HD 60364-4-43:2010
(Main)Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
IEC 60364-4-43:2008 provides requirements for the protection of live conductors from the effects of overcurrents. IEC 60364-4-43:2008 describes how live conductors are protected by one or more devices for the automatic disconnection of the supply in the event of overload (Clause 433) and short-circuit (Clause 434) except in cases where the overcurrent is limited in accordance with Clause 436 or where the conditions described in 433.3 (omission of devices for protection against overload) or 434.3 (omission of devices for protection against short-circuit) are met. Coordination of overload protection and short-circuit protection is also covered (Clause 435). This third edition cancels and replaces the second edition, published in 2001, and constitutes a technical revision. The main changes with respect to the previous edition are: - Introduction of new informative Annexes B, C and D. - Information concerning flexible cables added to Scope. - Requirements added for overload detection for the neutral conductor for harmonic currents. - Requirement that devices for protection against short-circuit current be capable of making as well as breaking short-circuit current added. - Information added to clarify protection against overload current. - Requirements where devices for protection against overload need not be provided expanded. - Requirements where devices for protection against short-circuit need not be provided expanded. - Requirements for short-circuit current ratings of busbar trunking systems added. The contents of the corrigendum of October 2008 have been included in this copy.
Errichten von Niederspannungsanlagen - Teil 4-43: Schutzmaßnahmen - Schutz bei Überstrom
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité - Protection contre les surintensités
La CEI 60364-4-43:2008 donne les exigences pour les protections des conducteurs contre les effets des surintensités. Cette norme décrit comment protéger les conducteurs par un appareil ou plus de déconnexion automatique de l'alimentation en cas de surcharge (Article 433) et court-circuit (Article 434), à l'exception où les surintensités sont limitées conformément à l'Article 436 ou si les conditions décrites en 433.3 (omission d'appareils de protection contre les surcharges) ou 434.3 (omission d'appareils de protection contre les courts-circuits) sont remplies. La coordination entre les protections contre les surintensités et les courts-circuits est aussi incluse (Article 435). Cette troisième édition annule et remplace la seconde édition, publiée en 2001, et constitue une révision technique. Les principales modifications par rapport à l'édition précédente sont les suivantes: - Introduction des nouvelles Annexes B, C et D informatives. - Ajout d'information dans le domaine d'application concernant les câbles souples. - Ajout d'exigence pour la détection de surcharge dans le conducteur neutre en cas de courants harmoniques. - Ajout d'exigence pour que les dispositifs de protection contre les court-circuits soient capables d'opérer aussi bien à l'ouverture qu'à la fermeture sur un courant de court-circuit. - Développement des exigences où des dispositifs de protection contre les surcharges ne sont pas nécessaire. - Développement des exigences où des dispositifs de protection contre les courts-circuits ne sont pas nécessaires. - Ajout d'exigences pour les courants de court-circuit assignés des systèmes de canalisations préfabriquées. Le contenu du corrigendum d'octobre 2008 a été pris en considération dans cet exemplaire.
Nizkonapetostne električne inštalacije - 4-43. del: Zaščitni ukrepi - Zaščita pred nadtoki
Ta del HD 60364 zagotavlja zahteve za zaščito živih prevodnikov pred učinki nadtokov.
Ta standard opisuje, kako se živi prevodniki zaščitijo z eno ali več napravami za avtomatski odklop napajanja pri čezmerni obremenitvi (klavzula 433) in kratkem stiku (klavzula 434), razen kadar je nadtok omejen v skladu s klavzulo 436 ali ko so izpolnjeni pogoji, opisani v točki 433.3 (opustitev naprav za zaščito pred nadtokom) ali točki 434.3 (opustitev naprav za zaščito pred kratkim stikom). Zajeta je tudi uskladitev zaščite pred nadtokom in zaščite pred kratkim stikom (klavzula 435).
OPOMBA 1: Velja, da so živi prevodniki, zaščiteni pred preobremenitvijo v skladu s klavzulo 433, zaščiteni tudi pred okvarami, ki bi lahhko povzročile nadtokove podobne velikosti, kot so preobremenitveni tokovi.
OPOMBA 2: Zahteve tega standarda ne upoštevajo zunanjih vplivov.
OPOMBA 3: Zaščita prevodnikov v skladu s tem standardom ne ščiti nujno opreme, povezane s prevodniki.
OPOMBA 4: Gibljivi kabli, ki povezujejo opremo z vtiči in vtičnicami s pritrjeno napeljavo, niso del obsega uporabe tega standarda in zato niso nujno zaščiteni pred nadtokom.
OPOMBA 5: Odklop v tem standardu ne pomeni izolacije.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-maj-2011
1DGRPHãþD
SIST HD 384.4.43 S2:2003
1L]NRQDSHWRVWQHHOHNWULþQHLQãWDODFLMHGHO=DãþLWQLXNUHSL=DãþLWDSUHG
QDGWRNL
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against
overcurrent
Errichten von Niederspannungsanlagen - Teil 4-43: Schutzmaßnahmen - Schutz bei
Überstrom
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité
- Protection contre les surintensités
Ta slovenski standard je istoveten z: HD 60364-4-43:2010
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONIZATION DOCUMENT
HD 60364-4-43
DOCUMENT D'HARMONISATION
March 2010
HARMONISIERUNGSDOKUMENT
ICS 91.140.50; 29.120.50 Supersedes HD 384.4.43 S2:2001 + corr. Dec.2005
English version
Low-voltage electrical installations -
Part 4-43: Protection for safety -
Protection against overcurrent
(IEC 60364-4-43:2008, modified + corrigendum Oct. 2008)
Installations électriques à basse tension - Errichten von Niederspannungsanlagen -
Partie 4-43: Protection pour assurer la Teil 4-43: Schutzmaßnahmen -
sécurité - Schutz bei Überstrom
Protection contre les surintensités (IEC 60364-4-43:2008, modifiziert +
(CEI 60364-4-43:2008, modifiée + Corrigendum Oct. 2008)
corrigendum oct. 2008)
This Harmonization Document was approved by CENELEC on 2010-03-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this
Harmonization Document at national level.
Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: Avenue Marnix 17, B - 1000 Brussels
© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 60364-4-43:2010 E
Foreword
The text of document 64/1641/FDIS, future edition 1 of IEC 60364-4-43, prepared by TC 64, Electrical
installations and protection against electric shock, was submitted to the IEC-CENELEC parallel vote.
A draft amendment, prepared by SC 64B, Electrical installations and protection against electric shock –
Protection against thermal effects, of Technical Committee CENELEC TC 64, Electrical installations and
protection against electric shock, was submitted to the formal vote.
The combined texts were approved by CENELEC as HD 60364-4-43 on 2010-03-01.
This document supersedes HD 384.4.43 S2:2001 + corrigendum December 2005.
The main changes with respect to HD 384.4.43 S2:2001 are listed below:
– Introduction of new informative Annexes B, C and D.
– Information concerning flexible cables added to Scope.
– The word “phase” changed to “line” throughout the standard.
– Requirement not to distribute the neutral in IT systems changed to a NOTE.
– Requirements added for overload detection for the neutral conductor for harmonic currents.
– Requirement that devices for protection against short-circuit current be capable of making as well as
breaking short-circuit current added.
– Information added to clarify protection against overload current.
– Requirements where devices for protection against overload need not be provided expanded.
– More examples given where omission of devices for protection against overload is permitted.
– Requirements where devices for protection against short-circuit need not be provided expanded.
– Requirements for short-circuit current ratings of busbar trunking systems added.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following dates were fixed:
– latest date by which the HD has to be implemented
at national level by publication of a harmonized
national standard or by endorsement (dop) 2011-03-01
– latest date by which the national standards conflicting
with the HD have to be withdrawn (dow) 2013-03-01
In this Harmonization Document modifications to the International Standard are indicated by a vertical line
in the left margin of the text
Annexes ZA and ZB have been added by CENELEC.
- 3 - HD 60364-4-43:2010
43 Protection against overcurrent
430.1 Scope
This part of HD 60364 provides requirements for the protection of live conductors from the effects of
overcurrents.
This standard describes how live conductors are protected by one or more devices for the automatic
disconnection of the supply in the event of overload (Clause 433) and short-circuit (Clause 434) except in
cases where the overcurrent is limited in accordance with Clause 436 or where the conditions described
in 433.3 (omission of devices for protection against overload) or 434.3 (omission of devices for protection
against short-circuit) are met. Coordination of overload protection and short-circuit protection is also
covered (Clause 435).
NOTE 1 Live conductors protected against overload in accordance with Clause 433 are considered to be protected also against
faults likely to cause overcurrents of a magnitude similar to overload currents.
NOTE 2 The requirements of this standard do not take account of external influences.
NOTE 3 Protection of conductors according to this standard does not necessarily protect the equipment connected to the
conductors.
NOTE 4 Flexible cables connecting equipment by plugs and socket-outlet to fixed installations are not part of the scope of this
standard and for this reason are not necessarily protected against overcurrent.
NOTE 5 Disconnection does not mean isolation in this standard.
430.2 Normative references
See Annex ZA
430.3 General requirements
Protective devices shall be provided to disconnect any overcurrent in the circuit conductors before such a
current could cause danger due to thermal or mechanical effects detrimental to insulation, joints,
terminations or material surrounding the conductors.
431 Requirements according to the nature of the circuits
431.1 Protection of line conductors
431.1.1 Detection of overcurrent shall be provided for all line conductors, except where 431.1.2 applies.
It shall cause the disconnection of the conductor in which the overcurrent is detected but not necessarily
the disconnection of the other live conductors.
If disconnection of a single phase may cause danger, for example in the case of a three-phase motor,
appropriate precautions shall be taken.
431.1.2 In a TT or TN system, for a circuit supplied between line conductors and in which the neutral
conductor is not distributed, overcurrent detection need not be provided for one of the line conductors,
provided that the following conditions are simultaneously fulfilled:
a) there exists, in the same circuit or on the supply side, protection intended to detect unbalanced loads
and intended to cause disconnection of all the line conductors;
b) the neutral conductor is not distributed from an artificial neutral point of the circuits situated on the
load side of the protective device mentioned in a).
431.2 Protection of the neutral conductor
431.2.1 TT or TN systems
Where the cross-sectional area of the neutral conductor is at least equivalent to that of the line
conductors, and the current in the neutral is expected not to exceed the value in the line conductors, it is
not necessary to provide overcurrent detection for the neutral conductor or a disconnecting device for that
conductor.
Where the cross-sectional area of the neutral conductor is less than that of the line conductors, it is
necessary to provide overcurrent detection for the neutral conductor, appropriate to the cross-sectional
area of that conductor; this detection shall cause the disconnection of the line conductors, but not
necessarily of the neutral conductor.
In both cases the neutral conductor shall be protected against short-circuit current.
NOTE This protection may be achieved by the overcurrent protective devices in the line conductors. In that case it is not
necessary to provide overcurrent protection for the neutral conductor or a disconnecting device for that conductor.
Where the current in the neutral conductor is expected to exceed the value in the line conductors, refer to
431.2.3.
Except for disconnection the requirements for a neutral conductor apply to a PEN conductor.
431.2.2 IT systems
Where the neutral conductor is distributed, it is necessary to provide overcurrent detection for the neutral
conductor of every circuit. The overcurrent detection shall cause the disconnection of all the live
conductors of the corresponding circuit, including the neutral conductor. This measure is not necessary if
– the particular neutral conductor is effectively protected against overcurrent by a protective device
placed on the supply side, for example at the origin of the installation, or if
– the particular circuit is protected by a residual current operated protective device with a rated
residual current not exceeding 0,20 times the current-carrying capacity of the corresponding neutral
conductor. This device shall disconnect all the live conductors of the corresponding circuit, including
the neutral conductor. The device shall have sufficient breaking capacity for all poles.
NOTE In IT systems, it is strongly recommended that the neutral conductor should not be distributed.
431.2.3 Harmonic currents
Overload detection shall be provided for the neutral conductor in a multi-phase circuit where the harmonic
content of the line currents is such that the current in the neutral conductor is expected to exceed the
current-carrying capacity of that conductor. The overload detection shall be compatible with the nature of
the current through the neutral and shall cause the disconnection of the line conductors but not
necessarily the neutral conductor. Where the neutral is disconnected, the requirements of 431.3 apply.
NOTE Further requirements regarding protection of neutral conductors are given in IEC 60364-5-52.
431.3 Disconnection and reconnection of the neutral conductor in multi-phase systems
Where disconnection of the neutral conductor is required, disconnection and reconnection shall be such
that the neutral conductor shall not be disconnected before the line conductors and shall be reconnected
at the same time as or before the line conductors.
432 Nature of protective devices
The protective devices shall be of the appropriate types indicated by 432.1 to 432.3.
- 5 - HD 60364-4-43:2010
432.1 Devices providing protection against both overload current and short-circuit current
Except as stated in 434.5.1, a device providing protection against both overload and short-circuit current
shall be capable of breaking, and for a circuit-breaker making, any overcurrent up to and including the
prospective short-circuit current at the point where the device is installed. They shall satisfy the
requirements of Clauses 433.1 and 434.5. Such devices may be:
– circuit-breakers incorporating overload and short-circuit release;
– circuit-breakers in conjunction with fuses;
– fuses having fuse links with gG characteristics.
NOTE 1 The fuse comprises all the parts that form the complete protective device.
NOTE 2 This subclause does not exclude the use of other protective devices if the requirements in 433.1 and 434.5 are fulfilled.
432.2 Devices ensuring protection against overload current only
These protective devices shall satisfy the requirements of Clause 433 and may have an interrupting
capacity below the value of the prospective short-circuit current at the point where the devices are
installed.
NOTE 1 These devices are generally inverse time lag protective devices.
NOTE 2 Fuses type aM do not protect against overload.
432.3 Devices ensuring protection against short-circuit current only
A device providing protection against short-circuit current only shall be installed where overload protection
is achieved by other means or where Clause 433 permits overload protection to be dispensed with. Such
a device shall be capable of breaking, and for a circuit-breaker making, the short-circuit current up to and
including the prospective short-circuit current. Such a device shall satisfy the requirements of Clause 434.
Such devices may be
− circuit-breakers with short-circuit release only,
− fuses with gM, aM type fuse links.
432.4 Characteristics of protective devices
The operating characteristics of overcurrent protective devices shall comply with those specified in, for
example, EN 60898 series, EN 60947-2, EN 60947-6-2, EN 61009 series, HD 60269-2, HD 60269-3,
EN 60269-4 or EN 60947-3.
NOTE The use of other devices is not excluded provided that their time/current characteristics provide an equivalent level of
protection to that specified in this clause.
433 Protection against overload current
433.1 Coordination between conductors and overload protective devices
The operating characteristics of a device protecting a cable against overload shall satisfy the two
following conditions:
I ≤ I ≤ I (1)
B n Z
I ≤ 1,45 × I (2)
2 Z
where
I is the design current for that circuit;
B
I is the continuous current-carrying capacity of the cable (see Clause 523);
Z
I is the rated current of the protective device;
n
NOTE 1 For adjustable protective devices, the rated current I is the current setting selected.
n
I is the current ensuring effective operation in the conventional time of the protective device.
The current I ensuring effective operation of the protective device shall be provided by the manufacturer
or as given in the product standard.
Protection in accordance with this clause may not ensure protection in certain cases, for example where
sustained overcurrents less than I occur. In such cases, consideration should be given to selecting a
cable with a larger cross-sectional area.
NOTE 2 I is the design current through the line conductors or the current through the neutral conductor in the case of the triplen
B
harmonics being greater than the line conductor current.
NOTE 3 The current ensuring effective operation in the conventional time of protective devices may also be named I or I
t f
according to the product standards. Both I and I are multiples of I and attention should be given to the correct representation of
t f
n
values and indexes.
NOTE 4 See Annex B for an illustration of conditions (1) and (2) of 433.1.
NOTE 5 Design current I can be considered as an actual current I after applying correction factors. See Clause 311.
B a
433.2 Position of devices for overload protection
433.2.1 A device ensuring protection against overload shall be placed at the point where a change,
such as a change in cross-sectional area, nature, method of installation or in constitution, causes a
reduction in the value of current-carrying capacity of the conductors, except where 433.2.2 and 433.3
apply.
433.2.2 The device protecting the conductor against overload may be placed along the run of that
conductor if the part of the run between the point where a change occurs (in cross-sectional area, nature,
method of installation or constitution) and the position of the protective device has neither branch circuits
nor socket-outlets and fulfils at least one of the following two conditions:
a) it is protected against short-circuit current in accordance with the requirements stated in Clause 434;
b) its length does not exceed 3 m, it is carried out in such a manner as to reduce the risk of short-circuit
to a minimum, and it is installed in such a manner as to reduce to a minimum the risk of fire or danger
to persons (see also 434.2.1).
NOTE For installation according to a) see Figure C.1. For installation according to b) see Figure C.2.
433.3 Omission of devices for protection against overload
The various cases stated in this subclause shall not be applied to installations situated in locations
presenting a fire risk or risk of explosion or where the requirements for special installations and locations
specify different conditions.
433.3.1 General
Devices for protection against overload need not be provided:
a) for a conductor situated on the load side of a change in cross-sectional area, nature, method of
installation or in constitution, that is effectively protected against overload by a protective device
placed on the supply side;
b) for a conductor that is not likely to carry overload current, provided that this conductor is protected
against short-circuit in accordance with the requirements of Clause 434 and that it has neither branch
circuits nor socket-outlets;
c) at the origin of an installation where the distributor provides an overload device and agrees that it
affords protection to the part of the installation between the origin and the main distribution point of
the installation where further overload protection is provided;
- 7 - HD 60364-4-43:2010
d) for circuits for telecommunications, control, signalling and the like.
NOTE For installations according to a), b) and d), see Figure C.3.
433.3.2 Position or omission of devices for protection against overload in IT systems
433.3.2.1 The provisions in 433.2.2 and 433.3.1 for an alternative position or omission of devices for
protection against overload are not applicable to IT systems unless each circuit not protected against
overload is protected by one of the following means:
a) use of the protective measures described in Clause 412 of HD 60364-4-41;
b) protection of each circuit by a residual current protective device that will operate immediately on a
second fault;
c) for permanently supervised systems only use of insulation monitoring which either:
− causes the disconnection of the circuit when the first fault occurs, or
− gives a signal indicating the presence of a fault. The fault shall be rectified according to the
operational requirements and recognizing the risk from a second fault.
NOTE It is recommended to install an insulation fault location system according to EN 61557-9. With the application of such a
system it is possible to detect and locate the insulation fault without interruption of the supply.
433.3.2.2 In IT systems without a neutral conductor, the overload protective device may be omitted in
one of the phase conductors if a residual current protective device is installed in each circuit.
433.3.3 Cases where omission of devices for overload protection shall be considered for safety
reasons
The omission of devices for protection against overload is permitted for circuits supplying current-using
equipment where unexpected disconnection of the circuit could cause danger or damage. Examples of
such cases include:
• exciter circuits of rotating machines;
• supply circuits of lifting magnets;
• secondary circuits of current transformers;
• circuits which supply fire extinguishing devices;
• circuits supplying safety services (burglar alarm, gas alarms, etc.).
NOTE In such cases, consideration should be given to the provision of an overload alarm.
433.4 Overload protection of conductors in parallel
Where a single protective device protects several conductors in parallel, there shall be no branch circuits
or devices for isolation or switching in the parallel conductors.
This subclause does not preclude the use of ring final circuits.
433.4.1 Equal current sharing between parallel conductors
Where a single device protects conductors in parallel sharing currents equally, the value of I to be used
z
in 433.1 is the sum of the current-carrying capacities of the various conductors.
It is deemed that current sharing is equal if the requirements of the first indent of 523.7 a) of
IEC 60364-5-52:2001 are satisfied.
433.4.2 Unequal current sharing between parallel conductors
Where the use of a single conductor, per phase, is impractical and the currents in the parallel conductors
are unequal, the design current and requirements for overload protection for each conductor shall be
considered individually.
NOTE Currents in parallel conductors are considered to be unequal if the difference between any currents is more than 10 % of
the design current for each conductor. Guidance is given in Clause A.2.
434 Protection against short-circuit currents
This standard only considers the case of short-circuit between conductors belonging to the same circuit.
434.1 Determination of prospective short-circuit currents
The prospective short-circuit current at every relevant point of the installation shall be determined. This
may be carried out either by calculation or by measurement.
NOTE The prospective short-circuit current at the supply point may be obtained from the supply utility.
434.2 Position of devices for short-circuit protection
A device ensuring protection against short-circuit shall be placed at the point where a reduction in the
cross-sectional area of the conductors or another change causes a change to the current-carrying
capacity of the conductors, except where 434.2.1, 434.2.2 or 434.3 applies.
434.2.1 The various cases stated in the following subclause shall not be applied to installations situated
in locations presenting a fire risk or risk of explosion and where special rules for certain locations specify
different conditions. The device for protection against short-circuit may be placed other than as specified
in 434.2, under the following conditions.
In the part of the conductor between the point of reduction of cross-sectional area or other change and
the position of the protective device there shall be no branch circuits nor socket-outlets and that part of
the conductor shall
a) not exceed 3 m in length, and
b) be installed in such a manner as to reduce the risk of a short-circuit to a minimum, and
NOTE 1 This condition may be obtained for example by reinforcing the protection of the wiring against external influences.
NOTE 2 See Figure D.1.
c) not be placed close to combustible material.
434.2.2 A protective device may be placed on the supply side of the reduced cross-sectional area or
another change made, provided that it possesses an operating characteristic such that it protects the
wiring situated on the load side against short-circuit, in accordance with 434.5.2.
NOTE The requirements of 434.2.2 may be met by the method given in Annex D.
434.3 Omission of devices for protection against short-circuit
Provided that both of the following conditions are simultaneously fulfilled:
• the wiring is installed in such a way as to reduce the risk of a short-circuit to a minimum (see item
b) of 434.2.1), and
• the wiring is not placed close to combustible material,
devices for protection against short-circuit need not be provided for applications such as:
- 9 - HD 60364-4-43:2010
a) conductors connecting generators, transformers, rectifiers, accumulator batteries to the associated
control panels, the protective devices being placed in these panels;
b) circuits where disconnection could cause danger for the operation of the installations concerned, such
as those cited in 433.3.3;
c) certain measuring circuits;
d) at the origin of an installation where the distributor installs one or more devices providing protection
against short-circuit and agrees that such a device affords protection to the part of the installation
between the origin and the main distribution point of the installation where further short-circuit
protection is provided.
434.4 Short-circuit protection of conductors in parallel
A single protective device may protect conductors in parallel against the effects of short-circuit provided
that the operating characteristics of that device ensures its effective operation should a fault occur at the
most onerous position in one of the parallel conductors. Account shall be taken of the sharing of the
short-circuit currents between the parallel conductors. A fault can be fed from both ends of a parallel
conductor.
If operation of a single protective device is not effective, then one or more of the following measures shall
be taken:
a) The wiring shall be carried out in such a way as to reduce to a minimum the risk of a short-circuit in
any parallel conductor, for example by protection against mechanical damage, and conductors shall
be installed in such a manner as to reduce to a minimum the risk of fire or danger to persons.
b) For two conductors in parallel, a short-circuit protective device shall be provided at the supply end of
each parallel conductor.
c) For more than two conductors in parallel, short-circuit protective devices shall be provided at the
supply and load ends of each parallel conductor.
Guidance is given in Clause A.3.
434.5 Characteristics of short-circuit protective devices
Each short-circuit protective device shall meet the requirements given in 434.5.1.
The rated breaking capacity shall be not less than the prospective maximum short-circuit current
434.5.1
at the place of its installation, except where the following paragraph applies.
A lower rated breaking capacity is permitted if another protective device having the necessary breaking
capacity is installed on the supply side. In that case, the characteristics of the devices shall be
coordinated so that the energy let through by these two devices does not exceed that which can be
withstood without damage by the device on the load side and the conductors protected by these devices.
NOTE 1 In certain cases other characteristics may need to be taken into account such as dynamic stresses and arcing energy for
the device on the load side. Details of the characteristics needing coordination should be obtained from the manufacturers of the
devices concerned.
NOTE 2 Technical data for the selection of protective devices for the purpose of selectivity can be requested from the manufacturer.
434.5.2 For cables and insulated conductors, all current caused by a short-circuit occurring at any point
of the circuit shall be interrupted in a time not exceeding that which brings the insulation of the conductors
to the permitted limit temperature.
For operating times of protective devices < 0,1 s where asymmetry of the current is of importance and for
2 2 2
current-limiting devices k S shall be greater than the value of the let-through energy (I t) quoted by the
manufacturer of the protective device.
Table 43A – Values of k for conductors
Type of conductor insulation
Property/
PVC EPR Rubber Mineral
PVC
condition
Thermoplastic XLPE 60 °C PVC Bare
Thermoplastic
90°C Thermosetting Thermosetting sheathed unsheathed
Conductor cross-
sectional area ≤ 300 > 300 ≤ 300 > 300
mm²
Initial temperature
70 90 90 60 70 105
°C
Final temperature
160 140 160 140 250 200 160 250
°C
Conductor
material:
a
Copper 115 103 100 86 143 141 115 135 -115
Aluminium 76 68 66 57 94 93 – –
Tin-soldered
joints in copper 115 – – – – – – –
conductors
a
This value shall be used for bare cables exposed to touch.
NOTE 1 Other values of k are under consideration for:
– small conductors (particularly for cross-sectional areas less than 10 mm²);
– other types of joints in conductors;
– bare conductors.
NOTE 2 The nominal current of the short-circuit protective device may be greater than the current-carrying capacity of the
cable.
NOTE 3 The above factors are based on IEC 60724.
NOTE 4 See Annex A of HD 60364-5-54:2007 for the calculation-method of factor k.
For short-circuits of duration up to 5 s, the time t, in which a given short-circuit current will raise the
insulation of the conductors from the highest permissible temperature in normal duty to the limit
temperature can, as an approximation, be calculated from the formula:
t = (k * S / I) (3)
where
t is the duration, in s;
S is the cross-sectional area, in mm ;
I is the effective short-circuit current, in A, expressed as an r.m.s. value;
k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor
material, and the appropriate initial and final temperatures. For common conductor insulation, the
values of k for line conductors are shown in Table 43A.
434.5.3 For busbar trunking syste
...
SLOVENSKI STANDARD
01-maj-2011
1DGRPHãþD
SIST HD 384.4.43 S2:2003
1L]NRQDSHWRVWQHHOHNWULþQHLQãWDODFLMHGHO=DãþLWQLXNUHSL=DãþLWDSUHG
QDGWRNL
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against
overcurrent
Errichten von Niederspannungsanlagen - Teil 4-43: Schutzmaßnahmen - Schutz bei
Überstrom
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité
- Protection contre les surintensités
Ta slovenski standard je istoveten z: HD 60364-4-43:2010
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONISIERUNGSDOKUMENT
HD 60364-4-43
HARMONIZATION DOCUMENT
März 2010
DOCUMENT D'HARMONISATION
ICS 91.140.50; 29.120.50 Ersatz für HD 384.4.43 S2:2001 + corr. Dec.2005
Deutsche Fassung
Errichten von Niederspannungsanlagen -
Teil 4-43: Schutzmaßnahmen -
Schutz bei Überstrom
(IEC 60364-4-43:2008, modifiziert + corrigendum Oct. 2008)
Low-voltage electrical installations - Installations électriques à basse tension -
Part 4-43: Protection for safety - Partie 4-43: Protection pour assurer
Protection against overcurrent la sécurité -
(IEC 60364-4-43:2008, modified + Protection contre les surintensités
corrigendum Oct. 2008) (CEI 60364-4-43:2008, modifiée +
corrigendum oct. 2008)
Dieses Harmonisierungsdokument wurde von CENELEC am 2010-03-01 angenommen. CENELEC-Mitglieder
sind gehalten, die CEN/CENELEC-Geschäftsordnung zu erfüllen, in der die Bedingungen für die Übernahme
dieses Harmonisierungsdokuments auf nationaler Ebene festgelegt sind.
Auf dem letzten Stand befindliche Listen dieser nationalen Übernahmen mit ihren bibliographischen Angaben
sind beim Zentralsekretariat oder bei jedem CENELEC-Mitglied auf Anfrage erhältlich.
Dieses Harmonisierungsdokument besteht in drei offiziellen Fassungen (Deutsch, Englisch, Französisch).
CENELEC-Mitglieder sind die nationalen elektrotechnischen Komitees von Belgien, Bulgarien, Dänemark,
Deutschland, Estland, Finnland, Frankreich, Griechenland, Irland, Island, Italien, Kroatien, Lettland, Litauen,
Luxemburg, Malta, den Niederlanden, Norwegen, Österreich, Polen, Portugal, Rumänien, Schweden, der
Schweiz, der Slowakei, Slowenien, Spanien, der Tschechischen Republik, Ungarn, dem Vereinigten Königreich
und Zypern.
CENELEC
Europäisches Komitee für Elektrotechnische Normung
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Management Centre: Avenue Marnix 17, B - 1000 Brüssel
© 2010 CENELEC - Alle Rechte der Verwertung, gleich in welcher Form und in welchem Verfahren, sind weltweit den Mitgliedern von
CENELEC vorbehalten.
Ref. Nr. HD 60364-4-43:2010 D
Vorwort
Der Text des Dokuments 64/1641/FDIS, künftige Ausgabe 1 der IEC 60364-4-43, von TC 64, Elektrische
Anlagen und Schutz gegen elektrischen Schlag vorbereitet, wurde zur parallelen Abstimmung IEC -
CENELEC verteilt.
Ein Entwurf zur Änderung, vorbereitet von SC 64B, Elektrische Anlagen und Schutz gegen elektrischen
Schlag - Schutz gegen thermische Effekte, des Technischen Komitees CENELEC TC 64, Elektrische
Anlagen und Schutz gegen elektrischen Schlag, wurde zur formellen Abstimmung verteilt.
Die zusammengefassten Texte wurden von CENELEC als HD 60364-4-43 am 2010-03-01 genehmigt.
Dieses Dokument ersetzt HD 384.4.43 S2:2001 + Corrigendum Dezember 2005.
Die wichtigsten Änderungen in Bezug auf HD 384.4.43 S2: 2001 sind unten aufgeführt:
- Einfügen von neuen informativen Anhängen B, C und D;
- Aufnahme von Informationen bezüglich flexibler Kabel/Leitungen zum Anwendungsbereich;
- Ersatz des Begriffs „Phase“ durch „Line“ in der gesamten Norm;
- Änderung der Anforderungen, bei IT-Systemen den Neutralleiter nicht mit zu verteilen, in eine ANMER-
KUNG;
- Aufnahme von Anforderungen für die Überlast-Erkennung im Neutralleiter bei
Oberschwingungsströmen;
- Aufnahme von Anforderungen, dass Einrichtungen zum Schutz bei Kurzschlussströmen in der Lage sein
müssen, Kurzschlussströme einzuschalten und auszuschalten;
- Aufnahme von Information zur Erklärung des Schutzes bei Überlastströmen;
- Erweiterung der Anforderungen, wo Einrichtungen zum Schutz bei Überlastströmen nicht vorgesehen
werden müssen;
- Einfügung von weiteren Beispielen, wo Einrichtungen zum Schutz bei Überlast entfallen dürfen;
- Erweiterung der Anforderungen, wann Einrichtungen zum Schutz bei Kurzschluss nicht vorgesehen
werden müssen;
- Aufnahme von Anforderungen für Kurzschlussbemessungsströme von Schienenverteiler-Systemen.
Nachstehende Daten wurden festgelegt:
– spätestes Datum, zu dem das HD auf nationaler
Ebene durch Veröffentlichung einer harmonisierten
nationalen Norm oder durch Anerkennung
übernommen werden muss (dop): 2011-03-01
– spätestes Datum, zu dem nationale Normen, die
dem HD entgegenstehen, zurückgezogen werden
müssen (dow): 2013-03-01
In diesem Harmonisierungsdokument sind Änderungen zur internationalen Norm durch eine senkrechte Linie
am linken Rand des Textes gekennzeichnet.
Anhänge ZA und ZB wurden von CENELEC hinzugefügt.
- 3 – HD 60364-4-43:2010
Text des HD 60364-4-43:200X
43 Schutz bei Überstrom
430.1 Anwendungsbereich
Dieser Teil von HD 60364 enthält Anforderungen zum Schutz von aktiven Leitern bezüglich der
Auswirkungen bei Überströmen.
Diese Norm beschreibt, wie aktive Leiter in Fällen von Überlast (Abschnitt 433) und Kurzschluss (Abschnitt
434) durch eine oder mehrere Einrichtungen für die automatische Abschaltung der Stromversorgung zu
schützen sind. Ausgenommen sind Fälle, bei denen der Überstrom in Übereinstimmung mit Abschnitt 436
begrenzt ist oder wo die Bedingungen, die in 433.3 (Verzicht auf Einrichtungen zum Schutz bei Überlast)
oder 434.3 (Verzicht auf Einrichtungen zum Schutz bei Kurzschluss) beschrieben sind, eingehalten werden.
Die Koordination des Schutzes bei Überlast und bei Kurzschluss wird ebenfalls behandelt (siehe Abschnitt
435).
ANMERKUNG 1 Aktive Leiter, die in Übereinstimmung mit Abschnitt 433 bei Überlast geschützt sind, werden auch bei
Fehlern, die Überströme erzeugen, deren Größe ähnlich ist wie bei Überlastströmen, als geschützt betrachtet.
ANMERKUNG 2 Die Anforderungen dieser Norm berücksichtigen nicht die äußeren Einflüsse.
ANMERKUNG 3 Durch den Schutz von Leitern entsprechend dieser Norm ist nicht notwendigerweise das an diese
Leiter angeschlossene Betriebsmittel geschützt.
ANMERKUNG 4 Flexible Kabel und Leitungen, die Betriebsmittel über Stecker und Steckdosen mit der festen
elektrischen Anlage verbinden, gehören nicht zum Anwendungsbereich dieses Teils. Aus diesem Grunde sind sie nicht
notwendigerweise bei Überstrom geschützt.
ANMERKUNG 5 Abschalten bedeutet in dieser Norm nicht Trennen.
430.2 Normative Verweisungen
Siehe Anhang ZA.
430.3 Allgemeine Anforderungen
Schutzeinrichtungen müssen vorgesehen werden, um jegliche Überströme in den Leitern des Stromkreises
zu unterbrechen, bevor solch ein Strom durch schädliche thermische oder mechanische Auswirkungen auf
die Isolierung, Verbindungen, Anschlüsse oder Umgebung der Leiter eine Gefahr hervorrufen kann.
431 Anforderungen entsprechend der Art der Stromkreise
431.1 Schutz der Außenleiter
431.1.1 Eine Erfassung des Überstroms muss für alle Außenleiter vorgesehen werden, es sei denn,
431.1.2 trifft zu. Diese Erfassung muss die Abschaltung des Leiters, in dem der Überstrom auftritt, bewirken,
nicht jedoch unbedingt die Abschaltung der anderen aktiven Leiter.
Falls die Abschaltung eines einzelnen Außenleiters eine Gefahr hervorruft, z. B. bei einem Dreiphasen-
Motor, müssen entsprechende Vorkehrungen getroffen werden.
431.1.2 In einem TT- oder einem TN-System darf auf die Überstromerfassung in einem der Außenleiter
verzichtet werden, wenn der Stromkreis ausschließlich aus Außenleitern besteht und deshalb der
Neutralleiter nicht mitgeführt wird, vorausgesetzt, die folgenden Bedingungen sind gleichzeitig erfüllt:
a) im gleichen Stromkreis oder auf der Versorgungsseite ist ein Schutz zur Erkennung von
ungleichmäßiger Last vorgesehen, der die Abschaltung aller Außenleiter bewirkt;
b) von einem künstlichen Neutralpunkt der Stromkreise auf der Lastseite der in a) angeführten
Schutzeinrichtung wird ein Neutralleiter nicht verteilt.
431.2 Schutz des Neutralleiters
431.2.1 TT- oder TN-Systeme
Ist der Querschnitt des Neutralleiters mindestens gleichwertig zum Querschnitt der Außenleitern und ist zu
erwarten, dass der Strom im Neutralleiter nicht den Wert in den Außenleitern übersteigt, ist weder eine Über-
stromerfassung im Neutralleiter noch eine Abschalteinrichtung für diesen Leiter gefordert.
Ist der Querschnitt des Neutralleiters geringer als der Querschnitt der Außenleiter, ist gefordert, eine dem
Neutralleiterquerschnitt entsprechende Überstromerfassung im Neutralleiter vorzusehen; diese Erfassung
muss die Abschaltung der Außenleiter, jedoch nicht unbedingt die des Neutralleiters bewirken.
In beiden Fällen muss der Neutralleiter bei Kurzschlussströmen geschützt sein.
ANMERKUNG Dieser Schutz kann erreicht werden durch die Überstrom-Schutzeinrichtungen in den Außenleitern. In
diesem Falle ist nicht gefordert, im Neutralleiter eine Überstromerfassung oder eine Abschalteinrichtung für diesen Leiter
vorzusehen.
Wenn zu erwarten ist, dass der Strom im Neutralleiter den Wert in den Außenleitern übersteigt, ist 431.2.3 zu
beachten.
Mit Ausnahme der Abschaltung gelten die Anforderungen für Neutralleiter auch für PEN-Leiter.
431.2.2 IT-Systeme
Wenn der Neutralleiter mitgeführt wird, ist gefordert, im Neutralleiter jedes Stromkreises eine Überstromer-
fassung vorzusehen. Die Überstromerfassung muss die Abschaltung aller aktiven Leiter des entsprechenden
Stromkreises einschließlich des Neutralleiters bewirken. Diese Maßnahme ist nicht gefordert, wenn
– der betrachtete Neutralleiter durch eine Schutzeinrichtung auf der Versorgungsseite, z. B. an der
Einspeisung der Anlage, wirksam bei Überstrom geschützt ist, oder wenn
– der betrachtete Stromkreis durch eine Fehlerstrom-Schutzeinrichtung (RCD) geschützt ist, deren
Bemessungsdifferenzstrom höchstens das 0,20-fache der Strombelastbarkeit des betreffenden
Neutralleiters beträgt. Diese Einrichtung muss alle aktiven Leiter des betreffenden Stromkreises
einschließlich des Neutralleiters abschalten. Die Einrichtung muss ein ausreichendes
Ausschaltvermögen für alle Pole haben.
ANMERKUNG In IT-Systemen wird dringend empfohlen, den Neutralleiter nicht mitzuführen.
431.2.3 Oberschwingungsströme
Eine Überlasterfassung muss für den Neutralleiter in einem Drehstromkreis vorgesehen werden, wenn der
Anteil der Oberschwingungen des Außenleiterstroms so groß ist, dass zu erwarten ist, dass der Strom im
Neutralleiter die Dauerstrombelastbarkeit dieses Leiters übersteigt. Diese Überlasterfassung muss mit der
Art des Stromes durch den Neutralleiter übereinstimmen und die Abschaltung der Außenleiter, aber nicht
unbedingt des Neutralleiters bewirken. Wenn der Neutralleiter abgeschaltet wird, gelten die Anforderungen
von 431.3.
ANMERKUNG Weitere Anforderungen bezüglich des Schutzes von Neutralleitern sind in IEC 60364-5-52 enthalten.
431.3 Abschalten und Wiedereinschalten des Neutralleiters in Drehstromsystemen
Wenn die Abschaltung des Neutralleiters gefordert ist, darf er weder vor den Außenleitern abgeschaltet noch
nach den Außenleitern eingeschaltet werden.
432 Art der Schutzeinrichtungen
Die Schutzeinrichtungen müssen einer geeigneten Bauart nach 432.1 bis 432.3 entsprechen.
432.1 Einrichtungen, die den Schutz sowohl bei Überlast als auch bei Kurzschluss
sicherstellen
Unter Berücksichtigung der Ausnahme nach 434.5.1 muss eine Einrichtung, die sowohl zum Schutz bei
Überlast, als auch bei Kurzschluss vorgesehen ist, jeden Überstrom bis einschließlich des unbeeinflussten
Kurzschlussstromes an der Einbaustelle der Schutzeinrichtung unterbrechen und bei Leistungsschaltern/
Leitungsschutzschaltern auch einschalten können. Sie müssen die Anforderungen von Abschnitt 433.1 und
434.5 erfüllen. Solche Einrichtungen dürfen sein:
– Leistungsschalter/Leitungsschutzschalter mit integriertem Überlast- und Kurzschlussauslöser;
– Leistungsschalter in Zusammenwirken mit Sicherungen;
– Sicherungen mit Sicherungseinsätzen der Charakteristik gG.
ANMERKUNG 1 Die Sicherung beinhaltet alle Teile einer kompletten Schutzeinrichtung.
ANMERKUNG 2 Dieser Abschnitt schließt die Verwendung anderer Schutzeinrichtungen nicht aus, wenn die Anforde-
rungen von 433.1 und 434.5 erfüllt sind.
- 5 – HD 60364-4-43:2010
432.2 Einrichtungen, die nur den Schutz bei Überlast sicherstellen
Diese Schutzeinrichtungen müssen die Anforderungen nach Abschnitt 433 erfüllen und dürfen ein Ausschalt-
vermögen haben, das unter den Werten des zu erwartenden Kurzschlussstromes an der Einbaustelle dieser
Einrichtungen liegt.
ANMERKUNG 1 Solche Einrichtungen sind im Allgemeinen stromabhängig verzögerte Schutzeinrichtungen.
ANMERKUNG 2 Sicherungen vom Typ aM schützen nicht bei Überlast.
432.3 Einrichtungen, die nur den Schutz bei Kurzschluss sicherstellen
Eine Einrichtung, die nur den Schutz bei Kurzschlussströmen sicherstellt, muss dort errichtet werden, wo der
Schutz bei Überlast durch andere Maßnahmen erreicht wird oder wo nach Abschnitt 433 auf den Schutz bei
Überlast verzichtet werden darf. Sie muss in der Lage sein, den Kurzschlussstrom bis einschließlich des zu
erwartenden Kurzschlussstroms auszuschalten; ein Leistungsschalter/Leitungsschutzschalter muss diese
Ströme auch einschalten können. Diese Einrichtung muss die Anforderungen von Abschnitt 434 erfüllen.
Geeignete Einrichtungen können sein:
– Leistungsschalter nur mit Kurzschlussauslösung;
– Sicherungen mit gM und aM Sicherungseinsätzen.
432.4 Kenngrößen von Schutzeinrichtungen
Das Auslöseverhalten von Überstrom-Schutzeinrichtungen muss übereinstimmen mit den Anforderungen z.
B. den Normen der Reihe EN 60898, EN 60947-2, EN 60947-6-2, Normen der Reihe EN 61009, HD 60269-
2, HD 60269-3, EN 60269-4 oder EN 60947-3.
ANMERKUNG Die Verwendung anderer Einrichtungen ist nicht ausgeschlossen, vorausgesetzt, dass ihre Zeit/Strom-
Kennlinien einen zu diesem Abschnitt gleichwertigen Schutz bieten.
433 Schutz bei Überlastströmen
433.1 Koordination von Leitern und Einrichtungen zum Schutz bei Überlast
Das Auslöseverhalten einer Einrichtung, die ein Kabel oder eine Leitung bei Überlast schützt, muss folgende
zwei Bedingungen erfüllen:
I≤≤II (1)
Bn Z
I ≤ 1, 45 I (2)
2 Z
Dabei sind
I der Betriebsstrom für diesen Stromkreis;
B
I die zulässige Dauerstrombelastbarkeit des Kabels/der Leitung (siehe Abschnitt 523);
Z
I der Bemessungsstrom der Schutzeinrichtung;
n
ANMERKUNG 1 Bei einstellbaren Schutzeinrichtungen ist der Bemessungsstrom I der eingestellte Strom.
n
I der Strom, der eine wirksame Abschaltung in der für die Schutzeinrichtung festgelegten Zeit sicherstellt.
Der Strom I , der eine wirksame Abschaltung sicherstellt, muss entweder vom Hersteller angegeben
werden oder in den Produktnormen festgelegt sein.
Der Schutz in Übereinstimmung mit diesem Abschnitt kann den Schutz in bestimmten Fällen nicht sicher
stellen, z. B., wenn lang andauernde Überströme kleiner als I auftreten. In solchen Fällen sollte die
Auswahl eines Kabels/einer Leitung mit größerem Querschnitt geprüft werden.
ANMERKUNG 2 I ist der Betriebsstrom durch die Außenleiter oder im Falle der dritten Oberschwingung der Strom
B
durch den Neutralleiter, wenn dieser größer ist als der Außenleiterstrom.
ANMERKUNG 3 Der Strom, der in der festgelegten Zeit das wirksame Ansprechen der Schutzeinrichtung sicherstellt,
kann entsprechend der Produktnorm auch als I oder I bezeichnet sein. I und I sind ein Vielfaches von I ; die richtige
t f t f n
Verwendung von Werten und Indizes sollte beachtet werden.
ANMERKUNG 4 Siehe Anhang B für die Darstellung der Bedingungen (1) und (2) von 433.1
ANMERKUNG 5 Der Betriebsstrom I kann nach Anwendung der Korrekturfaktoren als tatsächlicher Strom I
B a
betrachtet werden (siehe Abschnitt 311).
433.2 Anordnung von Einrichtungen zum Schutz bei Überlast
433.2.1 Eine Einrichtung zum Schutz bei Überlast muss an der Stelle angeordnet werden, an der die
Strombelastbarkeit reduziert wird, wie zum Beispiel durch eine Änderung des Leiterquerschnitts, der Bauart,
der Verlegeart oder Anordnung der Kabel oder Leitungen; ausgenommen sind die in 433.2.2 und 433.3
aufgeführten Fälle.
433.2.2 Die Einrichtung zum Schutz der Leiter bei Überlast darf im Zuge des Leiters angeordnet werden,
wenn der Abschnitt zwischen der Änderung (wie Leiterquerschnitt, Bauart, Verlegeart oder Anordnung) und
der Stelle, an der die Schutzeinrichtung angeordnet ist, weder Abzweige noch Steckvorrichtungen enthält
und mindestens eine der beiden folgenden Bedingungen erfüllt wird:
a) das Kabel oder die Leitung ist entsprechend den Anforderungen von Abschnitt 434 bei
Kurzschlussströmen geschützt;
b) die Länge beträgt nicht mehr als 3 m, der Leitungsabschnitt ist so ausgeführt, dass die Gefahr eines
Kurzschlusses auf ein Minimum begrenzt wird, und die Kabel/Leitungen sind derart errichtet, dass das
Risiko von Feuer oder die Gefahr für Personen auf ein Minimum begrenzt wird (siehe auch 434.2.1).
ANMERKUNG Für Anlagen nach Aufzählung a) siehe Bild C.1. Für Anlagen nach Aufzählung b) siehe Bild C.2.
433.3 Verzicht auf Einrichtungen zum Schutz bei Überlast
Die verschiedenen Fälle dieses Abschnitts dürfen nicht angewendet werden für Anlagen in feuer- und
explosionsgefährdeten Räumen/Bereichen oder wenn in den Anforderungen für besondere Anlagen und
Räume/Bereiche abweichende Bedingungen festgelegt sind.
433.3.1 Allgemeines
Einrichtungen zum Schutz bei Überlast müssen nicht vorgesehen werden:
a) für einen Leiter auf der Lastseite hinter einer Änderung des Leiterquerschnitts, der Bauart der Leitungen
oder des Kabels oder der Verlegeart, wenn der Leiter wirksam durch eine Schutzeinrichtung,
angeordnet an der Versorgungsseite, bei Überlast geschützt ist;
b) für einen Leiter, der üblicherweise Überlastströme nicht führt, vorausgesetzt dieser Leiter ist
entsprechend den Anforderungen von Abschnitt 434 bei Kurzschluss geschützt und weist weder
Abzweige noch Steckvorrichtungen auf;
c) an der Einspeisung einer Anlage, wenn der Netzbetreiber eine Überlastschutzeinrichtung vorsieht und
bestätigt, dass sie den Schutz des Teiles der Anlage zwischen der Einspeisung und dem
Hauptverteilungspunkt der Anlage, wo ein weiterer Schutz bei Überlast vorgesehen ist, sicherstellt
d) für Anlagen in Fernmelde-, Steuer-, Signalanlagen und dergleichen;
ANMERKUNG Für Anlagen nach a), b) und d) siehe Bild C.3.
433.3.2 Anordnung von oder Verzicht auf Einrichtungen zum Schutz bei Überlast in IT-Systemen
433.3.2.1 Die Vorkehrungen in 433.2.2 und 433.3.1 für eine alternative Anordnung von oder den Verzicht
auf Einrichtungen zum Schutz bei Überlast sind in IT-Systemen nicht anwendbar, es sei denn, jeder nicht bei
Überlast geschützte Stromkreis ist durch eine der folgenden Maßnahmen geschützt:
a) Anwenden von Schutzmaßnahmen wie in 412 von HD 60364-4-41 beschrieben;
b) Schutz eines jeden Stromkreises durch eine Fehlerstrom-Schutzeinrichtung (RCD), die beim zweiten
Fehler unverzüglich abschaltet;
c) nur für dauernd überwachte Anlagen: Verwenden einer Isolationsüberwachungseinrichtung, die
entweder
• eine Abschaltung des Stromkreises bewirkt, wenn der erste Fehler auftritt, oder
• ein Signal beim Auftreten eines Fehlers erzeugt. Der Fehler muss entsprechend den betrieblichen
Anforderungen und dem Risiko eines zweiten Fehlers beseitigt werden.
ANMERKUNG Es wird empfohlen, ein Isolationsfehlersuchsystem nach EN 61557-9 zu errichten. Durch die
Anwendung eines solchen Systems ist es möglich, Isolationsfehler ohne Unterbrechung der Stromversorgung zu
erkennen und zu lokalisieren.
433.3.2.2 In IT-Systemen ohne Neutralleiter darf der Schutz bei Überlast in einem der Außenleiter entfallen,
wenn eine Fehlerstrom-Schutzeinrichtung (RCD) in jedem Stromkreis errichtet ist.
- 7 – HD 60364-4-43:2010
433.3.3 Fälle, in denen der Verzicht auf Einrichtungen zum Schutz bei Überlast aus
Sicherheitsgründen in Betracht gezogen werden muss
Der Verzicht auf Einrichtungen zum Schutz bei Überlast ist für Stromkreise erlaubt, die elektrische
Verbrauchsmittel versorgen, bei denen eine unvorhergesehene Unterbrechung des Stromkreises eine
Gefahr oder einen Schaden verursachen kann.
Beispiele für solche Fälle sind:
– Erregerstromkreise von drehenden Maschinen,
– Speisestromkreise von Hubmagneten,
– Sekundärstromkreise von Stromwandlern,
– Speisestromkreise von Feuerlöscheinrichtungen,
– Stromkreise zur Versorgung von Sicherheitseinrichtungen (Alarmanlagen für Diebstahlwarnung, Gasalarm
usw.).
ANMERKUNG In diesen Fällen sollte eine Überlast-Meldeeinrichtung in Betracht gezogen werden.
433.4 Schutz bei Überlast von parallel geschalteten Leitern
Wenn eine einzelne Schutzeinrichtung mehrere parallel geschaltete Leiter schützt, dürfen Abzweige und Ein-
richtungen zum Trennen und Schalten in den parallel geschalteten Leitern nicht vorhanden sein.
Dieser Abschnitt schließt die Anwendung von Endstromkreisen mit Ringleitungen nicht aus.
433.4.1 Gleichmäßige Stromaufteilung zwischen parallel geschalteten Leitern
Wenn eine einzelne Einrichtung parallel geschaltete Leiter mit gleicher Stromaufteilung schützt, ist der Wert
I , der nach 433.1 zur Anwendung kommt, die Summe der Strombelastbarkeit der einzelnen Leiter.
Z
Es ist davon auszugehen, dass die Stromaufteilung gleich ist, wenn die Anforderungen des ersten
Aufzählungsstrichs von 523.7 a) von IEC 60364-5-52:2001 erfüllt sind.
433.4.2 Ungleichmäßige Stromaufteilung zwischen parallel geschalteten Leitern
Wenn die Verwendung eines Leiters pro Phase nicht praktikabel ist und der Strom in den parallelen Leitern
ungleichmäßig ist, muss der Betriebsstrom und die Anforderungen zum Schutz bei Überlast für jeden Leiter
getrennt betrachtet werden.
ANMERKUNG Der Strom in den parallelen Leitern wird als ungleich betrachtet, wenn die Differenz zwischen den
einzelnen Strömen mehr als 10 % des Betriebsstroms für jeden Leiter beträgt. Eine Anleitung ist im Abschnitt A.2
enthalten.
434 Schutz bei Kurzschlussströmen
Diese Norm behandelt nur Kurzschlüsse zwischen Leitern, die zum gleichen Stromkreis gehören.
434.1 Bestimmung von unbeeinflussten Kurzschlussströmen
Der unbeeinflusste Kurzschlussstrom muss für jede relevante Stelle der elektrischen Anlage bestimmt
werden. Dies darf entweder durch Berechnung oder Messung erfolgen.
ANMERKUNG Der unbeeinflusste Kurzschlussstrom am Speisepunkt kann bei dem Netzbetreiber erfragt werden.
434.2 Anordnung der Einrichtungen zum Schutz bei Kurzschluss
Eine Einrichtung, die den Schutz bei Kurzschluss sicherstellt, muss an dem Punkt angeordnet werden, an
dem eine Reduzierung des Querschnitts der Leiter oder eine andere Änderung erfolgt, die zu einer
Änderung der Strombelastbarkeit der Leiter führt, ausgenommen wenn 434.2.1, 434.2.2 oder 434.3 zur
Anwendung kommt.
434.2.1 Die verschiedenen Fälle des folgenden Abschnitts dürfen nicht angewendet werden für Anlagen in
feuer- und explosionsgefährdeten Räumen/Bereichen oder wenn in den Anforderungen für besondere
Anlagen und Räume/Bereiche abweichende Bedingungen festgelegt sind. Die Einrichtung zum Schutz bei
Kurzschluss darf unter den folgenden Bedingungen auch an anderen Stellen als in 434.2 festgelegt
eingebaut werden.
In dem Teil des Leiters zwischen der Reduzierung des Querschnitts oder anderer Änderungen und der
Anordnung der Schutzeinrichtung dürfen Abzweige und Steckdosen nicht enthalten sein und dieser Teil des
Leiters
a) darf nicht länger als 3 m sein, und
b) muss so errichtet werden, dass das Risiko eines Kurzschlusses auf ein Minimum reduziert wird, und
ANMERKUNG 1 Diese Bedingung darf z. B. erfüllt werden durch Verstärkung des Schutzes der Kabel- und
Leitungsanlage gegen äußere Einflüsse.
ANMERKUNG 2 Siehe Bild D.1.
c) darf nicht in der Nähe von brennbarem Material errichtet werden.
434.2.2 Eine Schutzeinrichtung darf auf der Versorgungsseite des reduzierten Querschnitts oder bei
anderen Änderungen vorgesehen werden, vorausgesetzt die Auslösecharakteristik ist so, dass sie die
Kabel/Leitungen, die an der Lastseite angeordnet sind, in Übereinstimmung mit den Anforderungen von
434.5.2, bei Kurzschluss schützt.
ANMERKUNG Die Anforderung von 434.2.2 kann durch die Methode von Anhang D erfüllt werden.
434.3 Verzicht auf Einrichtungen zum Schutz bei Kurzschluss
Unter der Voraussetzung, dass beide der folgenden Anforderungen gleichzeitig erfüllt sind:
– das Kabel/die Leitung ist so verlegt, dass das Risiko eines Kurzschlusses auf ein Minimum reduziert ist
(siehe Aufzählungsstrich b) von 434.2.1) und
– das Kabel/die Leitung ist nicht in der Nähe von brennbaren Materialien verlegt,
brauchen Einrichtungen zum Schutz bei Kurzschluss nicht vorgesehen zu werden für Anwendungen wie:
a) Leiter, die Generatoren, Transformatoren, Gleichrichter und Akkumulatorenbatterien mit ihren zuge-
hörigen Steuerschränken verbinden, wobei die Schutzeinrichtungen in diesen Schränken angeordnet
sind;
b) Stromkreise, deren Unterbrechung den Betrieb der entsprechenden Anlagen gefährden könnte, wie sie
in 433.3.3 zitiert sind;
c) bestimmte Messstromkreise;
d) am Anfang einer Anlage, bei der der Netzbetreiber eine oder mehrere Einrichtungen zum Schutz bei
Kurzschluss vorsieht und einwilligt, dass diese Einrichtung den Schutz des Teils der Anlage zwischen
der Einspeisung und der Hauptverteilung der Anlage, in der ein weiterer Schutz bei Kurzschluss
vorgesehen ist, erfüllt.
434.4 Schutz bei Kurzschluss von parallel geschalteten Leitern
Eine einzelne Schutzeinrichtung darf parallel geschaltete Leiter vor den Auswirkungen bei Kurzschluss
schützen, vorausgesetzt, dass das Auslöseverhalten dieser Einrichtung ein wirksames Ansprechen
sicherstellt, wenn ein Fehler an der kritischsten Stelle in einem der parallel geschalteten Leiter auftritt. Die
Aufteilung der Kurzschlussströme zwischen den parallel geschalteten Leitern muss betrachtet werden. Ein
Fehler kann von beiden Enden der parallel geschalteten Leiter gespeist werden.
Falls die Auslösung einer einzelnen Schutzeinrichtung nicht wirksam ist, muss eine oder müssen mehrere
der folgenden Maßnahmen angewendet werden:
a) Kabel/Leitungen müssen derart ausgewählt und verlegt werden, dass das Risiko eines Kurzschlusses in
jedem der parallel geschalteten Leiter auf ein Minimum reduziert ist, z. B. durch einen Schutz gegen
mechanische Beschädigung, und die Leiter müssen so verlegt sein, dass das Risiko eines Feuers oder
eines Schadens von Personen auf ein Minimum reduziert ist.
b) Für zwei parallel geschaltete Leiter muss an der Versorgungsseite eines jeden parallel geschalteten
Leiters eine Schutzeinrichtung zum Schutz bei Kurzschluss vorgesehen werden.
c) Für mehr als zwei parallel geschaltete Leiter muss an der Versorgungsseite und an der Lastseite eines
jeden parallel geschalteten Leiters eine Schutzeinrichtung zum Schutz bei Kurzschluss vorgesehen
werden.
Eine Anleitung ist in Abschnitt A.3 enthalten.
434.5 Kenngrößen von Schutzeinrichtungen zum Schutz bei Kurzschluss
Jede Schutzeinrichtung zum Schutz bei Kurzschluss muss die Anforderungen von 434.5.1 erfüllen.
434.5.1 Ihr Bemessungsausschaltvermögen darf nicht geringer sein als der zu erwartende maximale Kurz-
schlussstrom am Einbauort in der Anlage, mit Ausnahme des folgenden Abschnitts.
- 9 – HD 60364-4-43:2010
Ein geringeres Bemessungsausschaltvermögen ist zulässig, wenn eine andere Schutzeinrichtung, die an der
Versorgungsseite errichtet wird, das geforderte Kurzschlussausschaltvermögen aufweist. In diesem Fall
müssen die Charakteristiken der Einrichtungen so aufeinander abgestimmt sein, dass die Gesamtdurchlass-
energie beider Einrichtungen nicht die Durchlassenergie überschreitet, welche von der Einrichtung auf der
Lastseite und von den zu schützenden Leitern ohne Schaden überstanden wird.
ANMERKUNG 1 In einigen Fällen kann es notwendig sein, andere Einflussgrößen wie die dynamische Beanspruchung
und die Lichtbogenenergie für die Einrichtung auf der Lastseite in Betracht zu ziehen. Für die Abstimmung der
Kenngrößen der beiden Schutzeinrichtungen sind die Angaben der Hersteller heranzuziehen.
ANMERKUNG 2 Technische Daten für die Auswahl von Schutzeinrichtungen bezüglich der Selektivität können beim
Hersteller angefordert werden.
434.5.2 Für Kabel, Leitungen und isolierte Leiter müssen alle Ströme, hervorgerufen durch einen
Kurzschluss an einem beliebigen Punkt des Stromkreises, in einer Zeit unterbrochen werden, bei der die
Isolierung der Leiter nicht die erlaubte Grenztemperatur überschreitet.
Für Ansprechzeiten der Schutzeinrichtungen < 0,1 s, wenn die Asymmetrie des Kurzschlussstromverlaufs
2 2
von Bedeutung ist, und für strombegrenzende Schutzeinrichtungen muss k S größer sein, als der vom
Hersteller der Schutzeinrichtung angegebene Wert der Durchlassenergie (I t).
Tabelle 43A: Werte von k für Leiter
Werkstoff der Isolierung
Eigenschaft/ PVC PVC EPR Gummi mineralisoliert
Bedingung XLPE
thermoplastisch thermoplastisch 90 °C vernetzt 60 °C PVC blank
vernetzt nicht
umhüllt
umhüllt
Leiterquerschnitt mm ≤ 300 > 300 ≤ 300 > 300
Anfangstemperatur °C
70 90 90 60 70 105
Endtemperatur °C 160 140 160 140 250 200 160 250
Leitermaterial:
a
Kupfer 143
115 103 100 86 141 115 135/115
Aluminium 76 68 66 57 94 93 – –
Zinn-Lötstellen in
115 – – – – – – –
Kupferleitern
a
Dieser Wert ist zu verwenden für blanke Kabel/Leitungen, wenn sie berührt werden können.
ANMERKUNG 1 Andere Werte für k sind in Bearbeitung für:
– kleine Querschnitte (speziell für Querschnitte < 10 mm ),
– andere Arten von Verbindungen in den Leitern,
– blanke Leiter.
ANMERKUNG 2 Der Nennstrom der Schutzeinrichtung zum Schutz bei Kurzschluss darf größer sein als die Strombelastbarkeit der
Leiter.
ANMERKUNG 3 Die obigen Faktoren basieren auf IEC 60724
ANMERKUNG 4 Siehe Anhang A von HD 60364-5-54:2007 bezüglich der Berechnung von Faktor k.
Bei Kurzschlüssen mit einer Dauer bis einschließlich 5 s darf die Zeit t, in der ein gegebener
Kurzschlussstrom die Isolierung der Leiter von der höchstzulässigen Temperatur im Normalbetrieb bis zur
Grenztemperatur erwärmt, in erster Näherung durch die Formel berechnet werden:
S
tk=⋅
I
Dabei ist
t die Kurzschlussdauer in s;
S der Leiterquerschnitt in mm ;
I der wirksame Kurzschlussstrom in A, angegeben als Effektivwert;
k ein Faktor unter Berücksichtigung von Widerstand, Temperaturkoeffizient und Wärmekapazität des
Leitermaterials und den entsprechenden Anfangs- und Endtemperaturen. Für gebräuchliche Leiter-
isolierungen ist der Wert k für Außenleiter in Tabelle 43A angegeben.
434.5.3 Für Schienenverte
...










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...