prEN IEC 61076-8-106:2022
(Main)Connectors for electrical and electronic equipment - Product requirements - Part 8-106: Power connectors - Detail specification for 2-poles push-pull coupling rectangular connectors with fuses, for 400 V DC rated voltage and 16 A rated current
Connectors for electrical and electronic equipment - Product requirements - Part 8-106: Power connectors - Detail specification for 2-poles push-pull coupling rectangular connectors with fuses, for 400 V DC rated voltage and 16 A rated current
This part of IEC 61076-8 applies to free and fixed, 2-pole push-pull and snap locking power rectangular connectors with fuses, with rated voltage of 400 V DC and rated current of 16 A. It includes overall dimensions, interface dimensions, technical characteristics, performance requirements, and test methods. Connectors according to this document are connectors with breaking capacity (CBC) according to IEC 61984 which are mainly used in DC power conduction, in the field of electrical and electronic equipment.
Connecteurs pour équipements électriques et électroniques - Exigences de produit - Partie 8-106: Connecteurs d’alimentation - Spécification particulière pour les connecteurs bipolaires rectangulaires à accouplement pousser-tirer équipés de coupe-circuits, pour une tension assignée de 400 V en courant continu et un courant assigné de 16 A
IEC 61076-8-106: 2023 s'applique aux connecteurs rectangulaires libres et fixes, à 2 pôles à verrouillage push-pull et à verrouillage par encliquetage avec fusibles, avec une tension nominale de 400 V CC et un courant nominal de 16 A. Il comprend les dimensions globales, les dimensions de l'interface, les caractéristiques techniques, les exigences de performance et les méthodes d'essai. Les connecteurs selon ce document sont des connecteurs à capacité de rupture (CBC) selon IEC 61984 qui sont principalement utilisés dans la conduction de puissance DC, dans le domaine des équipements électriques et électroniques.
Konektorji za električno in elektronsko opremo - Zahteve za izdelek - 8-106. del: Močnostni konektorji - Podrobna specifikacija za dvopolne pravokotne zaklepne konektorje z varovalkami za naznačeno enosmerno napetost 400 V in naznačeni tok 16 A
General Information
- Status
- Not Published
- Publication Date
- 24-Mar-2024
- Technical Committee
- CLC/SR 48B - Connectors
- Drafting Committee
- IEC/SC 48B - IEC_SC_48B
- Current Stage
- 4098 - Decision to drop project - Standstill maintained / released - Enquiry
- Start Date
- 03-Aug-2022
- Completion Date
- 10-Feb-2026
Overview
The prEN IEC 61076-8-106:2022 standard specifies product requirements for 2-poles push-pull coupling rectangular power connectors equipped with fuses. These connectors are designed for use with a rated voltage of 400 V DC and a rated current of 16 A. Developed under the International Electrotechnical Commission (IEC) by Technical Committee 48B on electrical connectors, the standard covers free and fixed connector types with robust locking mechanisms. It establishes comprehensive guidelines on dimensions, interface compatibility, electrical and mechanical performance requirements, and test methods to ensure safety, reliability, and interoperability across electrical and electronic equipment.
Key Topics
- Connector Types and Design: Defines free and fixed 2-pole rectangular connectors with push-pull and snap-lock coupling, integrated with fuse holders.
- Electrical Ratings: Rated for 400 V DC and 16 A current, with details on fuse characteristics and breaking capacity compliant with IEC 61984.
- Dimensional Specifications: Precise overall and interface dimension guidelines for mating compatibility, including coding dimensions to prevent mating errors.
- Safety Aspects: Requirements include clearance and creepage distances, insulation resistance, contact resistance, and fuse tripping performance.
- Mechanical Performance: Encompasses insertion and withdrawal forces, contact retention, locking device effectiveness, vibration and shock resistance.
- Environmental Requirements: Classification into climatic categories, protection degrees (IP rating), and tests on damp heat, rapid temperature changes, corrosion, and cold and dry heat exposure.
- Test Methods and Quality Assurance: Detailed test schedules covering electrical, mechanical, environmental, and dynamic stress tests, along with marking and termination recommendations.
Applications
This IEC standard is critical for manufacturers and designers of electrical and electronic equipment requiring reliable DC power connections. Typical applications include:
- DC Power Distribution: Ensuring safe and secure connections with integrated fuse protection in industrial and commercial equipment.
- Renewable Energy Systems: Facilitating connection interfaces in solar power systems and battery management setups that operate at 400 V DC.
- Electronics and Control Equipment: Providing standardized power connectors with push-pull coupling for ease of maintenance and secure operation.
- Transportation and Automation: Used in DC-powered vehicles and automated machinery where safe disconnection with fuse protection is essential.
By adhering to the prEN IEC 61076-8-106:2022, users can implement connectors that meet international safety, performance, and interoperability requirements, enhancing product quality and user safety.
Related Standards
- IEC 61984: Specifies the safety requirements and tests for connectors with breaking capacity (CBC), referenced for fuse integration and safety verification.
- IEC 61076 Series: Defines product requirements for various connector types used in electrical and electronic equipment.
- ISO/IEC Standards: Collaboration with the International Organization for Standardization ensures alignment with global standardization in connector technology.
- Environmental and EMC Standards: Complementary standards for electromagnetic compatibility (EMC), environmental testing, and quality assurance are relevant for comprehensive compliance.
Adopting the prEN IEC 61076-8-106:2022 standard supports the design and manufacturing of high-performance DC power connectors with fuse protection, meeting rigorous industry demands for safety, reliability, and international compatibility. This standard is an essential resource for engineers, product developers, and quality controllers engaged in electrical connector technologies.
Get Certified
Connect with accredited certification bodies for this standard

NSF International
Global independent organization facilitating standards development and certification.
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
prEN IEC 61076-8-106:2022 is a draft published by CLC. Its full title is "Connectors for electrical and electronic equipment - Product requirements - Part 8-106: Power connectors - Detail specification for 2-poles push-pull coupling rectangular connectors with fuses, for 400 V DC rated voltage and 16 A rated current". This standard covers: This part of IEC 61076-8 applies to free and fixed, 2-pole push-pull and snap locking power rectangular connectors with fuses, with rated voltage of 400 V DC and rated current of 16 A. It includes overall dimensions, interface dimensions, technical characteristics, performance requirements, and test methods. Connectors according to this document are connectors with breaking capacity (CBC) according to IEC 61984 which are mainly used in DC power conduction, in the field of electrical and electronic equipment.
This part of IEC 61076-8 applies to free and fixed, 2-pole push-pull and snap locking power rectangular connectors with fuses, with rated voltage of 400 V DC and rated current of 16 A. It includes overall dimensions, interface dimensions, technical characteristics, performance requirements, and test methods. Connectors according to this document are connectors with breaking capacity (CBC) according to IEC 61984 which are mainly used in DC power conduction, in the field of electrical and electronic equipment.
prEN IEC 61076-8-106:2022 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting. The ICS classification helps identify the subject area and facilitates finding related standards.
prEN IEC 61076-8-106:2022 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
01-julij-2022
Konektorji za električno in elektronsko opremo - Zahteve za izdelek - 8-106. del:
Močnostni konektorji - Podrobna specifikacija za dvopolne pravokotne zaklepne
konektorje z varovalkami za naznačeno enosmerno napetost 400 V in naznačeni
tok 16 A
Connectors for electrical and electronic equipment - Product requirements - Part 8-106:
Power connectors - Detail specification for 2-poles push-pull coupling rectangular
connectors with fuses, for rated voltage of 400 V DC and rated current of 16 A
Connecteurs pour équipements électriques et électroniques - Exigences de produit -
Partie 8-106: Connecteurs d’alimentation - Spécification particulière pour les
connecteurs bipolaires rectangulaires à accouplement pousser-tirer équipés de coupe-
circuits, pour une tension assignée de 400 V en courant continu et un courant assigné
de 16 A
Ta slovenski standard je istoveten z: prEN IEC 61076-8-106:2022
ICS:
31.220.10 Vtiči in vtičnice, konektorji Plug-and-socket devices.
Connectors
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
48B/2956/CDV
COMMITTEE DRAFT FOR VOTE (CDV)
PROJECT NUMBER:
IEC 61076-8-106 ED1
DATE OF CIRCULATION: CLOSING DATE FOR VOTING:
2022-05-13 2022-08-05
SUPERSEDES DOCUMENTS:
48B/2906/CD, 48B/2923/CC
IEC SC 48B : ELECTRICAL CONNECTORS
SECRETARIAT: SECRETARY:
United States of America Mr Jeffrey Toran
OF INTEREST TO THE FOLLOWING COMMITTEES: PROPOSED HORIZONTAL STANDARD:
Other TC/SCs are requested to indicate their interest, if
any, in this CDV to the secretary.
FUNCTIONS CONCERNED:
EMC ENVIRONMENT QUALITY ASSURANCE SAFETY
SUBMITTED FOR CENELEC PARALLEL VOTING NOT SUBMITTED FOR CENELEC PARALLEL VOTING
Attention IEC-CENELEC parallel voting
The attention of IEC National Committees, members of
CENELEC, is drawn to the fact that this Committee Draft
for Vote (CDV) is submitted for parallel voting.
The CENELEC members are invited to vote through the
CENELEC online voting system.
This document is still under study and subject to change. It should not be used for reference purposes.
Recipients of this document are invited to submit, with their comments, notification of any relevant patent rights of
which they are aware and to provide supporting documentation.
TITLE:
Connectors for electrical and electronic equipment– Product requirements - Part 8-106: Power
connectors – Detail specification for 2-poles push-pull coupling rectangular connectors with
fuses, for rated voltage of 400 V DC and rated current of 16 A
PROPOSED STABILITY DATE: 2025
NOTE FROM TC/SC OFFICERS:
electronic file, to make a copy and to print out the content for the sole purpose of preparing National Committee positions.
You may not copy or "mirror" the file or printed version of the document, or any part of it, for any other purpose without
permission in writing from IEC.
IEC CDV 61076-8-106/Ed1 IEC:2022 – 2 – 48B/2956/CDV
1 CONTENTS
2 CONTENTS . 1
3 INTERNATIONAL ELECTROTECHNICAL COMMISSION . 5
4 CONNECTORS FOR ELECTRICAL AND ELECTRONIC EQUIPMENT– . 5
5 FOREWORD . 5
6 PRODUCT REQUIREMENTS . 8
7 1 Scope . 8
8 2 Normative references . 8
9 3 Terms and definitions . 10
10 4 Technical information . 10
11 4.1 Number of contacts and contact cavities . 10
12 4.2 Ratings and characteristics . 11
13 4.2.1 Ratings and characteristics of connectors . 11
14 4.2.2 Rating and characteristics of fuses . 11
15 4.3 Recommended method of termination . 11
16 4.4 Safety aspects . 11
17 4.5 Systems of levels . 11
18 4.5.1 Performance levels . 11
19 4.5.2 Compatibility levels . 11
20 4.6 Classification into climatic categories . 11
21 4.7 Clearance and creepage distances . 11
22 4.8 Current-carrying capacity . 11
23 4.9 Marking . 12
24 5 Dimensional information . 12
25 5.1 General . 12
26 5.2 Isometric view and common features . 12
27 5.2.1 Isometric view of free connector . 12
28 5.2.2 Isometric view of fixed connector . 12
29 5.3 Engagement (mating) information . 13
30 5.4 Fixed connectors . 13
31 5.4.1 Dimensions . 13
32 5.4.2 Terminations. 15
33 5.5 Free connectors . 15
34 5.5.1 Dimensions . 16
35 5.5.2 Terminations. 17
36 5.6 Accessories . 17
37 5.7 Mounting information . 17
38 5.8 Gauges . 18
39 5.8.1 Sizing gauges and retention force gauges . 18
40 6 Technical characteristics . 18
41 6.1 Classification into climatic categories . 18
42 6.2 Electrical characteristics . 18
43 6.2.1 Clearance and creepage distance . 18
44 6.2.2 Voltage proof . 18
45 6.2.3 Contact resistance . 18
46 Requirements: . 19
47 Final: 14 mΩ max. 19
IEC CDV 61076-8-106/Ed1 IEC:2022 – 3 – 48B/2956/CDV
48 6.2.4 Insulation resistance . 19
49 Requirements: . 19
50 6.3 Temperature rise . 19
51 6.3.2 Electrical load and temperature . 20
52 6.3.3 Fuse tripping . 20
53 6.4 Mechanical characteristics . 20
54 6.4.1 Mechanical operation . 20
55 6.4.2 Effectiveness of connector coupling devices . 20
56 6.4.3 Insertion and withdrawal force . 20
57 6.4.4 Contact retention in insert . 21
58 6.4.5 Polarizing and keying method . 21
59 6.4.6 retention force (resilient contact) . 21
60 6.4.7 Conductor secureness . 21
61 6.4.8 capacity . 21
62 6.5 Dynamic stress test . 22
63 6.5.1 Vibration (sine) . 22
64 6.5.2 Shock . 22
65 6.5.3 IP degree of protection . 22
66 6.6 Climatic test . 22
67 6.6.1 Damp heat, steady state . 22
68 6.6.2 Rapid change of temperature . 22
69 6.6.3 Corrosion, salt mist . 23
70 6.6.4 Dry heat . 23
71 6.6.5 Cold . 23
72 6.7 Environmental aspects . 23
73 6.7.1 Marking of insulation material (plastic) . 23
74 6.7.2 Design/use of material . 23
75 7 Test schedule . 23
76 7.1 General . 23
77 7.2 Test schedules. 24
78 7.2.1 Basic (minimum) test schedule . 24
79 7.2.2 Full test schedule . 24
80 Table 11 – Test group AP (continued). Error! Bookmark not defined.
81 Table 12 – Test group BP (continued). Error! Bookmark not defined.
82 Table 13 – Test group CP (continued). Error! Bookmark not defined.
83 Table 14 – Test group DP (continued). Error! Bookmark not defined.
84 7.3 Test procedures and measurement methods . 32
85 7.4 Pre-conditioning . 33
86 7.5 Wiring and mounting of test specimens . 33
87 7.5.1 Wiring . 33
88 7.5.2 Mounting . 33
90 Figure 1 – Free connector . 12
91 Figure 2 – Fixed connector . 13
92 Figure 3 – Fixed connector . 13
93 Figure 5 – Free connector . 16
94 Figure 6 – Free connector coding dimensions . 17
95 Figure 7 – Gauge for contacts . 18
IEC CDV 61076-8-106/Ed1 IEC:2022 – 4 – 48B/2956/CDV
96 Figure 8 – Current-temperature derating (4 mm wire size) . 20
98 Table 1 – Fixed connector dimensions . 13
99 Figure 4 – Fixed connector coding . 14
100 Table 2 – Fixed connector coding dimensions . 15
101 Table 3 – Free connector dimensions . 16
102 Table 4 – Free connector coding dimensions . 17
103 Table 5 – Gauge dimensions . 18
104 Table 6 – Climatic categories . 18
105 Table 7 – Conductor secureness test . 21
106 Table 8 – Vibration . 22
107 Table 9 – Number of test specimens . 24
108 Table 10 – Test group P . 24
109 Table 11 – Test group AP . 26
110 Table 12 – Test group BP . 28
111 Table 13 – Test group CP . 29
112 Table 14 – Test group DP . 30
113 Table 15 – Test group EP . 31
114 Table 16 – Test group JP . 32
115 Table 17 – Test group KP . 32
IEC CDV 61076-8-106/Ed1 IEC:2022 – 5 – 48B/2956/CDV
118 INTERNATIONAL ELECTROTECHNICAL COMMISSION
119 ____________
121 CONNECTORS FOR ELECTRICAL AND ELECTRONIC EQUIPMENT–
122 PRODUCT REQUIREMENTS
123 Part 8-106: Power connectors – Detail specification for 2-poles push-pull
124 coupling rectangular connectors with fuses, for rated voltage of 400 V DC and
125 rated current of 16 A
127 FOREWORD
128 1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising all national
129 electrotechnical committees (IEC National Committees). The object of IEC is to promote international co-operation on all
130 questions concerning standardization in the electrical and electronic fields. To this end and in addition to other activities, IEC
131 publishes International Standards, Technical Specifications, Technical Reports, Publicly Available Specifications (PAS) and
132 Guides (hereafter referred to as “IEC Publication(s)”). Their preparation is entrusted to technical committees; any IEC
133 National Committee interested in the subject dealt with may participate in this preparatory work. International, governmental
134 and non-governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely with
135 the International Organization for Standardization (ISO) in accordance with conditions determined by agreement between
136 the two organizations.
137 2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international consensus
138 of opinion on the relevant subjects since each technical committee has representation from all interested IEC National
139 Committees.
140 3) IEC Publications have the form of recommendations for international use and are accepted by IEC National Committees in
141 that sense. While all reasonable efforts are made to ensure that the technical content of IEC Publications is accurate, IEC
142 cannot be held responsible for the way in which they are used or for any misinterpretation by any end user.
143 4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications transparently to
144 the maximum extent possible in their national and regional publications. Any divergence between any IEC Publication and
145 the corresponding national or regional publication shall be clearly indicated in the latter.
146 5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity assessment
147 services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any services carried out by
148 independent certification bodies.
149 6) All users should ensure that they have the latest edition of this publication.
150 7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and members of its
151 technical committees and IEC National Committees for any personal injury, property damage or other damage of any nature
152 whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication, use of,
153 or reliance upon, this IEC Publication or any other IEC Publications.
154 8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is indispensable
155 for the correct application of this publication.
156 9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent rights.
157 IEC shall not be held responsible for identifying any or all such patent rights.
158 IEC 61076-8-106 Ed.1 has been prepared by subcommittee 48B: Electrical connectors, of IEC
159 technical committee 48: Electrical connectors and enclosures for electrical and electronic equipment. It
160 is an International Standard.
162 The text of this International Standard is based on the following documents:
Draft Report on voting
XX/XX/FDIS XX/XX/RVD
164 Full information on the voting for its approval can be found in the report on voting indicated in the
165 above table.
166 The language used for the development of this International Standard is English.
167 This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
168 accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available at
IEC CDV 61076-8-106/Ed1 IEC:2022 – 6 – 48B/2956/CDV
169 www.iec.ch/members_experts/refdocs. The main document types developed by IEC are described in
170 greater detail at www.iec.ch/standardsdev/publications.
171 The committee has decided that the contents of this document will remain unchanged until the stability
172 date indicated on the IEC website under webstore.iec.ch in the data related to the specific document.
173 At this date, the document will be
174 • reconfirmed,
175 • withdrawn,
176 • replaced by a revised edition, or
177 • amended.
IEC CDV 61076-8-106/Ed1 IEC:2022 – 7 – 48B/2956/CDV
The International Electrotechnical Commission
IEC 61076-8-106 Ed.1
IEC SC 48B—Electrical connectors
Detail specification in accordance with IEC 61076-1
Free rectangular connector;
For rated voltage of 400 V DC. and rated
current of 16 A;
Free
2-pole;
connector
Receptacle contacts for power;
Push-pull and snap locking l;
Two codings.
2-pole 16 A free connector
Fixed rectangular connector;
For rated voltage of 400 V DC and rated
current of 16 A
2-pole;
Fixed
connector with two fuses
Blade contacts for power;
Push-pull and snap locking;
Two codings.
2-pole 16 A fixed connector
IEC CDV 61076-8-106/Ed1 IEC:2022 – 8 – 48B/2956/CDV
180 CONNECTORS FOR ELECTRICAL AND ELECTRONIC EQUIPMENT–
181 PRODUCT REQUIREMENTS
183 Part 8-106: Power connectors – Detail specification for 2 poles push-pull
184 coupling rectangular connectors with fuses, for rated voltage of 400 V DC and
185 rated current of 16 A
187 1 Scope
188 This part of IEC 61076-8 applies to free and fixed, 2-pole push-pull and snap locking power
189 rectangular connectors with fuses, with rated voltage of 400 V DC and rated current of 16 A. It
190 includes overall dimensions, interface dimensions, technical characteristics, performance
191 requirements, and test methods.
192 Connectors according to this document are connectors with breaking capacity (CBC) according
193 to IEC 61984 which are mainly used in DC power conduction, in the field of electrical and
194 electronic equipment.
195 2 Normative references
196 The following documents, in whole or in part, are normatively referenced in this document and
197 are indispensable for its application. For dated references, only the edition cited applies. For
198 undated references, the latest edition of the referenced document (including any amendments)
199 applies.
200 IEC 60050-581:2008, International Electrotechnical Vocabulary-Part 581: Electromechanical
201 components for electronic equipment
202 IEC 60068-1:2013, Environmental testing – Part 1: General and guidance
203 IEC 60127-1:2006, Miniature fuses – Part 1: Definitions for miniature fuses andgeneral
204 requirements for miniature fuse-links
205 IEC 60228:2004, Conductors of insulated cables
206 IEC 60352-2, Solderless connections - Part 2: Spring clamp connections-General
207 requirements, test methods and practical guidance
208 IEC 60352-3, Solderless connections – Part 3: Solderless accessible insulation displacement
209 connections – General requirements, test methods and practical guidance
210 IEC 60352-4, Solderless connections – Part 4: Solderless non-accessible insulation
211 displacement connections – General requirements, test methods and practical guidance
212 IEC 60352-5, Solderless connections – Part 5: Press-in connections – General requirements,
213 test methods and practical guidance
214 IEC 60352-6, Solderless connections – Part 6: Insulation piercing connections – General
215 requirements, test methods and practical guidance
216 IEC 60352-7, Solderless connections – Part 7: Spring-clamp connections – General
217 requirements, test methods and practical guidance
IEC CDV 61076-8-106/Ed1 IEC:2022 – 9 – 48B/2956/CDV
IEC 60512-1-2, Connectors for electronic equipment – Test and measurements – Part 1-2:
219 General examination - Test 1b: Examination of dimension and mass
220 IEC 60512-2-1, Connectors for electronic equipment – Tests and measurements – Part 2-1:
221 Electrical continuity and contact resistance tests – Test 2a: Contact resistance - Millivolt level
222 method
223 IEC 60512-3-1, Connectors for electronic equipment – Tests and measurements – Part 3-1:
224 Insulation tests - Test 3a: Insulation resistance
225 IEC 60512-4-1, Connectors for electronic equipment – Tests and measurements – Part 4-1:
226 Voltage stress tests – Test 4a: Voltage proof
227 IEC 60512-5-1, Connectors for electronic equipment – Tests and measurements – Part 5-1:
228 Current-carrying capacity tests – Test 5a: Temperature rise
229 IEC 60512-6-3, Connectors for electronic equipment – Tests and measurements – Part 6-3:
230 Dynamic stress tests – Test 6c: Shock
231 IEC 60512-6-4, Connectors for electronic equipment – Tests and measurements – Part 6-4:
232 Dynamic stress tests – Test 6d: Vibration (sinusoidal)
233 IEC 60512-9-1, Connectors for electronic equipment – Tests and measurements – Part 9-1:
234 Endurance tests – Test 9a: Mechanical operation
235 IEC 60512-9-2, Connectors for electronic equipment – Tests and measurements – Part 9-2:
236 Endurance tests – Test 9b: Electrical load and temperature
237 IEC 60512-11-3, Connectors for electronic equipment – Tests and measurements – Part 11-3:
238 Climatic tests – Test 11c: Damp heat, steady state
239 IEC 60512-11-4, Connectors for electronic equipment – Tests and measurements – Part 11-4:
240 Climatic tests – Test 11d: Rapid change of temperature
241 IEC 60512-11-6, Connectors for electronic equipment – Tests and measurements – Part 11-6:
242 Climatic tests – Test 11f: Corrosion, salt mist
243 IEC 60512-11-9, Connectors for electronic equipment – Tests and measurements – Part 11-9:
244 Climatic tests – Test 11i: Dry heat
245 IEC 60512-11-10, Connectors for electronic equipment – Tests and measurements - Part 11-
246 10: Climatic tests - Test 11j: Cold
247 IEC 60512-13-2, Connectors for electronic equipment – Tests and measurements – Part 13-
248 2:Mechanical operation tests –Test 13a: Insertion and withdrawal forces
249 IEC 60512-13-5, Connectors for electronic equipment – Tests and measurements – Part 13-5:
250 Mechanical operation tests – Test 13e: Polarizing and keying method
251 IEC 60512-15-1, Connectors for electronic equipment – Tests and measurements – Part 15-1:
252 Connector tests (mechanical) – Test 15a: Contact retention in insert
253 IEC 60512-15-6, Connectors for electronic equipment – Tests and measurements – Part 15-6:
254 Connector tests (mechanical) – Test 15f: Effectiveness of connector coupling devices
IEC CDV 61076-8-106/Ed1 IEC:2022 – 10 – 48B/2956/CDV
IEC 60512-16-5, Connectors for electronic equipment – Tests and measurements – Part 16-5:
256 Mechanical tests on contacts and terminations – Test 16e: Gauge retention force (resilient
257 contacts)
258 IEC 60529, Degrees of protection provided by enclosures (IP code)
259 IEC 60664-1:2007, Insulation coordination for equipment within low-voltage systems – Part
260 1:Principles,requirements and tests
261 IEC 60695-2-12: Fire hazard testing – Part 2-12: Glowing/hot-wire based test methods – Glow-
262 wire flammability index (GWFI) test method for materials
263 IEC 60999-1:1999, Connecting devices – Electrical copper conductors – Safety requirements
264 for screw – type and screwless – type clamping units – Part 1: General requirements and
2 2
265 particular requirements for clamping units for conductors from 0,2 mm up to 35 mm (included)
266 IEC 61076-1:2006, Connectors for electronic equipment – Part 1: Generic specification
267 IEC 61076-3-001:2008, Connectors for electronic equipment – Product requirements – Part 3-
268 001: Rectangular connectors - Blank detail specification
269 IEC 61076-3:2008, Connectors for electronic equipment – Product requirements – Part 3:
270 Rectangular connectors – Sectional specification
271 IEC 61984:2008, Connectors – Safety requirements and tests
272 IEC Guide 109:2012, Environmental aspects-Inclusion in electrotechnical product standards
273 IEC 62430:2009, Environmentally conscious design for electrical and electronic products
274 ISO 1302:2002, Metallic materials - Rockwell hardness test – Part 1: Test method
275 ISO 6508-1:2015, Geometrical Product Specifications (GPS) – Indication of surface texture in
276 technical product documentation
277 ISO 11469:2000, Plastics-Generic identification and marking of plastic products
278 3 Terms and definitions
279 For the purposes of this document, the terms and definitions given in IEC 60050-581 apply.
280 ISO and IEC maintain terminological databases for use in standardization at the following
281 addresses:
282 • IEC Electropedia: available at http://www.electropedia.org/
283 • ISO Online browsing platform: available at http://www.iso.org/obp
284 4 Technical information
285 4.1 Number of contacts and contact cavities
286 Number of contacts: power contacts: 2
287 Number of contact cavities: 2 (for removable contacts only)
.
288 Conductor cross-sectional area range: 4,0 mm
IEC CDV 61076-8-106/Ed1 IEC:2022 – 11 – 48B/2956/CDV
289 4.2 Ratings and characteristics
290 4.2.1 Ratings and characteristics of connectors
291 Rated voltage: 400 V DC.
292 Rated impulse voltage : 4 000 V.
...