FprEN IEC 62920:2026 is the CLC draft of IEC 62920 for photovoltaic power generating systems. It specifies EMC requirements and test methods for power conversion equipment (PCE) used in PV systems, including grid-connected and stand-alone equipment, so manufacturers, test laboratories, and system integrators can assess emissions and immunity in a consistent way.

What does FprEN IEC 62920:2026 specify?

FprEN IEC 62920:2026 specifies EMC requirements for PCE used in photovoltaic power generating systems, including PCE with radio functionality. It also gives the test methods, test setups, and operating conditions used to check those requirements at a test site.

The scope covers DC to DC, DC to AC, and AC to DC conversion equipment. It applies to PCE connected to low-voltage, medium-voltage, or high-voltage AC networks, with or without electrical energy storage devices, but it does not cover photovoltaic modules or other balance of system components.

The document is organized into clauses for scope, normative references, terms and definitions, PCE classification, test setup, operating conditions, immunity requirements, emission requirements, and test reporting. It also includes annexes with example setups, alternative high-power arrangements, and a normative annex for conditional conducted-emission methods at ports other than power ports.

AnnexWhat it covers
Annex AInformative examples of test setups for wall-mounted PCE, including immunity and high-frequency emission tests
Annex BInformative example circuits for low-frequency emission tests such as harmonics and flicker
Annex CInformative test setup examples for conducted disturbance measurement
Annex DInformative alternative setups for high-power PCE
Annex ENormative conditional measurement methods and limits for conducted common mode disturbance at ports other than power ports

What are the key requirements of FprEN IEC 62920:2026?

FprEN IEC 62920:2026 is built around two product classes, defined test conditions, and separate immunity and emission limits. In practice, users need to know the PCE class, the port types present, the installation location, and the intended operating mode before testing begins.

Classification and test setup

  • Clause 4 classifies PCE by location and by Class A or Class B. This matters because the class determines the applicable immunity levels, emission limits, and the suitability of the equipment for residential, commercial/light-industrial, or industrial locations.
  • Clause 5 requires the PCE to be tested in its actual installation condition as far as practical, with cables connected as in the installation manual. This matters because cable routing, mounting, and earthing can change EMC performance.
  • The standard allows testing with suitable DC and AC power supplies that simulate PV modules, batteries, or grid conditions. The supplies must be stable and must not add their own harmonics or disturbances, otherwise the results are not reliable.

Operating conditions

  • Clause 6 requires preliminary testing to find the most sensitive or worst-case operating point. This matters because the EMC result must represent the real operating mode that is most likely to fail or emit most strongly.
  • Immunity tests are carried out in standby mode and operating modes as specified, while low-frequency emission tests are carried out at 25 %, 50 %, and 100 % of rated power. This means the tester must repeat measurements across load points, not just at full power.
  • High-frequency emission tests must consider standby and operating modes, including wired and wireless communication functions where relevant. This matters for PCE with network ports or radio functions because communication activity can change emissions.

Immunity requirements

  • Clause 7 sets immunity requirements for enclosure, AC power, DC power, signal and control ports, wired network ports, and antenna ports, with separate tables for Class A and Class B PCE. The practical effect is that each port type must be checked against the relevant test method and level.
  • The immunity tests include electrostatic discharge, radiated RF fields, electrical fast transient/burst, surge, conducted RF disturbances, and voltage dips and interruptions. This gives a complete set of disturbance types to verify that the PCE keeps operating or recovers as required.
  • Table 7 defines the performance criteria. In practice, the test report must state whether the PCE stayed within acceptable operating status, whether any power-output variation was temporary, and whether communication remained acceptable.

Emission requirements

  • Clause 8.1 covers low-frequency emissions from AC power ports, including auxiliary AC power ports. Harmonics and voltage changes or flicker are checked against the limits from the referenced low-frequency EMC standards.
  • Clause 8.2.2 covers conducted emissions at AC power ports, DC power ports, and ports other than power ports. This matters because disturbance can leave the PCE through several different interfaces, not only the mains connection.
  • Clause 8.2.3 covers radiated emissions up to 1 GHz and above 1 GHz. The document also ties the upper measurement frequency to the highest internal frequency and, when relevant, to wireless communication frequencies inside the PCE.

Reporting

  • Clause 9 requires a detailed test report with the product identification, configuration, operating conditions, cable lengths, earth connection, test setup, acceptance criteria, and measured values. This matters because another lab should be able to repeat the test from the report alone.

What terms does FprEN IEC 62920:2026 define?

  • Photovoltaic power generating system (PV system) - An electric power generating system that converts solar power into electricity by the photovoltaic effect.
  • Power conversion equipment (PCE) - Electrical equipment that converts electrical power from one form to another in terms of voltage, current, frequency, phase, or number of phases.
  • Electrical energy storage devices (ESS) - Devices that absorb electrical energy, store it for a period, and release it later, possibly with energy conversion during the process.
  • Grid connected power converter (GCPC) - A PCE used as a grid-interactive converter.
  • High power electronic equipment and system (HPE) - One or more PCE with a combined rated power greater than 75 kVA, or a system containing such equipment.
  • Artificial mains network (AMN) - A network that presents a defined RF impedance, couples disturbance voltage to the measuring receiver, and decouples the test circuit from the AC mains supply.
  • Coupling/decoupling network (CDN) - An artificial network used to inject or measure signals on one circuit while preventing them from affecting another circuit.
  • PCE with radio functionality - PCE that includes one or more radio devices or plug-in radio modules for control or data exchange.

Who uses FprEN IEC 62920:2026?

FprEN IEC 62920:2026 is used by PCE manufacturers and suppliers who need to design equipment for a declared EMC class and location class. It is also used by EMC test laboratories that perform immunity and emission measurements, and by quality or compliance teams that need a documented test basis.

It is relevant to PV system integrators, installers, and project engineers because the document links EMC results to installation conditions, cable lengths, and location type. Buyers and specifiers can use it to check whether the equipment is intended for residential use, commercial/light-industrial use, or professional installation in larger systems.

What changed in FprEN IEC 62920:2026 from the previous edition?

This draft continues the maintenance of IEC 62920 Ed.1.1 and develops IEC 62920 Ed.2.0. The changes stated in the document include:

  • addition of PCE with radio functionality in the scope
  • updated normative references
  • revised, deleted, and newly added terms and definitions
  • revised PCE classification with location classes
  • revised test setups for wired and wireless functions
  • updated high-frequency emission setups to align with CISPR 16-1-2 and CISPR 16-2-3
  • revised operating conditions to cover wired and wireless communications
  • added immunity requirements for antenna ports
  • added surge testing for wired and wireless network ports of Class B PCE
  • revised IEC 61000-4-3 coverage to close a frequency-range gap
  • revised performance criteria for wired and wireless communications
  • added current limits for certain DC-port measurements using artificial networks as voltage probes
  • added conducted common mode disturbance limits at the antenna port
  • added conditional measurement methods and limits for ports other than power ports
  • added radiated disturbance limits above 1 GHz

Which standards are used with FprEN IEC 62920:2026?

FprEN IEC 62920:2026 uses several referenced standards to define the measurement methods, test levels, and environmental categories:

  • IEC TS 61836 - provides PV-related terms and definitions.
  • IEC 61000-3-2, -3-12 - provide harmonic current emission limits.
  • IEC 61000-3-3, -3-11 - provide limits for voltage changes, voltage fluctuations, and flicker.
  • IEC 61000-4-2, -4-3, -4-4, -4-5, -4-6, -4-11, -4-34 - provide immunity test methods for ESD, radiated RF fields, EFT/burst, surge, conducted RF disturbances, and voltage dips or interruptions.
  • IEC 61000-4-7 and IEC 61000-4-15 - support harmonic and flicker measurement methods.
  • CISPR 11 and CISPR 32 - provide emission measurement context and port-related measurement provisions.
  • CISPR 16-1-1, 16-1-2, 16-1-4, 16-1-6, 16-2-1, 16-2-3 - provide receivers, networks, antennas, test sites, and measurement methods for conducted and radiated disturbance testing.
  • IEC 61000-6-3, IEC 61000-6-4, IEC 61000-6-8 - provide the environmental definitions used for residential, industrial, and commercial/light-industrial locations.

What does the FprEN IEC 62920:2026 document contain?

The document contains immunity tables, emission limit tables, operating-condition rules, and report requirements. It also contains figures showing example test setups for wall-mounted PCE, including direct and indirect ESD, radiated immunity, EFT/burst, surge, conducted disturbance measurements, and radiated disturbance measurements.

Annex B gives example circuits for harmonics and flicker testing across single-phase and three-phase arrangements. Annex C shows standardized conducted-disturbance setups with AC mains supply and with a laboratory AC power source, while Annex D gives alternative high-power arrangements where standard coupling or decoupling hardware is not practical.

Annex E is especially important because it explains the reasoning behind conditional limits for conducted common mode disturbance at wired network ports, signal and control ports, and antenna ports. For engineers and labs, that annex shows when the communication-module view of the port is used and when the PCE power-conversion view is used.

Relations

Effective Date
27-Sep-2022
Effective Date
14-Dec-2021
Effective Date
14-Dec-2021
Effective Date
14-Dec-2021

Buy Documents

Draft

prEN IEC 62920:2025 - BARVE

English language (65 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DNV Energy Systems

Energy and renewable energy certification.

NA Norway Verified

Sponsored listings

Frequently Asked Questions

FprEN IEC 62920:2026 is a draft published by CLC. Its full title is "Photovoltaic power generating systems - EMC requirements and test methods for power conversion equipment". This standard covers: Photovoltaic power generating systems - EMC requirements and test methods for power conversion equipment

Photovoltaic power generating systems - EMC requirements and test methods for power conversion equipment

FprEN IEC 62920:2026 is classified under the following ICS (International Classification for Standards) categories: 27.160 - Solar energy engineering. The ICS classification helps identify the subject area and facilitates finding related standards.

FprEN IEC 62920:2026 has the following relationships with other standards: It is inter standard links to EN 62920:2017/prAB, EN 62920:2017, EN 62920:2017/A1:2021, EN 62920:2017/A11:2020. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

FprEN IEC 62920:2026 is associated with the following European legislation: EU Directives/Regulations: 2014/30/EU; Standardization Mandates: M/552. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

FprEN IEC 62920:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 2 CONTENTS
  • 3 FOREWORD
  • 4 INTRODUCTION
  • 5 Background
  • 6 Maintenance of IEC 62920 Ed.1.1
  • 7 1 Scope
  • 8 2 Normative references
  • 9 3 Terms and definitions
  • 10 4 Classification of PCE
  • 11 4.1 Category of locations
  • 12 4.2 Division into classes
  • 13 4.3 Information for users
  • 14 5 Test setup
  • 15 5.1 General
  • 16 5.2 Configuration of test setups
  • 17 5.2.1 General
  • 18 5.2.2 Setups for immunity requirement test
  • 19 5.2.3 Setups for low frequency emission requirement tests
  • 20 5.2.4 Setups for high frequency emission requirement tests
  • 21 6 Operating conditions during testing
  • 22 6.1 General
  • 23 6.2 Operating conditions for immunity requirement test
  • 24 6.3 Operating conditions for low frequency emission requirement test
  • 25 6.4 Operating conditions for high frequency emission requirement test
  • 26 7 Immunity requirements
  • 27 7.1 Requirements
  • 28 7.2 Performance criteria
  • 29 8 Emission requirements
  • 30 8.1 Low frequency
  • 31 8.1.1 General
  • 32 8.1.2 Harmonics
  • 33 8.1.3 Voltage change
  • 34 8.2 High frequency
  • 35 8.2.1 General
  • 36 8.2.2 Conducted emission
  • 37 8.2.3 Radiated emission
  • 38 9 Test procedures, results and report
  • 39 Annex A (informative) Configuration examples of test setups
  • 40 A.1 General
  • 41 A.2 Setups for immunity requirement test
  • 42 A.2.1 Electrostatic discharge
  • 43 A.2.2 Radiated immunity
  • 44 A.2.3 Electrical fast transient/burst
  • 45 A.2.4 Surge
  • 46 A.2.5 Conducted disturbances, induced by radio-frequency fields
  • oSIST prEN IEC 62920:2025 IEC CDV 62920 © IEC 2025 – 3 – 47 A.2.6 Voltage dips and interruption
  • 48 A.3 Setups for high frequency emission requirement test
  • 49 A.3.1 Conducted disturbances
  • 50 A.3.2 Radiated disturbances
  • 51 Annex B (informative) Setups for low frequency emission requirement test
  • 52 B.1 General
  • 53 B.2 Example of a test circuit for low frequency emission requirement test
  • 54 B.2.1 Harmonics
  • 55 B.2.2 Voltage fluctuations and flicker
  • 56 Annex C (informative) Test setup for conducted disturbance measurement
  • 57 C.1 General
  • 58 C.2 Examples of a test setup
  • 59 Annex D (informative) Alternative test setups for high-power PCE
  • 60 D.1 General
  • 61 D.2 Alternative setup for immunity requirement test
  • 62 D.2.1 Alternative setups for EFT/burst immunity test
  • 63 D.2.2 Alternative setup for surge test
  • 64 D.2.3 Alternative test setup for conducted disturbances, induced by radio- 65 frequency fields
  • 66 D.2.4 Conducted disturbances measurement
  • 67 Annex E (normative) Conditional measurement methods and limits of conducted 68 common mode (asymmetric mode) disturbance at ports other than power ports
  • 69 E.1 Consideration of requirements specified in CISPR32 and covered in IEC 70 62920
  • 71 E.2 Configuration of EUT specified in CISPR 32
  • 72 E.3 Measurement conditions specified in CISPR 32
  • 73 E.4 Proposals on measurements for wired network ports cover in IEC 62920
  • 74 E.5 Consideration of the interface model covered in IEC 62920
  • 75 E.6 Applicable conducted emission limits at wired network ports in IEC 62920
  • 76 Bibliography
  • 78 Figure 1 – Example of ports
  • 79 Figure A.1 – Example of a test setup for direct application of discharges to PCE
  • 80 Figure A.2 – Example of a test setup for indirect application of discharges to PCE
  • 81 Figure A.3 – Example of a test setup for wall-mounted PCE
  • 82 Figure A.4 – Example of a test setup for direct coupling of the test voltage to AC 83 mains power ports
  • 84 Figure A.5 – Example of a test setup for application of the test voltage with a 85 capacitive coupling clamp
  • 86 Figure A.6 – Example of a test setup for AC mains power ports
  • 87 Figure A.7 – Example of a test setup for DC power ports
  • 88 Figure A.8 – Example of a setup of conducted disturbances immunity test applied for 89 wall-mounted PCE
  • 90 Figure A.9 – Example of a test setup using a generator for voltage dips and short 91 interruptions
  • 92 Figure A.10 – Example of a test setup of conducted disturbances measurement 93 applied for wall-mounted PCE

209 INTRODUCTION 210 Background 211 Power conversion equipment (PCE) is indispensable for solar photovoltaic power energy 212 systems in order to convert the DC electric power energy generated by solar photovoltaic 213 modules into AC or DC electric power, and to feed the AC power energy into the AC mains 214 network or loads. PCE consists of DC to DC, DC to AC or AC to DC converters and forms 215 systems with or without DC-coupled electrical energy storage devices.

216 Manufacturers of PCE ensure the performance and reliability of PCE. Electromagnetic 217 compatibility (EMC) is one aspect of performance which must be ensured wherever PCE is used 218 in or exposed to an electromagnetic environment.

219 IEC Guide 107 specifies that TC 77 and CISPR, which are called EMC committees, have 220 responsibility for the development of basic, product family and generic standards on EMC 221 requirements, and product committees must use the emission limits developed by EMC 222 committees and must refer to basic immunity standards for the specification of test techniques. 223 However, when the EMC standards which are developed by TC 77 and CISPR are not 224 considered suitable for a particular product or electromagnetic environment, product 225 committees must seek their assistance and advice for any change in the emission limits and/or 226 measurement requirements. Product committees are responsible for selecting the appropriate 227 immunity test items and levels for their products as well as for defining the relevant performance 228 criteria for the evaluation of the immunity test results. Consequently, product committees, such 229 as TC 22, TC 26, TC 9, and TC 69, have their own EMC standard to define EMC requirements 230 and test methods for their particular types of products.

231 TC 82 also has the responsibility to consider EMC requirements for PCE applying to the solar 232 photovoltaic power energy systems, and TC 82 has taken action as follows to develop its own 233 product EMC standards:

234 a) selection of the immunity test items in accordance with EMC environments for the solar 235 photovoltaic power energy systems, 236 b) supplement of generic standards with a detailed description of test conditions and test set 237 up, 238 c) development of the conditional limits and alternative test methods in terms of installation 239 environmental and operational conditions, and 240 d) development of appropriate requirements and test method for high power equipment. 241 In 2017, TC82 published IEC 62920 (Ed.1.0) and covered the minimum EMC requirements for 242 PCE applying to solar photovoltaic power energy systems in consideration with the above- 243 mentioned items.

244 Following the state-of-the-art technology as well as the latest market needs, IEC 62920:2017 245 (Ed.1.0) is amended to extend the scope of IEC 62920:2017 (Ed.1.0) by taking into account the 246 following technical items:

247 • DC to DC power conversion equipment used in photovoltaic power energy systems, 248 • Electrical energy storage devices connected to DC power ports of PCE used in photovoltaic 249 power energy systems, 250 • 5 m antenna distance of radiated disturbance measurements for the medium size PCE.

252 Maintenance of IEC 62920 Ed.1.1 253 For the purpose of keeping the consistency with EMC basic standards and considering market 254 needs, TC82 started the maintenance of IEC 62920 Ed.1.1 for the development of Ed.2.0 in 255 November 2021.

256 The Ed. 2.0 of IEC 62920 covers the following items:

257 • PCE with radio functionality is added in the scope, 258 • normative references are updated, 259 • some terms and definitions are updated or deleted, 260 • terms and definitions relevant to radio functionality are added, 261 • the classification of PCE is revised to introduce the location classes, 262 • the configurations of test setups are revised to cover the operation of the wired and wireless 263 functions, 264 • setups for high frequency emission requirement test are updated to keep the consistency 265 with EMC basic standards, such as CISPR 16-1-2 and CISPR 16-2-3, 266 • operating conditions for tests are revised to cover wired and wireless communications, 267 • immunity requirements for antenna ports are added, 268 • the surge test is added in the immunity requirements for wired and wireless network ports 269 of Class B PCE, 270 • immunity requirements regarding IEC 61000-4-3 are revised to fill the gap of frequency 271 range, 272 • performance criteria are revised to cover wired and wireless communications, 273 • current limits are added in the table of disturbance limits at the DC power port for class A 274 PCE to cover requirements of the measurement of common mode current when artificial 275 networks are used as voltage probes, 276 • limits of conducted common mode disturbance at the antenna port are added, 277 • conditional measurement methods and limits of conducted common mode (asymmetric 278 mode) disturbance at ports other than power ports are added, 279 • electromagnetic radiation disturbance limits above 1 GHz are added, 280 • an annex for the rational conditional measurement methods and limits of conducted common 281 mode (asymmetric mode) disturbance at ports other than power ports is added.

283 PHOTOVOLTAIC POWER GENERATING SYSTEMS – 284 EMC REQUIREMENTS AND TEST METHODS FOR 285 POWER CONVERSION EQUIPMENT 286 287 288 289 1 Scope 290 This document specifies electromagnetic compatibility (EMC) requirements for power 291 conversion equipment (PCE) (e.g., DC to DC, DC to AC and AC to DC) for use in photovoltaic 292 (PV) power systems with or without electrical energy storage devices.

293 PCE covered by this document can be grid-interactive, which is termed as a grid connected 294 power converter (GCPC), or stand-alone. It can be supplied by single or multiple photovoltaic 295 modules grouped in various array configurations. The PCE can be intended for use in 296 conjunction with batteries or other forms of energy storage and therefore a uni- or bidirectional. 297 This document covers not only PCE connected to a public low voltage AC mains network or 298 other low voltage AC mains installation, but also PCE connected to a medium or high voltage 299 AC network with or without step-down power transformers. Requirements for the PCE 300 connected to a medium or high voltage AC network are specified in this document. However, 301 some requirements relevant to grid interconnection are addressed with other standards 302 specifying power quality or their own grid codes in some countries.

303 This document provides test methods and test conditions for PCE at a test site, but not for 304 photovoltaic modules and other balance of system components.

305 PCE which incorporates radio transmit/receive functions or wireless communication functions 306 (PCE with radio functionality), is included in the scope of this document. However, the emission 307 requirements in this document are not intended to be applicable to the intentional transmissions 308 from a radio transmitter as defined by the ITU including their spurious emissions. 309 When compliance with EMC requirements at the test site cannot be shown due to technical 310 reasons of the test site, PCE can be assessed in situ. Clause 7.6 of CISPR 16-2-1 specifies 311 conditions of in situ measurements for conducted emission, and Clause 7.7 of CISPR 16-2-3 312 for radiated emission. Immunity tests are not required in the case of in situ. 313 2 Normative references 314 The following documents are referred to in the text in such a way that some or all of their content 315 constitutes requirements of this document. For dated references, only the edition cited applies. 316 For undated references, the latest edition of the referenced document (including any 317 amendments) applies.

318 IEC 61000-3-2:2024, Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for 319 harmonic current emissions (equipment with input current ≤ 16 A per phase) 320 IEC 61000-3-3:2021, Electromagnetic compatibility (EMC) – Part 3-3: Limits – Limitation of 321 voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for 322 equipment with rated current ≤ 16 A per phase and not subject to conditional connection 323 IEC 61000-3-11:2017, Electromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of 324 voltage changes, voltage fluctuations and flicker in public low-voltage supply systems – 325 Equipment with rated current ≤ 75 A and subject to conditional connection 326 IEC 61000-3-12:2021, Electromagnetic compatibility (EMC) – Part 3-12: Limits – Limits for 327 harmonic currents produced by equipment connected to public low-voltage systems with input 328 current > 16 A and ≤ 75 A per phase 329 IEC 61000-4-2:2025, Electromagnetic compatibility (EMC) – Part 4-2: Testing and 330 measurement techniques – Electrostatic discharge immunity test 331 IEC 61000-4-3:2020, Electromagnetic compatibility (EMC) – Part 4-3: Testing and measure- 332 ment techniques – Radiated, radio-frequency, electromagnetic field immunity test 333 IEC 61000-4-4:2012, Electromagnetic compatibility (EMC) – Part 4-4: Testing and 334 measurement techniques – Electrical fast transient/burst immunity test 335 IEC 61000-4-5:2017, Electromagnetic compatibility (EMC) – Part 4-5: Testing and 336 measurement techniques – Surge immunity test 337 IEC 61000-4-6:2023, Electromagnetic compatibility (EMC) – Part 4-6: Testing and measure- 338 ment techniques – Immunity to conducted disturbances, induced by radio-frequency fields 339 IEC 61000-4-7:2008, Electromagnetic compatibility (EMC) – Part 4-7: Testing and 340 measurement techniques – General guide on harmonics and interharmonics measurements and 341 instrumentation, for power supply systems and equipment connected thereto 342 IEC 61000-4-11:2020, Electromagnetic compatibility (EMC) – Part 4-11: Testing and 343 measurement techniques – Voltage dips, short interruptions and voltage variations immunity 344 tests 345 IEC 61000-4-34:2009, Electromagnetic compatibility (EMC) – Part 4-34: Testing and 346 measurement techniques – Voltage dips, short interruptions and voltage variations immunity 347 tests for equipment with input current more than 16 A per phase 348 CISPR 11:2024, Industrial, scientific and medical equipment – Radio-frequency disturbance 349 characteristics – Limits and methods of measurement 350 CISPR 16-1-2:2017, Specification for radio disturbance and immunity measuring apparatus and 351 methods – Part 1-2: Radio disturbance and immunity measuring apparatus – Coupling devices 352 for conducted disturbance measurements 353 CISPR 32:2019, Electromagnetic compatibility of multimedia equipment – Emission 354 requirements 355 CISPR 16-2-1:2017, Specification for radio disturbance and immunity measuring apparatus and 356 methods - Part 2-1: Methods of measurement of disturbances and immunity - Conducted 357 disturbance measurements 358 CISPR 16-2-3:2023, Specification for radio disturbance and immunity measuring apparatus and 359 methods - Part 2-3: Methods of measurement of disturbances and immunity - Radiated 360 disturbance measurements 361 CISPR 16-1-1:2019, Specification for radio disturbance and immunity measuring apparatus and 362 methods - Part 1-1: Radio disturbance and immunity measuring apparatus - Measuring 363 apparatus 364 CISPR 16-1-4:2023, Specification for radio disturbance and immunity measuring apparatus and 365 methods - Part 1-4: Radio disturbance and immunity measuring apparatus - Antennas and test 366 sites for radiated disturbance measurements 367 CISPR 16-1-6:2022, Specification for radio disturbance and immunity measuring apparatus and 368 methods - Part 1-6: Radio disturbance and immunity measuring apparatus - EMC antenna 369 calibration 370 IEC 61000-6-3:2020, Electromagnetic compatibility (EMC) – Part 6-3: Generic standards - 371 Emission standard for equipment in residential environments 372 IEC 61000-6-8:2020, Electromagnetic compatibility (EMC) – Part 6-8: Generic standards - 373 Emission standard for professional equipment in commercial and light-industrial locations 374 IEC 61000-6-4:2018, Electromagnetic compatibility (EMC) – Part 6-4: Generic standards - 375 Emission standard for industrial environments 376 3 Terms and definitions 377 For the purposes of this document, the terms and definitions in IEC TS 61836, as well as the 378 following apply.

379 ISO and IEC maintain terminological databases for use in standardization at the following 380 addresses:

381 • IEC Electropedia: available at https://www.electropedia.org/ 382 • ISO Online browsing platform: available at https://www.iso.org/obp 383 3.1 384 photovoltaic power generating system 385 PV system 386 electric power generating system which uses the photovoltaic effect to convert solar power into 387 electricity 388 3.2 389 power conversion equipment 390 PCE 391 electrical device converting one form of electrical power to another form of electrical power with 392 respect to voltage, current, frequency, phase and the number of phases 393 [SOURCE: IEC 62109-1:2010, 3.66, modified – The definition has been rephrased, and the note 394 has been deleted.] 395 3.3 396 photovoltaic module 397 PV modules 398 complete and environmentally protected assembly of interconnected photovoltaic cells 399 [SOURCE: IEC TS 61836:2016, 3.1.45.g, modified – The note has been deleted.] 400 3.4 401 electrical energy storage devices 402 ESS 403 devices that are able to absorb electrical energy, to store it for a certain amount of time and to 404 release electrical energy during which energy conversion processes may be included 405 [SOURCE: IEC 62933-1:2018, 3.1, modified – The example and the note have been deleted.] 407 port 408 physical interface of the PCE with the external electromagnetic environment 409 Note 1 to entry: See Figure 1 for examples of ports.

410 411 412 Figure 1 – Example of ports 413 3.6 414 enclosure port 415 physical boundary of the PCE product which electromagnetic fields may radiate through or 416 impinge on 417 3.7 418 AC mains power port 419 port used to connect to a public low voltage AC mains power distribution network or other low 420 voltage AC mains installation 421 3.8 422 auxiliary AC power port 423 additional low voltage AC power port for purposes other than feeding in AC power 424 3.9 425 DC power port 426 port used to connect a local low voltage DC power generating system or electrical energy 427 storage devices 428 3.10 429 auxiliary DC power port 430 additional low voltage DC power port for purposes other than supplying DC power for the DC 431 to AC conversion or electrical energy storage devices 432 3.11 433 signal and control port 434 port intended for the interconnection of components of PCE, or between PCE and local auxiliary 435 equipment, and used in accordance with relevant functional specifications 436 Note 1 to entry: Examples include RS-232, Universal Serial Bus (USB), High-Definition Multimedia Interface (HDMI), 437 IEEE standard 1394 (“Fire Wire”) and control pilot.

438 [SOURCE: CISPR 32:2019, 3.1.30, modified] 439 3.12 440 wired network port 441 point to connection for voice, data and signalling transfers intended to interconnect widely 442 dispersed systems by direct connection to a single-user or multi-user communication network 443 Note 1 to entry: Examples include CATV, PSTN, ISDN, xDSL, LAN and similar networks. These ports can support 444 screened or unscreened cables and can also carry AC or DC power where this is an integral part of the 445 telecommunication specification.

446 3.13 447 antenna port 448 port for connection of an antenna used for intentional transmission and/or reception of radiated 449 RF energy 450 [SOURCE: CISPR 32:2019, 3.1.3, modified] 451 3.14 452 high power electronic equipment and system 453 HPE 454 one or more power conversion equipment with a combined rated power greater than 75 kVA, or 455 a system containing such equipment 456 3.15 457 low voltage 458 LV 459 voltage not exceeding a conventionally adopted limit 460 Note 1 to entry: For AC, the conventionally adopted limit is 1 000 V.

461 Note 2 to entry: For DC, the conventionally adopted limit is 1 500 V.

462 [SOURCE: IEC 60050-195:2021, 195-05-25] 463 3.16 464 high voltage 465 HV 466 voltage exceeding the conventionally adopted limit for low voltage 467 [SOURCE: IEC 60050-195:2021, 195-05-26] 468 3.17 469 medium voltage 470 MV 471 any set of voltage levels lying between low and high voltage 472 [SOURCE: IEC 60050-601:1985, 601-01-28, modified – The note has been deleted.] 473 3.18 474 small equipment under test 475 small EUT 476 equipment under test, either positioned on a table top or standing on the floor, which, including 477 its cables, fits in a cylindrical volume of 1,5 m in diameter and 1,5 m height (as measured from 478 the floor) 479 Note 1 to entry: At an OATS or in a SAC, the radiated emission measurement distance of 3 m shall only be used 480 for small EUT 481 [SOURCE: CISPR 16-2-3:2023, 3.1.35, modified – only use the volume for 3 m measurement 482 distance] 484 medium equipment under test 485 medium EUT 486 equipment under test, either positioned on a table top or standing on the floor, which, including 487 its cables, fits in a cylindrical volume of 2 m in diameter and 2 m height (as measured from the 488 floor) 489 Note 1 to entry: At an OATS or in a SAC, the radiated emission measurement distance of 5 m shall only be used 490 for medium EUT 491 [SOURCE: CISPR 16-2-3:2023, 3.1.35, modified – only use the volume for 5 m measurement 492 distance] 493 3.20 494 residential location 495 area of land designated for domestic dwellings where the mains power within these locations is 496 directly connected to the low-voltage public mains network 497 Note 1 to entry: Examples of residential locations are: houses, apartments, farm buildings housing people. 498 Note 2 to entry: A dwelling can be a single building, separate building or a separate section of a larger building. 499 Note 3 to entry: Within these locations it is expected to operate a radio receiver within a distance of 10 m from the 500 equipment.

501 Note 4 to entry: Domestic dwellings are places for one or more people to live. 502 [SOURCE: IEC 61000-6-3:2020] 503 3.21 504 commercial and light-industrial location 505 location which are not residential in accordance with 3.20, where the mains supply is directly 506 connected to the low-voltage publ

...