997
Blank page
Page 5
ETS 300 019-1-8: September 1997
Foreword
This multi-part European Telecommunication Standard (ETS) has been produced by the Equipment
Engineering (EE) Technical Committee of the European Telecommunications Standards Institute (ETSI).
This ETS consists of 2 parts as follows:
Part 1: "Classification of environmental conditions";
Part 2: "Specification of environmental tests".
Part 1 specifies different standardized environmental classes covering climatic and biological conditions,
chemically and mechanically active substances and mechanical conditions during storage, transportation
and in use.
Part 2 specifies the recommended test requirements for the different environmental classes.
Each part of the standard is divided into sub-parts. Sub-part 1-0 forms a general overview of part 1. This
sub-part 1-8, deals with stationary use at underground locations and supersedes the application of
class 3.2 in ETS 300 019-1-3 for such locations.
Transposition dates
Date of adoption: 5 September 1997
Date of latest announcement of this ETS (doa): 31 December 1997
Date of latest publication of new National Standard
or endorsement of this ETS (dop/e): 30 June 1998
Date of withdrawal of any conflicting National Standard (dow): 30 June 1998
Page 6
ETS 300 019-1-8: September 1997
Blank page
Page 7
ETS 300 019-1-8: September 1997
1 Scope
The purpose of this sub-part of this standard is to define the classes of environmental conditions and their
severities to which equipment may be exposed at specified locations below ground level. The severities
specified are those which will have a low probability of being exceeded; generally less than 1 %.
This sub-part applies to equipment installed for stationary use at underground locations during:
- normal operation;
- on site installation and lining up;
- repair, maintenance and restoration of functions failed.
2 Normative references
This ETS incorporates by dated and undated reference, provisions from other publications. These
normative references are cited at the appropriate places in the text and the publications are listed
hereafter. For dated references, subsequent amendments to or revisions of any of these publications
apply to this ETS only when incorporated in it by amendment or revision. For undated references the latest
edition of the publication referred to applies.
[1] [reserved]
[2] [reserved]
[3] IEC Publication 721-3-3: "Stationary use at weatherprotected locations".
[4] IEC Publication 68-2-27: "Test Ea: Shock".
[5] IEC Publication 721-2-6: "Earthquake vibration and shock".
[6] IEC Publication 68-3-3: "Guidance. Seismic test methods for equipment".
3 Definitions and abbreviations
3.1 Definitions
For the purposes of this ETS, the following definitions apply:
stationary use: The equipment is permanently placed at a certain site. It is not intended for portable use
but short periods of handling during erection work, down time, maintenance and repair at the location are
accepted.
totally weatherprotected location: Direct weather influences are totally excluded.
partly weatherprotected location: Direct weather influences are not completely excluded.
3.2 Abbreviations
For the purposes of this ETS, the following abbreviations apply:
RS Response Spectrum
ZPA Zero Period Acceleration
Page 8
ETS 300 019-1-8: September 1997
4 Environmental class
4.1 Class 8.1: Partly weatherprotected underground locations
At present no underground classes in IEC 721 Publication series exist.
This class is a combination of classes 3Z7/3B2/3C2(3C3)/3S3/3M3(3M5) in IEC Publication 721-3-3 [3].
No IEC Publication 721-3-3 [3] climatic class is applicable.
Seismic environment: zone 4 as defined in IEC Publication 721-2-6 [5].
Option zone 4 (modified Mercalli scale ≥ 9): if earthquake conditions are specified by the customer, the
conditions stated in subclause 5.6 apply.
This class applies to partly weatherprotected underground locations. The location has no temperature or
humidity control, but the variations in the temperature are limited due to the stabilizing influence of the
surroundings.
The climatogram is shown in figure 1.
This class applies to locations:
- where the installed equipment is normally protected from direct weather influences;
- where the surrounding medium is normally air, but the equipment may be immersed in water during
exceptional conditions;
- where mould growth or attacks by animals, except termites, may occur;
- with nor
...