Surge arresters - Part 6: Surge arresters containing both series and parallel gapped structures - Rated 52 kV and less

This standard basically applies to all metal-oxide surge arresters with gaps and housed in either porcelain or polymeric housings. This standard also specifies requirements and tests for metal-oxide surge arresters with internal series gaps,with rated voltages of 52KV and below.

General Information

Status
Published
Publication Date
13-Aug-2002
Technical Committee
Drafting Committee
Current Stage
DELPUB - Deleted Publication
Start Date
22-May-2019
Completion Date
30-Mar-2018
Ref Project

Relations

Standard
IEC 60099-6:2002 - Surge arresters - Part 6: Surge arresters containing both series and parallel gapped structures - Rated 52 kV and less Released:8/14/2002 Isbn:2831865360
English language
46 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


INTERNATIONAL IEC
STANDARD
60099-6
First edition
2002-08
Surge arresters –
Part 6:
Surge arresters containing both series
and parallel gapped structures –
Rated 52 kV and less
Reference number
Publication numbering
As from 1 January 1997 all IEC publications are issued with a designation in the

60000 series. For example, IEC 34-1 is now referred to as IEC 60034-1.

Consolidated editions
The IEC is now publishing consolidated versions of its publications. For example,

edition numbers 1.0, 1.1 and 1.2 refer, respectively, to the base publication, the

base publication incorporating amendment 1 and the base publication incorporating

amendments 1 and 2.
Further information on IEC publications
The technical content of IEC publications is kept under constant review by the IEC,
thus ensuring that the content reflects current technology. Information relating to
this publication, including its validity, is available in the IEC Catalogue of
publications (see below) in addition to new editions, amendments and corrigenda.
Information on the subjects under consideration and work in progress undertaken
by the technical committee which has prepared this publication, as well as the list
of publications issued, is also available from the following:
• IEC Web Site (www.iec.ch)
• Catalogue of IEC publications
The on-line catalogue on the IEC web site (www.iec.ch/catlg-e.htm) enables
you to search by a variety of criteria including text searches, technical
committees and date of publication. On-line information is also available on
recently issued publications, withdrawn and replaced publications, as well as
corrigenda.
• IEC Just Published
This summary of recently issued publications (www.iec.ch/JP.htm) is also
available by email. Please contact the Customer Service Centre (see below) for
further information.
• Customer Service Centre
If you have any questions regarding this publication or need further assistance,
please contact the Customer Service Centre:
Email: custserv@iec.ch
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
INTERNATIONAL IEC
STANDARD
60099-6
First edition
2002-08
Surge arresters –
Part 6:
Surge arresters containing both series
and parallel gapped structures –
Rated 52 kV and less
 IEC 2002  Copyright - all rights reserved
No part of this publication may be reproduced or utilized in any form or by any means, electronic or
mechanical, including photocopying and microfilm, without permission in writing from the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch  Web: www.iec.ch
PRICE CODE
Commission Electrotechnique Internationale
X
International Electrotechnical Commission
Международная Электротехническая Комиссия
For price, see current catalogue

– 2 – 60099-6  IEC:2002(E)
CONTENTS
FOREWORD . 4

INTRODUCTION .5

1 General . 6

1.1 Scope . 6

1.2 Normative references . 6

2 Definitions . 7
3 Identification and classification .14
3.1 Arrester identification.14
3.2 Arrester classification .14
4 Standard ratings .15
4.1 Standard rated voltages.15
4.2 Standard rated frequencies.15
4.3 Standard nominal discharge currents.15
4.4 Service conditions .15
5 Requirements .16
5.1 Insulation withstand of the arrester housing.16
5.2 Reference voltage .16
5.3 Impulse protective levels .16
5.4 Partial discharges .16
5.5 Seal leakage.16
5.6 Thermal stability .16
5.7 Long duration current impulse withstand.16
5.8 Operating duty.17
5.9 Power frequency voltage versus time characteristics of an arrester .17
5.10 Short-circuit withstand .18
5.11 Disconnectors.18
5.12 Requirements for internal and external grading components .18
5.13 Power frequency sparkover .18
5.14 Grading current .18
5.15 Weather ageing tests.18

6 General procedures .18
6.1 Measuring equipment and accuracy.18
6.2 Reference voltage measurements.19
6.3 Test samples .19
7 Type tests (design tests).19
7.1 General .19
7.2 Insulation withstand tests on the arrester housing.20
7.3 Impulse protective level tests.21
7.4 Long duration current impulse withstand test .25
7.5 Operating duty tests .27
7.6 Tests of arrester disconnectors.33
7.7 Power frequency voltage sparkover tests.35
7.8 Moisture ingress tests.35
7.9 Weather ageing tests.35

60099-6  IEC:2002(E) – 3 –
8 Routine tests and acceptance tests.36

8.1 Routine tests .36

8.2 Acceptance tests .36

Annex A (normative) Abnormal service conditions .39

Annex B (normative) Test to verify thermal equivalency between complete arrester

and arrester section .40

Annex C (normative) Procedure to verify the power frequency voltage versus time
characteristics of an arrester.41

Annex D (normative) Artificial pollution testing of metal-oxide surge arresters
containing gapped structures .42
Annex E (informative) Typical information given with inquiries and tenders .43
Annex F (informative) Typical maximum protective levels.45
Bibliography.46
Figure 1 – Power losses of arrester at elevated temperatures vs. time .30
Table 1 – Arrester classification and tests .14
Table 2 – Steps of rated voltages.15
Table 3 – Peak currents for switching impulse residual voltage tests.22
Table 4 – Parameters for the line discharge test (10 000 A arresters) .26
Table 5 – Requirements for the long-duration current impulse test
on 5 000 A and 2 500 A arresters.27
Table 6 – Arrester design and ageing test requirements.28
Table 7 – Determination of elevated rated and continuous operating voltages.30
Table 8 – Requirements for high current impulses.32
Table 9 – Weather ageing test selection.35
Table 10 – Summary of high current operating duty test (see 7.5.3) .38
Table 11 – Thermal stability test .38
Table F.1 – Typical maximum protective levels for 10 kA, 5 kA, 2,5 kA and 1,5 kA
arresters per unit of rated voltage .45

– 4 – 60099-6  IEC:2002(E)
INTERNATIONAL ELECTROTECHNICAL COMMISSION

___________
SURGE ARRESTERS –
Part 6: Surge arresters containing both series

and parallel gapped structures –

Rated 52 kV and less
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International
Organization for Standardization (ISO) in accordance with conditions determined by agreement between the
two organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard lEC 60099-6 has been prepared by lEC technical committee 37: Surge
arresters.
The text of this standard is based on the following documents:
FDIS Report on voting
37/282/FDIS 37/283/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
Annexes A, B, C and D form an integral part of this standard.
Annexes E and F are for information only.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 3.
The committee has decided that the contents of this publication will remain unchanged until 2004.
At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
60099-6  IEC:2002(E) – 5 –
INTRODUCTION
This part of IEC 60099 presents the minimum criteria for the requirements and testing of

metal-oxide surge arresters containing gapped structures that are applied to a.c. power

systems.
Arresters covered by this standard can be applied to overhead installations in place of the

non-linear type arresters covered in lEC 60099-1 and IEC 60099-4.

An accelerated ageing procedure is incorporated in the standard to simulate the long-term

effects of voltage and temperature on the arrester. This is necessary since during the

arrester's service life the gaps and resistor elements will have portions of the system power
frequency voltage continuously applied across them.

– 6 – 60099-6  IEC:2002(E)
SURGE ARRESTERS –
Part 6: Surge arresters containing both series

and parallel gapped structures –

Rated 52 kV and less
1 General
1.1 Scope
This part of IEC 60099 applies to non-linear metal-oxide resistor type surge arresters with
spark gaps designed to limit voltage surges on a.c. power circuits.
This standard basically applies to all metal-oxide surge arresters with gaps and housed in
either porcelain or polymeric housings.
This standard specifies requirements and tests for metal-oxide surge arresters with internal
series gaps, with rated voltages 52 kV and below.
The following arrester types and ratings are presently under consideration, but are not
addressed in this standard. They will not be addressed until more information can be
ascertained on the individual subjects:
• series gapped arresters above 54 kV;
• externally gapped arresters, all ratings;
• shunt gapped arresters, all ratings;
• line discharge class 2, 3, 4 and 5.
1.2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
lEC 60060-1:1989, High-voltage test techniques – Part 1: General definitions and test
requirements
IEC 60060-2:1994, High-voltage test techniques – Part 2: Measuring systems
lEC 60099-1:1991, Surge arresters – Part 1: Non-linear resistor type gapped surge arresters

for a.c. systems
lEC 60099-3:1990, Surge arresters – Part 3: Artificial pollution testing of surge arresters
IEC 60099-4:1991, Surge arresters – Part 4: Metal-oxide surge arresters without gaps for a.c.
systems
Amendment 1 (1998)
Amendment 2 (2001)
IEC 60270: 2000, High-voltage test techniques – Partial discharge measurements
___________
A consolidated edition 1.2 exists (2001) that includes edition 1.0 (1991), its amendment 1 (1998) and
amendment 2 (2001).
60099-6  IEC:2002(E) – 7 –
2 Definitions
For the purposes of this part of IEC 60099, the following definitions apply.

2.1
metal-oxide surge arrester without gaps

arrester having non-linear metal-oxide resistors connected in series and/or in parallel without

any integrated series or parallel spark gaps

NOTE See 2.55 for metal-oxide surge arrester with series gapped structures.

2.2
non-linear metal-oxide resistor
part of the surge arrester which by its non-linear voltage versus current characteristics acts as
a low resistance to overvoltages, thus limiting the voltage across the arrester terminals, and
as a high resistance at normal power frequency voltage
2.3
internal grading system of an arrester
grading impedance, in particular linear/non-linear resistors and/or grading capacitors
connected in parallel to one or to a group of non-linear metal-oxide resistors and/or series
gap, to control the voltage distribution along the arrester and/or between the metal oxide
resistors and gaps
2.4
grading ring of an arrester
metal part usually circular in shape, mounted to modify electrostatically the voltage
distribution along the arrester
2.5
section of an arrester
complete, suitably assembled part of an arrester necessary to represent the behaviour of a
complete arrester with respect to a particular test
NOTE A section of an arrester is not necessarily a unit of an arrester.
2.6
unit of an arrester
completely housed part of an arrester which may be connected in series and/or in parallel with
other units to construct an arrester of higher voltage and/or current rating
NOTE A unit of an arrester is not necessarily a section of an arrester.

2.7
pressure relief device of an arrester
means for relieving internal pressure in an arrester and preventing violent shattering of the
housing following prolonged passage of fault current or internal flashover of the arrester
2.8
rated voltage of an arrester, U
r
maximum permissible r.m.s. value of power frequency voltage between its terminals at which
it is designed to operate correctly under temporary overvoltage conditions as established in
the operating duty tests, see 7.5
NOTE 1 The rated voltage is used as a reference parameter for the specification of operating characteristics.
NOTE 2 The rated voltage as defined in this standard is the 10 s power frequency voltage used in the operating
duty test after high current. Tests used to establish the voltage rating in the lEC 60099 series, as well as some
national standards, involve the application of repetitive impulses at nominal impulse current with power frequency
voltage applied. Attention is drawn to the fact that these two methods used to establish rating do not necessarily
produce equivalent values. (A resolution to this discrepancy is under consideration.)

– 8 – 60099-6  IEC:2002(E)
2.9
continuous operating voltage of an arrester, U
c
continuous operating voltage is the designated permissible r.m.s. value of power frequency

voltage that may be applied continuously between the arrester terminals in accordance

with 7.5
2.10
rated frequency of an arrester

frequency of the power system on which the arrester is designed to be used

2.11
disruptive discharge
phenomena associated with the failure of insulation under electric stress, which include a
collapse of voltage and the passage of current
NOTE 1 The term applies to electrical breakdowns in solid, liquid and gaseous dielectric, and combinations of
these.
NOTE 2 A disruptive discharge in a solid dielectric produces permanent loss of electric strength. In a liquid or
gaseous dielectric the loss may be only temporary.
2.12
puncture (breakdown)
disruptive discharge through a solid
2.13
flashover
disruptive discharge over a solid surface
2.14
impulse
unidirectional wave of voltage or current which without appreciable oscillations rises rapidly to
a maximum value and falls – usually less rapidly – to zero with small, if any, excursions of
opposite polarity
NOTE The parameters which define a voltage or current impulse are polarity, peak value, front time and time to
half value on the tail.
2.15
designation of an impulse shape
combination of two numbers, the first representing the virtual front time (T ) and the second
the virtual time to half value on the tail (T ), written as T /T , both in µs, the sign “/” having no
2 1 2
mathematical meaning
2.16
steep current impulse
current impulse with a virtual front time of 1 µs with limits in the adjustment of equipment such
that the measured values are from 0,9 µs to 1,1 µs and the virtual time to half value on the tail
not longer than 20 µs
NOTE The time to half value on the tail is not critical and may have any tolerance during the residual voltage type
tests, see 7.3.1.
2.17
lightning current impulse
an 8/20 current impulse with limits on the adjustment of equipment such that the measured
values are from 7 µs to 9 µs for the virtual front time and from 18 µs to 22 µs for the time to
half value on the tail
NOTE The time to half value on the tail is not critical and may have any tolerance during the residual voltage type
tests, see 7.3.1.
60099-6  IEC:2002(E) – 9 –
2.18
long duration current impulse
rectangular impulse which rises rapidly to maximum value, remains substantially constant for

a specified period and then falls rapidly to zero. The parameters which define a rectangular

impulse are polarity, peak value, virtual duration of the peak and virtual total duration.

2.19
peak (crest) value of an impulse

maximum value of a voltage or current impulse

NOTE Superimposed oscillations may be disregarded, see 7.4.2 c) and 7.5.3.2 e).

2.20
front of an impulse
part of an impulse which occurs prior to the peak
2.21
tail of an impulse
part of an impulse which occurs after the peak
2.22
virtual origin of an impulse
point on a graph of voltage versus time or current versus time determined by the intersection
between the time axis at zero voltage or zero current and the straight line drawn through two
reference points on the front of the impulse
NOTE 1 For current impulses the reference points are 10 % and 90 % of the peak value.
NOTE 2 This definition applies only when scales of both ordinate and abscissa are linear.
NOTE 3 If oscillations are present on the front, the reference points at 10 % and 90 % should be taken on the
mean curve drawn through the oscillations.
2.23
virtual front time of a current impulse, T
time in μs equal to 1,25 multiplied by the time in µs for the current to increase from 10 % to
90 % of its peak value
NOTE If oscillations are present on the front, the reference points at 10 % and 90 % should be taken on the mean
curve drawn through the oscillations.
2.24
virtual steepness of the front of an impulse
quotient of the peak value and the virtual front time of an impulse
2.25
virtual time to half value on the tail of an impulse, T
time interval between the virtual origin and the instant when the voltage or current has
decreased to half its peak value, expressed in µs
2.26
virtual duration of the peak of a rectangular impulse
time during which the amplitude of the impulse is greater than 90 % of its peak value
2.27
virtual total duration of a rectangular impulse
time during which the amplitude of the impulse is greater than 10 % of its peak value
NOTE If small oscillations are present on the front, a mean curve should be drawn in order to determine the time
at which the 10 % value is reached.

– 10 – 60099-6  IEC:2002(E)
2.28
peak (crest) value of opposite polarity of an impulse

maximum amplitude of opposite polarity reached by a voltage or current impulse when it

oscillates about zero before attaining a permanent zero value

2.29
discharge current of an arrester

impulse current which flows through the arrester

2.30
nominal discharge current of an arrester, I
n
peak value of lightning current impulse (see 2.17 and table 1) which is used to classify an
arrester
2.31
high current impulse of an arrester
peak value of discharge current having a 4/10 impulse shape which is used to test the stability
of the arrester on direct lightning strokes
2.32
switching current impulse of an arrester
peak value of discharge current having a virtual front time greater than 30 µs but less than
100 µs and a virtual time to half value on the tail of roughly twice the virtual front time
2.33
continuous current of an arrester
continuous current is the current flowing through the arrester when energized at the
continuous operating voltage, expressed either by its r.m.s. or peak value
NOTE The continuous current, which consists of a resistive and a capacitive component, may vary with
temperature, stray capacitance and external pollution effects. The continuous current of a test sample may,
therefore, not be the same as the continuous current of a complete arrester.
2.34
reference current of an arrester
peak value (the higher peak value of the two polarities if the current is asymmetrical) of the
resistive component of a power frequency current used to determine the reference voltage of
the arrester
NOTE 1 The reference current should be high enough to make the effects of stray capacitance at the measured
reference voltage of the arrester units (with designed grading system) negligible and should be specified by the
manufacturer.
NOTE 2 Depending on the nominal discharge current and/or line discharge class of the arrester, the reference
current will be typically in the range of 0,05 mA to 1,0 mA per square centimetre of disc area for single column
arresters.
2.35
reference voltage of the main series metal-oxide resistors
peak value of power frequency voltage divided by 2 applied to the main series metal-oxide
resistors of arrester to obtain the reference current
NOTE The reference voltage of a multi-unit arrester is the sum of the reference voltages of the main series metal-
oxide resistors of the individual units.
2.36
residual voltage of an arrester, U
res
peak value of voltage that appears between the terminals of an arrester during the passage of
discharge current
NOTE The term “discharge voltage” is used in some countries.

60099-6  IEC:2002(E) – 11 –
2.37
power frequency withstand voltage versus time characteristic of an arrester

(temporary overvoltage, TOV)
power frequency withstand voltage versus time characteristic showing maximum time dura-

tions for which corresponding power frequency voltages may be applied to arresters without

causing damage or thermal instability under specified conditions in accordance with 5.9.

2.38
prospective current of a circuit

current which would flow at a given location in a circuit if it were short-circuited at that
location by a link of negligible impedance

2.39
protective characteristics of an arrester
Regarded as a combination of the following:
a) residual voltage for steep current impulse and front-of-wave sparkover according to 7.3.2
and 7.3.6.2
b) residual voltage versus discharge current characteristic for lightning impulses and the
1,2/50 impulse sparkover according to 7.3.3 and 7.3.7.2
c) residual voltage for switching impulse and the switching impulse sparkover according
to 7.3.4 and 7.3.8.2
2.40
thermal runaway of an arrester
situation when the sustained power loss of an arrester exceeds the thermal dissipation
capability of the housing and connections, leading to a cumulative increase in the temperature
of the resistor elements culminating in failure
2.41
thermal stability of an arrester
arrester is thermally stable if, after an operating duty causing temperature rise, the
temperature of the resistor elements decreases with time when the arrester is energized
at specified continuous operating voltage and at specified ambient conditions
2.42
arrester disconnector
device for disconnecting an arrester from the system in the event of arrester failure, to
prevent a persistent fault on the system and to give visible indication of the failed arrester
NOTE The device is not required to clear arrester fault current.

2.43
type tests
(design tests)
tests, which are made upon the completion of the development of a new arrester design,
to establish representative performance and to demonstrate compliance with the relevant
standard
NOTE Once made, these tests need not be repeated unless the design is changed so as to modify its
performance. In such a case only the relevant tests need be repeated.
2.44
routine tests
tests made on each arrester, or on parts and materials, as required, to ensure that the
product meets the design specifications

– 12 – 60099-6  IEC:2002(E)
2.45
acceptance tests
tests which are made when it has been agreed between the manufacturer and the purchaser

that the arresters or representative samples of an order are to be tested

2.46
sparkover of an arrester
disruptive discharge between the electrodes of the gaps of an arrester

2.47
follow current of an arrester
current from the connected power source which flows through an arrester following the
passage of discharge current
2.48
average sparkover voltage
This can be sub-divided into two types:
2.48.1
power frequency sparkover voltage
average of at least five successive power frequency sparkovers
2.48.2
lightning impulse sparkover voltage
average of at least five successive lightning impulse sparkovers
2.49
impulse sparkover voltage of an arrester
highest value of voltage attained before sparkover during an impulse of given waveshape and
polarity applied between the terminals of an arrester
2.50
front-of-wave sparkover voltage of an arrester
impulse sparkover voltage obtained on the wavefront of the voltage which increases linearly
with time
2.51
standard lightning impulse sparkover voltage of an arrester
lowest prospective peak value of a standard lightning voltage impulse which, when applied to
an arrester, causes sparkover on every application
2.52
time to sparkover of an arrester
time interval between virtual origin and the instant of sparkover of the arrester, expressed
in µs
2.53
impulse sparkover voltage-time curve
curve which relates the impulse sparkover of the voltage to the time to sparkover
2.54
grading current
peak value of current flowing through the arrester while power frequency voltage is applied
2.55
metal-oxide surge arrester with gapped structures
arrester having non-linear metal-oxide resistors connected in series and/or in parallel with any
internal or external series or shunt spark gaps

60099-6  IEC:2002(E) – 13 –
2.56
power frequency sparkover voltage

value of the power frequency voltage, measured as the peak value divided by 2 applied

between the terminals of an arrester, which causes sparkover

2.57
line arrester
type of arrester that is commonly applied to power systems to reduce the risk of insulator

flashover during a lightning transient

NOTE It is not generally used to protect the insulator from other types of transients such as switching surges.

Neither is it generally used to protect any equipment other than line insulators.

2.58
impulse protective levels
These can be sub-divided into three types:
2.58.1
fast front protective level
highest of either the steep current residual voltage at (I ) or the front-of-wave impulse
n
sparkover voltage
2.58.2
standard lightning impulse protective level
highest of either the residual voltage at nominal current (I ) or 1,2/50 lighting impulse
n
sparkover voltage
2.58.3
switching impulse protective level
highest of either the maximum residual voltage for the specified switching current or the
specified switching impulse sparkover voltage
2.59
main series metal oxide resistors
resistors that carry energy during an impulse, not to be confused with resistors that separate
gaps for voltage grading
NOTE Measurement of reference voltage is necessary for the selection of a correct test sample in the operating
duty test, see 6.2
2.60
series gap
intentional gap(s), between spaced electrodes in series with one or more metal-oxide

resistors, across which all or part of the imparted terminal voltage appears
2.61
shunt gap
intentional gap(s) between spaced electrodes electrically in parallel with one or more main
metal-oxide resistors
2.62
switching voltage impulse
impulse voltage having a virtual front time greater than 30 µs

– 14 – 60099-6  IEC:2002(E)
3 Identification and classification

3.1 Arrester identification
Metal-oxide surge arresters containing gapped structures shall be identified by the following

minimum information which shall appear on a nameplate permanently attached to the arrester:

– continuous operating voltage;

– rated voltage;
– rated frequency, only if other than one of the standard frequencies, see 4.2;

– nominal discharge current;
– short-circuit withstand current rating in kA r.m.s. (for arresters with short-circuit withstand
ratings);
– manufacturer's name or trade mark, type and identification of the complete arrester;
– identification of the assembling position of the unit (for multi-unit arresters only);
– year of manufacture.
3.2 Arrester classification
Surge arresters are classified by their standard nominal discharge currents and they shall
meet at least the test requirements and performance characteristics specified in table 1.
Table 1 – Arrester classification and tests
Standard nominal discharge current
10 000 A 5 000 A 2 500 A 1 500 A
1 Rated voltage U (kV ) 3 ≤ U ≤ 52 3 ≤ U ≤ 52 3 ≤ U ≤ 52 3 ≤ U ≤ 52
r
RMS r r r r
2 Insulation withstand tests on arrester housings 7.2 7.2 7.2 7.2
3 Residual voltage tests: Table F.1 Table F.1 Table F.1 Table F.1
a) steep current impulse residual voltage test 7.3.2 7.3.2 7.3.2 7.3.2
b) lighting impulse residual voltage test 7.3.3 7.3.3 7.3.3 7.3.3
c) switching impulse residual voltage test 7.3.4 Not required Not required Not required
4 Sparkover voltage tests:
a) front-of-wave impulse sparkover voltage test 7.3.6 7.3.6 7.3.6 7.3.6
b) lightning impulse sparkover voltage test 7.3.7 7.3.7 7.3.7 7.3.7
c) switching impulse sparkover voltage test 7.3.8 Not required Not required Not required

5 Long duration current impulse withstand test 7.4.3 7.4.3 7.4.3 Not required
6 High current impulse operating duty test 7.5.3 and 7.5.3 and 7.5.3 and 7.5.3 and
table 8 table 8 table 8 table 8
7 Power frequency voltage versus time curve 5.9 5.9 5.9 5.9
8 Short-circuit withstand (when it applies) 5.10 5.10 Not required Not required
9 Arrester disconnector (when fitted) 7.6 7.6 7.6 7.6
10 Power frequency sparkover voltage test 7.7 7.7 7.7 7.7
11 Moisture ingress tests 7.8 7.8 7.8 7.8
12 Weather ageing tests (polymeric housing only) 7.9 and 7.9 and 7.9 and table 7.9 and
table 9 table 9 9 table 9
13 Artificial pollution test Annex D Annex D Annex D Annex D

60099-6  IEC:2002(E) – 15 –
4 Standard ratings
4.1 Standard rated voltages
Standard values of rated voltages for arresters (in kV r.m.s.) are specified in table 2 in equal

voltage steps within specified voltage ranges:

Table 2 – Steps of rated voltages

Range of rated voltage Steps of rated voltage

kV kV r.m.s.
3-30 1 kV
30-52 3 kV
NOTE All other ratings are considered non-standard but are still subject to conformance to this standard.
4.2 Standard rated frequencies
The standard rated frequencies are 50 Hz and 60 Hz.
4.3 Standard nominal discharge currents
The standard nominal 8/20 discharge currents are: 10 000 A, 5 000 A, 2 500 A and 1 500 A,
see 2.30.
4.4 Service conditions
4.4.1 Normal service conditions
Surge arresters that conform to this standard shall be suitable for normal operation under the
following normal service conditions:
a) ambient air temperature within the range of –40 °C to +40°C;
b) solar radiation;
NOTE The effects of maximum solar radiation (1,1 kW/m ) have been taken into account by preheating the
test specimen in the type tests. If there are other heat sources near the arrester, the application of the arrester
shall be subject to an agreement between the manufacturer and the purchaser.
c) altitude not exceeding 1 000 m;
d) frequency of the a.c. power supply shall not be less than 48 Hz and not exceeding 62 Hz;
e) power frequency voltage applied continuously between the terminals of the arrester not
exceeding its continuous operating voltage;

f) mechanical conditions (under consideration);
g) pollution conditions (no requirement at this time).
4.4.2 Abnormal service conditions
Surge arresters subject to other than normal application or service conditions may require
special consideration in design, manufacture or application. The use of this standard in case
of abnormal service conditions is subject to agreement between the manufacturer and the
purchaser. A list of possible abnormal service conditions is given in annex A.

– 16 – 60099-6  IEC:2002(E)
5 Requirements
5.1 Insulation withstand of the arrester housing

The arrester housing shall withstand the following voltages when tested according to 7.2:

– the standard lightning impulse protection level of the arresters (see 2.58.2) multiplied

by 1,3;
NOTE The 1,3 factor covers variations in atmospheric conditions and discharge currents higher than nominal.

– power frequency voltage in wet conditions for arrester housings for outdoor use and in dry
conditions for arrester housings for indoor use.
Housings of 1 500 A, 2 500 A and 5 000 A arresters shall withstand a power frequency
voltage with a peak value equal to the standard lightning impulse protection level (see 2.58.2)
multiplied by 0,88 for a duration of 1 min.
Housings of 10 000 A arresters shall withstand a power frequency voltage with a peak value
equal to the switching impulse protection level multiplied by 1,06 for a duration of 1 min
(see 2.58.3)
5.2 Reference voltage
The reference voltage of each of the main series metal-oxide resistors shall be measured by
the manufacturer at the reference current selected by the manufacturer, see 6.2. The
minimum reference voltage of the main series of metal-oxide prorated section shall be stated
in the type test report.
5.3 Impulse protective levels
The arrester shall be tested to determine whether the protective level for a specified wave-
shape (7.3.6, 7.3.7, 7.3.8) is a function of the maximum impulse sparkover value or residual
voltage (7.3.2, 7.3.3, 7.3.4), whichever is greatest.
5.4 Partial discharges
When required, the partial discharge level in the arrester energized at 1,05 times its
continuous operating voltage shall not exceed 10 pC, see 8.1 b) and 8.2.1 c).
5.5 Seal leakage
Arrester units with sealed housings containing gaseous material shall meet the gas leakage

requirements of 8.1 c). Arresters with polymeric housings shall be tested per the moisture
ingress test see 7.8.
5.6 Thermal stability
When agreed between manufacturer and purchaser, a special thermal stability test may be
performed according to 8.2.2.
5.7 Long duration current impulse withstand
Arresters shall withstand long duration currents as verified during type tests, see 7.4.
For 10 000 A arresters, the long duration withstand is demonstrated by a line discharge test
(see 7.4.2) with the line discharge class specified by the user.

60099-6  IEC:2002(E) – 17 –
For 5 000 A and 2 500 A arresters, the long duration withstand is demonstrated by a long

duration impulse test, see 7.4.3.

The samples shall be considered to have passed if all the following requirements are met:

a) The residual voltage at nominal discharge current has not changed by more than 5 %.

b) The average power frequency sparkover voltage or average standard lightning impulse
sparkover voltage has not changed by more than 5 %.

c) If the manufacturer declares that the resistors may be removed, then visual examination

of the test samples after the test shall reveal no evidence of puncture, flashover, cracking

or other significant damage of the metal-oxide resistors, or the gap structure. In other
cases, visual inspection only applies to external parts. To check the integrity of the
internal parts, an additional long duration impulse shall be performed after the sample
has cooled down to ambient temperature to verify that no damage occurred. If the sample
withstood the nineteenth long duration current impulse with no damage (checked by
oscillographic records) then the sample has passed the test.
5.8 Operating duty
Arresters shall be able to withstand the combination of stresses arising in service as
demonstrated by the operating duty tests, see 7.5. These stresses shall not cause damage or
thermal runaway.
For 1 500 A, 2 500 A, 5 000 A and 10 000 A line discharge class 1 arresters, this is
demonstrated by the high current impulse operating duty test, see 7.5.3 and table 8.
The arrester has passed the test if:
a) residual voltage has not changed by more than 5 %;
b) the average power frequency sparkover voltage or average standard lightning impulse
sparkover voltage has not changed by more than 5 %;
c) if the manufacturer declares that the internal components may be removed, then visual
examination of the test samples after the test shall reveal no evidence of puncture,
flashover, cracking or other significant damage of the metal-oxide resistors or gap
structures. In other cases. visual inspection only applies to external parts;
d) there is a decrease in watts loss, leakage current, or temperature during the application
of U for 30 min after the application of U ;
c r
e) final interruption of the follow current occurs not later than at the end of the half cycle
following that in which the impulse is applied. There shall be no further sparkover of
the test sample in any subsequent half-cycle.
5.9 Power frequency voltage versus time characteristics of an arrester

The manufacturer shall supply data on the allowable time duration of power frequency voltage
and the corresponding voltage value which may be applied to the arrester after the arrester
has been preheated to 60 °C and subjected to the high current or line discharge class energy
duty respectively, without damage or thermal runaway.
This information shall be presented, together with initial temperature, as power frequency voltage
versus time curves with the impulse energy absorption prior to this power frequency voltage
application stated on the curve.
NOTE 1 Such curves are necessary for the selection of the arrester rated voltage depending on local system
conditions, such as lightning, switching and temporary overvoltages.
NOTE 2 The curves may be established by calculation.
NOTE 3
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...