IEC 61558-2-4:1997
(Main)Safety of power transformers, power supply units and similar - Part 2: Particular requirements for isolating transformers for general use
Safety of power transformers, power supply units and similar - Part 2: Particular requirements for isolating transformers for general use
This part 2 of IEC 61558 applies to stationary or portable, single-phase or polyphase, air-cooled isolating transformers, associated or otherwise. It has the status of a group safety publication in accordance with IEC Guide 104. This part 2 supplements or modifies the corresponding clauses in IEC 61558-1, This Standard replaces Chapter I of IEC 742.
Sécurité des transformateurs, blocs d'alimentation et analogues - Partie 2: Règles particulières pour les transformateurs de séparation des circuits pour usage général
La présente partie 2 de la CEI 61558 est applicable aux transformateurs de séparation des circuits, fixes ou mobiles, monophasés ou polyphasés, à refroidissement par air, associés ou non. Elle a le statut de publication groupée de sécurité conformément au guide CEI 104. La présente partie 2 complète ou modifie les articles correspondants de la CEI 61558-1 La présente norme remplace le Chapitre I de la CEI 742.
General Information
Relations
Standards Content (Sample)
NORME CEI
INTERNATIONALE
IEC
61558-2-4
INTERNATIONAL
Première édition
STANDARD
First edition
1997-02
PUBLICATION GROUPÉE DE SÉCURITÉ
GROUP SAFETY PUBLICATION
Sécurité des transformateurs, blocs d'alimentation
et analogues –
Partie 2:
Règles particulières pour les transformateurs
de séparation des circuits pour usage général
Safety of power transformers, power supply units
and similar –
Part 2:
Particular requirements for isolating
transformers for general use
Numéro de référence
Reference number
CEI/IEC 61558-2-4: 1997
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est cons- The technical content of IEC publications is kept under
tamment revu par la CEI afin qu'il reflète l'état actuel de constant review by the IEC, thus ensuring that the content
la technique. reflects current technology.
Des renseignements relatifs à la date de reconfirmation de Information relating to the date of the reconfirmation of the
la publication sont disponibles auprès du Bureau Central de publication is available from the IEC Central Office.
la CEI.
Les renseignements relatifs à ces révisions, à l'établis- Information on the revision work, the issue of revised
sement des éditions révisées et aux amendements peuvent editions and amendments may be obtained from IEC
être obtenus auprès des Comités nationaux de la CEI et National Committees and from the following IEC
dans les documents ci-dessous: sources:
• Bulletin de la CEI • IEC Bulletin
• Annuaire de la CEI • IEC Yearbook
Publié annuellement Published yearly
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour régulièrement Published yearly with regular updates
Terminologie Terminology
En ce qui concerne la terminologie générale, le lecteur se For general terminology, readers are referred to IEC 50:
reportera à la CEI 50: Vocabulaire Electrotechnique Inter- International Electrotechnical Vocabulary (IEV), which is
national (VEI), qui se présente sous forme de chapitres issued in the form of separate chapters each dealing
séparés traitant chacun d'un sujet défini. Des détails with a specific field. Full details of the IEV will be
complets sur le VEI peuvent être obtenus sur demande. supplied on request. See also the IEC Multilingual
Voir également le dictionnaire multilingue de la CEI. Dictionary.
Les termes et définitions figurant dans la présente publi- The terms and definitions contained in the present publi-
cation ont été soit tirés du VEI, soit spécifiquement cation have either been taken from the IEV or have been
approuvés aux fins de cette publication. specifically approved for the purpose of this publication.
Symboles graphiques et littéraux Graphical and letter symbols
Pour les symboles graphiques, les symboles littéraux et les For graphical symbols, and letter symbols and signs
signes d'usage général approuvés par la CEI, le lecteur approved by the IEC for general use, readers are referred to
consultera: publications:
– la CEI 27: Symboles littéraux à utiliser en – IEC 27: Letter symbols to be used in electrical
électrotechnique; technology;
– la CEI 417: Symboles graphiques utilisables – IEC 417: Graphical symbols for use on
sur le matériel. Index, relevé et compilation des equipment. Index, survey and compilation of the
feuilles individuelles; single sheets;
– la CEI 617: Symboles graphiques pour schémas; – IEC 617: Graphical symbols for diagrams;
et pour les appareils électromédicaux, and for medical electrical equipment,
– la CEI 878: Symboles graphiques pour – IEC 878: Graphical symbols for electromedical
équipements électriques en pratique médicale. equipment in medical practice.
Les symboles et signes contenus dans la présente publi- The symbols and signs contained in the present publication
cation ont été soit tirés de la CEI 27, de la CEI 417, de la have either been taken from IEC 27, IEC 417, IEC 617
CEI 617 et/ou de la CEI 878, soit spécifiquement approuvés and/or IEC 878, or have been specifically approved for the
aux fins de cette publication. purpose of this publication.
Publications de la CEI établies par le IEC publications prepared by the same
même comité d'études technical committee
L'attention du lecteur est attirée sur les listes figurant à la fin The attention of readers is drawn to the end pages of this
de cette publication, qui énumèrent les publications de la publication which list the IEC publications issued by the
CEI préparées par le comité d'études qui a établi la technical committee which has prepared the present
présente publication. publication.
NORME
CEI
INTERNATIONALE
IEC
61558-2-4
INTERNATIONAL
Première édition
STANDARD
First edition
1997-02
PUBLICATION GROUPÉE DE SÉCURITÉ
GROUP SAFETY PUBLICATION
Sécurité des transformateurs, blocs d'alimentation
et analogues –
Partie 2:
Règles particulières pour les transformateurs
de séparation des circuits pour usage général
Safety of power transformers, power supply units
and similar –
Part 2:
Particular requirements for isolating
transformers for general use
IEC 1997 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni utilisée No part of this publication may be reproduced or utilized in
sous quelque forme que ce soit et par aucun procédé, électronique any form or by any means, electronic or mechanical, including
ou mécanique, y compris la photocopie et les microfilms, sans photocopying and microfilm, without permission in writing from
l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
PRICE CODE L
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61558-2-4 © CEI:1997
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
_________
SÉCURITÉ DES TRANSFORMATEURS, BLOCS D'ALIMENTATION
ET ANALOGUES –
Partie 2: Règles particulières pour les transformateurs de séparation
des circuits pour usage général
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes Internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques, représentent, dans la mesure
du possible un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 61558-2-4 a été établie par le comité d'études 96 de la CEI: Petits
transformateurs, bobines d'inductance et blocs d'alimentation. Transformateurs, bobines
d'inductance et blocs d'alimentation spéciaux: Prescriptions de sécurité.
Elle a le statut de publication groupée de sécurité conformément au guide CEI 104: Guide pour
la rédaction des normes de sécurité et rôle des comités chargés de fonctions pilotes de
sécurité et de fonctions groupées de sécurité (1984).
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
96/49/FDIS 96/72/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
La présente partie 2 est destinée à être utilisée avec la CEI 61558-1. Elle a été établie sur les
bases de la première édition (1997) de cette norme
La présente partie 2 complète ou modifie les articles correspondants de la CEI 61558-1, de
façon à la transformer en norme CEI: Règles particulières pour les transformateurs de
séparation des circuits pour usage général.
61558-2-4 © IEC:1997 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
_________
SAFETY OF POWER TRANSFORMERS, POWER SUPPLY UNITS
AND SIMILAR −
Part 2: Particular requirements for isolating transformers
for general use
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61558-2-4 has been prepared by IEC technical committee 96: Small
power transformers, reactors and power supply units and special transformers, reactors and
power supply units: Safety requirements.
It has the status of a group safety publication in accordance with IEC Guide 104: Guide for the
drafting of safety standards, and the role of Committees with safety pilot functions and safety
group functions (1984).
The text of this standard is based on the following documents:
FDIS Report on voting
96/49/FDIS 96/72/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This part 2 is intended to be used in conjunction with IEC 61558-1. It was established on the
basis of the first edition (1997) of that standard.
This part 2 supplements or modifies the corresponding clauses in IEC 61558-1, so as to convert that
publication into the IEC standard: Particular requirements for isolating transformers for general use.
– 4 – 61558-2-4 © CEI:1997
Lorsqu'un paragraphe particulier de la partie 1 n'est pas mentionné dans cette partie 2, ce
paragraphe s'applique pour autant qu'il soit raisonnable. Lorsque la présente norme spécifie
«addition», «modification» ou «remplacement», le texte correspondant de la partie 1 doit être
adapté en conséquence.
La présente norme remplace le Chapitre I de la CEI 742.
Dans la présente norme, les caractères d'imprimerie suivants sont employés:
– prescriptions proprement dites: caractères romains;
– modalités d'essais: caractères italiques;
– commentaires: petits caractères romains.
Dans le texte de la norme les mots en gras sont définis à l'article 3.
Les paragraphes ou figures complémentaires à ceux de la partie 1 sont numérotés à partir
de 101; les annexes complémentaires sont appelées AA, BB, etc.
61558-2-4 © IEC:1997 – 5 –
When a particular subclause of part 1 is not mentioned in this part 2, that subclause applies as
far as is reasonable. Where this standard states "addition", "modification" or "replacement", the
relevant text of part 1 is to be adapted accordingly.
This Standard replaces Chapter I of IEC 742.
In this standard, the following print types are used:
– requirements proper: in roman type;
– test specifications: in italic type;
– explanatory matter: in smaller roman type.
In the text of the standard the words in bold are defined in clause 3.
Subclauses which are additional to those in part 1 are numbered starting from 101;
supplementary annexes are entitled AA,BB, etc.
– 6 – 61558-2-4 © CEI:1997
SÉCURITÉ DES TRANSFORMATEURS, BLOCS D'ALIMENTATION
ET ANALOGUES –
Partie 2: Règles particulières pour les transformateurs de séparation
des circuits pour usage général
1 Domaine d’application
Remplacement:
La présente partie 2 de la CEI 61558 est applicable aux transformateurs de séparation des
circuits, fixes ou mobiles, monophasés ou polyphasés, à refroidissement par air, associés ou
non, ayant une tension primaire assignée ne dépassant pas 1000 V courant alternatif, une
fréquence assignée ne dépassant pas 500 Hz, la puissance assignée ne dépassant pas:
– 25 kVA pour les transformateurs monophasés;
– 40 kVA pour les transformateurs polyphasés.
Cette norme est aussi applicable aux transformateurs de séparation des circuits sans
limitation de la puissance; toutefois de tels transformateurs sont considérés comme des
transformateurs spéciaux et sont soumis à un agrément entre l'acheteur et le fournisseur.
La tension secondaire à vide ou la tension secondaire assignée ne dépasse pas 500 V
courant alternatif ou 708 V courant continu lissé.
NOTES
1 La tension secondaire à vide peut aller jusqu’à 1000 V en courant alternatif ou 1 415 V en courant continu
lissé en accord avec les règles nationales d’installation ou pour des applications spéciales.
2 Cette norme est applicable aux utilisés lorsque les règles
transformateurs de séparation des circuits
d’installation demandent la séparation de l’alimentation de certaines parties des circuits ou des équipements
(outils portatifs, tondeuses à gazon, etc.).
La tension secondaire à vide et/ou la tension secondaire assignée doit être supérieure à
50 V courant alternatif et/ou 120 V courant continu lissé.
La présente norme est également applicable aux transformateurs associés avec des parties
spécifiques d’équipements dans la mesure décidée par les comités techniques
correspondants.
Cette norme est applicable aux transformateurs secs. Les enroulements peuvent être
enrobés ou non enrobés.
NOTES
3 Pour les transformateurs à remplissage par diélectrique liquide ou par des matières pulvérulentes telles que
le sable, des prescriptions supplémentaires sont à l’étude.
4 Pour l’emploi dans des emplacements présentant des conditions particulières d’environnement les règles
spéciales peuvent être exigées, conformément à la CEI 364-5-51.
2 Références normatives
L’article de la partie 1 est applicable.
3 Définitions
L’article de la partie 1 est applicable.
61558-2-4 © IEC:1997 – 7 –
SAFETY OF POWER TRANSFORMERS, POWER SUPPLY UNITS
AND SIMILAR −
Part 2: Particular requirements for isolating transformers
for general use
1 Scope
Replacement:
This part 2 of IEC 61558 applies to stationary or portable, single-phase or polyphase, air-cooled
isolating transformers, associated or otherwise, having a rated supply voltage not exceeding
1000 V a.c. and rated frequency not exceeding 500 Hz, the rated output not exceeding:
– 25 kVA for single-phase transformers;
– 40 kVA for polyphase transformers.
This standard is also applicable to isolating transformers without limitation of the rated
output, however such transformers are considered as special transformers and are subjected
to an agreement between the purchaser and the supplier.
The no-load output voltage or the rated output voltage does not exceed 500 V a.c. or 708 V
ripple-free d.c.
NOTES
1 The no-load output voltage or the rated output voltage may be up to 1000 V a.c. or 1 415 V ripple-free d.c.
to be in accordance with the national wiring rules or for a special purpose.
2 This standard is applicable to those isolating transformers used when the installation rules call for the
separation of circuits for the supply of certain parts of the circuits or of equipment (portable tools, lawn mowers,
etc.).
The no-load output voltage and/or the rated output voltage shall exceed 50 V a.c. and/or
120 V ripple-free d.c.
This standard is also applicable to transformers associated with specific items of equipment,
to the extent decided upon by the relevant IEC technical committees.
This standard is applicable to dry type transformers. The windings may be encapsulated or
non-encapsulated.
NOTES
3 For transformers filled with liquid dielectric or pulverized material, such as sand, additional requirements are
under consideration.
4 In locations where special environmental conditions prevail, particular requirements may be necessary in
accordance with IEC 364-5-51.
2 Normative references
This clause of part 1 is applicable.
3 Definitions
This clause of part 1 is applicable.
– 8 – 61558-2-4 © CEI:1997
4 Prescriptions générales
L’article de la partie 1 est applicable.
5 Généralités sur les essais
L’article de la partie 1 est applicable.
6 Caractéristiques assignées
L’article de la première partie est applicable à l’exception de ce qui suit:
Addition:
6.101 La tension secondaire assignée ne doit pas dépasser 250 V courant alternatif pour
les transformateurs mobiles monophasés et 500 V courant alternatif ou 708 V courant
continu lissé pour les autres transformateurs.
NOTE – La tension secondaire assignée peut aller jusqu’à 1000 V en courant alternatif ou 1415 V en courant
continu lissé en accord avec les règles nationales d’installation ou pour des applications spéciales.
Les valeurs préférentielles de la tension secondaire assignée sont:
– 120 V et 230 V pour les transformateurs mobiles monophasés;
– 72 V, 120 V, 230 V, 400 V et 440 V pour les autres transformateurs.
6.102 La puissance assignée ne doit pas dépasser 25 kVA pour les transformateurs
monophasés et 40 kVA pour les transformateurs polyphasés.
Les valeurs préférentielles de la puissance assignée sont:
– 25 VA, 40 VA, 63 VA, 100 VA, 160 VA, 250 VA, 400 VA, 630 VA, 1000 VA, 1600 VA,
2500 VA, 4000 VA, 6300 VA et 10 kVA, 16 kVA et 25 kVA pour les transformateurs
monophasés;
– 630 VA, 1000 VA, 1600 VA, 2500 VA, 4000 VA, 6300 VA, 10 kVA, 16 kVA, 25 kVA et
40 kVA pour les transformateurs polyphasés.
La conformité aux prescriptions de 6.101 et 6.102 est vérifiée par examen du marquage.
6.103 La fréquence assignée de doit pas dépasser 500 Hz.
6.104 La tension d'alimentation assignée ne doit pas dépasser 1000 V courant alternatif.
7 Classification
L’article de la partie 1 est applicable.
8 Marquage et indications
L’article de la partie 1 est applicable à l’exception de ce qui suit:
61558-2-4 © IEC:1997 – 9 –
4 General requi
...