ISO 10094-2:2021
(Main)Pneumatic fluid power - Electro-pneumatic pressure control valves - Part 2: Test methods to determine main characteristics to include in the supplier's literature
Pneumatic fluid power - Electro-pneumatic pressure control valves - Part 2: Test methods to determine main characteristics to include in the supplier's literature
This document specifies the test procedures and a method of presenting results concerning the parameters which define the main characteristics to be included in the supplier's literature of the electro-pneumatic continuous pressure control valves, conforming to ISO 10094-1. The purpose of this document is: - to facilitate comparison by standardizing the test methods and the presentation of the test results, and - to assist in the proper application of these components in compressed air systems. The specified tests are intended to allow comparison between the different types of continuous pressure control valves; these are not production tests to be carried out on each manufactured product. The tests described in this document are for components with an exhaust port vented to the atmosphere. NOTE 1 The tests related to non-electrically modulated pneumatic continuous pressure control valves are specified in ISO 6953-2. NOTE 2 The tests related to electro-pneumatic continuous flow control valves are specified in ISO 10041-2. NOTE 3 ISO 6953-3 provides an alternate dynamic test method for flow-rate characteristics using an isothermal tank instead of a flow meter. However, this method measures only the decreasing flow rate part of the hysteresis curve of the forward flow and relief flow characteristics.
Transmissions pneumatiques — Appareils électropneumatiques de distribution à commande continue de pression — Partie 2: Méthodes d'essai pour déterminer les principales caractéristiques à inclure dans la documentation des fournisseurs
Le présent document spécifie les modes opératoires d'essai et donne une méthode de présentation des résultats relatifs aux paramètres qui définissent les principales caractéristiques à inclure dans la documentation des fournisseurs d'appareils électropneumatiques de distribution à commande continue de pression conformes à l'ISO 10094‑1. Le but du présent document est: — de faciliter la comparaison en normalisant les méthodes d'essai et la présentation des résultats d'essais, et — d'apporter une aide afin que ces composants soient correctement utilisés dans les systèmes d'air comprimé. Les essais spécifiés ont pour but de permettre la comparaison entre les différents types d'appareils de distribution à commande continue de pression; il ne s'agit en aucun cas d'essais de production à effectuer pour chaque produit fabriqué. Les essais décrits dans le présent document sont réalisés pour des composants ayant un orifice d'échappement vers l'atmosphère. NOTE 1 Les essais concernant les appareils pneumatiques de distribution à commande continue de pression qui ne sont pas modulés électriquement sont spécifiés dans l'ISO 6953‑2. NOTE 2 Les essais concernant les distributeurs électropneumatiques à commande continue de débit sont spécifiés dans l'ISO 10041‑2. NOTE 3 L'ISO 6953‑3 fournit une méthode d'essai dynamique alternative pour les caractéristiques de débit utilisant un réservoir isotherme au lieu d'un débitmètre. Toutefois, cette méthode permet d’obtenir uniquement la partie de la courbe d’hystérésis des caractéristiques de débit d’alimentation et de débit d’échappement correspondant à des débits décroissants.
General Information
- Status
- Published
- Publication Date
- 21-Nov-2021
- Technical Committee
- ISO/TC 131/SC 5 - Control products and components
- Drafting Committee
- ISO/TC 131/SC 5/WG 3 - Pneumatic control products
- Current Stage
- 6060 - International Standard published
- Start Date
- 22-Nov-2021
- Due Date
- 29-Nov-2021
- Completion Date
- 22-Nov-2021
Relations
- Effective Date
- 12-Aug-2017
Overview
ISO 10094-2:2021 is an international standard in the pneumatic fluid power series that specifies test methods and a standardized presentation of results for electro‑pneumatic continuous pressure control valves. It defines the procedures to determine the main characteristics that manufacturers should include in the supplier’s literature for valves that conform to ISO 10094-1. The tests are intended to facilitate comparison between valve types and to assist correct application in compressed air systems. These tests apply to components with an exhaust port vented to atmosphere and are not intended as routine production inspections.
Key topics and requirements
- Scope and test conditions: Requirements for gas supply, temperature, inlet and test pressures, and electrical supply conditions to ensure repeatable measurements.
- Static characteristics:
- Control signal vs. pressure at null forward or relief flow
- Flow-rate vs. pressure characteristics (forward and relief)
- Leakage at null flow
- Pressure regulation behaviour under specified loads
- Dynamic characteristics:
- Step response tests (charge/discharge) to determine response time, settling time and shifting time
- Frequency response (informative annex) and procedures for gain/phase calculation
- Performance metrics and calculations:
- Characteristic curves, hysteresis, linearity, resolution, repeatability, sensitivity, offset, and sonic conductance
- Test installation and circuits: Standardized test circuits and measurement points for pressure, flow and electrical inputs to ensure comparable data.
- Presentation of results: Prescribed formats and curves for inclusion in supplier’s literature to allow direct comparison by specifiers and purchasers.
Applications and users
ISO 10094-2:2021 is most useful for:
- Valve manufacturers preparing technical datasheets and supplier literature
- Independent test laboratories performing compliance and comparative testing
- System designers and pneumatic engineers selecting electro‑pneumatic pressure control valves
- Procurement and specification writers who require standardized performance data
- Quality and R&D teams validating valve performance and dynamic behaviour
Practical benefits include clearer product comparisons, improved selection for pressure tracking and regulation tasks, and better integration of valves into compressed air and pneumatic control systems.
Related standards
- ISO 10094-1 - product definitions and basic requirements for electro‑pneumatic pressure control valves (conformance reference)
- ISO 6953-2 - tests for non‑electrically modulated pneumatic continuous pressure control valves
- ISO 10041-2 - tests for electro‑pneumatic continuous flow control valves
- ISO 6953-3 - alternate dynamic test method (isothermal tank) - measures specific hysteresis behaviour
Keywords: ISO 10094-2:2021, electro‑pneumatic pressure control valves, pneumatic fluid power, test methods, supplier’s literature, static characteristics, dynamic response, leakage, hysteresis.
ISO 10094-2:2021 - Pneumatic fluid power — Electro-pneumatic pressure control valves — Part 2: Test methods to determine main characteristics to include in the supplier's literature Released:11/22/2021
ISO 10094-2:2021 - Transmissions pneumatiques — Appareils électropneumatiques de distribution à commande continue de pression — Partie 2: Méthodes d'essai pour déterminer les principales caractéristiques à inclure dans la documentation des fournisseurs Released:11/22/2021
Frequently Asked Questions
ISO 10094-2:2021 is a standard published by the International Organization for Standardization (ISO). Its full title is "Pneumatic fluid power - Electro-pneumatic pressure control valves - Part 2: Test methods to determine main characteristics to include in the supplier's literature". This standard covers: This document specifies the test procedures and a method of presenting results concerning the parameters which define the main characteristics to be included in the supplier's literature of the electro-pneumatic continuous pressure control valves, conforming to ISO 10094-1. The purpose of this document is: - to facilitate comparison by standardizing the test methods and the presentation of the test results, and - to assist in the proper application of these components in compressed air systems. The specified tests are intended to allow comparison between the different types of continuous pressure control valves; these are not production tests to be carried out on each manufactured product. The tests described in this document are for components with an exhaust port vented to the atmosphere. NOTE 1 The tests related to non-electrically modulated pneumatic continuous pressure control valves are specified in ISO 6953-2. NOTE 2 The tests related to electro-pneumatic continuous flow control valves are specified in ISO 10041-2. NOTE 3 ISO 6953-3 provides an alternate dynamic test method for flow-rate characteristics using an isothermal tank instead of a flow meter. However, this method measures only the decreasing flow rate part of the hysteresis curve of the forward flow and relief flow characteristics.
This document specifies the test procedures and a method of presenting results concerning the parameters which define the main characteristics to be included in the supplier's literature of the electro-pneumatic continuous pressure control valves, conforming to ISO 10094-1. The purpose of this document is: - to facilitate comparison by standardizing the test methods and the presentation of the test results, and - to assist in the proper application of these components in compressed air systems. The specified tests are intended to allow comparison between the different types of continuous pressure control valves; these are not production tests to be carried out on each manufactured product. The tests described in this document are for components with an exhaust port vented to the atmosphere. NOTE 1 The tests related to non-electrically modulated pneumatic continuous pressure control valves are specified in ISO 6953-2. NOTE 2 The tests related to electro-pneumatic continuous flow control valves are specified in ISO 10041-2. NOTE 3 ISO 6953-3 provides an alternate dynamic test method for flow-rate characteristics using an isothermal tank instead of a flow meter. However, this method measures only the decreasing flow rate part of the hysteresis curve of the forward flow and relief flow characteristics.
ISO 10094-2:2021 is classified under the following ICS (International Classification for Standards) categories: 23.100.50 - Control components. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO 10094-2:2021 has the following relationships with other standards: It is inter standard links to ISO 10094-2:2010. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase ISO 10094-2:2021 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.
Standards Content (Sample)
INTERNATIONAL ISO
STANDARD 10094-2
Second edition
2021-11
Pneumatic fluid power — Electro-
pneumatic pressure control valves —
Part 2:
Test methods to determine main
characteristics to include in the
supplier's literature
Transmissions pneumatiques — Appareils électropneumatiques de
distribution à commande continue de pression —
Partie 2: Méthodes d'essai pour déterminer les principales
caractéristiques à inclure dans la documentation des fournisseurs
Reference number
© ISO 2021
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
Contents Page
Foreword .v
Introduction . vi
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 2
4 Symbols and units. 2
5 Test conditions .3
5.1 Gas supply . 3
5.2 Temperature . 3
5.3 Pressures . 3
5.3.1 General . 3
5.3.2 Inlet pressure . 3
5.3.3 Test pressures . 3
5.3.4 Checking . . 3
5.4 Electrical supplies . 3
6 Test procedures . 4
6.1 Test conditions . 4
6.2 Inlet pressure . 4
6.3 Static tests . 4
7 Control signal/pressure static-characteristics test at null forward or relief flow rate .4
7.1 Test installation . 4
7.1.1 Test circuit . 4
7.1.2 Pressure measurement . 5
7.2 Test procedures . 5
7.2.1 Control signal/pressure static characteristic test . 5
7.2.2 Minimum regulated pressure test . 5
7.2.3 Resolution test . 6
7.2.4 Repeatability test . 6
7.3 Calculation of characteristics . 7
7.3.1 Characteristic curve . 7
7.3.2 Linearity . 8
7.3.3 Control signal/pressure hysteresis . 9
7.3.4 Minimum regulated pressure . 10
7.3.5 Resolution . 11
7.3.6 Repeatability . 11
7.3.7 Sensitivity . .12
7.3.8 Offset .12
8 Flow/pressure static characteristics test .12
8.1 Test circuit for flow rate measurement .12
8.2 General requirements . 13
8.3 Test procedures . 14
8.3.1 Initial test procedure . . 14
8.3.2 Forward flow rate/pressure characteristics test . 14
8.3.3 Relief flow rate/pressure characteristics test . 14
8.3.4 Procedure for other control signal values . 15
8.4 Calculation of characteristics .15
8.4.1 Characteristic curves . 15
8.4.2 Flow rate/pressure hysteresis . 15
8.4.3 Maximum forward sonic conductance . 15
8.4.4 Maximum relief sonic conductance . 16
9 Pressure regulation characteristics test .17
iii
9.1 Test circuit . 17
9.2 Test procedure . 17
10 Leakage at null forward flow rate or relief flow rate characteristic test .17
10.1 Test circuit . 17
10.2 Test procedure . 18
10.3 Calculation of characteristic . 18
11 Dynamic characteristics – Step responses .18
11.1 Test Installation . 18
11.2 Test procedures . 19
11.3 Calculation of characteristics .20
11.3.1 Charge characteristic curves . 20
11.3.2 Discharge characteristic curves . 20
11.3.3 Charge characteristics . 20
11.3.4 Discharge characteristics . 21
12 Presentation of test results .22
12.1 General .22
12.2 Control signal/pressure static characteristics . 22
12.3 Flow rate/pressure characteristics . 23
12.4 Pressure regulation characteristics . 23
12.5 Leakage characteristic . 23
12.6 Dynamic characteristics .23
Annex A (informative) Frequency responses .24
Annex B (informative) Calculation procedures of gain and phase lag .26
Bibliography .30
iv
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to
the World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT), see
www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 131, Fluid power systems], Subcommittee
SC 5, Control products and components.
This second edition cancels and replaces the first edition (ISO 10094-2:2010), which has been
technically revised.
The main changes are as follows:
— Addition of definitions for response time, settling time, and shifting time in Clause 3;
— Revision of the procedure for the repeatability test: addition of 15 % and 85 % of the electrical
control signal full-scale to tested values (in addition to 50 %) in 7.2.4;
— Addition of two subclauses relating to Sensitivity (7.3.7) and Offset (7.3.8) respectively;
— Revision of the test procedure to determine leakage characteristics to simplify the test practice
(10.2).
— Deletion of the no tank test version and test circuit from the test practices in Clause 11 related to
dynamic characteristics;
— The former subclause 11.2, frequency characteristics, has been made an informative annex
(Annex A).
A list of all parts in the ISO 10094 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
v
Introduction
In pneumatic fluid power systems, power is transmitted and controlled through a gas under pressure
within a circuit.
When pressure tracking or pressure regulation is required, electro-pneumatic continuous pressure
control valves can be used to track a variable set point with low tracking error or to maintain the
pressure of the gas at an approximately constant level.
These control valves continuously modulate the pneumatic pressure of a system in response to a
continuous electrical input signal and link the electrical input value to a proportional pressure value.
It is therefore necessary to know some performance characteristics of these electro-pneumatic
continuous pressure control valves in order to determine their suitability.
vi
INTERNATIONAL STANDARD ISO 10094-2:2021(E)
Pneumatic fluid power — Electro-pneumatic pressure
control valves —
Part 2:
Test methods to determine main characteristics to include
in the supplier's literature
1 Scope
This document specifies the test procedures and a method of presenting results concerning the
parameters which define the main characteristics to be included in the supplier's literature of the
electro-pneumatic continuous pressure control valves, conforming to ISO 10094-1.
The purpose of this document is:
— to facilitate comparison by standardizing the test methods and the presentation of the test results,
and
— to assist in the proper application of these components in compressed air systems.
The specified tests are intended to allow comparison between the different types of continuous
pressure control valves; these are not production tests to be carried out on each manufactured product.
The tests described in this document are for components with an exhaust port vented to the atmosphere.
NOTE 1 The tests related to non-electrically modulated pneumatic continuous pressure control valves are
specified in ISO 6953-2.
NOTE 2 The tests related to electro-pneumatic continuous flow control valves are specified in ISO 10041-2.
NOTE 3 ISO 6953-3 provides an alternate dynamic test method for flow-rate characteristics using an
isothermal tank instead of a flow meter. However, this method measures only the decreasing flow rate part of the
hysteresis curve of the forward flow and relief flow characteristics.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
ISO 5598, Fluid power systems and components — Vocabulary
ISO 6358-1, Pneumatic fluid power — Determination of flow-rate characteristics of components using
compressible fluids — Part 1: General rules and test methods for steady-state flow
ISO 6953-1, Pneumatic fluid power — Compressed air pressure regulators and filter-regulators — Part 1:
Main characteristics to be included in literature from suppliers and product-marking requirements
ISO 10094-1:2021, Pneumatic fluid power — Electro-pneumatic pressure control valves — Part 1: Main
characteristics to include in the supplier’s literature
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 5598, ISO 6953-1 and
ISO 10094-1 and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1
response time
time from initial electrical signal change to an observed output pressure equal to 90 % of the total
change in pressure
3.2
settling time
time lapse from initial change to the time from which the observed output pressure remains between
95 % and 105 % of its total change in pressure
3.3
shifting time
time from initial electrical signal change to an observed output pressure equal to 10 % of the total
change in pressure
4 Symbols and units
Table 1 — Symbols and units
Description Symbol Units
3 b
Maximum sonic conductance at the inlet C m /(s·Pa) (ANR)
f,max
3 b
Sonic conductance at the exhaust C m /(s·Pa) (ANR)
r
Hysteresis H % FS
Linearity L % FS
Pa/V, Pa/mA or Pa/numeri-
Sensitivity m
cal signal
Offset O %
Atmospheric pressure p Pa
atm
Reference pressure p Pa
a
Total relative pressure at the inlet port p Pa
a
Total relative pressure at the outlet port p Pa
Maximum inlet pressure p Pa
1,max
Maximum regulated pressure p Pa
2,max
3 b
Volume flow rate at standard reference atmosphere q m /s (ANR)
V
3 b
Maximum volume flow rate at the inlet q m /s (ANR)
V,f,max
3 b
Volume flow rate at the outlet q m /s (ANR)
V,r
Repeatability r % FS
Resolution S % FS
Reference temperature T K
a
As described in ISO 11727.
b
The reference atmosphere is defined in ISO 8778, i.e.: T = 293,15 K, p = 100 kPa (1 bar) and a relative humidity
0 0
of 65 %.
Table 1 (continued)
Description Symbol Units
a
Temperature at the inlet port T K
a
Temperature at the outlet port T K
Electrical control signal w V, mA or numerical signal
Pressure difference Δp Pa
Maximal difference of hysteresis Δp Pa
2,h,max
Maximal difference of the linearity Δp Pa
2,l,max
a
As described in ISO 11727.
b
The reference atmosphere is defined in ISO 8778, i.e.: T = 293,15 K, p = 100 kPa (1 bar) and a relative humidity
0 0
of 65 %.
5 Test conditions
5.1 Gas supply
Unless otherwise specified, testing shall be conducted with compressed air. If another gas is used, it
shall be noted in the test report.
5.2 Temperature
The ambient, fluid and the component-under-test temperatures shall be maintained at 23 °C ± 10 °C
during all the tests.
5.3 Pressures
5.3.1 General
The specified pressures shall be maintained within ±2 %.
5.3.2 Inlet pressure
The inlet pressure used for testing shall be the lower of the following pressures:
— the maximum regulated pressure, p , plus 200 kPa (2 bar); and
2,max
— the specified maximum inlet pressure, p .
1,max
5.3.3 Test pressures
The preferential test pressures are chosen as approximately equal to 20 %, 40 %, 60 %, 80 % and 100 %
of the maximum of the setting pressure scale.
5.3.4 Checking
It shall be periodically verified that no pressure bleed of measuring instruments is obstructed by solid
or liquid particles.
5.4 Electrical supplies
The tests shall be carried out under nominal electrical conditions.
6 Test procedures
6.1 Test conditions
The component under test shall be used according to the manufacturer's application instructions.
6.2 Inlet pressure
During every measurement concerning the static or dynamic tests described in Clauses 7 to 11, the
inlet pressure, p , shall be constant (within 10 % FS).
In the case of the dynamic tests as described in Clause 11, a tank buffer shall be used in order to reduce
the inlet pressure, p , fluctuations, as indicated in Figure 10.
6.3 Static tests
During every measurement series concerning static tests described in Clauses 7, 8, 9 and 10, as soon as
the steady conditions are reached, every series of results obtained with related specified test conditions
shall be recorded. When these measurements are performed step by step, slowly modify the conditions
to prevent instability.
NOTE 1 Figures 1, 7, 9 and 10 represent typical circuits that do not show the electrical supply circuit necessary
to operate electrically modulated pneumatic valves and that do not contain all the necessary safety devices for
protection against hazards that can be caused by the failure of a component or piping. It is important that those
responsible for conducting the tests take into account the necessity to protect personnel and property.
NOTE 2 The symbols used in the circuit diagrams shown in Figures 1, 7, 9 and 10 are in accordance with
ISO 1219-1.
7 Control signal/pressure static-characteristics test at null forward or relief flow
rate
7.1 Test installation
7.1.1 Test circuit
Figure 1 represents a typical test circuit for the control signal/pressure static characteristics testing.
This test is conducted with no forward flow and with the relief port open to atmosphere. For all tests
described in 7.2, apply the inlet pressure chosen according to 5.3.2.
Key
1 supply pressure regulator 6 inlet temperature T measuring-element
2 shut off valve 7 inlet pressure p transducer
3 inlet volume or optional pressure measuring tube 8 regulated pressure p transducer
with transition connector
4 component under test 9 signal generator
5 plug 10 data recorder
Figure 1 — Typical test circuit for control signal/pressure characterization
7.1.2 Pressure measurement
The inlet pressure sensor is connected to the volume or pressure-measuring tube with transition
connector in accordance with ISO 6358-1. The regulated pressure sensor is an external measurement
sensor, even if the component under test has an internal pressure sensor. The regulated pressure
transducer shall be connected as close as possible to the outlet port.
7.2 Test procedures
7.2.1 Control signal/pressure static characteristic test
Using a signal generator to create a triangular signal to explore the control signal full-scale (0 % to
100 %), record the electrical control signal, w, in the X-axis and the regulated pressure, p , in the Y-axis
of a recorder so as to obtain a hysteresis curve.
The triangular electrical control signal shall evolve with a sufficiently low ramp speed so as to avoid
dynamic effects and influence the regulated pressure measurements: 0,5 % of full-scale per second is
the recommended ramp speed.
7.2.2 Minimum regulated pressure test
Leave the component under test pressurized with the minimum control signal (0 %) at rest for at least
5 min.
From the minimum electrical control signal (0 %), measure the regulated pressure, p for the following
control signal values. This defines response to the lower portion of the signal:
— 0 %, 0,5 %, 1 % of the control signal full-scale;
— then every 1 % up to 5 % of the control signal full-scale.
Every measurement is made after a rest time of 10 s at each stage. The measurements shall always be
made by increasing the control signal.
7.2.3 Resolution test
7.2.3.1 From the minimal electrical control signal (0 %), gradually modify the electrical control
signal value by increasing values only, until reaching the value corresponding to 15 % of the regulated
pressure full-scale.
7.2.3.2 Note this electrical control signal value, w , and record the pressure evolution as a function
stop
of the electrical signal.
7.2.3.3 Maintain this state for more than 10 s and gradually re-increase the input signal. Then note
the electrical control signal, w , for which the regulated pressure, p , starts re-increasing.
start 2
7.2.3.4 Repeat the operations described in 7.2.3.2 and 7.2.3.3 for the electrical control signal values
corresponding to 50 % and 85 % of the regulated pressure full-scale. Gradually modify the control
signal, by increasing values only, until reaching these values.
7.2.4 Repeatability test
Using a signal generator to create a stepped signal between 0 % to 15 %, 15 % to 50 % and 50 % to
85 % of the electrical control signal full-scale, according to Figure 2, record the regulated pressure, p ,
as a function of time for at least 20 periods.
The frequency of the electrical control signal shall be sufficiently low so as to have a good stabilization
of the regulated pressure at 15 %, 50 % and 85 % of the electrical control signal full-scale.
At each period indicated by the index j = 1, …, 20, when the regulated pressure is stabilized for
15 %, 50 % and 85 % of the electrical control signal full-scale (hereinafter referred to as x), note the
corresponding regulated pressure, p
2,x,j
Key
X time in seconds
Y electrical control signal in %
measuring point for repeatability
Figure 2 — Repeatability test
7.3 Calculation of characteristics
7.3.1 Characteristic curve
For each value of the control signal, calculate the mean value of the two corresponding pressures
measured according to the procedure described in 7.2.1, respectively with an increasing and a
decreasing control signal.
Plot the mean pressure curve as a function of the control signal as represented in Figure 3.
The characteristic line is the straight line passing by the mean regulated pressure values of 5 % and
95 % of the regulated pressure full-scale according to Figure 3.
The offset of the straight line shall be determined by the intersection of the straight line with the
abscissa axis (regulated pressure, p , equal to 0 kPa) as shown in Figure 3 and Figure 6.
The sensitivity and the offset of the straight line shall be indicated on the graph, as represented in
Figure 3.
Key
c
X electrical control signal, % 5 % of p .
2,max
d
Y regulated pressure p in kPa Offset.
e
characteristic line Sensitivity.
f
mean pressure curve Control value w(p ) for 5 % of p .
2, 5 % 2,max
a g
p . Control value w(p ) for 95 % of p .
2,max 2, 95 % 2,max
b
95 % of p .
2,max
Figure 3 — Determination of the characteristic curve
7.3.2 Linearity
For each control signal value corresponding to regulated pressure value between 5 % and 95 % of the
regulated pressure full-scale, calculate, in absolute value, the difference between the mean regulated
pressure value calculated in 7.3.1 and the corresponding value on the characteristic straight line
plotted in 7.3.1.
Determine the maximal difference, Δp , according to Figure 4, and calculate the linearity value, L
2,l,max
expressed as a percentage of the regulated pressure full-scale using Formula (1):
Δp
2,l,max
L=⋅100 (1)
p
2,max
Key
a
X electrical control signal, % characteristic line p .
2,max
b
Y regulated pressure p , in kPa mean pressure curve 95 % of p .
2 2,max
c
maximum linearity limits 5 % of p .
2,max
d
Δp .
2,l,max
Figure 4 — Representation of the maximal scattering of linearity
7.3.3 Control signal/pressure hysteresis
For each control signal value corresponding to regulated pressure value between 5 % and 95 % of the
regulated pressure full-scale, calculate in absolute value, the difference between the regulated pressure
values p measured respectively with an increasing and a decreasing control signal. These values are
obtained according to the procedure described in 7.2.1.
Determine the maximal difference, Δp , according to Figure 5. Calculate the hysteresis
2,h,max
characteristic value, H, evaluating this difference in percentage of the regulated pressure full-scale
according to Formula (2):
Δp
2,h,max
H=⋅100 (2)
p
2,max
Key
a
X electrical control signal, % characteristic line measured with increasing signal p .
2,max
b
Y regulated pressure p , in kPa characteristic line measured with decreasing signal 95 % of p .
2 2,max
c
5 % of p .
2,max
d
Δp .
2,h,max
Figure 5 — Representation of the maximal scattering of hysteresis difference
7.3.4 Minimum regulated pressure
With the data measured according to the procedure described in 7.2.2, determine the pressure at the
first point from which all subsequent data points fall within the allowable limits of linearity of the
control signal/pressure characteristic curve, as shown in Figure 6.
This regulated pressure value, expressed as a percentage of the regulated pressure full-scale,
corresponds to the minimum regulated pressure value.
Key
a
X electrical control signal, % Offset.
b
Y regulated pressure p , in kPa Minimum regulated pressure.
c
characteristic line Δp .
2,l,max
Figure 6 — Graphic determination of the minimum regulated pressure value and of the offset
7.3.5 Resolution
7.3.5.1 For each of the three tests performed according to 7.2.3, for electrical control signal values
corresponding to 15 %, 50 % and 85 % of the regulated pressure full-scale, calculate the corresponding
resolution, expressed as a percentage of the control signal full-scale, using Formula (3):
ww−
startstop
S = ⋅100 (3)
ww−
maxmin
7.3.5.2 Calculate the resolution by taking the maximal value of the three values obtained in 7.3.5.1.
7.3.6 Repeatability
Using the stabilized regulated pressures values, p , obtained according to the procedure described
2,x,j
in 7.2.4, calculate the repeatability value, r , expressed as a percentage of the regulated pressure full-
x
scale, using Formula (4):
pp−
22,,xxmaxm,, in
r = ⋅100 (4)
x
p
2,max
where
p is the maximum value of the 20 repeat measurements p ( j=1.20) from the measurement
2,x,max 2,x,j
series for the percentage x (x = 15 %, 50 % or 85 %) of the regulated full-scale pressure; and
p is the minimum value of the 20 repeat measurements p ( j=1.20) from the measurement
2,x,min 2,x,j
series for the percentage x (x = 15 %, 50 % or 85 %) of the regulated full-scale pressure.
The value r for the repeatability shall be the highest value from the calculated values r , r and
15 % 50 %
r .
85 %
7.3.7 Sensitivity
With the mean regulated pressure values of 5 % (p ) and 95 % (p ) of regulated pressure full
2,5 % 2,95 %
scale, measured respectively with electrical control signal w(p ) and w(p ) and used to plot the
2,5 % 2,95 %
characteristic line in paragraph 7.3.1, the sensitivity, expressed as Pa/V, Pa/mA or Pa/numerical signal,
is calculated using Formula (5):
pp −
2 ,,95%2 5 %
m= ⋅100 (5)
wp(()) −wp
2 ,,95%2 5 %
7.3.8 Offset
The offset, expressed in percentage, shall be calculated using Formula (6):
mwp⋅−( ) p
2 ,,55%2 %
O= ⋅100 (6)
mw⋅−(w )
maxmin
8 Flow/pressure static characteristics test
8.1 Test circuit for flow rate measurement
A suitable test circuit, as shown in Figure 7, shall be used for measuring forward or relief flow rates.
This test circuit combines:
a) the in-line test circuit, as described in ISO 6358-1 for characterizing, in steady state conditions, the
components with upstream and downstream pressure-measuring tubes and transition connectors
(used for forward flow rate measurements), and
b) the exhaust-to-atmosphere test circuit, as described in ISO 6358-1 for characterizing, in steady
state conditions, the components exhausting directly to atmosphere (used for relief flow rate
measurements).
This test circuit shall be used for:
— the flow-pressure static characteristics measurements, and
— the pressure regulation characteristics measurements.
Key
1 shut-off valve 10 inlet pressure p transducer
2 supply pressure regulator 11 regulated pressure p transducer
3 pressure measuring tube with transition connector 12 temperature T measuring element
4 component under test 13 pressure regulator (for relief flow rates)
5 pressure measuring tube with transition connector 14 relief flow meter
6 solenoid valve 15 solenoid valve
7 forward flow meter 16 signal generator
8 flow control valve (for forward flow rates) 17 data acquisition system (optional)
9 inlet temperature T measuring element
NOTE If the component under test already operates with an external sensor, place it at the same place as the
regulated pressure sensor.
Figure 7 — Test circuit for flow rate/pressure characterization and pressure regulation
8.2 General requirements
8.2.1 The component under test shall be located in the test circuit so as to connect its inlet port to the
upstream transition connector and pressure-measuring tube, and its exhaust port to the atmosphere.
Its outlet port is connected to a transition connector and a pressure-measuring tube enabling
measurement of the regulated pressure, p .
8.2.2 Pressure-measuring tubes and transition connectors shall be in accordance with ISO 6358-1.
8.2.3 Components 1, 2, 3, 9 and 10 in Figure 7 correspond to the upstream part of the test circuit
used for forward flow rates measurements. These components shall be also used for relief flow rate
measurements as the inlet port of the component under test shall be connected to the supply circuit,
following the normal use of the component.
8.2.4 Components 5, 6, 7, 8, 11, and 12 in Figure 7 correspond to the downstream part of the test
circuit used for forward flow rates measurements.
8.2.5 The sonic conductances of the supply pressure regulator 2 and of the solenoid valve 6 should be
at least twice the forward sonic conductance of the component under test.
8.2.6 Components 5, 11, 12, 13, 14, and 15 in Figure 7 correspond to the upstream part of the test
circuit used for relief flow rate measurements.
8.2.7 The sonic conductances of the pressure regulator 13 and of the solenoid valve, 15, should be at
least twice the relief sonic conductance of the component under test.
8.2.8 The flow-meters shall always be located at the outlet port in order to measure the actual
forward or relief flow rate.
8.3 Test procedures
8.3.1 Initial test procedure
8.3.1.1 Install the electro-pneumatic continuous pressure control valve according to Figure 7, without
flow, with shut-off valve, solenoid valves and flow control valve closed.
8.3.1.2 Open shut-off valve, 1, and set the pressure regulator, 2, to apply the inlet pressure, p , chosen
according to 5.3.2.
8.3.1.3 From the minimal electrical control signal (0 %), gradually modify the control signal by
increasing values only, until reaching the regulated pressure value, p , corresponding to 20 % of the
regulated pressure full-scale.
8.3.1.4 Follow successively the procedure described in 8.3.2 for forward flow rates and then the
procedure described in 8.3.3 for relief flow rates.
8.3.2 Forward flow rate/pressure characteristics test
8.3.2.1 Open the solenoid valve 6. By using the flow rate control valve 8, let the air pass through the
component under test.
8.3.2.2 When the flow is steady, measure the forward flow rate using the flow meter, 7, the
corresponding regulated pressure, p , using the pressure transducer, and the inlet temperature, T .
2 1
8.3.2.3 Continue the measurements by gradually modifying the flow value, by increasing values only
until reaching the maximal flow rate in the test circuit. Measure the additional data for a decreasing
forward flow rate until zero. During the variations of the forward flow (increasing and decreasing),
keep the inlet pressure, p , constant.
8.3.3 Relief flow rate/pressure characteristics test
8.3.3.1 Set the pressure regulator, 13, at the same pressure value as the regulated pressure value of
the component under test obtained without flow at the end of the procedure described in 8.3.2.3. Close
the solenoid valve, 6, and open the solenoid valve, 15, to apply this pressure on the outlet side of the
component under test.
8.3.3.2 Increase the regulated pressure using the pressure regulator, 13. When the flow is steady,
measure the relief flow using the flow meter 14, the corresponding regulated pressure, p , using the
pressure transducer and the temperature, T , since the air passes through the exhaust port of the
component under test.
8.3.3.3 Continue the measurements by gradually increasing the flow rate by increasing the pressure
using the pressure regulator until the pressure reaches a level of the maximum regulated pressure
plus 200 kPa (2 bar). Measure the additional data for decreasing pressure until the flow rate reaches
zero. During the variations of the relief flow (increasing and decreasing), keep the inlet pressure, p ,
constant. Close the solenoid valve, 15.
8.3.4 Procedure for other control signal values
Repeat the above procedures described in 8.3.1.4 for control signal values corresponding to about 40 %,
60 %, 80 % and 100 % of the regulated pressure full-scale. Without flow, gradually modify the control
signal, by increasing values only, until reaching these values.
8.4 Calculation of characteristics
8.4.1 Characteristic curves
8.4.1.1 From the measurements obtained for the electrical control signal corresponding
approximately to about 20 % of the regulated pressure full scale, for each forward flow rate value,
calculate the mean value of the two corresponding regulated pressures, p , measured according to the
procedure described in 8.3.2, respectively with increasing and decreasing forward flow rates.
Plot in a graph the mean regulated pressure values, as a function of the forward flow rate, as represented
in the first quadrant of Figure 8.
8.4.1.2 From the measurements obtained for the electrical control signal corresponding
approximately to about 20 % of the regulated pressure full scal
...
NORME ISO
INTERNATIONALE 10094-2
Deuxième édition
2021-11
Transmissions pneumatiques —
Appareils électropneumatiques de
distribution à commande continue de
pression —
Partie 2:
Méthodes d'essai pour déterminer
les principales caractéristiques à
inclure dans la documentation des
fournisseurs
Pneumatic fluid power — Electro-pneumatic pressure control
valves —
Part 2: Test methods to determine main characteristics to include in
the supplier's literature
Numéro de référence
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2021
Tous droits réservés. Sauf prescription différente ou nécessité dans le contexte de sa mise en œuvre, aucune partie de cette
publication ne peut être reproduite ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique,
y compris la photocopie, ou la diffusion sur l’internet ou sur un intranet, sans autorisation écrite préalable. Une autorisation peut
être demandée à l’ISO à l’adresse ci-après ou au comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Case postale 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Genève
Tél.: +41 22 749 01 11
E-mail: copyright@iso.org
Web: www.iso.org
Publié en Suisse
ii
Sommaire Page
Avant-propos .v
Introduction .vii
1 Domaine d'application .1
2 Références normatives .1
3 Termes et définitions . 2
4 Symboles et unités . 2
5 Conditions d'essai . 3
5.1 Alimentation en gaz . 3
5.2 Température . 3
5.3 Pressions . 3
5.3.1 Généralités . 3
5.3.2 Pression d'alimentation . 3
5.3.3 Pressions d'essai . 3
5.3.4 Vérification . 4
5.4 Alimentation électrique. 4
6 Modes opératoires d'essai . 4
6.1 Conditions d'essai . 4
6.2 Pression d'alimentation . 4
6.3 Essais statiques . 4
7 Essai relatif aux caractéristiques statiques de pression/signal de commande à
débit d'alimentation ou d'échappement nul . 4
7.1 Installation d'essai . 4
7.1.1 Circuit d'essai . 4
7.1.2 Mesurage de la pression . 5
7.2 Modes opératoires d'essai . 5
7.2.1 Essai relatif aux caractéristiques de pression/signal de commande . 5
7.2.2 Essai relatif à la pression régulée minimale . 5
7.2.3 Essai relatif à la résolution . 6
7.2.4 Essai de répétabilité . 6
7.3 Calcul des caractéristiques . 7
7.3.1 Courbe caractéristique . 7
7.3.2 Linéarité . 8
7.3.3 Hystérésis signal de commande/pression . 9
7.3.4 Pression régulée minimale . 10
7.3.5 Résolution . 11
7.3.6 Répétabilité .12
7.3.7 Sensibilité .12
7.3.8 Décalage . 12
8 Essai relatif aux caractéristiques statiques de débit-pression .12
8.1 Circuit d'essai pour le mesurage du débit.12
8.2 Exigences générales .13
8.3 Modes opératoires d'essai . 14
8.3.1 Mode opératoire d’essai initial. 14
8.3.2 Essai des caractéristiques de débit d’alimentation/pression. 14
8.3.3 Essai relatif aux caractéristiques de débit d'échappement/pression .15
8.3.4 Mode opératoire pour d'autres valeurs du signal de commande .15
8.4 Calcul des caractéristiques . .15
8.4.1 Courbes caractéristiques . 15
8.4.2 Hystérésis débit/pression . 16
8.4.3 Conductance sonique maximale d'alimentation . 16
8.4.4 Conductance sonique maximale d'échappement . 17
iii
9 Essai des caractéristiques de régulation de pression .17
9.1 Circuit d'essai . 17
9.2 Mode opératoire d'essai. 17
10 Essai relatif à la caractéristique de fuite à débit d'alimentation ou d'échappement
nul .18
10.1 Circuit d'essai . 18
10.2 Mode opératoire d'essai. 18
10.3 Calcul de la caractéristique . 19
11 Caractéristiques dynamiques - Réponses indicielles .19
11.1 Installation d'essai . 19
11.2 Modes opératoires d'essai .20
11.3 Calcul des caractéristiques . . 21
11.3.1 Courbes caractéristiques de charge . 21
11.3.2 Courbes caractéristiques de décharge . 21
11.3.3 Caractéristiques de charge. 21
11.3.4 Caractéristiques de décharge . 22
12 Présentation des résultats d'essai .23
12.1 Généralités . 23
12.2 Caractéristiques statiques de signal de commande/pression . 23
12.3 Caractéristiques de débit/pression. 24
12.4 Caractéristiques de régulation de pression . 24
12.5 Caractéristique de fuite . 24
12.6 Caractéristiques dynamiques . 24
Annexe A (informative) Réponses en fréquence .25
Annexe B (informative) Méthodes de calcul du gain et du déphasage .27
Bibliographie .31
iv
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes
nationaux de normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est
en général confiée aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude
a le droit de faire partie du comité technique créé à cet effet. Les organisations internationales,
gouvernementales et non gouvernementales, en liaison avec l'ISO participent également aux travaux.
L'ISO collabore étroitement avec la Commission électrotechnique internationale (IEC) en ce qui
concerne la normalisation électrotechnique.
Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont
décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier, de prendre note des différents
critères d'approbation requis pour les différents types de documents ISO. Le présent document a
été rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir
www.iso.org/directives).
L'attention est attirée sur le fait que certains des éléments du présent document peuvent faire l'objet de
droits de propriété intellectuelle ou de droits analogues. L'ISO ne saurait être tenue pour responsable
de ne pas avoir identifié de tels droits de propriété et averti de leur existence. Les détails concernant
les références aux droits de propriété intellectuelle ou autres droits analogues identifiés lors de
l'élaboration du document sont indiqués dans l'Introduction et/ou dans la liste des déclarations de
brevets reçues par l'ISO (voir www.iso.org/brevets).
Les appellations commerciales éventuellement mentionnées dans le présent document sont données
pour information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer un
engagement.
Pour une explication de la nature volontaire des normes, la signification des termes et expressions
spécifiques de l'ISO liés à l'évaluation de la conformité, ou pour toute information au sujet de l'adhésion
de l'ISO aux principes de l’Organisation mondiale du commerce (OMC) concernant les obstacles
techniques au commerce (OTC), voir www.iso.org/avant-propos.
Le présent document a été élaboré par le comité technique ISO/TC 131, Transmissions hydrauliques et
pneumatiques, sous-comité SC 5, Appareils de régulation pneumatiques.
Cette deuxième édition annule et remplace la première édition (ISO 10094-2:2010), qui a fait l’objet
d’une révision technique.
Les principales modifications sont les suivantes:
— Ajout de définitions dans l’Article 3 pour le temps de commutation, le temps de réponse, et le temps
de basculement;
— Révision du mode opératoire de l'essai de répétabilité: ajout de 15 % et 85 % du signal de commande
électrique à pleine échelle pour les valeurs soumises à essai (en plus de 50 %) en 7.2.4;
— Ajout de deux paragraphes relatifs à la Sensibilité (7.3.7) et au Décalage (7.3.8) respectivement;
— Révision du mode opératoire d'essai pour déterminer les caractéristiques de fuite pour simplifier la
pratique de l’essai (10.2).
— Suppression de la version de l’essai sans réservoir et du circuit d'essai correspondant dans les
pratiques d’essai de l’Article 11 relative aux caractéristiques dynamiques;
— L’ancien paragraphe 11.2, Réponses en fréquence, a été transformé en annexe informative
(Annexe A).
Une liste de toutes les parties de la série ISO 10094 se trouve sur le site web de l’ISO.
v
Il convient que l’utilisateur adresse tout retour d’information ou toute question concernant le présent
document à l’organisme national de normalisation de son pays. Une liste exhaustive desdits organismes
se trouve à l’adresse www.iso.org/fr/members.html.
vi
Introduction
Dans les systèmes de transmissions pneumatiques, l'énergie est transmise et contrôlée par
l'intermédiaire d'un gaz sous pression circulant dans un circuit.
Lorsqu'il est nécessaire de suivre précisément une consigne de pression variable ou lorsqu'une
régulation précise de la pression est requise, des appareils électropneumatiques de distribution à
commande continue de pression peuvent être utilisés.
Ces appareils de distribution à commande continue de pression modulent en continu la pression
pneumatique d'un système en réponse à un signal de commande électrique continu et font correspondre
à chaque valeur du signal de commande électrique une valeur de pression proportionnelle.
Il est donc nécessaire de connaître certaines caractéristiques de performance de ces appareils
électropneumatiques de distribution à commande continue de pression afin de déterminer s'ils
conviennent pour une application particulière.
vii
NORME INTERNATIONALE ISO 10094-2:2021(F)
Transmissions pneumatiques — Appareils
électropneumatiques de distribution à commande
continue de pression —
Partie 2:
Méthodes d'essai pour déterminer les principales
caractéristiques à inclure dans la documentation des
fournisseurs
1 Domaine d'application
Le présent document spécifie les modes opératoires d'essai et donne une méthode de présentation
des résultats relatifs aux paramètres qui définissent les principales caractéristiques à inclure dans la
documentation des fournisseurs d'appareils électropneumatiques de distribution à commande continue
de pression conformes à l'ISO 10094-1.
Le but du présent document est:
— de faciliter la comparaison en normalisant les méthodes d'essai et la présentation des résultats
d'essais, et
— d'apporter une aide afin que ces composants soient correctement utilisés dans les systèmes d'air
comprimé.
Les essais spécifiés ont pour but de permettre la comparaison entre les différents types d'appareils
de distribution à commande continue de pression; il ne s'agit en aucun cas d'essais de production à
effectuer pour chaque produit fabriqué.
Les essais décrits dans le présent document sont réalisés pour des composants ayant un orifice
d'échappement vers l'atmosphère.
NOTE 1 Les essais concernant les appareils pneumatiques de distribution à commande continue de pression
qui ne sont pas modulés électriquement sont spécifiés dans l'ISO 6953-2.
NOTE 2 Les essais concernant les distributeurs électropneumatiques à commande continue de débit sont
spécifiés dans l'ISO 10041-2.
NOTE 3 L'ISO 6953-3 fournit une méthode d'essai dynamique alternative pour les caractéristiques de débit
utilisant un réservoir isotherme au lieu d'un débitmètre. Toutefois, cette méthode permet d’obtenir uniquement
la partie de la courbe d’hystérésis des caractéristiques de débit d’alimentation et de débit d’échappement
correspondant à des débits décroissants.
2 Références normatives
Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie de leur
contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s’applique.
Pour les références non datées, la dernière édition du document de référence s'applique (y compris les
éventuels amendements).
ISO 5598, Transmissions hydrauliques et pneumatiques — Vocabulaire
ISO 6358-1, Transmissions pneumatiques — Détermination des caractéristiques de débit des composants
traversés par un fluide compressible — Partie 1: Règles générales et méthodes d'essai en régime stationnaire
ISO 6953-1, Transmissions pneumatiques — Régulateurs de pression et filtres-régulateurs pour air
comprimé — Partie 1: Principales caractéristiques à inclure dans la documentation des fournisseurs et
exigences de marquage du produit
ISO 10094-1:2021, Transmissions pneumatiques — Appareils électropneumatiques de distribution à
commande continue de pression — Partie 1: Principales caractéristiques à inclure dans la documentation
des fournisseurs
3 Termes et définitions
Pour les besoins du présent document, les termes et les définitions de l'ISO 5598, l'ISO 6853-1,
l’ISO 10094-1 ainsi que les suivants s’appliquent.
L’ISO et l’IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en
normalisation, consultables aux adresses suivantes:
— ISO Online browsing platform: disponible à l’adresse https:// www .iso .org/ obp
— IEC Electropedia: disponible à l’adresse https:// www .electropedia .org/
3.1
temps de commutation
temps écoulé entre la variation initiale du signal électrique et une pression de sortie observée égale à
90 % de la variation totale de la pression
3.2
temps de réponse
temps écoulé entre la variation initiale et le moment à partir duquel la pression de sortie observée reste
entre 95 % et 105 % de sa variation totale de pression
3.3
temps de basculement
temps écoulé entre la variation initiale du signal électrique et une pression de sortie observée égale à
10 % de la variation totale de la pression
4 Symboles et unités
Tableau 1 — Symboles et unités
Description Symbole Unités
3 b
Conductance sonique maximale à l'alimentation C m /(s·Pa) (ANR)
f,max
3 b
Conductance sonique à l'échappement C m /(s·Pa) (ANR)
r
Hystérésis H % PE
Linéarité L % PE
Pa/V, Pa/mA ou
Sensibilité m
Pa/signal numérique
Décalage O %
Pression atmosphérique p Pa
atm
Pression de référence p Pa
a
Pression relative totale à l'orifice d'alimentation p Pa
a
Pression relative totale à l’orifice d'utilisation p Pa
Pression maximale d'alimentation p Pa
1,max
a
Comme décrit dans l’ISO 11727.
b
L'atmosphère de référence est définie dans l'ISO 8778, c'est-à-dire: T = 293,15 K, p = 100 kPa (1 bar) et humidité
0 0
relative de 65 %.
Tableau 1 (suite)
Description Symbole Unités
Pression régulée maximale p Pa
2,max
3 b
Débit volumique à l'atmosphère normale de référence q m /s (ANR)
V
3 b
Débit volumique maximal à l'alimentation q m /s (ANR)
V,f,max
3 b
Débit volumique à l'échappement q m /s (ANR)
V,r
Répétabilité r % PE
Résolution S % PE
Température de référence T K
a
Température à l'orifice d'alimentation T K
a
Température à l'orifice de sortie T K
Signal de commande électrique w V, mA ou signal numérique
Différence de pression Δp Pa
Écart maximal d'hystérésis Δp Pa
2,h,max
Écart maximal de linéarité Δp Pa
2,l,max
a
Comme décrit dans l’ISO 11727.
b
L'atmosphère de référence est définie dans l'ISO 8778, c'est-à-dire: T = 293,15 K, p = 100 kPa (1 bar) et humidité
0 0
relative de 65 %.
5 Conditions d'essai
5.1 Alimentation en gaz
Sauf spécification contraire, les essais doivent être effectués avec de l'air comprimé. Si un autre gaz est
utilisé, il doit être mentionné dans le rapport d'essai.
5.2 Température
La température ambiante, la température du fluide et la température du composant soumis à essai
doivent être maintenues à 23 °C ± 10 °C pendant tous les essais.
5.3 Pressions
5.3.1 Généralités
Les pressions spécifiées doivent être maintenues à ±2 % près.
5.3.2 Pression d'alimentation
La pression d’alimentation utilisée pour les essais doit être la plus faible des pressions suivantes:
— la pression régulée maximale, p , augmentée de 200 kPa (2 bar); et
2,max
— la pression maximale d'alimentation spécifiée, p .
1,max
5.3.3 Pressions d'essai
Les pressions d'essai préférentielles sont choisies comme étant approximativement égales à 20 %, 40 %,
60 %, 80 % et 100 % de la valeur maximale de la plage des pressions régulées.
5.3.4 Vérification
Il est nécessaire de vérifier périodiquement qu'aucun orifice de purge des instruments de mesure n'est
obstrué par des particules solides ou liquides.
5.4 Alimentation électrique
Les essais doivent être effectués dans les conditions électriques nominales.
6 Modes opératoires d'essai
6.1 Conditions d'essai
Le composant soumis à essai doit être utilisé conformément aux instructions d'application du fabricant.
6.2 Pression d'alimentation
Pour chaque série de mesurages concernant les essais statiques ou dynamiques décrits dans les
Articles 7 à 11, la pression d'alimentation, p , doit être maintenue constante (à 10 % PE).
Dans le cas des essais dynamiques décrits dans l'Article 11, un réservoir tampon doit être utilisé afin de
réduire les fluctuations de la pression d'alimentation, p , comme indiqué à la Figure 10.
6.3 Essais statiques
Durant chaque série de mesurages concernant les essais statiques décrits dans les Articles 7, 8, 9 et 10,
dès que des conditions de régime stationnaire sont atteintes, chaque série de mesures obtenue selon
les modalités d'essai spécifiées correspondantes doit être enregistrée. Lorsque ces mesurages sont
effectués pas-à-pas, modifier lentement les conditions d'essai afin d'éviter toute instabilité.
NOTE 1 Les Figures 1, 7, 9 et 10 représentent des circuits types qui ne montrent pas le circuit d'alimentation
électrique nécessaire au fonctionnement des appareils de distribution pneumatiques modulés électriquement
et qui ne contiennent pas tous les dispositifs de sécurité nécessaires à la protection contre les phénomènes
dangereux pouvant être engendrés par la défaillance d'un composant ou d'une tuyauterie. Il est important que les
personnes chargées de mener les essais tiennent compte de la nécessité de protéger le personnel et les biens.
NOTE 2 Les symboles utilisés dans les schémas de circuits représentés dans les Figures 1, 7, 9 et 10 sont
conformes à l'ISO 1219-1.
7 Essai relatif aux caractéristiques statiques de pression/signal de commande à
débit d'alimentation ou d'échappement nul
7.1 Installation d'essai
7.1.1 Circuit d'essai
La Figure 1 représente un circuit d'essai type pour les essais relatifs aux caractéristiques statiques
de pression/signal de commande. Ce test est réalisé sans débit d’alimentation et avec l’orifice
d’échappement à l’air libre. Pour tous les essais décrits en 7.2, appliquer la pression d'alimentation
choisie conformément au 5.3.2.
Légende
1 régulateur de pression d'alimentation 6 élément de mesure de la température
d’alimentation, T
2 robinet d'isolement 7 capteur de pression d'alimentation p
3 volume d’alimentation ou tube de mesure de 8 capteur de pression régulée p
pression optionnel avec connecteur de transition
4 composant soumis à essai 9 générateur de signal
5 bouchon 10 enregistreur de données
Figure 1 — Circuit d'essai type pour la caractérisation pression/signal de commande
7.1.2 Mesurage de la pression
Le capteur de pression d'alimentation est connecté à un volume ou à un tube de mesure de pression avec
connecteur de transition conformément à l'ISO 6358-1. Le capteur de pression régulée est un capteur
de mesure externe, même si le composant soumis à essai comporte un capteur de pression interne. Le
capteur de pression régulée doit être connecté le plus près possible de l’orifice d’utilisation.
7.2 Modes opératoires d'essai
7.2.1 Essai relatif aux caractéristiques de pression/signal de commande
En utilisant un générateur de signaux pour produire un signal triangulaire permettant d'explorer
toute la plage de variation du signal de commande (0 % à 100 %), enregistrer le signal de commande
électrique, w, sur l'axe X et la pression régulée, p , sur l'axe Y d'un enregistreur de manière à obtenir une
courbe d'hystérésis.
Le signal de commande électrique triangulaire doit évoluer avec une vitesse de variation suffisamment
faible pour éviter tous les effets dynamiques qui pourraient avoir une influence sur les mesures de
pression régulée: la vitesse de variation recommandée est de 0,5 % de la plage de réglage par seconde.
7.2.2 Essai relatif à la pression régulée minimale
Laisser au repos pendant au moins 5 min le composant soumis à essai, sous pression, et au signal de
commande minimal (0 %).
À partir du signal de commande électrique minimal (0 %), mesurer la pression régulée, p , pour les
valeurs suivantes du signal de commande. Cela définit la réponse pour la région des plus faibles valeurs
du signal:
— 0 %, 0,5 % et 1 % de la plage de variation du signal de commande;
— puis tous les 1 % jusqu'à 5 % de la plage de variation du signal de commande.
Chaque mesurage est effectué après une période de repos de 10 s à chaque étape. Les mesurages doivent
toujours être réalisés en augmentant le signal de commande.
7.2.3 Essai relatif à la résolution
7.2.3.1 À partir du signal de commande électrique minimal (0 %), modifier progressivement la valeur
du signal de commande électrique par valeurs croissantes uniquement, jusqu'à atteindre la valeur
correspondant à 15 % de la plage de variation de la pression régulée.
7.2.3.2 Noter cette valeur du signal de commande électrique, w , et enregistrer l'évolution de la
stop
pression en fonction du signal électrique.
7.2.3.3 Maintenir cet état pendant plus de 10 s et augmenter de nouveau progressivement le signal de
commande. Noter ensuite le signal de commande électrique, w , pour lequel la pression régulée, p ,
start 2
commence à augmenter de nouveau.
7.2.3.4 Répéter les opérations décrites en 7.2.3.2 et en 7.2.3.3 pour les valeurs du signal de
commande électrique correspondant à 50 % et 85 % de la pression régulée à pleine échelle. Modifier
progressivement le signal de commande, par valeurs croissantes uniquement, jusqu'à atteindre ces
valeurs.
7.2.4 Essai de répétabilité
En utilisant un générateur de signaux pour produire un signal pas à pas de 0 % à 15 %, de 15 % à 50 %,
et de 50 % à 85 % de la plage de réglage du signal de commande électrique, comme représenté à la
Figure 2, enregistrer la pression régulée, p , en fonction du temps pendant au moins 20 périodes.
La fréquence du signal de commande électrique doit être suffisamment faible de manière à obtenir une
bonne stabilisation de la pression régulée à 15 %, 50 % et 85 % du signal de commande électrique à
pleine échelle.
A chaque période indiquée par l'indice j = 1, ., 20, lorsque la pression régulée est stabilisée pour 15 %,
50 % et 85 % du signal de commande électrique à pleine échelle (ci-après dénommée x), on note la
pression régulée correspondante, p
2,x,j
Légende
X temps en secondes
Y signal de commande électrique en %
point de mesure pour la répétabilité
Figure 2 — Essai de répétabilité
7.3 Calcul des caractéristiques
7.3.1 Courbe caractéristique
Pour chaque valeur du signal de commande, calculer la valeur moyenne des deux pressions
correspondantes mesurées conformément au mode opératoire décrit en 7.2.1, avec un signal de
commande respectivement croissant et décroissant.
Tracer la courbe de pression moyenne en fonction du signal de commande, telle que représentée à la
Figure 3.
La droite caractéristique est celle qui passe par les valeurs moyennes de pression régulée de 5 % et de
95 % de la plage de la pression régulée, conformément à la Figure 3.
Le décalage de la droite doit être déterminé par l'intersection de la droite avec l'axe des abscisses
(pression régulée, p , égale à 0 kPa) comme représenté à la Figure 3 et à la Figure 6.
La sensibilité et le décalage de la droite doivent être indiqués sur le graphique, comme représenté à la
Figure 3.
Légende
c
X signal de commande électrique, % 5 % de p .
2,max
d
Y pression régulée p , en kPa Décalage.
e
droite caractéristique Sensibilité.
f
courbe de pression moyenne Valeur de commande w (p ) pour 5 % de p .
2, 5 % 2,max
a g
p . Valeur de commande w (p ) pour 95 % de p .
2,max 2, 95 % 2,max
b
95 % de p .
2,max
Figure 3 — Détermination de la courbe caractéristique
7.3.2 Linéarité
Pour chaque valeur du signal de commande correspondant à une valeur de la pression régulée
comprise entre 5 % et 95 % de la plage de la pression régulée, calculer, en valeur absolue, l'écart entre
la valeur moyenne de la pression régulée calculée en 7.3.1 et la valeur correspondante sur la droite
caractéristique tracée en 7.3.1.
Déterminer l'écart maximal, Δp , conformément à la Figure 4 et calculer la valeur de linéarité, L
2,l,max
exprimée en pourcentage de la plage de la pression régulée à l'aide de la Formule (1):
Δp
2,l,max
L=⋅100 (1)
p
2,max
Légende
a
X signal de commande électrique, % droite caractéristique p .
2,max
b
Y pression régulée p2, en kPa courbe de pression moyenne 95 % de p .
2,max
c
limites de linéarité maximales 5 % of p .
2,max
d
Δp .
2,l,max
Figure 4 — Représentation de l'écart maximal de linéarité
7.3.3 Hystérésis signal de commande/pression
Pour chaque valeur du signal de commande correspondant à une valeur de la pression régulée comprise
entre 5 % et 95 % de la plage de la pression régulée, calculer, en valeur absolue, l'écart entre les valeurs
de la pression régulée, p , mesurées respectivement avec un signal de commande croissant et un signal
de commande décroissant. Ces valeurs sont obtenues conformément au mode opératoire décrit en 7.2.1.
Déterminer la différence maximale, Δp conformément à la Figure 5. Calculer la valeur
2,h,max
caractéristique d’hystérésis H, en évaluant cet écart en pourcentage de la pleine échelle de la pression
régulée, à l’aide de la Formule (2):
Δp
2,h,max
H=⋅100 (2)
p
2,max
Légende
a
X signal de commande courbe caractéristique mesurée avec un signal p .
2,max
électrique, % croissant
b
Y pression régulée p , en kPa courbe caractéristique mesurée avec un signal 95 % de p .
2 2,max
décroissant
c
5 % de p .
2,max
d
Δ p .
2,h,max
Figure 5 — Représentation de l'écart maximal d'hystérésis
7.3.4 Pression régulée minimale
À l'aide des données mesurées conformément au mode opératoire décrit en 7.2.2, déterminer la pression
au niveau du premier point à partir duquel tous les points de données suivants sont dans la limite de
linéarité de la courbe caractéristique signal de commande/pression, telle que représentée à la Figure 6.
Cette valeur de pression régulée, exprimée en pourcentage de la plage de la pression régulée, correspond
à la valeur minimale de la pression régulée.
Légende
a
X signal de commande électrique, % Décalage.
b
Y pression régulée p , en kPa Pression régulée minimale.
c
droite caractéristique Δp .
2,l,max
Figure 6 — Détermination graphique de la valeur de la pression régulée minimale et du
décalage
7.3.5 Résolution
7.3.5.1 Pour chacun des trois essais réalisés conformément à 7.2.3, pour les valeurs du signal de
commande électrique correspondant à 15 %, 50 % et 85 % de la plage de la pression régulée, calculer la
résolution correspondante, exprimée en pourcentage de la plage du signal de commande, à l'aide de la
Formule (3):
ww−
startstop
S = ⋅100 (3)
ww−
maxmin
7.3.5.2 Calculer la résolution en prenant la valeur maximale des trois valeurs obtenues en 7.3.5.1.
7.3.6 Répétabilité
En utilisant les valeurs des pressions régulées stabilisées, p , obtenues conformément au mode
2,x,j
opératoire décrit en 7.2.4, calculer la valeur de répétabilité, r , exprimée en pourcentage de la plage de
x
la pression régulée, à l'aide de la Formule (4):
pp−
22,,xxmaxm,, in
r = ⋅100 (4)
x
p
2,max
où
p est la valeur maximale des 20 répétitions de mesures p (j = 1.20) des séries de mesures
2,x,max 2,x,j
pour le pourcentage x (x = 15 %, 50 % ou 85 %) de la plage de pression régulée; et
p est la valeur minimale des 20 répétitions de mesures p (j = 1.20) des séries de mesures
2,x,min 2,x,j
pour le pourcentage x (x = 15 %, 50 % ou 85 %) de la plage de pression régulée.
La valeur r de répétabilité doit correspondre à la valeur maximale des valeurs calculées r , r et
15 % 50 %
r .
85 %
7.3.7 Sensibilité
Avec les valeurs moyennes de pression régulée de 5 % (p ) et 95 % (p ) de la plage de pression
2,5 % 2,95 %
régulée, mesurées respectivement avec un signal de commande électrique w(p ) et w(p ) et
2,5 % 2,95 %
utilisées pour tracer la droite caractéristique décrite au 7.3.1, la sensibilité, exprimée en Pa/V, Pa/mA
ou Pa/signal numérique, est calculée en utilisant la Formule (5):
pp −
2 ,,95%2 5 %
m= ⋅100 (5)
wp(()) −wp
2 ,,95%2 5 %
7.3.8 Décalage
Le décalage, exprimé en pourcentage, doit être calculé en utilisant la Formule (6):
mwp⋅−( ) p
2 ,,55%2 %
O= ⋅100 (6)
mw⋅−(w )
maxmin
8 Essai relatif aux caractéristiques statiques de débit-pression
8.1 Circuit d'essai pour le mesurage du débit
Un circuit d'essai approprié, tel que représenté à la Figure 7, doit être utilisé pour mesurer les débits
d'alimentation ou d'échappement. Ce circuit d'essai combine:
a) le circuit d'essai en ligne, tel que décrit dans l'ISO 6358-1 pour la caractérisation, en régime
stationnaire, des composants avec des tubes de mesure de pression en amont et en aval et des
connecteurs de transition (utilisé pour les mesurages des débits d'alimentation), et
b) le circuit d'essai d'échappement vers l'atmosphère, tel que décrit dans l'ISO 6358-1 pour la
caractérisation, en régime stationnaire, des composants avec échappement direct vers l'atmosphère
(utilisé pour les mesurages des débits d'échappement).
Ce circuit d'essai doit être utilisé pour:
— les mesurages des caractéristiques statiques de débit-pression, et
— les mesurages des caractéristiques de régulation de pression.
Légende
1 robinet d'isolement 10 capteur de pression d'alimentation, p
2 régulateur de pression d'alimentation 11 capteur de pression régulée, p
3 tube de mesure de pression avec connecteur de 12 capteur de température, T
transition
4 composant soumis à essai 13 régulateur de pression (pour les débits
d'échappement)
5 tube de mesure de pression avec connecteur de 14 débitmètre d'échappement
transition
6 électrovanne 15 électrovanne
7 débitmètre d'alimentation 16 générateur de signal
8 vanne de contrôle de débit (pour les débits 17 système d'acquisition de données (facultatif)
d'alimentation)
9 capteur de température d'alimentation, T
NOTE Si le composant soumis à essai fonctionne déjà avec un capteur externe, le placer au même endroit que
le capteur de mesure.
Figure 7 — Circuit d'essai pour la caractérisation de débit/pression et la régulation de pression
8.2 Exigences générales
8.2.1 Le composant soumis à essai doit être installé dans le circuit d'essai de manière à raccorder son
orifice d'alimentation au connecteur de transition et au tube de mesure de pression amont et son orifice
d'échappement vers l'atmosphère. Son orifice de sortie est raccordé à un connecteur de transition et à
un tube de mesure de pression permettant la mesure de la pression régulée, p .
8.2.2 Les tubes de mesure de pression et les connecteurs de transition doivent être conformes à
l'ISO 6358-1.
8.2.3 Les composants 1, 2, 3, 9 et 10 de la Figure 7 correspondent à la partie amont du circuit d'essai
utilisée pour les mesurages des débits d'alimentation. Ces composants doivent être également utilisés
pour les mesurages des débits d'échappement car l'orifice d'alimentation du composant soumis à essai
doit être raccordé au circuit d'alimentation, selon l'utilisation normale du composant.
8.2.4 Les composants 5, 6, 7, 8, 11 et 12 de la Figure 7 correspondent à la partie aval du circuit d'essai
utilisée pour les mesurages des débits d'alimentation.
8.2.5 Il convient que les conductances soniques du régulateur de pression d’alimentation 2 et de
l'électrovanne 11 soient au moins égales au double de la conductance sonique d'alimentation du
composant soumis à essai.
8.2.6 Les composants 5, 11, 12, 13, 14 et 15 de la Figure 7 correspondent à la partie amont du circuit
d'essai utilisée pour les mesurages des débits d'échappement.
8.2.7 Il convient que les conductances soniques du régulateur de pression 13 et de l'électrovanne 15
soient au moins égales au double de la conductance sonique d'échappement du composant soumis à
essai.
8.2.8 Les débitmètres doivent toujours être installés au niveau de l'orifice d'utilisation afin de
mesurer le débit réel d'alimentation ou d'échappement.
8.3 Modes opératoires d'essai
8.3.1 Mode opératoire d’essai initial
8.3.1.1 Installer l'appareil électropneumatique de distribution à commande continue de pression
conformément à la Figure 7, sans écoulement, l’électrovanne
...
記事のタイトル:ISO 10094-2:2021 - 気体圧動力 - 電気-気体圧縮空気バルブ - 第2部:サプライヤーの文書に含まれる主な特性を決定するための試験方法 記事内容:本文書は、ISO 10094-1に準拠する電気-気体圧縮空気連続圧力制御バルブのメーカーの文書に含まれる主な特性を定義するパラメータに関する試験手順と結果の提示方法を規定しています。この文書の目的は次の通りです:- 試験方法と試験結果の提示を標準化することにより、比較を容易にすること、および- これらの構成要素を圧縮空気システムに適切に適用するための支援をすることです。指定された試験は、連続圧力制御バルブの異なるタイプ間の比較を可能にすることを目的としており、各製造製品に対して実施する生産試験ではありません。本文書に記載された試験は、大気に排気される排出口を持つ部品を対象としています。 注意:非電気変調気体連続圧力制御バルブに関連する試験は、ISO 6953-2で指定されています。 注意2:電気-気体連続流量制御バルブに関連する試験は、ISO 10041-2で指定されています。 注意3:ISO 6953-3は等温タンクを使用した流量特性の代替動的試験方法を提供していますが、この方法では前向き流量およびリリーフ流量特性のヒステリシス曲線の減少する流量部分のみを測定します。
この記事では、ISO 10094-2:2021について説明されており、これは電気-空気圧制御バルブの主な特性を決定し、サプライヤーの資料に含めるためのテスト手法と結果の提示方法を規定した規格です。この規格の目的は、テスト手法とテスト結果の提示を標準化することによって比較を容易にし、これらのコンポーネントを圧縮空気システムに適切に適用することを支援することです。規定されているテストは、連続的な圧力制御バルブの異なるタイプ間の比較を可能にするものであり、製造された製品ごとに実施する製品テストではありません。この規格で説明されているテストは、大気に排気される排気ポートを持つコンポーネントに適用されます。注意事項1では、非電気変調空気圧連続圧力制御バルブに関連するテストがISO 6953-2で指定されていることが示されています。注意事項2では、電気-空気圧連続流量制御バルブに関連するテストがISO 10041-2で指定されていることが示されています。注意事項3では、流量特性に関連する別の動的テスト方法がISO 6953-3で提供されていることが示されていますが、この方法では順方向の流れとリリーフ流れ特性の減少する部分のみを測定します。
The article discusses ISO 10094-2:2021, which is a standard that specifies test methods for determining the main characteristics of electro-pneumatic pressure control valves. The purpose of this document is to standardize test methods and presentation of results, allowing for easier comparison between different types of valves and assisting in their proper application in compressed air systems. The tests described in the article are not meant to be conducted on each manufactured product, but rather serve as a means of comparison. The document also provides notes regarding other standards related to different types of pneumatic control valves.
이 문서는 ISO 10094-2:2021에 대해 논의하고 있으며, 이는 공기 압축 시스템에서의 적절한 응용을 지원하고 다양한 유형의 압력 제어 밸브 간의 비교를 용이하게 하기 위해 주요 특성을 결정하는 테스트 절차와 결과를 제시하는 방법을 명시하는 표준입니다. 이 표준에서 설명하는 테스트는 제조된 제품마다 수행되는 제품 테스트가 아니라 다른 유형의 연속 압력 제어 밸브 간의 비교를 가능하게 하는 것을 목적으로 합니다. ISO 6953-2에서 비전기적으로 변조된 공압 연속 압력 제어 밸브에 대한 테스트가 명시되어 있으며, ISO 10041-2에서는 전기-공압 연속 유량 제어 밸브에 대한 테스트가 명시되어 있습니다. 또한, ISO 6953-3은 유량 특성에 대한 대체 동적 테스트 방법을 제공하며, 흐름계 대신 등온 탱크를 사용합니다. 그러나 이 방법은 진행 흐름과 방출 흐름 특성의 감소하는 흐름 속도 부분만을 측정합니다.
The article discusses ISO 10094-2:2021, which is a standard that specifies test methods for determining the main characteristics of electro-pneumatic continuous pressure control valves. The purpose of the standard is to facilitate comparison between different types of valves and assist in their proper application in compressed air systems. The tests described in the standard are not meant to be performed on each manufactured product, but rather enable comparisons between valves. It is noted that tests for non-electrically modulated pneumatic valves are specified in ISO 6953-2, while tests for electro-pneumatic continuous flow control valves are specified in ISO 10041-2. Additionally, ISO 6953-3 provides an alternate test method for flow-rate characteristics.
기사 제목: ISO 10094-2:2021 - 기공 유압 압력 제어 밸브 - 제2부: 공급자의 문헌에 포함될 주요 특성을 결정하기 위한 시험 방법 기사 내용: 이 문서는 ISO 10094-1에 준하는 기공 유압 연속 압력 제어 밸브의 공급자 문헌에 포함될 주요 특성을 정의하는 매개변수에 대한 시험 절차와 결과를 제시하는 방법을 명시합니다. 이 문서의 목적은 다음과 같습니다: - 표준화된 시험 방법과 시험 결과의 제시를 통해 비교를 용이하게 하며, - 압축 공기 시스템에서 이러한 구성 요소가 올바르게 적용되도록 지원합니다. 지정된 시험은 연속 압력 제어 밸브의 다른 유형 간의 비교를 가능하게 할 목적으로 수행됩니다. 이러한 시험은 각 제품 제조별로 실시되는 생산 시험은 아닙니다. 이 문서에 설명된 시험은 대기로 배출되는 배기구가 있는 구성 요소를 대상으로 합니다. 참고: 비전기 조절 기계 기공 연속 압력 제어 밸브에 대한 시험은 ISO 6953-2에 명시되어 있습니다. 참고 2: 전기-기공 유압 흐름 제어 밸브에 대한 시험은 ISO 10041-2에 명시되어 있습니다. 참고 3: ISO 6953-3은 흐름계 대신 등온 탱크를 사용하여 유량 특성의 대체 동적 시험 방법을 제공합니다. 그러나 이 방법은 전진 유량 및 완화 유량 특성의 히스테리시스 곡선의 감소하는 유량 부분만을 측정합니다.














Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...