Abstract

IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows:
- insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance;
- insulating down‑conductors, including their specific fasteners.
Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018:
a) title and scope of the standard has been adjusted;
b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment;
c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment;
d) two different possible example configurations for pull out tests have been introduced;
e) additional information on pollution has been included;
f) an alternate test arrangement for high voltage impulse test has been included;
g) a new normative Annex H for applicability of previous tests has been introduced;
h) pass criteria for high voltage impulse testing updated;
i) explanation on high voltage impulse testing with negative polarity has been added.

Status
Published
Publication Date
14-Jun-2026
Technical Committee
TC 81 - Lightning protection
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
15-Jun-2026
Due Date
03-Jul-2026
Completion Date
03-Jul-2026

Buy Documents

Standard

REDLINE IEC 62561-8:2026 CMV - Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS

ISBN:978-2-8327-1340-2
Release Date:15-Jun-2026
English language (119 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

iec62561-8{ed1.0}en - Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS

ISBN:978-2-8327-1299-3
Release Date:15-Jun-2026
English and French language (107 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

iec62561-8{ed1.0}fr - Composants des systemes de protection contre la foudre (CSPF) - Partie 8: Exigences pour les composants de systeme électriquement isolé de protection contre la foudre

ISBN:978-2-8327-1299-3
Release Date:15-Jun-2026
English and French language (107 pages)
sale 15% off
Preview
sale 15% off
Preview

IEC 62561-8:2026 is an IEC International Standard for lightning protection system components used in electrically insulated LPS. It specifies requirements and tests for insulating stand-offs and insulating down-conductors, including their specific fasteners, so manufacturers, test laboratories, designers, and installers can verify that these parts maintain the required separation distance under mechanical, environmental, and high-voltage stress.

What does IEC 62561-8:2026 specify?

IEC 62561-8:2026 covers the components used to reduce the separation distance in electrically insulated LPS. It applies to insulating stand-offs used with air-termination systems and down-conductors, and to insulating down-conductors with their specific fasteners.

The document does not cover testing for explosive atmospheres. It is organized into five main clauses, followed by annexes A to H.

AnnexWhat it covers
AEnvironmental corrosion tests: salt mist, humid sulphurous atmosphere, ammonia
BEnvironmental UV resistance tests
CTest flow for insulating stand-offs
DTest flow for insulating down-conductors
EInformative high-voltage impulse test to determine the real correction factor k for insulating stand-offs
FInformative installation-device test to assess the influence of support structures on separation distance
GAlternative test arrangement for the high-voltage impulse test
HApplicability of previous tests from IEC TS 62561-8:2018

What are the key requirements of IEC 62561-8:2026?

For insulating stand-offs

IEC 62561-8:2026 classifies insulating stand-offs by conductor clamping arrangement and by mounting arrangement. That matters in practice because the test sequence and the declared use must match the actual product configuration.

The stand-off must support, fix, and insulate the conductor under lightning impulse conditions and under environmental loads such as snow, ice, wind, and thermal expansion. It must also be compatible with the conductor and the mounting surface.

Clause 4 requires a sound surface finish, corrosion resistance, UV resistance, mechanical resistance, clear installation instructions, and durable marking. In practice, this means the manufacturer has to declare the product limits and the installer needs enough information to fit it safely and correctly.

Type testing in 4.3 uses three specimens per sequence, with the order given in Annex C. If one specimen fails, the affected sequence is repeated with three new specimens; if two fail, the design is not compliant. The document also fixes the test environment, torque tool accuracy, and the minimum waiting time for non-metallic specimens.

The key tests for stand-offs are:

  • documentation and marking review
  • corrosion and UV conditioning
  • flexion, impact, and pull-out tests
  • a high-voltage impulse test that compares the stand-off against a comparison spark gap

That electrical test is important because the declared effective length or correction factor k must support the required separation distance from IEC 62305-3.

For insulating down-conductors

IEC 62561-8:2026 classifies insulating down-conductors by lightning current withstand level. Table 2 gives the current and related energy values used for the manufacturer’s declared class.

The document also gives preferred values for equivalent separation distance s. These are practical reference values for selection and design, while the actual installation may require lower or, in some cases, higher values.

A down-conductor system must insulate safely under lightning stress, resist mechanical and environmental influences, and remain compatible with the mounting surface. Its documentation must include the declared class, dimensions, compatible materials, recommended mounting method, separation distance s, and, for indoor use, information relevant to flame spread and smoke density.

The main tests in 5.5 are:

  • documentation and marking review
  • construction inspection
  • UV resistance and corrosion resistance
  • lightning current withstand test
  • high-voltage impulse test for equivalent separation distance
  • installation-device test when support structures may affect dielectric performance

The lightning current test in 5.5.7.1 simulates installation stress by bending and straightening the specimen before the test. The impulse test in 5.5.7.2 uses negative polarity only and a comparison spark gap, with the test timing constrained by the specified cut-off interval. For readers, that means the whole assembly, not just the cable, has to be planned and tested as installed.

What terms does IEC 62561-8:2026 define?

  • support isolant - A non-metallic or composite component made of the insulator and its fixings, designed to fix, support, and insulate a conductor at the required separation distance.
  • conducteur de descente isolant - A down-conductor with an electrical insulation layer intended to reduce the separation distance.
  • distance de séparation équivalente s - The corrected distance used instead of the stand-off’s insulating length when comparing with the separation distance required by IEC 62305-3.
  • longueur effective l_eff - The equivalent spark-gap length used to represent the insulating performance of a stand-off.
  • facteur de correction de la longueur effective k - The factor used to relate the effective length to the insulating length for stand-offs.
  • facteur de correction de raideur is_st / dc_st - The correction factor used in the impulse tests to account for steeper impulse conditions and the likelihood of short-duration negative strokes.
  • dispositif d'installation - The complete installation, including one or more insulating down-conductors and the additional mounting means needed to maintain the declared separation distance.
  • courant admissible de foudre - The lightning impulse current level that the down-conductor can withstand, as declared by the manufacturer and verified by test.

Who uses IEC 62561-8:2026?

IEC 62561-8:2026 is used by manufacturers of lightning protection system components, especially makers of insulating stand-offs and insulating down-conductors. It is also used by test laboratories that perform type tests and generate reports to the prescribed format.

Designers and specifiers use it when selecting components for an electrically insulated LPS and when checking the required separation distance against IEC 62305-3. Quality, compliance, and procurement teams use it to define product acceptance, compare declarations against test evidence, and review documentation and marking.

What changed in IEC 62561-8:2026 from the previous edition?

IEC 62561-8:2026 is the first edition and it cancels and replaces IEC TS 62561-8:2018. The standard identifies these technical changes:

  • title and scope adjusted
  • updated for IEC 60068-2-52:2017 salt mist treatment
  • updated for ISO 22479:2019 humid sulphurous atmosphere treatment
  • two pull-out test configurations added
  • more information on pollution added
  • alternative high-voltage impulse test arrangement added
  • new normative Annex H on applicability of previous tests added
  • high-voltage impulse pass criteria updated
  • explanation added for negative-polarity high-voltage impulse testing

Which standards are used with IEC 62561-8:2026?

StandardWhat it contributes
IEC 60060-2:2025High-voltage measuring systems for impulse tests
IEC 60068-2-52:2017Cyclic salt mist test used in Annex A
IEC 60068-2-75:2014Hammer impact test method used for mechanical impact
IEC 61083-1Requirements for instruments used in impulse measurements
IEC 61083-2Software requirements for impulse measurements
IEC 62305-3Separation distance reference for electrically insulated LPS
IEC 62561-1:2023Connector requirements and tests used for conductor assemblies
IEC 62561-2:2025Down-conductor and earth electrode requirements used for conductor-related checks
IEC 62561-4Requirements for conductor fixings used with down-conductors
ISO 4892-2Xenon-arc UV exposure method used in Annex B
ISO 4892-3:2024UV fluorescent exposure method used in Annex B
ISO 4892-4Carbon-arc UV exposure method used in Annex B
ISO 6957:1988Ammonia atmosphere corrosion test used in Annex A
ISO 22479:2019Humid sulphurous atmosphere corrosion test used in Annex A

What does the IEC 62561-8:2026 document contain?

IEC 62561-8:2026 contains test sequences, acceptance criteria, and reporting requirements for both product families. Tables 1 and 3 set out the type-test sequences for insulating stand-offs and insulating down-conductors, while Table 2 gives the lightning current classes for down-conductors.

The figures show typical product constructions and the detailed test arrangements, including pull-out, flexion, impact, UV preparation, lightning current, and high-voltage impulse setups. Annexes C and D give the test order, and Annexes E, F, and G provide informative or alternative test arrangements for special cases.

It also defines the minimum content of test reports, so the same document supports design review, laboratory testing, certification work, and compliance audits.

Relations

Effective Date
05-Sep-2023

Buy Documents

Standard

REDLINE IEC 62561-8:2026 CMV - Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS

ISBN:978-2-8327-1340-2
Release Date:15-Jun-2026
English language (119 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

iec62561-8{ed1.0}en - Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS

ISBN:978-2-8327-1299-3
Release Date:15-Jun-2026
English and French language (107 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

iec62561-8{ed1.0}fr - Composants des systemes de protection contre la foudre (CSPF) - Partie 8: Exigences pour les composants de systeme électriquement isolé de protection contre la foudre

ISBN:978-2-8327-1299-3
Release Date:15-Jun-2026
English and French language (107 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

Sponsored listings

Frequently Asked Questions

IEC 62561-8:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Lightning protection system components (LPSC) - Part 8: Requirements for components for electrically insulated LPS". This standard covers: IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows: - insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance; - insulating down‑conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018: a) title and scope of the standard has been adjusted; b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment; c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment; d) two different possible example configurations for pull out tests have been introduced; e) additional information on pollution has been included; f) an alternate test arrangement for high voltage impulse test has been included; g) a new normative Annex H for applicability of previous tests has been introduced; h) pass criteria for high voltage impulse testing updated; i) explanation on high voltage impulse testing with negative polarity has been added.

IEC 62561-8:2026 specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows: - insulating stand-offs, used in conjunction with an air-termination system and down-conductors with the aim of maintaining the proper separation distance; - insulating down‑conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document. This first edition cancels and replaces IEC TS 62561-8 published in 2018. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to IEC TC 62561-8:2018: a) title and scope of the standard has been adjusted; b) the document has been updated in line with IEC 60068-2-52:2017 on salt mist treatment; c) the document has been updated in line with ISO 22479:2019 on humid sulphureous atmosphere treatment; d) two different possible example configurations for pull out tests have been introduced; e) additional information on pollution has been included; f) an alternate test arrangement for high voltage impulse test has been included; g) a new normative Annex H for applicability of previous tests has been introduced; h) pass criteria for high voltage impulse testing updated; i) explanation on high voltage impulse testing with negative polarity has been added.

IEC 62561-8:2026 is classified under the following ICS (International Classification for Standards) categories: 29.020 - Electrical engineering in general; 91.120.40 - Lightning protection. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 62561-8:2026 has the following relationships with other standards: It is inter standard links to IEC TS 62561-8:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 62561-8:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 insulating stand-off
  • 3.2 effective length correction factor
  • 3.3 steepness correction factor
  • 3.4 effective length
  • 3.5 corrected distance value of an insulating length
  • 3.6 equivalent separation distance
  • 3.7 down-conductor
  • 3.8 insulating down-conductor
  • 3.9 steepness correction factor
  • 3.10 partial insulating down-conductor
  • 3.10 clearance of the comparison arrangement
  • 3.11 time to chopping
  • 3.12 effective material insulating factor
  • 3.13 installation arrangement
  • 3.14 fasteners for insulating down-conductors
  • 4 Insulating stand-off
  • 4.1 Classification
  • 4.2 Requirements
  • 4.3 Tests
  • 4.4 Electromagnetic compatibility (EMC)
  • 4.5 Structure and content of the test report
  • 5 Insulating down-conductor
  • 5.1 Classification
  • 5.2 Lightning current carrying capability
  • 5.3 Preferred values of equivalent separation distance (s )
  • 5.4 Requirements
  • 5.5 Tests
  • 2 Metallic and composite fasteners
  • 3 Non-metallic and composite fasteners
  • 4 Installation arrangement test 5.5.7.3 C Depends on the
  • 5.6 Electromagnetic compatibility (EMC)
  • 5.7 Structure and content of the test report
  • Annex A
  • Annex B
  • Annex C
  • Annex D
  • Annex E
  • Annex F
  • Annex G
  • Annex H
  • Bibliography
  • 1 The title of IEC 62561-8 has been revised, and the new term “electrically insulated LPS”
  • 2 The scope of the standard and the description of the components covered by the standard
  • 9 A new normative annex describing an alternative test arrangement for the high-voltage
  • 11 The document has been updated in line with IEC 60068-2-52:2017 regarding salt mist
  • 12 The document has been updated in line with ISO 22479:2019 regarding humid sulfurous
  • 14 An alternative test arrangement for the high-voltage impulse test has been included as an
  • 15 A new normative annex describing an alternative test arrangement for the high-voltage
  • 16 A new normative annex has been introduced to align with IEC 62561 requirements for
  • Annex E (informative) High voltage impulse test to determine the actual correction
  • Annex F (informative) Installation arrangement test to determine the influence of
  • FOREWORD
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 insulating stand-off
  • 3.2 effective length correction factor
  • 3.3 steepness correction factor
  • 3.4 effective length
  • 3.5 insulating length
  • 3.6 equivalent separation distance
  • 3.7 down-conductor
  • 3.8 insulating down-conductor
  • 3.9 steepness correction factor
  • 3.10 clearance of the comparison arrangement
  • 3.11 time to chopping
  • 3.12 effective material insulating factor
  • 3.13 installation arrangement
  • 3.14 fasteners for insulating down-conductors
  • 4 Insulating stand-off
  • 4.1 Classification
  • 4.2 Requirements
  • 4.3 Tests
  • 4.4 Electromagnetic compatibility (EMC)
  • 4.5 Structure and content of the test report
  • 5 Insulating down-conductor
  • 5.1 Classification

INTRODUCTION This part of IEC 62561 deals with the requirements and tests for lightning protection system components (LPSC), specifically components for electrically insulated LPS, used for the installation of a lightning protection system (LPS) designed and implemented according to the

IEC 62305 series [1] .

Numbers in square brackets refer to the Bibliography.

1 Scope

This document specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows:

  • insulating stand-offs, used in conjunction with an air-termination system and downconductors with the aim of maintaining the proper separation distance, and the requirements and tests for insulating down-conductors, including their specific fasteners, able to reduce the separation distance.;
  • insulating down-conductors, including their specific fasteners. 2 Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document.

Requirements and tests for other types of components for isolated LPS are under consideration.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60060-2:20102025, High-voltage test techniques - Part 2: Measuring systems IEC 60068-2-52:2017, Environmental testing - Part 2-52: Tests - Test Kb: Salt mist, cyclic (sodium chloride solution) 3 IEC 60068-2-75:2014, Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests IEC 61083-1, Instruments and software used for measurements in high-voltage impulse and high-current tests - Part 1: Requirements for instruments for impulse tests IEC 61083-2, Instruments and software used for measurement in high-voltage and high-current tests - Part 2: Requirements for software for tests with impulse voltages and currents IEC 62305-3, Protection against lightning - Part 3: Physical damage to structures and life hazard IEC 62561-1:20172023, Lightning protection system components (LPSC) - Part 1:

Requirements for connection components IEC 62561-2:20122025, Lightning protection system components (LPSC) - Part 2:

Requirements for conductors and earth electrodes IEC 62561-4, Lightning protection system components (LPSC) - Part 4: Requirements for conductor fasteners ISO 4892-2, Plastics - Methods of exposure to laboratory light sources - Part 2: Xenon-arc lamps ISO 4892-3:20162024, Plastics - Methods of exposure to laboratory light sources - Part 3:

Fluorescent UV lamps ISO 4892-4, Plastics - Methods of exposure to laboratory light sources - Part 4: Open-flame carbon-arc lamps

ISO 6988:1985, Metallic and other non-organic coatings – Sulfur dioxide test with general condensation of moisture ISO 6957:1988, Copper alloys - Ammonia test for stress corrosion resistance ISO 22479:2019, Corrosion of metals and alloys - Sulfur dioxide test in a humid atmosphere (fixed gas method) 4

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:

  • IEC Electropedia: available at http://www.electropedia.org/
  • ISO Online browsing platform: available at http://www.iso.org/obp

3.1 insulating stand-off

non-metallic or composite component, consisting of the insulator and fixation parts, designed to retain, support and insulate the air-termination system and/or down-conductors at a required separation distance

3.2 effective length correction factor

k

factor evaluating the different withstand voltages of air gaps and insulators under test voltages and environmental influences like pollution and/or UV light degradation

3.3 steepness correction factor

is_st <insulating stand-off> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the flashover disruptive voltage of an insulating stand-off Note 1 to entry: The value is defined in the test procedure.

3.4 effective length

eff <insulating stand-off> length (distance) of an air gap with equivalent breakdown behaviour to an insulating stand-off

3.5 corrected distance value of an insulating length

st <insulating stand-off> shortest measured clearance distance between two conductive elements of different electrical potential, for example between a metallic conductor fastener and a mounting assembly

3.6 equivalent separation distance

s e corrected distance value to be used instead of the insulating length of a stand-off distance value equivalent to the separation distance of conventional down-conductors required in IEC 62305-3

3.7 down-conductor

conductor made of bare metal part of the down-conductor system intended to conduct lightning current from the air-termination system to the earth-termination system of the LPS [SOURCE: IEC 62561-2:2025, 3.7]

3.8 insulating down-conductor

conductor provided with a layer of electric insulation with the purpose to reduce the separation distance

3.9 steepness correction factor

dc_st <insulating down-conductor> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the withstand voltage of insulating down-conductors during testing Note 1 to entry: The value is defined in the test procedure.

3.10 partial insulating down-conductor

conductor provided with a layer of insulation with the purpose to reduce the separation distance, supported by insulating stand-offs

3.10 clearance of the comparison arrangement

s

gap distance of the comparison arrangement used for verification of the effective length correction factor k and separation distance s x e

3.11 time to chopping

T

virtual parameter defined as the interval between the virtual origin and the instant of chopping

3.12 effective material insulating factor

k m coefficient of material which depends on the electrical insulation material Note 1 to entry: See IEC 62305-3.

3.13 installation arrangement

installation containing one or more insulating down-conductors and additional installation means (according to the manufacturer's instruction) to keep the defined separation distance and to support the insulating down-conductor mechanically

Note 1 to entry: One example is given in Figure F.1.

3.14 fasteners for insulating down-conductors

metallic, non-metallic or composite components designed to retain and support down-conductor installed at intervals along the length of the conductors

4 Insulating stand-off

4.1 Classification

4.1.1 General

Classification of the product depends on the withstand capability of mechanical forces.

4.1.2 According to conductor clamping arrangement

There are two classes of insulating stand-off according to the conducting clamping arrangement:

a) conductor fasteners that are designed to clamp the conductor; b) conductor fasteners that are designed to clamp but allow axial movement of the conductor.

4.1.3 According to mounting

Regarding the mounting, there are two classes of insulating stand-off:

a) free standing; b) rigidly fixed on a structure.

4.2 Requirements

4.2.1 General

An insulating stand-off shall retain, support and insulate the conductor when subjected to the stress of a lightning discharge under high impulse voltage and shall withstand the mechanical and environmental influences such as perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion/ or contraction of the conductor.

An insulating stand-off shall be compatible with the conductor it is supporting and the surface to which it is fixed.

4.2.2 Construction
4.2.2.1 General

An insulating stand-off shall be so designed and constructed that a) the surface is free from burrs, flash moulding, deformation and similar inconsistencies which are likely to inflict injury to the installer or user, and Compliance is checked by visual inspection.

b) it carries the perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion/contraction of the conductor.

Compliance to a) is checked by visual inspection and compliance to b) is checked in accordance with 4.3.6.2 and 4.3.6.4.

4.2.2.2 Corrosion resistance

An insulating stand-off shall withstand the effects of corrosion typical of the environment to which it is exposed.

Compliance is checked by testing in accordance with 4.3.5.1.

4.2.2.3 UV light resistance

An insulating stand-off shall withstand the effects of UV exposure typical of the environment to which it is exposed.

Compliance is checked by testing in accordance with 4.3.5.2.

4.2.3 Mechanical requirements
4.2.3.1 General

An insulating stand-off may can consist of a mounting assembly, an insulator and a conductor fastener as shown in Figure 1 and/or Figure 2. The manufacturer of the insulating stand-off shall guarantee with appropriate mechanical tests or calculations that the stand-off fulfills the requirements stated in their documentation.

Compliance is checked by testing in accordance with 4.3.

Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor insulating length

st Figure 1 – Typical insulating stand-off with a metallic fastener

Key 1 mounting assembly 2 insulator 3 non metallic conductor fastener 4 conductor l insulating length st Figure 2 – Typical insulating stand-off with a non-metallic fastener

4.2.3.2 Mounting assembly

The mounting assembly, which holds the insulator in position on the structure, shall withstand mechanical stress.

Compliance is checked by testing in accordance with 4.3.6.

4.2.3.3 Insulator

The insulator shall withstand mechanical stress, for example pull out force, impact strength and bending load.

Compliance is checked by testing in accordance with 4.3.6.

4.2.3.4 Conductor fastener

The conductor fastener, which is part of the insulating stand-off, shall comply with the requirements and tests of IEC 62561-4.

4.2.4 Electrical requirements

An insulating stand-off shall be capable of withstanding the very high impulse voltages generated by a lightning strike.

An insulating stand-off has an insulating length l , as shown in Figure 1 and Figure 2. This is st different from its effective length l , which is the value which shall to be compared to the eff, required separation distance s according to IEC 62305-3. This effective length of the insulating stand-off shall be equal to or greater than the required separation distance s. The isolating capability of an insulating stand-off may can be provided by either a) its effective length l , or eff b) its effective length correction factor k .

The effective length correction factor k is determined from the effective length l and the x eff insulating length l as showed in Formula (1):

st I eff

k = (1)

I st

Compliance is checked by testing in accordance with 4.3.1, 4.3.2 and 4.3.7. For the purpose of calculating the separation distance as used in IEC 62305-3, the value of the effective material insulating factor k can be set equal to the value k . m x NOTE Based on experience, A value of k = 0,7 for GFRP, PE and PVC insulating stand-offs under normal operating

conditions has been found to be typical can be used, based on laboratory test results [2].

4.2.5 Documentation and installation instructions

The manufacturer or supplier of the insulating stand-off shall provide adequate information in the installation instructions to ensure that the installer can select and install the component in a suitable and safe manner in accordance with the requirements of IEC 62305-3. Compliance is checked by inspection in accordance with 4.3.3.

4.2.6 Marking
4.2.6.1 Content of marking

An insulating stand-off shall be marked with a) the manufacturer's or responsible vendor's name, logo or trademark, and b) the product identification or type.

Where it is not possible to make these marks directly onto the product, they shall be provided on the smallest supplied packaging.

Compliance is checked by visual inspection.

4.2.6.2 Durability and legibility

Marking on the product shall be durable and easily legible.

NOTE Marking can be applied for example by moulding, pressing, engraving, printing, adhesive labels or water slide transfers.

Compliance is checked by testing in accordance with 4.3.4.

4.3 Tests

4.3.1 General test conditions

Tests according to this document are type tests. These tests are of such a nature that, after they have been performed, they need are not required to be repeated unless changes are made to the materials, design or type of manufacturing process, which might can change the performance characteristics of the insulating stand-off.

Unless otherwise specified, All tests are carried out with the specimens assembled and installed as in normal use according to the manufacturer's or supplier's instructions, using the recommended conductor materials, sizes and tightening torques. The insulating length l of all specimens shall be (500 ± 5) mm unless otherwise specified in st the relevant test procedure. The manufacturer shall prepare the test specimens according to Figure 3 for a metallic fastener or Figure 4 for a non-metallic fastener. Dimensions in millimetres

Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor l insulating length st Figure 3 – Typical insulating stand-off with a metallic fastener prepared for testing

Dimensions in millimetres

Key 1 mounting assembly 2 insulator 3 non-metallic conductor fastener 4 conductor l insulating length st Figure 4 – Typical insulating stand-off with a non-metallic fastener prepared for testing This document cannot cover all possible types of insulating stand-offs and the way of fixing them on various surfaces of different materials. When required for these applications, agreement should be obtained between the test engineer and manufacturer on the specific testing regime.

An insulating stand-off classified by the manufacturer in more than one of the classifications in 4.1 shall be tested for each applicable category.

Type tests are carried out on three specimens according to the test sequence indicated in Table 1. Within any test sequence, the tests shall be carried out in the order given in Annex C. A specimen has passed a test sequence of Table 1 if all the requirements of the relevant test clauses and the relevant pass criteria have been fulfilled.

If the required number of specimens passes a test sequence, the design of the insulating stand-off is acceptable for that test sequence. If two or more test specimens fail a test sequence, the insulating stand-off does not comply with this document. In the event that a single specimen does not pass a test, this test, and those preceding in the same test sequence that may could have influenced the result of this test, shall be repeated with three new specimens. No failure of any specimen is allowed in the second sequence of tests. One set of three specimens may can be used for more than one test sequence if agreed by the manufacturer.

The applicants, when submitting the first set of specimens may, can also submit an additional set of specimens that may can be necessary should one specimen fail. The test house shall then, without further request, test the additional set of specimens and shall only reject if a further failure occurs. If the additional set of specimens is not submitted at the same time, a failure of one specimen shall entail rejection.

Tests on non-metallic specimens shall not commence earlier than 168 h from the time of manufacture.

NOTE The value of 168 h is a curing time and is a typical value based on experience. When not otherwise specified, The test shall be performed in free air, with an ambient temperature between +15 °C and +40 °C and relative humidity between 25 % and 75 %. A torque meter having a resolution of at least 0,5 Nm and an accuracy of at least 4 % shall be used for all tightening operations.

NOTE Upon the instructions of the manufacturer, a set of specimens previously tested may also be suitable for use in other tests of this document as well.

Table 1 – Type test requirements for an insulating stand-off Identification of Test sets (one set Test description Sub-clause Number of specimens sequence consists of three specimens) 1 Documentation 4.3.3 A 1 Marking test 4.3.4 A 3 Construction 4.3.6.1 A 3

Corrosion test 4.3.5.1 AE 3 Pull out test 4.3.6.4 AE 3 3 9 or more due to surface UV light test 4.3.5.2 B, C, D deterioration during high voltage test.

a Bending test 4.3.6.2 3 B a Impact test of the insulator 4.3.6.3 C 3 3 or more due to surface

a Electrical test 4.3.7 deterioration during high voltage D test.

a Upon the agreement between the manufacturer and the laboratory, a set of specimens previously tested can also be suitable for use in other tests of this document as well.

4.3.2 General test setup

Unless otherwise specified by the manufacturer, the conductors and specimens shall be cleaned by using a suitable degreasing agent followed by cleaning in demineralized water and drying. They shall then be assembled according to the manufacturer's installation instructions, for example with the recommended conductors and tightening torques. The tightening torque should be applied in a steady and uniform manner.

Any insulating stand-off accommodating a range of conductor diameters conductor's variance in diameter shall be tested on the minimum conductor size recommended.

4.3.3 Documentation

The manufacturer or responsible vendor shall provide the following in their literature:

a) classifications according to 4.1; b) maximum and minimum conductor dimensions; c) conductor materials to be used; d) type of mounting surface to be fixed; e) recommended method of assembly, installation and fixing to the mounting surface; f) pull out force; g) bending force; h) mechanical strength (e.g. load torque, support load); i) k coefficient.

Compliance is checked by inspection.

4.3.4 Marking test

Marking on the product shall be durable and easily legible.

The durability of marking shall be tested by easy rubbing for ten times with a piece of cloth soaked with water.

Markings made by moulding, pressing or engraving are not subjected to this test. Pass criteria:

The specimen is deemed to have passed the test if the marking remains legible. Marking may be applied, for example, by moulding, pressing, engraving, printing, adhesive labels, etc.

4.3.5 Environmental influence tests
4.3.5.1 Corrosion test

An insulating stand-off with metallic components, including its conductor fastener and mounting assembly, shall be subjected to environmental influence tests consisting of a salt mist test as specified in Clause A.2 followed by a humid sulphurous atmosphere test as specified in Clause A.3. An additional test by an ammonia atmosphere as specified in Clause A.4 shall be carried out on an insulating stand-off having parts made of copper alloy with a copper content less than 80 %.

Pass criteria:

The specimens are deemed to have passed the test if no base metals of the metallic components show any corrosive deterioration visible to normal or corrected vision. NOTE White rust, patina and surface oxidation are not considered as corrosive deterioration.

...

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 insulating stand-off
  • 3.2 effective length correction factor
  • 3.3 steepness correction factor
  • 3.4 effective length
  • 3.5 insulating length
  • 3.6 equivalent separation distance
  • 3.7 down-conductor
  • 3.8 insulating down-conductor
  • 3.9 steepness correction factor
  • 3.10 clearance of the comparison arrangement
  • 3.11 time to chopping
  • 3.12 effective material insulating factor
  • 3.13 installation arrangement
  • 3.14 fasteners for insulating down-conductors
  • 4 Insulating stand-off
  • 4.1 Classification
  • 4.2 Requirements
  • 4.3 Tests
  • 4.4 Electromagnetic compatibility (EMC)
  • 4.5 Structure and content of the test report
  • 5 Insulating down-conductor
  • 5.1 Classification
  • 5.2 Lightning current carrying capability
  • 5.3 Preferred values of equivalent separation distance (s )
  • 5.4 Requirements
  • 5.5 Tests
  • 4 Installation arrangement test 5.5.7.3 C Depends on the
  • 5.6 Electromagnetic compatibility (EMC)
  • 5.7 Structure and content of the test report
  • Annex A
  • Annex B
  • Annex C
  • Annex D
  • Annex E
  • Annex F
  • Annex G
  • Annex H
  • Bibliography

INTRODUCTION This part of IEC 62561 deals with the requirements and tests for lightning protection system components (LPSC), specifically components for electrically insulated LPS, used for the installation of a lightning protection system (LPS) designed and implemented according to the

IEC 62305 series [1] .

Numbers in square brackets refer to the Bibliography.

1 Scope

This document specifies the requirements and tests for components used for electrically insulated LPS. These components, which can reduce the separation distance, are as follows:

  • insulating stand-offs, used in conjunction with an air-termination system and downconductors with the aim of maintaining the proper separation distance;
  • insulating down-conductors, including their specific fasteners. Testing of insulating stand-offs and insulating down-conductor components for an explosive atmosphere is not covered by this document.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60060-2:2025, High-voltage test techniques - Part 2: Measuring systems IEC 60068-2-52:2017, Environmental testing - Part 2-52: Tests - Test Kb: Salt mist, cyclic (sodium chloride solution) IEC 60068-2-75:2014, Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests IEC 61083-1, Instruments and software used for measurements in high-voltage and high-current tests - Part 1: Requirements for instruments for impulse tests IEC 61083-2, Instruments and software used for measurement in high-voltage and high-current tests - Part 2: Requirements for software for tests with impulse voltages and currents IEC 62305-3, Protection against lightning - Part 3: Physical damage to structures and life hazard IEC 62561-1:2023, Lightning protection system components (LPSC) - Part 1: Requirements for connection components IEC 62561-2:2025, Lightning protection system components (LPSC) - Part 2: Requirements for conductors and earth electrodes IEC 62561-4, Lightning protection system components (LPSC) - Part 4: Requirements for conductor fasteners ISO 4892-2, Plastics - Methods of exposure to laboratory light sources - Part 2: Xenon-arc lamps ISO 4892-3:2024, Plastics - Methods of exposure to laboratory light sources - Part 3:

Fluorescent UV lamps ISO 4892-4, Plastics - Methods of exposure to laboratory light sources - Part 4: Open-flame carbon-arc lamps ISO 6957:1988, Copper alloys - Ammonia test for stress corrosion resistance

ISO 22479:2019, Corrosion of metals and alloys - Sulfur dioxide test in a humid atmosphere (fixed gas method)

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:

  • IEC Electropedia: available at http://www.electropedia.org/
  • ISO Online browsing platform: available at http://www.iso.org/obp

3.1 insulating stand-off

non-metallic or composite component, consisting of the insulator and fixation parts, designed to retain, support and insulate the air-termination system or down-conductors at a required separation distance

3.2 effective length correction factor

k

factor evaluating the different withstand voltages of air gaps and insulators under test voltages

3.3 steepness correction factor

is_st <insulating stand-off> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the disruptive voltage of an insulating stand-off Note 1 to entry: The value is defined in the test procedure.

3.4 effective length

eff <insulating stand-off> length (distance) of an air gap with equivalent breakdown behaviour to an insulating stand-off

3.5 insulating length

st <insulating stand-off> shortest measured clearance distance between two conductive elements of different electrical potential, for example between a metallic conductor fastener and a mounting assembly

3.6 equivalent separation distance

s e corrected distance value to be used instead of the insulating length of a stand-off distance value equivalent to the separation distance of conventional down-conductors required in IEC 62305-3

3.7 down-conductor

part of the down-conductor system intended to conduct lightning current from the air-termination system to the earth-termination system of the LPS [SOURCE: IEC 62561-2:2025, 3.7]

3.8 insulating down-conductor

conductor provided with a layer of electric insulation with the purpose to reduce the separation distance

3.9 steepness correction factor

dc_st <insulating down-conductor> factor considering the effect of higher steepness and the probability of occurrence of subsequent negative short strokes on the withstand voltage of insulating down-conductors during testing Note 1 to entry: The value is defined in the test procedure.

3.10 clearance of the comparison arrangement

s

gap distance of the comparison arrangement used for verification of the effective length correction factor k and separation distance s x e

3.11 time to chopping

T

virtual parameter defined as the interval between the virtual origin and the instant of chopping

3.12 effective material insulating factor

k m coefficient of material which depends on the electrical insulation material Note 1 to entry: See IEC 62305-3.

3.13 installation arrangement

installation containing one or more insulating down-conductors and additional installation means (according to the manufacturer's instruction) to keep the defined separation distance and to support the insulating down-conductor mechanically Note 1 to entry: One example is given in Figure F.1.

3.14 fasteners for insulating down-conductors

metallic, non-metallic or composite components designed to retain and support down-conductor installed at intervals along the length of the conductors

4 Insulating stand-off

4.1 Classification

4.1.1 General

Classification of the product depends on the withstand capability of mechanical forces.

4.1.2 According to conductor clamping arrangement

There are two classes of insulating stand-off according to the conducting clamping arrangement:

a) conductor fasteners that are designed to clamp the conductor; b) conductor fasteners that are designed to clamp but allow axial movement of the conductor.

4.1.3 According to mounting

Regarding the mounting, there are two classes of insulating stand-off:

a) free standing; b) rigidly fixed on a structure.

4.2 Requirements

4.2.1 General

An insulating stand-off shall retain, support and insulate the conductor when subjected to the stress of a lightning discharge under high impulse voltage and shall withstand the mechanical and environmental influences such as perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion or contraction of the conductor.

An insulating stand-off shall be compatible with the conductor it is supporting and the surface to which it is fixed.

4.2.2 Construction
4.2.2.1 General

An insulating stand-off shall be so designed and constructed that a) the surface is free from burrs, flash moulding, deformation and similar inconsistencies which are likely to inflict injury to the installer or user, and b) it carries the perpendicular and axial compression loads caused by the weight of the supported conductor along with snow, ice, wind and thermal expansion/contraction of the conductor.

Compliance to a) is checked by visual inspection and compliance to b) is checked in accordance with 4.3.6.2 and 4.3.6.4.

4.2.2.2 Corrosion resistance

An insulating stand-off shall withstand the effects of corrosion typical of the environment to which it is exposed.

Compliance is checked by testing in accordance with 4.3.5.1.

4.2.2.3 UV light resistance

An insulating stand-off shall withstand the effects of UV exposure typical of the environment to which it is exposed.

Compliance is checked by testing in accordance with 4.3.5.2.

4.2.3 Mechanical requirements
4.2.3.1 General

An insulating stand-off can consist of a mounting assembly, an insulator and a conductor fastener as shown in Figure 1 and Figure 2. The manufacturer of the insulating stand-off shall guarantee with appropriate mechanical tests or calculations that the stand-off fulfills the requirements stated in their documentation.

Compliance is checked by testing in accordance with 4.3.

Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor l insulating length st Figure 1 – Typical insulating stand-off with a metallic fastener

Key 1 mounting assembly 2 insulator 3 non metallic conductor fastener 4 conductor l insulating length st Figure 2 – Typical insulating stand-off with a non-metallic fastener

4.2.3.2 Mounting assembly

The mounting assembly, which holds the insulator in position on the structure, shall withstand mechanical stress.

Compliance is checked by testing in accordance with 4.3.6.

4.2.3.3 Insulator

The insulator shall withstand mechanical stress, for example pull out force, impact strength and bending load.

Compliance is checked by testing in accordance with 4.3.6.

4.2.3.4 Conductor fastener

The conductor fastener, which is part of the insulating stand-off, shall comply with the requirements and tests of IEC 62561-4.

4.2.4 Electrical requirements

An insulating stand-off shall be capable of withstanding the very high impulse voltages generated by a lightning strike.

An insulating stand-off has an insulating length l , as shown in Figure 1 and Figure 2. This is st different from its effective length l , which is the value to be compared to the required eff separation distance s according to IEC 62305-3. This effective length of the insulating stand-off shall be equal to or greater than the required separation distance s. The isolating capability of an insulating stand-off can be provided by either a) its effective length l , or eff b) its effective length correction factor k .

The effective length correction factor k is determined from the effective length l and the x eff insulating length l as showed in Formula (1):

st I eff

k = (1)

I st

Compliance is checked by testing in accordance with 4.3.1, 4.3.2 and 4.3.7. For the purpose of calculating the separation distance as used in IEC 62305-3, the value of the effective material insulating factor k can be set equal to the value k . m x NOTE A value of k = 0,7 for GFRP, PE and PVC insulating stand-offs under normal operating conditions can be

used, based on laboratory test results [2].

4.2.5 Documentation and installation instructions

The manufacturer or supplier of the insulating stand-off shall provide adequate information in the installation instructions to ensure that the installer can select and install the component in a suitable and safe manner in accordance with the requirements of IEC 62305-3. Compliance is checked by inspection in accordance with 4.3.3.

4.2.6 Marking
4.2.6.1 Content of marking

An insulating stand-off shall be marked with a) the manufacturer's or responsible vendor's name, logo or trademark, and b) the product identification or type.

Where it is not possible to make these marks directly onto the product, they shall be provided on the smallest supplied packaging.

Compliance is checked by visual inspection.

4.2.6.2 Durability and legibility

Marking on the product shall be durable and easily legible.

NOTE Marking can be applied for example by moulding, pressing, engraving, printing, adhesive labels or water slide transfers.

Compliance is checked by testing in accordance with 4.3.4.

4.3 Tests

4.3.1 General test conditions

Tests according to this document are type tests. These tests are of such a nature that, after they have been performed, they are not required to be repeated unless changes are made to the materials, design or type of manufacturing process, which can change the performance characteristics of the insulating stand-off.

All tests are carried out with the specimens assembled and installed as in normal use according to the manufacturer's or supplier's instructions, using the recommended conductor materials, sizes and tightening torques.

The insulating length l of all specimens shall be (500 ± 5) mm unless otherwise specified in st the relevant test procedure. The manufacturer shall prepare the test specimens according to Figure 3 for a metallic fastener or Figure 4 for a non-metallic fastener. Dimensions in millimetres

Key 1 mounting assembly 2 insulator 3 metallic conductor fastener 4 conductor l insulating length st Figure 3 – Typical insulating stand-off with a metallic fastener prepared for testing

Dimensions in millimetres

Key 1 mounting assembly 2 insulator 3 non-metallic conductor fastener 4 conductor l insulating length st Figure 4 – Typical insulating stand-off with a non-metallic fastener prepared for testing This document cannot cover all possible types of insulating stand-offs and the way of fixing them on various surfaces of different materials. When required for these applications, agreement should be obtained between the test engineer and manufacturer on the specific testing regime.

An insulating stand-off classified by the manufacturer in more than one of the classifications in 4.1 shall be tested for each applicable category.

Type tests are carried out on three specimens according to the test sequence indicated in Table 1. Within any test sequence, the tests shall be carried out in the order given in Annex C. A specimen has passed a test sequence of Table 1 if all the requirements of the relevant test clauses and the relevant pass criteria have been fulfilled.

If the required number of specimens passes a test sequence, the design of the insulating stand-off is acceptable for that test sequence. If two or more test specimens fail a test sequence, the insulating stand-off does not comply with this document. In the event that a single specimen does not pass a test, this test, and those preceding in the same test sequence that could have influenced the result of this test, shall be repeated with three new specimens. No failure of any specimen is allowed in the second sequence of tests. One set of three specimens can be used for more than one test sequence if agreed by the manufacturer.

The applicants, when submitting the first set of specimens, can also submit an additional set of specimens that can be necessary should one specimen fail. The test house shall then, without further request, test the additional set of specimens and shall only reject if a further failure occurs. If the additional set of specimens is not submitted at the same time, a failure of one specimen shall entail rejection.

Tests on non-metallic specimens shall not commence earlier than 168 h from the time of manufacture.

NOTE The value of 168 h is a curing time and is a typical value based on experience. The test shall be performed in free air, with an ambient temperature between +15 °C and +40 °C and relative humidity between 25 % and 75 %.

A torque meter having a resolution of at least 0,5 Nm and an accuracy of at least 4 % shall be used for all tightening operations.

Table 1 – Type test requirements for an insulating stand-off Test Identification of Test description Sub-clause Number of specimens sequence sets 1 Documentation 4.3.3 A 1 Marking test 4.3.4 A 3 Construction 4.3.6.1 A 3

Corrosion test 4.3.5.1 E 3 Pull out test 4.3.6.4 E 3 9 or more due to surface

UV light test 4.3.5.2 B, C, D deterioration during high voltage test.

a Bending test 4.3.6.2 B 3 a Impact test of the insulator 4.3.6.3 3 C 3 or more due to surface a Electrical test 4.3.7 deterioration during high voltage D test.

a Upon the agreement between the manufacturer and the laboratory, a set of specimens previously tested can also be suitable for use in other tests of this document as well.

4.3.2 General test setup

Unless otherwise specified by the manufacturer, the conductors and specimens shall be cleaned by using a suitable degreasing agent followed by cleaning in demineralized water and drying. They shall then be assembled according to the manufacturer's installation instructions, for example with the recommended conductors and tightening torques. The tightening torque should be applied in a steady and uniform manner. Any insulating stand-off accommodating a range of conductor's variance in diameter shall be tested on the minimum conductor size recommended.

4.3.3 Documentation

The manufacturer or responsible vendor shall provide the following in their literature:

a) classifications according to 4.1; b) maximum and minimum conductor dimensions; c) conductor materials to be used; d) type of mounting surface to be fixed; e) recommended method of assembly, installation and fixing to the mounting surface; f) pull out force; g) bending force; h) mechanical strength (e.g. load torque, support load); i) k coefficient.

Compliance is checked by inspection.

4.3.4 Marking test

The durability of marking shall be tested by easy rubbing for ten times with a piece of cloth soaked with water.

Markings made by moulding, pressing or engraving are not subjected to this test. The specimen is deemed to have passed the test if the marking remains legible.

4.3.5 Environmental influence tests
4.3.5.1 Corrosion test

An insulating stand-off with metallic components, including its conductor fastener and mounting assembly, shall be subjected to environmental influence tests consisting of a salt mist test as specified in Clause A.2 followed by a humid sulphurous atmosphere test as specified in Clause A.3. An additional test by an ammonia atmosphere as specified in Clause A.4 shall be carried out on an insulating stand-off having parts made of copper alloy with a copper content less than 80 %.

The specimens are deemed to have passed the test if no base metals of the metallic components show any corrosive deterioration visible to normal or corrected vision. NOTE White rust, patina and surface oxidation are not considered as corrosive deterioration.

4.3.5.2 UV light test

The insulating part (insulator) of the insulating stand-off shall be subjected to an environmental test consisting of an ultraviolet light test as specified in Annex B. The length of the test specimen shall be sufficient so that, after the UV light test, a complete insulating stand-off can be assembled for further tests requiring an insulating length l of st (500 ± 5) mm.

The specimens are deemed to have passed the test if there are no signs of disintegration and cracks visible under normal or corrected vision.

4.3.5.3 Pollution test

As the voltage stress for insulating stand-offs and insulating down-conductors is in the range of microseconds, pollution is not effective. Therefore, a specific test is not applicable [3], [4].

4.3.6 Mechanical tests
4.3.6.1 Construction

The surface of the insulating stand-off shall be free from burrs associated with the cutting process, moulding joint deformation and similar inconsistencies which are likely to inflict injury to the installer or user.

Compliance is checked by visual and manual inspection.

4.3.6.2 Bending test

Upon completion of the UV light test described in 4.3.5.2, one set of specimens shall be subjected to a bending test. A load declared by the manufacturer but not less than 10 N is applied at the end distant from the mounting as illustrated in Figure 5. The load shall be applied for a period of (60 ± 1) min.

...

Contents

  • 1 Domaine d'application
  • 2 Références normatives
  • 3 Termes et définitions
  • 3.1 support isolant
  • 3.2 facteur de correction de la longueur effective
  • 3.3 facteur de correction de raideur
  • 3.4 longueur effective
  • 3.5 longueur isolante
  • 3.6 distance de séparation équivalente
  • 3.7 conducteur de descente
  • 3.8 conducteur de descente isolant
  • 3.9 facteur de correction de raideur
  • 3.10 distance d'isolement de l'installation de comparaison
  • 3.11 durée jusqu'à la coupure
  • 3.12 facteur d'isolation du matériel effectif
  • 3.13 dispositif d'installation
  • 3.14 fixations pour les conducteurs de descente isolants
  • 4 Support isolant
  • 4.1 Classification
  • 4.2 Exigences
  • 4.3 Essais
  • 4.4 Compatibilité électromagnétique (CEM)
  • 4.5 Structure et contenu du rapport d'essai
  • 5 Conducteur de descente isolant
  • 5.1 Classification
  • 5.2 Courant admissible de foudre
  • 5.3 Valeurs préférentielles de la distance de séparation équivalente (s )
  • 5.4 Exigences
  • 5.5 Essais
  • 4 Essai de dispositif d'installation 5.5.7.3 C Selon
  • 5.6 Compatibilité électromagnétique (CEM)
  • 5.7 Structure et contenu du rapport d'essai
  • Annexe A
  • Annexe B
  • Annexe C
  • Annexe D
  • Annexe E
  • Annexe F
  • Annexe G
  • Annexe H
  • Bibliographie

INTRODUCTION La présente partie de l'IEC 62561 traite des exigences et des essais pour les composants des systèmes de protection contre la foudre (CSPF), en particulier pour les composants des systèmes électriquement isolés de protection contre la foudre, utilisés pour l'installation d'un système de protection contre la foudre (SPF) conçu et mis en œuvre conformément à la série

IEC 62305 [1] .

Les chiffres entre crochets renvoient à la Bibliographie.

1 Domaine d'application

Le présent document spécifie les exigences et les essais pour les composants utilisés pour les systèmes électriquement isolés de protection contre la foudre. Ces composants peuvent réduire la distance de séparation, notamment:

  • les supports isolants, utilisés conjointement avec un dispositif de capture et des conducteurs de descente afin de maintenir une distance de séparation appropriée;
  • les conducteurs de descente isolants, y compris leurs fixations spécifiques. Les essais réalisés sur les composants des supports isolants et des conducteurs de descente isolants pour une atmosphère explosive ne sont pas couverts par le présent document.

2 Références normatives

Les documents suivants sont cités dans le texte de sorte qu'ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du document de référence s'applique (y compris les éventuels amendements).

IEC 60060-2:2025, Techniques des essais à haute tension - Partie 2: Systèmes de mesure IEC 60068-2-52:2017, Essais d'environnement - Partie 2-52: Essais - Essai Kb: Brouillard salin, essai cyclique (solution de chlorure de sodium) IEC 60068-2-75:2014, Essais d'environnement - Partie 2-75: Essais - Test Eh: Essais au marteau IEC 61083-1, Appareils et logiciels utilisés pour les mesurages pendant les essais à tension et courant élevés - Partie 1: Exigences pour les appareils utilisés pour les essais de choc IEC 61083-2, Appareils et logiciels utilisés pour les mesures pendant les essais à haute tension et haute intensité - Partie 2: Exigences pour le logiciel pour les essais avec des tensions et des courants de choc IEC 62305-3, Protection contre la foudre - Partie 3: Dommages physiques sur les structures et risques humains IEC 62561-1:2023, Composants des systèmes de protection contre la foudre (CSPF) - Partie 1:

Exigences pour les composants de connexion IEC 62561-2:2025, Composants des systèmes de protection contre la foudre (CSPF) - Partie 2:

Exigences pour les conducteurs et les électrodes de terre IEC 62561-4, Composants des systèmes de protection contre la foudre (CSPF) - Partie 4:

Exigences pour les fixations de conducteurs ISO 4892-2, Plastiques - Méthodes d'exposition à des sources lumineuses de laboratoire - Partie 2: Lampes à arc au xénon ISO 4892-3:2024, Plastiques - Méthodes d'exposition à des sources lumineuses de laboratoire - Partie 3: Lampes fluorescentes UV ISO 4892-4, Plastiques - Méthodes d'exposition à des sources lumineuses de laboratoire - Partie 4: Lampes à arc au carbone

ISO 6957:1988, Alliages de cuivre - Essai à l'ammoniaque pour la résistance à la corrosion sous contrainte ISO 22479:2019, Corrosion des métaux et alliages - Essai au dioxyde de soufre en atmosphère humide (méthode avec volume fixe de gaz)

3 Termes et définitions

Pour les besoins du présent document, les termes et définitions suivants s'appliquent. L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:

  • IEC Electropedia: disponible à l'adresse http://www.electropedia.org/
  • ISO Online browsing platform: disponible à l'adresse http://www.iso.org/obp

3.1 support isolant

composant non métallique ou composite composé de l'isolateur et des fixations, conçu pour fixer, soutenir et isoler le dispositif de capture ou les conducteurs de descente à une distance de séparation exigée

3.2 facteur de correction de la longueur effective

k

facteur qui permet d'évaluer les différentes tensions de tenue des entrefers et des isolateurs soumis à des tensions d'essai

3.3 facteur de correction de raideur

is_st <support isolant> facteur qui tient compte de l'effet d'une raideur plus importante et de la probabilité que des coups de foudre de courte durée aux effets négatifs surviennent ultérieurement sur la tension disruptive de contournement du support isolant Note 1 à l'article: La valeur est définie dans la procédure d'essai.

3.4 longueur effective

eff <support isolant> longueur (distance) d'un entrefer à claquage équivalent à un support isolant

3.5 longueur isolante

st <support isolant> distance d'isolement la plus courte mesurée entre deux éléments conducteurs au potentiel électrique différent, par exemple entre une fixation de conducteur métallique et un dispositif de montage

3.6 distance de séparation équivalente

s e valeur corrigée de la distance à utiliser à la place de la longueur isolante d'une valeur de la distance d'un support, équivalente à la distance de séparation des conducteurs de descente conventionnels exigée dans l'IEC 62305-3

3.7 conducteur de descente

partie du réseau de conducteurs de descente destinée à conduire le courant de décharge atmosphérique depuis le dispositif de capture vers le réseau de prises de terre du SPF [SOURCE: IEC 62561-2:2025, 3.7]

3.8 conducteur de descente isolant

conducteur qui comporte une couche d'isolation électrique dans le but de réduire la distance de séparation

3.9 facteur de correction de raideur

dc_st <conducteur de descente isolant> facteur qui tient compte de l'effet d'une raideur plus importante et de la probabilité que des coups de foudre de courte durée aux effets négatifs surviennent ultérieurement sur la tension de tenue des conducteurs de descente isolants au cours des essais Note 1 à l'article: La valeur est définie dans la procédure d'essai.

3.10 distance d'isolement de l'installation de comparaison

s

distance d'écartement de l'installation de comparaison utilisée pour la vérification du facteur de correction de la longueur effective k et de la distance de séparation s x e

3.11 durée jusqu'à la coupure

T

paramètre virtuel défini comme l'intervalle de temps entre l'origine virtuelle et l'instant de coupure

3.12 facteur d'isolation du matériel effectif

k m coefficient du matériau qui dépend du matériau d'isolation électrique Note 1 à l'article: Voir l'IEC 62305-3

3.13 dispositif d'installation

installation qui comprend un ou plusieurs conducteurs de descente isolants et des moyens d'installation complémentaires (selon les instructions du fabricant) afin de maintenir la distance de séparation définie et de soutenir mécaniquement le conducteur de descente isolant Note 1 à l'article: Un exemple est donné à la Figure F.1.

3.14 fixations pour les conducteurs de descente isolants

composants métalliques, non métalliques ou composites qui permettent de fixer et de supporter le conducteur de descente, installé à intervalles réguliers le long des conducteurs

4 Support isolant

4.1 Classification

4.1.1 Généralités

La classification des produits dépend de la capacité de tenue des forces mécaniques.

4.1.2 Selon le dispositif de serrage du conducteur

Il existe deux classes de supports isolants selon le dispositif de serrage du conducteur:

a) fixations de conducteurs conçues pour emprisonner le conducteur; b) fixations de conducteurs conçues pour emprisonner le conducteur, mais permettre un déplacement axial de ce conducteur.

4.1.3 Selon le montage

En ce qui concerne le montage, il existe deux classes de supports isolants:

a) en pose libre; b) fixé fermement à une structure.

4.2 Exigences

4.2.1 Généralités

Un support isolant doit fixer, soutenir et isoler le conducteur quand ce dernier est soumis à une haute tension de choc de décharge de foudre et doit résister à des contraintes mécaniques et environnementales, telles que les charges perpendiculaires et de compression axiale dues au poids du conducteur soutenu et à la neige, à la glace, au vent et à la dilatation ou la contraction thermique du conducteur.

Un support isolant doit être compatible avec le conducteur qu'il soutient et la surface à laquelle il est fixé.

4.2.2 Construction
4.2.2.1 Généralités

Un support isolant doit être conçu et construit de façon que a) la surface ne comporte pas de bavures à l'issue du moulage, de déformations ou de défauts similaires susceptibles de blesser l'installateur ou l'utilisateur, et b) soient prises en compte les charges perpendiculaires et de compression axiale dues au poids du conducteur soutenu et à la neige, à la glace, au vent et à la dilatation/contraction thermique du conducteur.

La conformité au a) est vérifiée par examen visuel, et la conformité au b) est vérifiée selon le 4.3.6.2 et le 4.3.6.4.

4.2.2.2 Résistance à la corrosion

Un support isolant doit résister aux effets de la corrosion propres à l'environnement auquel il est exposé.

La conformité est vérifiée par essai selon le 4.3.5.1.

4.2.2.3 Résistance à la lumière UV

Un support isolant doit résister aux effets de l'exposition aux UV propres à l'environnement auquel il est exposé.

La conformité est vérifiée par essai selon le 4.3.5.2.

4.2.3 Exigences mécaniques
4.2.3.1 Généralités

Un support isolant peut être composé d'un dispositif de montage, d'un isolateur et d'une fixation de conducteur, comme cela est représenté à la Figure 1 et à la Figure 2. Le fabricant du support isolant doit s'assurer, à l'aide d'essais mécaniques ou de calculs appropriés, que le support satisfait aux exigences énoncées dans sa documentation.

La conformité est vérifiée par essai selon le 4.3.

Légende 1 dispositif de montage 2 isolateur 3 fixation de conducteur métallique 4 conducteur l longueur isolante st Figure 1 – Support isolant type équipé d'une fixation métallique

Légende 1 dispositif de montage 2 isolateur 3 fixation de conducteur non métallique 4 conducteur l longueur isolante st Figure 2 – Support isolant type équipé d'une fixation non métallique

4.2.3.2 Dispositif de montage

Le dispositif de montage qui maintient l'isolateur en place dans la structure doit résister à la contrainte mécanique.

La conformité est vérifiée par essai selon le 4.3.6.

4.2.3.3 Isolateur

L'isolateur doit résister à la contrainte mécanique, par exemple la force d'arrachement, la résistance à l'impact et la charge de flexion.

La conformité est vérifiée par essai selon le 4.3.6.

4.2.3.4 Fixation de conducteur

La fixation de conducteur, qui fait partie du support isolant, doit être conforme aux exigences et aux essais de l'IEC 62561-4.

4.2.4 Exigences électriques

Un support isolant doit être capable de résister aux très hautes tensions de choc générées par un coup de foudre.

Un support isolant possède une longueur isolante l , comme cela est représenté à la Figure 1 st et à la Figure 2. Elle se distingue de sa longueur effective l , qui est la valeur à comparer à la eff distance de séparation exigée s conformément à l'IEC 62305-3. Cette longueur effective du support isolant doit être supérieure ou égale à la distance de séparation exigée s. La capacité d'isolation d'un support isolant peut être donnée soit a) par sa longueur effective l , soit eff b) par son facteur de correction de la longueur effective k .

Le facteur de correction de la longueur effective k est déterminé à partir de la longueur

effective l et de la longueur isolante l , à l'aide de la Formule (1):

eff st I eff

k = (1)

I st

La conformité est vérifiée par essai selon le 4.3.1, le 4.3.2 et le 4.3.7. En vue de calculer la distance de séparation utilisée dans l'IEC 62305-3, la valeur du facteur d'isolation du matériel effectif k peut être prise égale à la valeur de k . m x NOTE Une valeur de k = 0,7 pour les supports isolants GFRP, PE et PVC dans des conditions normales de

fonctionnement peut être utilisée, d'après les résultats d'essai en laboratoire [2].

4.2.5 Documentation et instructions d'installation

Le fabricant ou le fournisseur du support isolant doit fournir dans les instructions d'installation les informations pertinentes afin de s'assurer que l'installateur puisse choisir et installer le composant de manière sûre et adaptée, conformément aux exigences de l'IEC 62305-3. La conformité est vérifiée par examen selon le 4.3.3.

4.2.6 Marquage
4.2.6.1 Contenu du marquage

Un support isolant doit comporter les marquages suivants:

a) le nom, le logo ou la marque du fabricant ou du fournisseur responsable, et b) le type ou l'identification du produit.

S'il n'est pas possible d'apposer ces marquages directement sur le produit, ils doivent être inscrits sur le plus petit emballage.

La conformité est vérifiée par examen visuel.

4.2.6.2 Durabilité et lisibilité

Le marquage sur le produit doit être durable et facilement lisible. NOTE Le marquage peut par exemple être réalisé par moulage, emboutissage, gravure, impression, étiquettes adhésives ou décalcomanies.

La conformité est vérifiée par essai selon le 4.3.4.

4.3 Essais

4.3.1 Conditions générales d'essais

Les essais réalisés selon le présent document sont des essais de type. Ces essais sont de telle nature qu'après avoir été réalisés, il n'est pas nécessaire de les répéter, à moins que des modifications n'aient été introduites dans les matériaux, dans la conception ou dans le type de procédé de fabrication, susceptibles de modifier les caractéristiques de performance du support isolant.

Tous les essais sont effectués avec des échantillons assemblés et installés dans les conditions d'utilisation normale spécifiées dans les instructions du fabricant ou du fournisseur, avec les matériaux de conducteur, les dimensions et les couples de serrage recommandés. La longueur isolante l de tous les échantillons doit être de (500 ± 5) mm, sauf spécification st contraire dans la procédure d'essai correspondante. Le fabricant doit préparer les échantillons d'essai conformément à la Figure 3 dans le cas d'une fixation métallique ou à la Figure 4 dans le cas d'une fixation non métallique.

Dimensions en millimètres

Légende 1 dispositif de montage 2 isolateur 3 fixation de conducteur métallique 4 conducteur l longueur isolante st Figure 3 – Support isolant type équipé d'une fixation métallique et préparé pour les essais

Dimensions en millimètres

Légende 1 dispositif de montage 2 isolateur 3 fixation de conducteur non métallique 4 conducteur l longueur isolante st Figure 4 – Support isolant type équipé d'une fixation non métallique et préparé pour les essais Le présent document ne peut pas couvrir tous les types de supports isolants et les façons de les fixer sur les différentes surfaces des matériaux. Lorsque cela est exigé pour ces applications, il convient de déterminer le protocole d'essai spécifique par accord entre l'ingénieur d'essai et le fabricant.

Un support isolant classé par le fabricant dans plus d'une des classifications du 4.1 doit être soumis à l'essai pour chaque catégorie applicable.

Les essais de type sont effectués sur trois échantillons conformément à la séquence d'essai indiquée dans le Tableau 1. Dans chaque séquence, les essais doivent être réalisés dans l'ordre indiqué à l'Annexe C.

Un échantillon satisfait à une séquence d'essai du Tableau 1 si toutes les exigences relatives aux articles d'essai et aux critères d'acceptation correspondants ont été remplies. Si le nombre exigé d'échantillons satisfait à une séquence d'essai, la conception du support isolant est acceptable pour cette séquence d'essai. Si au moins deux échantillons d'essai ne satisfont pas à une séquence d'essai, le support isolant n'est pas conforme au présent document.

Si un seul échantillon ne satisfait pas à un essai, cet essai (ainsi que ceux effectués précédemment dans la même séquence d'essai qui ont pu influencer le résultat de cet essai) doit être répété avec trois nouveaux échantillons. Aucune défaillance sur un quelconque échantillon n'est admise dans la seconde séquence d'essai. Un jeu de trois échantillons peut être utilisé pour plusieurs séquences d'essai avec l'accord du fabricant. Lorsqu'ils soumettent le premier jeu d'échantillons, les candidats peuvent aussi soumettre un jeu supplémentaire d'échantillons qui peut être nécessaire si un échantillon ne satisfait pas à l'essai. Sans demande supplémentaire, le laboratoire d'essai doit ensuite soumettre aux essais le jeu supplémentaire d'échantillons et ne doit rejeter ce dernier que si une nouvelle défaillance apparaît. Si le jeu supplémentaire d'échantillons n'est pas simultanément soumis aux essais, une défaillance d'un seul échantillon doit entraîner l'échec des essais. Les essais pour les échantillons non métalliques doivent démarrer au plus tôt 168 h après leur fabrication.

NOTE La valeur de 168 h correspond à un temps de traitement et est une valeur type fondée sur l'expérience. L'essai doit être effectué à l'air libre avec une température ambiante comprise entre +15 °C et +40 °C et une humidité relative comprise entre 25 % et 75 %.

Un torsiomètre qui présente une résolution d'au moins 0,5 Nm et une exactitude d'au moins 4 % doit être utilisé pour toutes les opérations de serrage.

Tableau 1 – Exigences applicables à l'essai de type pour un support isolant Séquence Identification des Description de l'essai Paragraphe Nombre d'échantillons d'essai jeux 1 Documentation 4.3.3 A 1 Essai du marquage 4.3.4 A 3 Construction 4.3.6.1 A 3

Essai de corrosion 4.3.5.1 E 3 Essai d'arrachement 4.3.6.4 E 3 3 9 ou plus en raison de la Essai à la lumière UV 4.3.5.2 B, C, D détérioration de la surface au cours de l'essai à haute tension.

a Essai de flexion 4.3.6.2 B 3 a Essai d'impact de l'isolateur 4.3.6.3 3 C 3 ou plus en raison de la a Essai électrique 4.3.7 détérioration de la surface au D cours de l'essai à haute tension.

a Par accord entre le fabricant et le laboratoire, un jeu d'échantillons déjà soumis à l'essai peut être réutilisé pour les autres essais du présent document.

4.3.2 Montage général d'essai

Sauf spécification contraire du fabricant, les conducteurs et les échantillons doivent être nettoyés avec un agent dégraissant adéquat, puis rincés à l'eau déminéralisée et séchés. Ils doivent alors être assemblés selon les instructions d'installation du fabricant, par exemple avec les conducteurs et les couples de serrage recommandés.

Il convient d'appliquer les couples de serrage de manière ferme et uniforme.

Chaque support isolant pouvant s'adapter en diamètre à la plage de variation d'un conducteur doit être soumis à l'essai sur la dimension minimale de conducteur recommandée.

4.3.3 Documentation

Le fabricant ou le fournisseur responsable doit fournir les informations suivantes dans sa documentation:

a) les classifications selon le 4.1; b) les dimensions maximales et minimales du conducteur; c) les matériaux des conducteurs à employer; d) le type de surface de montage à employer; e) la méthode recommandée de montage, d'installation et de fixation sur la surface de montage; f) la force d'arrachement; g) la force de flexion; h) la résistance mécanique (par exemple, couple de charge, charge de soutien); i) le coefficient k .

La conformité est vérifiée par examen.

4.3.4 Essai du marquage

La durabilité du marquage doit être soumise à l'essai en effectuant dix frottements avec un morceau de tissu imbibé d'eau.

Les marquages réalisés par moulage, emboutissage ou gravure ne sont pas soumis à cet essai. L'échantillon est considéré comme ayant satisfait à l'essai si le marquage demeure lisible.

...