Explosive atmospheres - Part 10-1: Classification of areas - Explosive gas atmospheres

IEC 60079-10-1:2008 is concerned with the classification of areas where flammable gas or vapour or mist hazards may arise and may then be used as a basis to support the proper selection and installation of equipment for use in a hazardous area. It is intended to be applied where there may be an ignition hazard due to the presence of flammable gas or vapour, mixed with air under normal atmospheric conditions, but it does not apply to a) mines susceptible to firedamp; b) the processing and manufacture of explosives; c) areas where a hazard may arise due to the presence of combustible dusts or fibres; d) catastrophic failures which are beyond the concept of abnormality; e) rommos used for medial purposes; f) domestic premises. This first edition of IEC 60079-10-1 cancels and replaces the fourth edition of IEC 60079-10, published in 2002, and constitutes a technical revision. The significant technical changes with respect to the previous edition are: - introduction of Annex D which deals with explosion hazard from flammable mists generated by the release under pressure of high flash point liquids; - introduction of Clause A.3 (release rate) which gives thermodynamic equations for release rate with a number of examples for estimating release rate of fluids and gases.

Explosionsfähige Atmosphäre - Teil 10-1: Einteilung der Bereiche - Gasexplosionsgefährdete Bereiche

Atmosphères explosives - Partie 10-1: Classement des emplacements - Atmosphères explosives gazeuses

La CEI 60079-10-1:2008 est relative au classement des emplacements dans lesquels des risques dus à des gaz, vapeurs ou brouillards inflammables peuvent apparaître, et ainsi constituer une base pour le choix et l'installation corrects du matériel utilisé dans de tels emplacements. Elle est destinée à être appliquée là où il peut exister un danger d'inflammation du fait de la présence de gaz ou vapeurs inflammables, en mélange avec l'air, dans les conditions atmosphériques normales; mais elle ne s'applique pas: a) aux mines grisouteuses; b) au traitement et à la fabrication des explosifs; c) aux emplacements dans lesquels un danger dû à la présence de poussières ou fibres inflammables peut apparaître; d) aux défaillances catastrophiques, qui dépassent le concept d'anormalité traité dans la présente norme; e) aux locaux utilisés à des fins médicales; f) aux locaux à usage domestique. Cette première édition de la CEI 60079-10-1 annule et remplace la quatrième édition de la CEI 60079-10, publiée en 2002, et constitue une révision technique. Les principales modifications techniques suivantes ont été apportées par rapport à l'édition précédente: - introduction de l'Annexe D qui traite du danger d'explosion du brouillard inflammable généré par l'échappement sous pression de liquides au point d'éclair élevé; - introduction de l'Article A.3 (taux de dégagement) qui donne des équations thermodynamiques pour le taux de dégagement avec des exemples pour l'estimation du taux de dégagement des fluides et de gaz.

Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske atmosfere (IEC 60079-10-1:2008)

General Information

Status
Withdrawn
Publication Date
25-Mar-2009
Withdrawal Date
29-Feb-2012
Drafting Committee
IEC/SC 31J - IEC_SC_31J
Parallel Committee
IEC/SC 31J - IEC_SC_31J
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
13-Oct-2018
Completion Date
13-Oct-2018

Relations

Effective Date
28-Jan-2023
Effective Date
15-Dec-2015
Standard

EN 60079-10-1:2009 (EN)

English language
69 pages
Preview
Preview
e-Library read for
1 day
Standard

EN 60079-10-1:2009 (FR)

French language
75 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

EN 60079-10-1:2009 is a standard published by CLC. Its full title is "Explosive atmospheres - Part 10-1: Classification of areas - Explosive gas atmospheres". This standard covers: IEC 60079-10-1:2008 is concerned with the classification of areas where flammable gas or vapour or mist hazards may arise and may then be used as a basis to support the proper selection and installation of equipment for use in a hazardous area. It is intended to be applied where there may be an ignition hazard due to the presence of flammable gas or vapour, mixed with air under normal atmospheric conditions, but it does not apply to a) mines susceptible to firedamp; b) the processing and manufacture of explosives; c) areas where a hazard may arise due to the presence of combustible dusts or fibres; d) catastrophic failures which are beyond the concept of abnormality; e) rommos used for medial purposes; f) domestic premises. This first edition of IEC 60079-10-1 cancels and replaces the fourth edition of IEC 60079-10, published in 2002, and constitutes a technical revision. The significant technical changes with respect to the previous edition are: - introduction of Annex D which deals with explosion hazard from flammable mists generated by the release under pressure of high flash point liquids; - introduction of Clause A.3 (release rate) which gives thermodynamic equations for release rate with a number of examples for estimating release rate of fluids and gases.

IEC 60079-10-1:2008 is concerned with the classification of areas where flammable gas or vapour or mist hazards may arise and may then be used as a basis to support the proper selection and installation of equipment for use in a hazardous area. It is intended to be applied where there may be an ignition hazard due to the presence of flammable gas or vapour, mixed with air under normal atmospheric conditions, but it does not apply to a) mines susceptible to firedamp; b) the processing and manufacture of explosives; c) areas where a hazard may arise due to the presence of combustible dusts or fibres; d) catastrophic failures which are beyond the concept of abnormality; e) rommos used for medial purposes; f) domestic premises. This first edition of IEC 60079-10-1 cancels and replaces the fourth edition of IEC 60079-10, published in 2002, and constitutes a technical revision. The significant technical changes with respect to the previous edition are: - introduction of Annex D which deals with explosion hazard from flammable mists generated by the release under pressure of high flash point liquids; - introduction of Clause A.3 (release rate) which gives thermodynamic equations for release rate with a number of examples for estimating release rate of fluids and gases.

EN 60079-10-1:2009 is classified under the following ICS (International Classification for Standards) categories: 29.260.20 - Electrical apparatus for explosive atmospheres. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 60079-10-1:2009 has the following relationships with other standards: It is inter standard links to EN 60079-10:2003, EN 60079-10-1:2015. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase EN 60079-10-1:2009 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2009
1DGRPHãþD
SIST EN 60079-10:2003
Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske
atmosfere (IEC 60079-10-1:2008)
Explosive atmospheres -- Part 10-1: Classification of areas - Explosive gas atmospheres
Explosionsfähige Atmosphäre – Teil 10-1: Einteilung der Bereiche –
Gasexplosionsgefährdete Bereiche
Atmosphères explosives -- Partie 10-1: Classement des emplacements - Atmosphères
explosives gazeuses
Ta slovenski standard je istoveten z: EN 60079-10-1:2009
ICS:
29.260.20 (OHNWULþQLDSDUDWL]D Electrical apparatus for
HNVSOR]LYQDR]UDþMD explosive atmospheres
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 60079-10-1
NORME EUROPÉENNE
March 2009
EUROPÄISCHE NORM
ICS 29.260.20 Supersedes EN 60079-10:2003

English version
Explosive atmospheres -
Part 10-1: Classification of areas -
Explosive gas atmospheres
(IEC 60079-10-1:2008)
Atmosphères explosives -  Explosionsfähige Atmosphäre -
Partie 10-1: Classement Teil 10-1: Einteilung der Bereiche -
des emplacements - Gasexplosionsgefährdete Bereiche
Atmosphères explosives gazeuses (IEC 60079-10-1:2008)
(CEI 60079-10-1:2008)
This European Standard was approved by CENELEC on 2009-03-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60079-10-1:2009 E
Foreword
The text of document 31J/159/FDIS, future edition 1 of IEC 60079-10-1, prepared by SC 31J,
Classification of hazardous areas and installation requirements, of IEC TC 31, Equipment for explosive
atmospheres, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as
EN 60079-10-1 on 2009-03-01.
This European Standard supersedes EN 60079-10:2003.
The significant technical changes with respect to EN 60079-10:2003 are as follows:
– introduction of Annex D which deals with explosion hazard from flammable mists generated by the
release under pressure of high flash point liquids;
– introduction of Clause A.3 (release rate) which gives thermodynamic equations for release rate with a
number of examples for estimating release rate of fluids and gases.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-12-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-03-01
Annexes ZA and ZB have been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 60079-10-1:2008 was approved by CENELEC as a European
Standard without any modification.
__________
- 3 - EN 60079-10-1:2009
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year

1)
IEC 60050-426 - International Electrotechnical Vocabulary - -
(IEV) -
Part 426: Equipment for explosive
atmospheres
1) 1)
IEC 60079-0 - Explosive atmospheres - EN 60079-0 -
Part 0: Equipment - General requirements

1)
IEC 60079-4 - Electrical apparatus for explosive gas - -
atmospheres -
Part 4: Method of test for ignition temperature

1)
IEC 60079-4A - Electrical apparatus for explosive gas - -
atmospheres -
Part 4: Method of test for ignition temperature
First supplement to IEC 60079-4A:1966

1)
IEC/TR 60079-20 - Electrical apparatus for explosive gas - -
atmospheres -
Part 20: Data for flammable gases and
vapours, relating to the use of electrical
apparatus
1)
Undated reference.
Annex ZB
(informative)
ATEX Categories and Equipment Protection Levels (EPLs)
This European Standard has been written to incorporate the concept of Equipment Protection Levels
(EPLs).
EPLs are analogous to the ATEX Categories, indeed the definitions are identical.
Wherever there is a reference to an EPL in the text it should be equated with the corresponding ATEX
Category:
– EPL ‘Ga’ equates to ATEX Category 1G;
– EPL ‘Gb’ equates to ATEX Category 2G;
– EPL ‘Gc’ equates to ATEX Category 3G;
– EPL ‘Da’ equates to ATEX Category 1D;
– EPL ‘Db’ equates to ATEX Category 2D;
– EPL ‘Dc’ equates to ATEX Category 3D.
__________
IEC 60079-10-1
Edition 1.0 2008-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres

Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XB
CODE PRIX
ICS 29.260.20 ISBN 2-8318-1019-3
– 2 – 60079-10-1 © IEC:2008
CONTENTS
FOREWORD.3
INTRODUCTION.5
1 Scope.6
2 Normative references .7
3 Terms and definitions .7
4 General .10
4.1 Safety principles.10
4.2 Area classification objectives .11
5 Area classification procedure.12
5.1 General .12
5.2 Sources of release .12
5.3 Type of zone .13
5.4 Extent of zone .13
5.4.1 Release rate of gas or vapour.13
5.4.2 Lower explosive limit (LEL).14
5.4.3 Ventilation .14
5.4.4 Relative density of the gas or vapour when it is released.15
5.4.5 Other parameters to be considered.15
5.4.6 Illustrative examples.15
6 Ventilation .16
6.1 General .16
6.2 Main types of ventilation.16
6.3 Degree of ventilation .16
6.4 Availability of ventilation.17
7 Documentation .17
7.1 General .17
7.2 Drawings, data sheets and tables.17
Annex A (informative) Examples of sources of release and release rate .18
Annex B (informative) Ventilation.24
Annex C (informative) Examples of hazardous area classification .40
Annex D (informative) Flammable mists .63
Bibliography.65

Figure C.1 – Preferred symbols for hazardous area zones .41
Figure C.2 – Schematic approach to the classification of hazardous areas.62

Table A.1 – Effect of openings on grade of release .19
Table B.1 – Influence of independent ventilation on type of zone .31
Table B.2 – Procedure for summation of multiple releases within location V .32
o
Table B.3 – Procedure for summation of multiple primary grade releases .32
Table C.1 − Hazardous area classification data sheet – Part I: Flammable material list
and characteristics.60
Table C.2 − Hazardous area classification data sheet − Part II: List of sources of
release .61

60079-10-1 © IEC:2008 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EXPLOSIVE ATMOSPHERES –
Part 10-1: Classification of areas –
Explosive gas atmospheres
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60079-10-1 has been prepared by subcommittee 31J:
Classification of hazardous areas and installation requirements, of IEC technical committee
31: Equipment for explosive atmospheres.
This first edition of IEC 60079-10-1 cancels and replaces the fourth edition of IEC 60079-10,
published in 2002, and constitutes a technical revision.
The significant technical changes with respect to the previous edition are as follows:
• Introduction of Annex D which deals with explosion hazard from flammable mists
generated by the release under pressure of high flash point liquids.
• Introduction of Clause A.3 (release rate) which gives thermodynamic equations for release
rate with a number of examples for estimating release rate of fluids and gases.

– 4 – 60079-10-1 © IEC:2008
The text of this standard is based on the following documents:
FDIS Report on voting
31J/159/FDIS 31J/160/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 60079 series, under the general title Explosive atmospheres, can
be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
60079-10-1 © IEC:2008 – 5 –
INTRODUCTION
In areas where dangerous quantities and concentrations of flammable gas or vapour may
arise, protective measures are to be applied in order to reduce the risk of explosions. This
part of IEC 60079 sets out the essential criteria against which the ignition hazards can be
assessed, and gives guidance on the design and control parameters which can be used in
order to reduce such a hazard.

– 6 – 60079-10-1 © IEC:2008
EXPLOSIVE ATMOSPHERES –
Part 10-1: Classification of areas –
Explosive gas atmospheres
1 Scope
This part of IEC 60079 is concerned with the classification of areas where flammable gas or
vapour or mist hazards (see Notes 1, 2 and 3) may arise and may then be used as a basis to
support the proper selection and installation of equipment for use in a hazardous area.
It is intended to be applied where there may be an ignition hazard due to the presence of
flammable gas or vapour, mixed with air under normal atmospheric conditions (see Note 4),
but it does not apply to
a) mines susceptible to firedamp;
b) the processing and manufacture of explosives;
c) areas where a hazard may arise due to the presence of combustible dusts or fibres (refer
to IEC 61241-10 / IEC 60079-10-2);
d) catastrophic failures which are beyond the concept of abnormality dealt with in this
standard (see Note 5);
e) rooms used for medical purposes;
f) domestic premises.
This standard does not take into account the effects of consequential damage.
Definitions and explanations of terms are given together with the main principles and
procedures relating to hazardous area classification.
For detailed recommendations regarding the extent of the hazardous areas in specific
industries or applications, reference may be made to national or industry codes relating to
those applications.
NOTE 1 Flammable mists may form or be present at the same time as flammable vapours. Liquids not considered
to be hazardous in terms of this standard (due to the flash point), when released under pressure may also generate
flammable mists. In such cases, the strict application of area classification for gases and vapours may not be
appropriate as the basis for selection of equipment.
Information on flammable mists is provided in Annex D.
NOTE 2 The use of IEC 60079-14 for selection of equipment and installations is not required for mist hazards.
NOTE 3 For the purpose of this standard, an area is a three-dimensional region or space.
NOTE 4 Atmospheric conditions include variations above and below reference levels of 101,3 kPa (1 013 mbar)
and 20 °C (293 K), provided that the variations have a negligible effect on the explosion properties of the
flammable materials.
NOTE 5 Catastrophic failure in this context is applied, for example, to the rupture of a process vessel or pipeline
and events that are not predictable.
NOTE 6 In any process plant, irrespective of size, there may be numerous sources of ignition apart from those
associated with equipment. Appropriate precautions will be necessary to ensure safety in this context. This
standard may be used with judgement for other ignition sources.

60079-10-1 © IEC:2008 – 7 –
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050-426, International Electrotechnical Vocabulary (IEV) – Part 426: Equipment for
explosive atmospheres
IEC 60079-0, Explosive atmospheres – Part 0: Equipment – General requirements
IEC 60079-4, Electrical apparatus for explosive gas atmospheres – Part 4: Method of test for
ignition temperature
IEC 60079-4A, First supplement to IEC 60079-4 (1966), Electrical apparatus for explosive gas
atmospheres – Part 4: Method of test for ignition temperature
IEC 60079-20, Electrical apparatus for explosive gas atmospheres – Part 20: Data for
flammable gases and vapours, relating to the use of electrical apparatus
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60079-0 and the
following apply.
NOTE Additional definitions applicable to explosive atmospheres can be found in the IEC 60050-426.
3.1
explosive atmosphere
mixture with air, under atmospheric conditions, of flammable substances in the form of gas,
vapour, dust, fibres, or flyings which, after ignition, permits self-sustaining propagation
[IEC 60079-0, definition 3.22]
3.2
explosive gas atmosphere
mixture with air, under atmospheric conditions, of flammable substances in the form of gas or
vapour, which, after ignition, permits self-sustaining flame propagation
[IEC 60079-0, definition 3.24]
NOTE 1 Although a mixture which has a concentration above the upper explosive limit (UEL) is not an explosive
gas atmosphere, it can readily become so and, in certain cases for area classification purposes, it is advisable to
consider it as an explosive gas atmosphere.
NOTE 2 There are some gases which are explosive with the concentration of 100 %.
3.3
hazardous area (on account of explosive gas atmospheres)
an area in which an explosive gas atmosphere is or may be expected to be present, in
quantities such as to require special precautions for the construction, installation and use of
equipment
3.4
non-hazardous area (on account of explosive gas atmospheres)
an area in which an explosive gas atmosphere is not expected to be present in quantities
such as to require special precautions for the construction, installation and use of equipment

– 8 – 60079-10-1 © IEC:2008
3.5
zones
hazardous areas are classified into zones based upon the frequency of the occurrence and
duration of an explosive gas atmosphere, as follows:
3.6
zone 0
an area in which an explosive gas atmosphere is present continuously or for long periods or
frequently
3.7
zone 1
an area in which an explosive gas atmosphere is likely to occur in normal operation
occasionally
3.8
zone 2
area in which an explosive gas atmosphere is not likely to occur in normal operation but, if it
does occur, will persist for a short period only
[IEV 426-03-05]
NOTE Indications of the frequency of the occurrence and duration may be taken from codes relating to specific
industries or applications.
3.9
source of release
a point or location from which a gas, vapour, mist or liquid may be released into the
atmosphere so that an explosive gas atmosphere could be formed
IEV 426-03-06, modified]
3.10
grades of release
there are three basic grades of release, as listed below in order of decreasing frequency and
likelihood of the explosive gas atmosphere being present:
a) continuous grade;
b) primary grade;
c) secondary grade.
A source of release may give rise to any one of these grades of release, or to a combination
of more than one
3.11
continuous grade of release
release which is continuous or is expected to occur frequently or for long periods
3.12
primary grade of release
release which can be expected to occur periodically or occasionally during normal operation
3.13
secondary grade of release
release which is not expected to occur in normal operation and, if it does occur, is likely to do
so only infrequently and for short periods

60079-10-1 © IEC:2008 – 9 –
3.14
release rate
quantity of flammable gas, vapour or mist emitted per unit time from the source of release
3.15
normal operation
situation when the equipment is operating within its designed parameters
NOTE 1 Minor releases of flammable material may be part of normal operation. For example, releases from seals
which rely on wetting by the fluid which is being pumped are considered to be minor releases.
NOTE 2 Failures (such as the breakdown of pump seals, flange gaskets or spillages caused by accidents) which
involve urgent repair or shut-down are not considered to be part of normal operation nor are they considered to be
catastrophic.
NOTE 3 Normal operation includes start-up and shut-down conditions.
3.16
ventilation
movement of air and its replacement with fresh air due to the effects of wind, temperature
gradients, or artificial means (for example, fans or extractors)
3.17
lower explosive limit (LEL)
concentration of flammable gas, vapour or mist in air below which an explosive gas
atmosphere will not be formed
[IEV 426-02-09]
3.18
upper explosive limit (UEL)
concentration of flammable gas, vapour or mist in air, above which an explosive gas
atmosphere will not be formed
[IEV 426-02-10]
3.19
relative density of a gas or a vapour
density of a gas or a vapour relative to the density of air at the same pressure and at the
same temperature (air is equal to 1,0)
3.20
flammable material (flammable substance)
material which is flammable of itself, or is capable of producing a flammable gas, vapour or
mist
3.21
flammable liquid
liquid capable of producing a flammable vapour under any foreseeable operating conditions
NOTE An example of a foreseeable operating condition is one in which the flammable liquid is handled at
temperatures close to or above its flash point.
3.22
flammable gas or vapour
gas or vapour which, when mixed with air in certain proportions, will form an explosive gas
atmosphere
3.23
flammable mist
droplets of liquid, dispersed in air so as to form an explosive atmosphere

– 10 – 60079-10-1 © IEC:2008
3.24
flashpoint
lowest liquid temperature at which, under certain standardized conditions, a liquid gives off
vapours in a quantity such as to be capable of forming an ignitable vapour/air mixture
3.25
boiling point
temperature of a liquid boiling at an ambient pressure of 101,3 kPa (1 013 mbar)
NOTE The initial boiling point that should be used for liquid mixtures is to indicate the lowest value of the boiling
point for the range of liquids present, as determined in a standard laboratory distillation without fractionation.
3.26
vapour pressure
pressure exerted when a solid or liquid is in equilibrium with its own vapour. It is a function of
the substance and of the temperature
3.27
ignition temperature of an explosive gas atmosphere
lowest temperature of a heated surface which, under specified conditions according to
IEC 60079-4, will ignite a flammable substance in the form of a gas or vapour mixture with air
[IEC 60079-0, definition 3.26]
3.28
extent of zone
distance in any direction from the source of release to the point where the gas/air mixture has
been diluted by air to a value below the lower explosive limit
3.29
liquefied flammable gas
flammable material which is stored or handled as a liquid and which at ambient temperature
and atmospheric pressure is a flammable gas
4 General
4.1 Safety principles
Installations in which flammable materials are handled or stored should be designed,
operated and maintained so that any releases of flammable material, and consequently the
extent of hazardous areas, are kept to a minimum, whether in normal operation or otherwise,
with regard to frequency, duration and quantity.
It is important to examine those parts of process equipment and systems from which release
of flammable material may arise and to consider modifying the design to minimise the
likelihood and frequency of such releases and the quantity and rate of release of material.
These fundamental considerations should be examined at an early stage of the design
development of any process plant and should also receive prime attention in carrying out the
area classification study.
In the case of activities other than those of normal operation, e.g. commissioning or
maintenance, the area classification may not be valid. It is expected that this would be dealt
with by a safe system of work.
In a situation in which there may be an explosive gas atmosphere, the following steps should
be taken:
60079-10-1 © IEC:2008 – 11 –
a) eliminate the likelihood of an explosive gas atmosphere occurring around the source of
ignition, or
b) eliminate the source of ignition.
Where this is not possible, protective measures, process equipment, systems and procedures
should be selected and prepared so the likelihood of the coincidence of a) and b) is so small
as to be acceptable. Such measures may be used singly, if they are recognized as being
highly reliable, or in combination to achieve the required level of safety.
4.2 Area classification objectives
Area classification is a method of analysing and classifying the environment where explosive
gas atmospheres may occur so as to facilitate the proper selection and installation of
equipment to be used safely in that environment. The classification also takes into account
the ignition characteristics of the gas or vapour such as ignition energy (gas group) and
ignition temperature (temperature class).
In most practical situations where flammable materials are used, it is difficult to ensure that an
explosive gas atmosphere will never occur. It may also be difficult to ensure that equipment
will never give rise to a source of ignition. Therefore, in situations where an explosive gas
atmosphere has a high likelihood of occurring, reliance is placed on using equipment which
has a low likelihood of creating a source of ignition. Conversely, where the likelihood of an
explosive gas atmosphere occurring is reduced, equipment constructed with less rigorous
requirements may be used.
Subsequent to the completion of the area classification, a risk assessment may be carried out
to assess whether the consequences of ignition of an explosive atmosphere requires the use
of equipment of a higher equipment protection level (EPL) or may justify the use of equipment
with a lower equipment protection level than normally required. The EPL requirements may be
recorded, as appropriate, on the area classification documents and drawings to allow proper
selection of equipment.
It is rarely possible by a simple examination of a plant or plant design to decide which parts of
the plant can be equated to the three zonal definitions (zones 0, 1 and 2). A more detailed
approach is therefore necessary and this involves the analysis of the basic possibility of an
explosive gas atmosphere occurring.
The first step is to assess the likelihood of this, in accordance with the definitions of zone 0,
zone 1 and zone 2. Once the likely frequency and duration of release (and hence the grade of
release), the release rate, concentration, velocity, ventilation and other factors which affect
the type and/or extent of the zone have been determined, there is then a firm basis on which
to determine the likely presence of an explosive gas atmosphere in the surrounding areas.
This approach therefore requires detailed consideration to be given to each item of process
equipment which contains a flammable material, and which could therefore be a source of
release.
In particular, zone 0 or zone 1 areas should be minimised in number and extent by design or
suitable operating procedures. In other words, plants and installations should be mainly
zone 2 or non-hazardous. Where release of flammable material is unavoidable, process
equipment items should be limited to those which give secondary grade releases or, failing
this (that is where primary or continuous grade releases are unavoidable), the releases should
be of very limited quantity and rate. In carrying out area classification, these principles should
receive prime consideration. Where necessary, the design, operation and location of process
equipment should ensure that, even when it is operating abnormally, the amount of flammable
material released into the atmosphere is minimised, so as to reduce the extent of the
hazardous area.
– 12 – 60079-10-1 © IEC:2008
Once a plant has been classified and all necessary records made, it is important that no
modification to equipment or operating procedures is made without discussion with those
responsible for the area classification. Unauthorised action may invalidate the area
classification. It is necessary to ensure that all equipment affecting the area classification
which has been subjected to maintenance is carefully checked during and after re-assembly
to ensure that the integrity of the original design, as it affects safety, has been maintained
before it is returned to service.
5 Area classification procedure
5.1 General
The area classification should be carried out by those who understand the relevance and
significance of properties of flammable materials and those who are familiar with the process
and the equipment along with safety, electrical, mechanical and other qualified engineering
personnel.
The following subclauses give guidance on the procedure for classifying areas in which there
may be an explosive gas atmosphere. An example of a schematic approach to the
classification of hazardous areas is given in Figure C.2.
The area classification should be carried out when the initial process and instrumentation line
diagrams and initial layout plans are available and confirmed before plant start-up. Reviews
should be carried out during the life of the plant.
5.2 Sources of release
The basic elements for establishing the hazardous zone types are the identification of the
source of release and the determination of the grade of release.
Since an explosive gas atmosphere can exist only if a flammable gas or vapour is present
with air, it is necessary to decide if any of these flammable materials can exist in the area
concerned. Generally speaking, such gases and vapours (and flammable liquids and solids
which may give rise to them) are contained within process equipment which may or may not
be totally enclosed. It is necessary to identify where a flammable atmosphere can exist inside
a process plant, or where a release of flammable materials can create a flammable
atmosphere outside a process plant.
Each item of process equipment (for example, tank, pump, pipeline, vessel, etc.) should be
considered as a potential source of release of flammable material. If the item cannot
foreseeably contain flammable material, it will clearly not give rise to a hazardous area
around it. The same will apply if the item contains a flammable material but cannot release it
into the atmosphere (for example, an all-welded pipeline is not considered to be a source of
release).
If it is established that the item may release flammable material into the atmosphere, it is
necessary, first of all, to determine the grade of release in accordance with the definitions, by
establishing the likely frequency and duration of the release. It should be recognized that the
opening-up of parts of enclosed process systems (for example, during filter changing or batch
filling) should also be considered as sources of release when developing the area
classification. By means of this procedure, each release will be graded either ‘continuous’,
‘primary’ or ’secondary’.
Having established the grade of the release, it is necessary to determine the release rate and
other factors which may influence the type and extent of the zone.

60079-10-1 © IEC:2008 – 13 –
If the total quantity of flammable material available for release is “small”, for example, labo-
ratory use, whilst a potential hazard may exist, it may not be appropriate to use this area
classification procedure. In such cases, account shall be taken of the particular risks involved.
The area classification of process equipment in which flammable material is burned, for
example, fired heaters, furnaces, boilers, gas turbines etc., should take into account purge
cycle, start-up and shut-down conditions.
Mists which can form through leaks of liquid can be flammable even though the liquid
temperature is below the flash point. It is important therefore to ensure that clouds of mist do
not occur (see Annex D).
NOTE While mists are identified as a form of hazard, the assessment criteria used in this standard for gases and
vapours may not apply to mists.
5.3 Type of zone
The likelihood of the presence of an explosive gas atmosphere depends mainly on the grade
of release and the ventilation. This is identified as a zone. Zones are recognized as: zone 0,
zone 1, zone 2 and the non-hazardous area.
NOTE 1 A continuous grade of release normally leads to a zone 0, a primary grade to zone 1 and a secondary
grade to zone 2 (see Annex B).
NOTE 2 Where zones created by adjacent sources of release overlap and are of different zonal classification, the
higher classification criteria will apply in the area of overlap. Where overlapping zones are of the same
classification, this common classification will normally apply.
5.4 Extent of zone
The extent of the zone depends on the estimated or calculated distance over which an
explosive atmosphere exists before it disperses to a concentration in air below its lower
explosive limit with an appropriate safety factor. When assessing the area of spread of gas or
vapour before dilution to below its lower explosive limit, expert advice should be sought.
Consideration should always be given to the possibility that a gas which is heavier than air
may flow into areas below ground level (for example, pits or depressions) and that a gas
which is lighter than air may be retained at high level (for example, in a roof space).
Where the source of release is situated outside an area or in an adjoining area, the pene-
tration of a significant quantity of flammable gas or vapour into the area can be prevented by
suitable means such as:
a) physical barriers;
b) maintaining a sufficient overpressure in the area relative to the adjacent hazardous areas,
so preventing the ingress of the explosive gas atmosphere;
c) purging the area with sufficient flow of fresh air, so ensuring that the air escapes from all
openings where the flammable gas or vapour may enter.
The extent of the zone is mainly affected by the following chemical and physical parameters,
some of which are intrinsic properties of the flammable material; others are specific to the
process. For simplicity, the effect of each parameter listed below assumes that the other
parameters remain unchanged.
5.4.1 Release rate of gas or vapour
The greater the release rate, the larger the extent of the zone. The release rate depends itself
on other parameters, namely
a) Geometry of the source of release

– 14 – 60079-10-1 © IEC:2008
This is related to the physical characteristics of the source of release, for example, an
open surface, leaking flange, etc. (see Annex A).
b) Release velocity
For a given source of release, the release rate increases with the release velocity. In the
case of a product contained within process equipment, the release velocity is related to
the process pressure and the geometry of the source of release. The size of a cloud of
flammable gas or vapour is determined by the rate of flammable vapour release and the
rate of dispersion. Gas and vapour flowing from a leak at high velocity will develop a cone-
shaped jet which will entrain air and be self-diluting. The extent of the explosive gas
atmosphere will be almost independent of air flow. If the material is released at low
velocity or if its velocity is reduced by impingement on a solid object, it will be carried by
the air flow and its dilution and extent will depend on air flow.
c) Concentration
The release rate increases with the concentration of flammable vapour or gas in the
released mixture.
d) Volatility of a flammable liquid
This is related principally to the vapour pressure, and the enthalpy (“heat”) of vaporization.
If the vapour pressure is not known, the boiling point and flashpoint can be used as a
guide.
An explosive gas atmosphere cannot exist if the flashpoint is above the relevant maximum
temperature of the flammable liquid. The lower the flashpoint, the greater may be the
extent of the zone. However, if a flammable material is released in a way that forms a mist
(for example, by spraying) an explosive atmosphere may be formed below the flashpoint
of the material.
NOTE 1 Flashpoints of flammable liquids are not precise physical quantities, particularly where mixtures are
involved.
NOTE 2 Some liquids (for example, certain halogenated hydrocarbons) do not possess a flashpoint although
they are capable of producing an explosive gas atmosphere. In these cases, the equilibrium liquid temperature
which corresponds to the saturated concentration at the lower explosive limit should be compared with the
relevant maximum liquid temperature.
e) Liquid temperature
The vapour pressure increases with temperature, thus increasing the release rate due to
evaporation.
NOTE The temperature of the liquid after it has been released may be increased, for example, by a hot
surface or by a high ambient temperature.
5.4.2 Lower explosive limit (LEL)
For a given release volume, the lower the LEL the greater will be the extent of the zone.
NOTE Experience has shown that a release of ammonia, with an LEL of 15 % by volume, will often dissipate
rapidly in the open air, so an explosive gas atmosphere will, in most cases be of negligible extent.
5.4.3 Ventilation
With increased ventilation, the extent of the zone will normally be reduced. Obstacles which
impede the ventilation may increase the extent of the zone. On the other hand, some
obstacles, for example, dykes, walls or ceilings, may limit the extent.
NOTE 1 A shelter with a large roof-ventilator and with the sides open sufficient to allow free passage of air
through all parts of the building in many cases is considered well ventilated and should be treated as an open air
area (i.e. “medium” degree and “good” availability).
NOTE 2 Increased air movement may also increase the rate of release of vapour due to increased evaporation on
open liquid surfaces.
60079-10-1 © IEC:2008 – 15 –
5.4.4 Relative density of the gas or vapour when it is released
If the gas or vapour is significantly lighter than air, it will tend to move upwards. If significantly
heavier, it will tend to accumulate at ground level. The horizontal extent of the zone at ground
level will increase with increasing relative density and the vertical extent above the source will
increase with de
...


SLOVENSKI STANDARD
01-september-2009
1DGRPHãþD
SIST EN 60079-10:2003
Eksplozivne atmosfere - 10-1. del: Razvrstitev prostorov - Eksplozivne plinske
atmosfere (IEC 60079-10-1:2008)
Explosive atmospheres -- Part 10-1: Classification of areas - Explosive gas atmospheres
Explosionsfähige Atmosphäre – Teil 10-1: Einteilung der Bereiche –
Gasexplosionsgefährdete Bereiche
Atmosphères explosives -- Partie 10-1: Classement des emplacements - Atmosphères
explosives gazeuses
Ta slovenski standard je istoveten z: EN 60079-10-1:2009
ICS:
29.260.20 (OHNWULþQLDSDUDWL]D Electrical apparatus for
HNVSOR]LYQDR]UDþMD explosive atmospheres
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

NORME EUROPÉENNE
EN 60079-10-1
EUROPÄISCHE NORM
Mars 2009
EUROPEAN STANDARD
ICS 29.260.20 Remplace EN 60079-10:2003

Version française
Atmosphères explosives -
Partie 10-1: Classement des emplacements -
Atmosphères explosives gazeuses
(CEI 60079-10-1:2008)
Explosionsfähige Atmosphäre -  Explosive atmospheres -
Teil 10-1: Einteilung der Bereiche - Part 10-1: Classification of areas -
Gasexplosionsgefährdete Bereiche Explosive gas atmospheres
(IEC 60079-10-1:2008) (IEC 60079-10-1:2008)

La présente Norme Européenne a été adoptée par le CENELEC le 2009-03-01. Les membres du CENELEC
sont tenus de se soumettre au Règlement Intérieur du CEN/CENELEC qui définit les conditions dans lesquelles
doit être attribué, sans modification, le statut de norme nationale à la Norme Européenne.

Les listes mises à jour et les références bibliographiques relatives à ces normes nationales peuvent être
obtenues auprès du Secrétariat Central ou auprès des membres du CENELEC.

La présente Norme Européenne existe en trois versions officielles (allemand, anglais, français). Une version
dans une autre langue faite par traduction sous la responsabilité d'un membre du CENELEC dans sa langue
nationale, et notifiée au Secrétariat Central, a le même statut que les versions officielles.

Les membres du CENELEC sont les comités électrotechniques nationaux des pays suivants: Allemagne,
Autriche, Belgique, Bulgarie, Chypre, Danemark, Espagne, Estonie, Finlande, France, Grèce, Hongrie, Irlande,
Islande, Italie, Lettonie, Lituanie, Luxembourg, Malte, Norvège, Pays-Bas, Pologne, Portugal, République
Tchèque, Roumanie, Royaume-Uni, Slovaquie, Slovénie, Suède et Suisse.

CENELEC
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
European Committee for Electrotechnical Standardization

Secrétariat Central: avenue Marnix 17, B - 1050 Bruxelles

© 2009 CENELEC - Tous droits d'exploitation sous quelque forme et de quelque manière que ce soit réservés dans le monde entier aux
membres du CENELEC.
Ref. n° EN 60079-10-1:2009 F
Avant-propos
Le texte du document 31J/159/FDIS, future édition 1 de la CEI 60079-10-1, préparé par le SC 31J,
Classification des emplacements dangereux et règles d'installation, du CE 31 de la CEI, Equipements
pour atmosphères explosives, a été soumis au vote parallèle CEI-CENELEC et a été approuvé par le
CENELEC comme EN 60079-10-1 le 2009-03-01.
Cette Norme Européenne remplace la EN 60079-10:2003.
Les principales modifications techniques suivantes ont été apportées par rapport à la EN 60079-10:2003:
– introduction de l’Annexe D qui traite du danger d’explosion du brouillard inflammable généré par
l’échappement sous pression de liquides au point d’éclair élevé;
– introduction de l’Article A.3 (taux de dégagement) qui donne des équations thermodynamiques pour le
taux de dégagement avec des exemples pour l’estimation du taux de dégagement des fluides et de
gaz.
Les dates suivantes ont été fixées:
– date limite à laquelle la EN doit être mise en application
au niveau national par publication d'une norme
nationale identique ou par entérinement (dop) 2009-12-01
– date limite à laquelle les normes nationales
conflictuelles doivent être annulées (dow) 2012-03-01
Les Annexes ZA et ZB ont été ajoutées par le CENELEC.
__________
Notice d’entérinement
Le texte de la Norme internationale CEI 60079-10-1:2008 a été approuvé par le CENELEC comme
Norme Européenne sans aucune modification.
__________
- 3 - EN 60079-10-1:2009
Annexe ZA
(normative)
Références normatives à d'autres publications internationales
avec les publications européennes correspondantes

Les documents de référence suivants sont indispensables pour l'application du présent document. Pour
les références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition
du document de référence s'applique (y compris les éventuels amendements).

NOTE  Dans le cas où une publication internationale est modifiée par des modifications communes, indiqué par (mod), l'EN / le HD
correspondant(e) s'applique.
Publication Année Titre EN/HD Année

1)
CEI 60050-426 - Vocabulaire Electrotechnique International - -
(VEI) -
Partie 426: Matériel pour atmosphères
explosives
1) 1)
CEI 60079-0 - Atmosphères explosives - EN 60079-0 -
Partie 0: Matériel - Exigences générales

1)
CEI 60079-4 - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 4: Méthode d'essai pour la
détermination de la température
d'inflammation
1)
CEI 60079-4A - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 4: Méthode d'essai pour la
détermination de la température
d'inflammation
Premier complément à la CEI 60079-4:1966

1)
CEI/TR 60079-20 - Matériel électrique pour atmosphères - -
explosives gazeuses -
Partie 20: Données pour gaz et vapeurs
inflammables, en relation avec l'utilisation des
matériels électriques
1)
Référence non datée.
Annexe ZB
(informative)
Catégories ATEX et niveaux de protection de matériel (EPL)
La présente Norme Européenne à été rédigée pour introduire le concept des niveaux de protection de
matériel (EPLs pour ‘Equipment Protection Levels’).
Les EPL sont analogues aux catégories ATEX et leurs définitions sont identiques.
Chaque fois qu’il est fait référence à un EPL dans le texte, il convient de le considérer équivalent à la
catégorie ATEX correspondante:
– EPL ‘Ga’ est équivalent à la catégorie ATEX 1G;
– EPL ‘Gb’ est équivalent à la catégorie ATEX 2G;
– EPL ‘Gc’ est équivalent à la catégorie ATEX 3G;
– EPL ‘Da’ est équivalent à la catégorie ATEX 1D;
– EPL ‘Db’ est équivalent à la catégorie ATEX 2D;
– EPL ‘Dc’ est équivalent à la catégorie ATEX 3D.
__________
IEC 60079-10-1
Edition 1.0 2008-12
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres

Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XB
CODE PRIX
ICS 29.260.20 ISBN 2-8318-1019-3
– 66 – 60079-10-1 © CEI:2008
SOMMAIRE
AVANT-PROPOS.68
INTRODUCTION.70
1 Domaine d’application .71
2 Références normatives.72
3 Termes et définitions .72
4 Généralités.76
4.1 Principes de sécurité.76
4.2 Objectifs du classement des emplacements dangereux .76
5 Procédure de classement des emplacements dangereux .77
5.1 Généralités.77
5.2 Sources de dégagement.78
5.3 Type de zone .79
5.4 Étendue de la zone .79
5.4.1 Taux de dégagement de gaz ou vapeur .79
5.4.2 Limite inférieure d’explosivité (LIE).80
5.4.3 Ventilation .80
5.4.4 Densité relative du gaz ou de la vapeur au moment de son
dégagement .80
5.4.5 Autres paramètres à considérer.81
5.4.6 Exemples .81
6 Ventilation .82
6.1 Généralités.82
6.2 Principaux types de ventilation .82
6.3 Degré de ventilation .82
6.4 Disponibilité de la ventilation .83
7 Documentation .83
7.1 Généralités.83
7.2 Plans, feuilles de données et tableaux .83
Annexe A (informative) Exemples de sources de dégagement et de taux de
dégagement.85
Annexe B (informative) Ventilation .92
Annexe C (informative) Exemples de classements d’emplacements dangereux .109
Annexe D (informative) Brouillards inflammables .133
Bibliographie.135

Figure C.1 – Symboles préférés pour les zones d’emplacements dangereux.110
Figure C.2 – Approche schématique pour le classement des emplacements dangereux.132

Tableau A.1 – Effet des ouvertures sur le degré de dégagement .86
Tableau B.1 – Influence de la ventilation sur le type de zone .100
Tableau B.2 – Procédure pour la sommation de plusieurs dégagements dans un
volume V .101
o
Tableau B.3 – Procédure pour la sommation de plusieurs dégagements de premier
degré .101

60079-10-1 © CEI:2008 – 67 –
Tableau C.1 − Feuille de données de classement des emplacements dangereux −
Partie I: Liste des matières inflammables et de leurs caractéristiques .130
Tableau C.2 − Feuille de données de classement des emplacements dangereux −
Partie II: Liste des sources de dégagement .131

– 68 – 60079-10-1 © CEI:2008
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
ATMOSPHÈRES EXPLOSIVES –
Partie 10-1: Classement des emplacements –
Atmosphères explosives gazeuses

AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60079-10-1 a été établie par le sous-comité 31J: Classification
des emplacements dangereux et règles d’installation, du comité d'études 31 de la CEI:
Equipements pour atmosphères explosives.
Cette première édition de la CEI 60079-10-1 annule et remplace la quatrième édition de la
CEI 60079-10, publiée en 2002, et constitue une révision technique.
Les principales modifications techniques suivantes ont été apportées par rapport à l’édition
précédente:
• Introduction de l’Annexe D qui traite du danger d’explosion du brouillard inflammable
généré par l’échappement sous pression de liquides au point d’éclair élevé.
• Introduction de l’Article A.3 (taux de dégagement) qui donne des équations
thermodynamiques pour le taux de dégagement avec des exemples pour l’estimation du
taux de dégagement des fluides et de gaz.

60079-10-1 © CEI:2008 – 69 –
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
31J/159/FDIS 31J/160/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
Une liste de toutes les parties de la série CEI 60079, présentée sous le titre général
Atmosphères explosives, peut être consultée sur le site web de la CEI.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous "http://webstore.iec.ch" dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.
– 70 – 60079-10-1 © CEI:2008
INTRODUCTION
Dans les emplacements où des quantités et concentrations dangereuses de gaz ou vapeurs
inflammables peuvent apparaître, des mesures préventives pour réduire le risque
d'explosions seront appliquées. La présente partie de la CEI 60079 expose les critères
essentiels par rapport auxquels les dangers d'inflammation peuvent être évalués et donne des
lignes directrices, relatives aux paramètres de conception et d'exploitation, que l'on peut
utiliser pour réduire ce danger.

60079-10-1 © CEI:2008 – 71 –
ATMOSPHÈRES EXPLOSIVES –
Partie 10-1: Classement des emplacements –
Atmosphères explosives gazeuses

1 Domaine d’application
La présente partie de la CEI 60079 est relative au classement des emplacements dans
lesquels des risques dus à des gaz, vapeurs ou brouillards inflammables (voir Notes 1, 2 et 3)
peuvent apparaître, et ainsi constituer une base pour le choix et l’installation corrects du
matériel utilisé dans de tels emplacements.
Elle est destinée à être appliquée là où il peut exister un danger d'inflammation du fait de la
présence de gaz ou vapeurs inflammables, en mélange avec l'air, dans les conditions
atmosphériques normales (voir Note 4); mais elle ne s'applique pas:
a) aux mines grisouteuses;
b) au traitement et à la fabrication des explosifs;
c) aux emplacements dans lesquels un danger dû à la présence de poussières ou fibres
inflammables peut apparaître (voir la CEI 61241-10 / CEI 60079-10-2);
d) aux défaillances catastrophiques, qui dépassent le concept d'anormalité traité dans la
présente norme (voir Note 5);
e) aux locaux utilisés à des fins médicales;
f) aux locaux à usage domestique.
La présente norme ne prend pas en compte les effets des sinistres induits.
Des définitions et explications des termes y sont données ainsi que les grands principes et
procédures relatifs au classement des emplacements dangereux.
On pourra se référer aux réglementations nationales ou industrielles relatives à des
applications particulières pour trouver des recommandations détaillées, quant à l'étendue des
emplacements dangereux dans ces industries ou applications.
NOTE 1 Des brouillards inflammables peuvent se former ou être présents en même temps que les vapeurs
inflammables. Les liquides qui ne sont pas considérés comme dangereux suivant les termes de cette norme (en
raison du point d’éclair), lorsqu'ils sortent sous pression, peuvent également générer des brouillards inflammables.
Dans de tels cas, l’application stricte de classement des zones pour les gaz et les vapeurs peut ne pas être
appropriée comme base pour la sélection du matériel.
Des informations relatives aux brouillards inflammables sont données à l’Annexe D.
NOTE 2 L’utilisation de la CEI 60079-14 pour la sélection du matériel et des installations n’est pas nécessaire
pour les dangers dus au brouillard.
NOTE 3 Pour les besoins de la présente norme, un emplacement désigne un secteur ou un espace
tridimensionnel.
NOTE 4 Les conditions atmosphériques englobent les écarts au-dessus et au-dessous des niveaux de référence
de 101,3 kPa (1 013 mbar) et 20 °C (293 K) à condition que cela ait un effet négligeable sur les propriétés
explosives des matières inflammables.
NOTE 5 Le terme « défaillance catastrophique » s'applique ici, par exemple, à l’éclatement d’une cuve ou d'une
canalisation et aux événements imprévisibles.
NOTE 6 Dans toute usine, quelle que soit son importance, il peut y avoir de nombreuses sources d'inflammation
en dehors de celles qui sont associées au matériel électrique. Il sera nécessaire dès lors de prendre les
précautions appropriées pour garantir la sécurité. On pourra utiliser avec prudence la présente norme pour ces
autres sources d'inflammation.

– 72 – 60079-10-1 © CEI:2008
2 Références normatives
Les documents référencés suivants sont indispensables pour l’application de ce document.
Pour les références datées, seule l’édition citée s’applique. Pour les références non datées,
la dernière édition du document référencé (incluant tout amendement) s’applique.
CEI 60050-426, Vocabulaire Electrotechnique International (VEI) – Chapitre 426: Matériel
pour atmosphères explosives
CEI 60079-0, Atmosphères explosives – Partie 0: Matériel – Exigences générales
CEI 60079-4, Matériel électrique pour atmosphères explosives gazeuses – Partie 4: Méthode
d’essai pour la détermination de la température d’inflammation
CEI 60079-4A, Premier complément à la CEI 60079-4 (1966), Matériel électrique pour
atmosphères explosives gazeuses – Partie 4: Méthode d’essai pour la détermination de la
température d’inflammation
CEI 60079-20, Matériel électrique pour atmosphères explosives gazeuses – Partie 20:
Données pour gaz et vapeurs inflammables, en relation avec l'utilisation des matériels
électriques
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions donnés dans la CEI 60079-0
et les suivants s’appliquent.
NOTE Des définitions supplémentaires applicables aux atmosphères explosives se trouvent dans la CEI 60050-
426.
3.1
atmosphère explosive
mélange d'air, dans des conditions atmosphériques, avec des substances inflammables sous
forme de gaz, de vapeur, de poussières, de fibres ou de particules en suspension dans
lequel, après inflammation, la combustion se propage à l’ensemble du mélange non brûlé
[définition 3.22 de la CEI 60079-0]
3.2
atmosphère explosive gazeuse
mélange avec l'air, dans des conditions atmosphériques, de substances inflammables sous
forme de gaz, vapeurs ou brouillards dans lequel, après inflammation, la combustion se
propage à l’ensemble du mélange non brûlé
[définition 3.24 de la CEI 60079-0]
NOTE 1 Bien qu'un mélange où la concentration est supérieure à la limite supérieure d'explosivité (LSE) ne soit
pas une atmosphère explosive gazeuse, il peut aisément le devenir et il est recommandé de le considérer comme
tel dans certains cas aux fins de classement des emplacements dangereux.
NOTE 2 Certains gaz sont explosifs pour une concentration de 100 %.
3.3
emplacement dangereux (en raison d’atmosphères explosives gazeuses)
emplacement dans lequel une atmosphère explosive gazeuse est présente, ou dans lequel on
peut s'attendre à ce qu'elle soit présente, en quantités suffisantes pour nécessiter des
précautions particulières pour la construction, l'installation et l'utilisation d’équipements

60079-10-1 © CEI:2008 – 73 –
3.4
emplacement non dangereux (en raison d’atmosphères explosives gazeuses)
emplacement dans lequel on ne prévoit pas qu’une atmosphère explosive gazeuse soit
présente en quantités suffisantes pour nécessiter des précautions particulières pour la
construction, l'installation et l'utilisation d’équipements
3.5
zones
les emplacements dangereux sont classés en zones, d'après la fréquence et la durée de la
présence d'une atmosphère explosive gazeuse, comme suit:
3.6
zone 0
emplacement dans lequel une atmosphère explosive est présente en permanence, ou
pendant de longues périodes ou encore fréquemment
3.7
zone 1
emplacement dans lequel il est probable qu'une atmosphère explosive gazeuse apparaîtra
occasionnellement en fonctionnement normal
3.8
zone 2
emplacement dans lequel une atmosphère explosive gazeuse n’est pas susceptible de se
présenter en fonctionnement normal mais qui si c’est le cas, peut persister uniquement sur
une durée courte
[VEI 426-03-05]
NOTE On peut obtenir des indications intéressant la fréquence d’apparition et la durée dans les réglementations
propres à certaines industries ou applications.
3.9
source de dégagement
point ou endroit d'où un gaz, une vapeur, un brouillard ou un liquide inflammable peut être
libéré dans l'atmosphère, de telle sorte qu'une atmosphère explosive gazeuse soit créée
[VEI 426-03-06, modifiée]
3.10
degrés de dégagement
il y a trois degrés de dégagement de base, énumérés ci-dessous par ordre décroissant de
probabilité de présence d'une atmosphère explosive gazeuse:
a) degré continu;
b) premier degré;
c) deuxième degré.
Une source de dégagement peut donner lieu à n'importe lequel de ces degrés de dégagement
ou à une combinaison de plusieurs d'entre eux
3.11
dégagement de degré continu
dégagement qui se produit en permanence ou dont on s'attend à ce qu'il se produise pendant
de longues périodes
– 74 – 60079-10-1 © CEI:2008
3.12
dégagement de premier degré
dégagement dont on peut s'attendre à ce qu'il se produise de façon périodique ou
occasionnelle en fonctionnement normal
3.13
dégagement de deuxième degré
dégagement dont on ne prévoit pas qu’il se produise en fonctionnement normal et dont il est
probable que, s'il se produit, ce sera seulement à une faible fréquence et pour de courtes
périodes
3.14
taux de dégagement
quantité de gaz, de vapeur ou de brouillard inflammable émise par unité de temps par la
source de dégagement
3.15
fonctionnement normal
situation dans laquelle l'installation fonctionne selon ses paramètres nominaux
NOTE 1 De petits dégagements de matière inflammable peuvent faire partie du fonctionnement normal. Par
exemple, des fuites des garnitures d'étanchéité lubrifiées par le liquide pompé sont considérées comme de petits
dégagements.
NOTE 2 Des défaillances (telles que la rupture de garnitures d'étanchéité de pompe ou de joints de brides ou des
épandages provoqués par des accidents) qui entraînent une réparation ou un arrêt urgent, ne sont pas
considérées comme faisant partie du fonctionnement normal, ni comme étant catastrophiques.
NOTE 3 Un fonctionnement normal comprend des conditions de démarrage et de fermeture.
3.16
ventilation
mouvement de l'air et remplacement de cet air par de l'air frais sous l'action du vent et de
gradients de température ou de moyens artificiels (par exemple ventilateurs ou extracteurs)
3.17
limite inférieure d'explosivité (LEL)
concentration de gaz, de vapeur ou de brouillard inflammable dans l’air, au-dessous de
laquelle une atmosphère explosive gazeuse ne peut pas être formée
[VEI 426-02-09]
3.18
limite supérieure d'explosivité (UEL)
concentration de gaz, de vapeur ou de brouillard inflammable dans l’air, au-dessus de
laquelle une atmosphère inflammable gazeuse ne peut pas être formée
[VEI 426-02-10]
3.19
densité relative d'un gaz ou d'une vapeur
rapport de la densité d'un gaz ou d'une vapeur à la densité de l'air à la même pression et à la
même température (elle est égale à 1,0 pour l'air)
3.20
matière inflammable (substance inflammable)
matière inflammable par elle-même ou capable de produire un gaz, une vapeur ou un
brouillard inflammable
60079-10-1 © CEI:2008 – 75 –
3.21
liquide inflammable
liquide capable de produire une vapeur inflammable dans toute condition d'exploitation
prévisible
NOTE Un exemple de condition de fonctionnement prévisible est la manipulation du liquide inflammable à des
températures proches ou au-dessus de son point d’éclair.
3.22
gaz ou vapeur inflammable
gaz ou vapeur qui, mélangé à l'air dans certaines proportions, forme une atmosphère
explosive gazeuse
3.23
brouillard inflammable
gouttelettes de liquide, dispersées dans l’air et qui forment une atmosphère explosive
3.24
point d’éclair
température la plus basse d'un liquide à laquelle, dans certaines conditions normalisées, ce
liquide libère des vapeurs en quantité telle qu’un mélange vapeur/air inflammable puisse se
former
3.25
point d'ébullition
température à laquelle un liquide bout à la pression ambiante de 101,3 kPa (1 013 mbar).
NOTE Le point d'ébullition initial qu'il convient d'utiliser dans les mélanges de liquides sert à indiquer la valeur la
plus basse du point d'ébullition de la gamme des liquides présents dans le mélange, telle que cette valeur est
déterminée par distillation en laboratoire normale sans fractionnement.
3.26
pression de vapeur
pression exercée quand un solide ou un liquide est en équilibre avec sa propre vapeur. Elle
est fonction de la substance et de la température
3.27
température d'inflammation d’une atmosphère explosive gazeuse
température la plus basse d'une surface chaude qui, dans des conditions spécifiées,
conformément à la CEI 60079-4, enflammera une substance inflammable sous la forme d'un
mélange de gaz ou de vapeur avec l'air
[définition 3.26 de la CEI 60079-0]
3.28
étendue de zone
distance en tout sens, de la source de dégagement au point où le mélange air/gaz a été dilué
par l'air à une valeur inférieure à la valeur au-dessous de la limite inférieure d'explosivité
3.29
gaz inflammable liquéfié
matériau inflammable qui est stocké ou manipulé sous forme liquide et qui, à température
ambiante et pression atmosphérique, est un gaz inflammable

– 76 – 60079-10-1 © CEI:2008
4 Généralités
4.1 Principes de sécurité
Il convient que les installations dans lesquelles des matières inflammables sont manipulées
ou stockées soient conçues, exploitées et entretenues de façon que tous les dégagements de
matières inflammables, et par conséquent, l'étendue des emplacements dangereux soient
maintenus les plus réduits possibles, que ce soit en fonctionnement normal ou non, en ce qui
concerne la fréquence, la durée et l'importance de ces dégagements.
Il importe d'examiner les parties du matériel de production et les systèmes d'où peut survenir
le dégagement de matériau inflammable et d'envisager la modification de la conception pour
minimiser à la fois la probabilité et la fréquence de tels dégagements ainsi que la quantité et
le taux de dégagement du matériau.
Il convient d'examiner ces considérations fondamentales à un stade précoce du
développement de la conception de toute usine et il convient également de leur accorder une
extrême attention lors de la réalisation de l'étude du classement des emplacements
dangereux.
Dans le cas d’activités autres que le fonctionnement normal, par exemple mise en service ou
maintenance, le classement de zone peut ne pas être valable. L’hypothèse est faite que ce
point est réglé par un système de travail sécurisé.
Dans les situations où il peut y avoir une atmosphère explosive gazeuse, il convient de
prendre les mesures suivantes:
a) éliminer la probabilité d'apparition d'une atmosphère explosive gazeuse à proximité de la
source d'inflammation, ou bien
b) éliminer la source d'inflammation.
Lorsque cela n'est pas possible, il convient de sélectionner et de préparer des mesures
préventives, des matériels de production, des systèmes et des procédures tels que la
probabilité de la simultanéité de a) et b) soit ramenée à un niveau suffisamment faible pour
être acceptable. De telles mesures peuvent être utilisées isolément, s'il est reconnu qu'elles
ont une grande fiabilité, ou en combinaison de façon à réaliser le niveau de sécurité
nécessaire.
4.2 Objectifs du classement des emplacements dangereux
Le classement des emplacements dangereux est une méthode d'analyse et de classement du
milieu dans lequel peuvent apparaître des atmosphères explosives gazeuses, de façon à
faciliter le choix et l’installation corrects du matériel utilisable sans danger dans ce milieu. Le
classement prend également en compte les caractéristiques d’inflammabilité du gaz ou des
vapeurs telles que l’énergie d’inflammation (groupe de gaz) et la température d'inflammation
(classe de température).
En pratique, dans la plupart des cas où l'on utilise des matières inflammables, il est difficile
de garantir qu'une atmosphère explosive gazeuse n'apparaîtra jamais. Il peut aussi être
difficile de garantir que l’équipement ne produira jamais de source d'inflammation. C'est
pourquoi, lorsque la présence d'une atmosphère explosive gazeuse est hautement probable,
on recourra à l'utilisation d'un équipement ayant une faible probabilité de créer une source
d'inflammation. Inversement, si la probabilité de présence d'une atmosphère explosive
gazeuse est faible, on pourra utiliser un équipement répondant à des exigences moins
sévères.
Une fois le classement des zones effectué, une évaluation du risque peut être réalisée pour
évaluer si les conséquences d'inflammation d'une atmosphère explosive nécessitent
l'utilisation d’un équipement de niveau de protection supérieur (EPL), ou peuvent justifier

60079-10-1 © CEI:2008 – 77 –
l’utilisation d’un équipement de niveau de protection inférieur à celui normalement exigé. Les
exigences d’EPL peuvent être, le cas échéant, enregistrées dans les documents et les plans
de classement des emplacements, afin de permettre la sélection correcte des matériels.
Il est rarement possible par un simple examen d’un site ou de la conception d’un site, de
décider quelles parties du site peuvent être réparties dans les trois définitions de zone (zones
0, 1 ou 2). Une approche plus détaillée est donc nécessaire et elle implique l’analyse de la
possibilité des apparitions d’une atmosphère explosive.
La première étape consiste à évaluer la probabilité de cette apparition, en accord avec les
définitions pour la zone 0, la zone 1 et la zone 2. Une fois qu’ont été déterminés la fréquence
probable et la durée de dégagement (et donc du degré de dégagement), le taux de
dégagement, la concentration, la vitesse, la ventilation et d’autres facteurs affectant le type
et/ou l’étendue de la zone, alors on dispose d’une base solide à partir de laquelle on peut
déterminer la présence probable d‘une atmosphère explosive gazeuse dans les
emplacements alentours.
Cette approche requiert par conséquent des considérations précises à apporter à chaque
point des matériels de processus qui contiennent des matières inflammables et qui pourraient
donc être source de dégagement.
En particulier, il convient de réduire tant en nombre qu‘en étendue, les emplacements de
zone 0 ou de zone 1 par conception ou par des procédures de fonctionnement adaptées. En
d’autres termes, il convient que les usines et les installations soient principalement en zone 2
ou non dangereuse. Quand un dégagement de matière inflammable est inévitable, il convient
de limiter les matériels de processus à ceux qui produisent des dégagements de deuxième
degré, ou sinon (quand des dégagements de premier degré ou continus sont inévitables), il
convient que les dégagements soient limités à de petites quantités et à des taux faibles. Lors
de la détermination du classement des emplacements, il y a lieu que ces principes soient
considérés en premier lieu. Si nécessaire, il convient que la conception, le fonctionnement et
le placement du matériel de processus assurent que même en condition anormale de
fonctionnement, la quantité de matière inflammable dégagée dans l'atmosphère est
suffisamment faible pour que l’étendue de l'emplacement dangereux soit réduite.
Une fois que le classement d’un site a été réalisé et que tous les enregistrements ont été
effectués, il importe qu’aucune modification de matériels ou de procédures ne soit faite sans
qu’elle soit discutée avec les responsables du classement des emplacements. Une action non
autorisée peut invalider le classement de l’emplacement. Il est nécessaire d’assurer que tout
matériel affectant le classement de l’emplacement et qui a été soumis à une maintenance,
soit vérifié avec précaution pendant et après son réassemblage, afin d’assurer que l'intégrité
de sa conception d’origine, qui affecte la sécurité, a été préservée avant son retour en
service.
5 Procédure de classement des emplacements dangereux
5.1 Généralités
Il convient que le classement des emplacements soit réalisé par des personnes qui sont au
fait de la pertinence et de la signification des propriétés des matières inflammables et qui
connaissent le processus ainsi que les matériels pour les points qui concernent les domaines
de la sécurité, de l‘électricité, de la mécanique et aussi par des ingénieurs qualifiés.
Les paragraphes suivants donnent des recommandations sur la procédure à suivre pour
classer les emplacements dans lesquels il peut y avoir une atmosphère explosive gazeuse.
Un exemple d’approche schématique du classement d’emplacements dangereux est donné à
la Figure C.2.
– 78 – 60079-10-1 © CEI:2008
Il convient d'effectuer le classement des emplacements dangereux lorsque les schémas
initiaux de lignes de production et d'instrumentation et les plans initiaux d'implantation sont
disponibles et confirmés, avant le démarrage d'usine. Il convient d'effectuer des examens au
cours de l’exploitation.
5.2 Sources de dégagement
Les éléments de base pour identifier le type des zones dangereuses sont l'identification de la
source de dégagement et la détermination du degré de dégagement.
Etant donné qu'il ne peut y avoir d'atmosphère explosive gazeuse qu’en présence de gaz ou
de vapeur inflammable dans l'air, il faut répondre à la question de la possibilité de l'existence
de l'une quelconque de ces matières inflammables dans l’emplacement concerné. En règle
générale, de tels gaz et vapeurs (et les liquides et solides inflammables susceptibles de les
engendrer) sont contenus à l'intérieur du matériel de production, lequel peut être entièrement
clos ou non. Il est nécessaire d'identifier les endroits où une atmosphère inflammable peut
exister à l'intérieur d'une usine ou les endroits où un dégagement de matières inflammables
peut engendrer une atmosphère inflammable à l'extérieur d'une usine.
Il convient que chaque matériel de production (par exemple réservoir, pompe, conduite, cuve,
etc.) soit considéré comme une source potentielle de dégagement de matière inflammable.
Lorsqu’on peut présumer que le matériel ne peut pas contenir de matière inflammable, il va
de soi qu'il ne peut engendrer autour de lui un emplacement dangereux. Cela vaut aussi si le
matériel contient une matière inflammable sans pouvoir la libérer dans l'atmosphère (par
exemple une conduite entièrement soudée n'est pas considérée comme une source de
dégagement).
S'il est constaté que le matériel peut libérer de la matière inflammable dans l'atmosphère, il
faut tout d'abord déterminer le degré de dégagement, conformément aux définitions, en
constatant la fréquence et la durée probables du dégagement. Il convient de noter que les
parties d'installations fermées que l'on ouvre (par exemple pendant un changement de filtre
ou un chargement de matière) sont aussi à considérer comme des sources de dégagement
lorsqu'on effectue le classement des emplacements dangereux. Par cette procédure, chaque
dégagement sera noté « de degré continu », « de premier degré » ou « de deuxième degré ».
Après avoir constaté le degré de dégagement, il est nécessaire de déterminer le taux de
dégagement et les autres facteurs susceptibles d’avoir une influence sur le type et l'étendue
de la zone.
Si la quantité totale de matériau inflammable disponible pour le dégagement est « faible »,
par exemple s'il s'agit d'une utilisation en laboratoire, alors qu'un danger potentiel peut
exister, il peut ne pas être approprié d'utiliser cette procédure de classement de zones
dangereuses. Dans de tels cas, il est nécessaire de tenir compte des risques particuliers
encourus.
Il convient que le classement des emplacements dangereux pour le matériel de production où
brûlent des matières inflammables (par exemple postes de chauffage, fours, chaudières,
turbines à gaz, etc.) prenne en compte le cycle de purge et les conditions de démarrage et de
fermeture.
Les brouillards qui peuvent résulter de fuites de liquide peuvent être inflammables, même si
la température du liquide est inférieure au point d’éclair. Il est donc important de s’assurer
que ces nuages de brouillard n’apparaissent pas (voir Annexe D).
NOTE Alors que les brouillards sont identifiés comme une forme de danger, les critères d’évaluation utilisés dans
cette norme pour les gaz et les vapeurs peuvent ne pas s’appliquer aux brouillards.

60079-10-1 © CEI:2008 – 79 –
5.3 Type de zone
La probabilité de présence d'une atmosphère explosive gazeuse dépend principalement du
degré du dégagement et de la ventilation. Cela est identifié comme une zone. Les zones sont
reconnues comme: zone 0, zone 1, zone 2 et zone non dangereuse.
NOTE 1 Un dégagement de degré continu conduit normalement à une zone 0, un dégagement du premier degré à
une zone 1 et un dégagement du deuxième degré à une zone 2 (voir Annexe B).
NOTE 2 Lorsque des zones créées par des sources adjacentes de dégagement se chevauchent et sont d'un
classement de zones différent, les critères de classement supérieur s'appliquent dans l’emplacement de
chevauchement. Lorsque les zones de chevauchement sont du même classement, ce classement commun
s'applique normalement.
5.4 Étendue de la zone
L'étendue de la zone dépend de la distance estimée ou calculée sur laquelle existe une
atmosphère inflammable avant sa dispersion pour atteindre une concentration dans l'air au-
dessous de sa limite d'inflammabilité inférieure avec un facteur de s
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

The article discusses the EN 60079-10-1:2009 standard, which pertains to the classification of areas with explosive gas atmospheres. The standard is meant to assist in selecting and installing equipment for use in hazardous areas where there may be flammable gas, vapor, or mist hazards. It does not apply to certain scenarios such as mines susceptible to firedamp, the processing of explosives, areas with combustible dusts or fibers, catastrophic failures, medical rooms, or domestic premises. This edition of the standard replaces the previous edition from 2002, and includes changes such as the addition of Annex D, which addresses the explosion hazard caused by flammable mists from high flash point liquids, and the inclusion of Clause A.3, which provides equations for estimating the release rate of fluids and gases.

아래 기사를 한국어로 요약하겠습니다: 기사 제목: EN 60079-10-1:2009 - 폭발성 분야에서의 등급 분류 - 폭발성 가스 분지 IEC 60079-10-1:2008은 가연 가스 또는 증기 또는 미스트 위험이 발생할 수 있는 지역의 분류에 관여하며 위험지역에서 적절한 장비 선택과 설치를 지원하기 위해 사용됩니다. 이는 일반 대기 조건에서 가연 가스나 증기가 공기와 혼합하여 발화 위험이 있는 곳에 적용될 수 있지만 다음과 같은 경우에는 적용되지 않습니다 : a) 일탈성 가스가 존재하는 광산; b) 폭발물의 처리 및 제조; c) 가연성 먼지 또는 섬유가 존재하여 위험이 발생할 수 있는 지역; d) 비정상적인 상황 개념을 벗어난 재난적인 실패; e) 의료 목적으로 사용되는 감실; f) 가정용 건물들. 이번 IEC 60079-10-1의 첫 버전은 2002년에 출판된 IEC 60079-10의 4번째 버전을 취소 및 대체하며 기술 개정을 구성합니다. 이전 버전과 비교하여 중요한 기술적 변화는 다음과 같습니다: - 고인젝션 액체의 압력하에서 생성되는 인화성 미스트로 인한 폭발 위험을 다루는 첨가사항 D의 도입; - 상황에 따른 액체와 가스의 인출 속도 추정을 위해 여러 예를 포함한 인출 속도에 대한 열역학 방정식을 제공하는 조항 A.3의 도입.

以下の記事を日本語で要約します: 記事タイトル:EN 60079-10-1:2009 - 爆発性大気 - Part 10-1:区域の分類 - 爆発性ガス大気 IEC 60079-10-1:2008は、可燃性ガスまたは蒸気またはミストの危険が発生する可能性のある地域の分類に関連しており、危険地域での適切な機器の選択と設置をサポートするために使用されます。通常の大気条件下で可燃性ガスまたは蒸気が空気と混合し、点火の危険がある場所で適用されるものですが、以下の場合には適用されません:a) 沸騰ガスに影響を受けやすい鉱山、b) 爆発物の処理や製造、c) 可燃性の粉塵や繊維が存在し、危険が発生する可能性のある地域、d) 異常の概念を超える破壊的な失敗、e) 医学的な目的で使用される部屋、f) 住宅の敷地。このIEC 60079-10-1の初版は、2002年に発行されたIEC 60079-10の第4版を取り消し、改訂を行っています。前版と比較しての主な技術的な変更点は以下の通りです:- 圧力下で生成される引火性ミストによる爆発の危険に対処する付録Dの導入、- 開放速度の推定のための熱力学の方程式を含む複数の例を提供する節A.3の導入。