EN 54-29:2015
(Main)Fire detection and fire alarm systems - Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors
Fire detection and fire alarm systems - Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors
This European Standard specifies requirements, test methods and performance criteria for point-type multi-sensor fire detectors for use in fire detection systems installed in buildings (see EN 54 1:2011), incorporating in one mechanical enclosure at least one optical or ionization smoke sensor and at least one heat sensor. The overall fire detection performance is determined utilizing the combination of the detected phenomena.
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of point detectors using a combination of smoke and heat sensors to this EN.
Point detectors using a combination of smoke and heat sensors having special characteristics suitable for the detection of specific fire risks are not covered by this European Standard. The performance requirements for any additional functions are beyond the scope of this European Standard (e.g. additional features or enhanced functionality for which this European Standard does not define a test or assessment method).
NOTE Certain types of detector contain radioactive materials. The national requirements for radiation protection differ from country to country and they are not specified in this European Standard.
Brandmeldeanlagen - Teil 29: Mehrfachsensor-Brandmelder - Punktförmige Melder mit kombinierten Rauch- und Wärmesensoren
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punktförmige Mehrfachsensor-Brandmelder fest, die in Brandmeldeanlagen für Gebäude (siehe EN 54 1:2011) eingesetzt werden, und die in einem mechanischen Gehäuse mindestens einen Rauchsensor nach dem Durchlicht- oder Ionisationsprinzip und mindestens einen Wärmesensor enthalten. Ihre Gesamtleistung bei der Brandmeldung ergibt sich aus der Kombination der erkannten Brandphänomene.
Diese Europäische Norm enthält die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP, en: assessment and verification of constancy of performance) von punktförmigen Meldern mit kombinierten Rauch- und Wärmesensoren nach dieser Europäischen Norm.
Punktförmige Melder mit kombinierten Rauch- und Wärmesensoren, die über spezielle Eigenschaften verfügen und zur Erkennung spezieller Brandrisiken geeignet sind, werden in der vorliegenden Europäischen Norm nicht behandelt. Die Leistungsanforderungen an alle zusätzlichen Funktionen fallen nicht in den Anwendungsbereich dieser Europäischen Norm (z. B. werden in dieser Europäischen Norm für zusätzliche Merkmale oder für eine verbesserte Funktionstüchtigkeit keine Prüf- oder Bewertungsverfahren festgelegt).
ANMERKUNG Bestimmte Meldertypen enthalten radioaktive Stoffe. Die nationalen Anforderungen zum Schutz gegen radioaktive Strahlung sind in den einzelnen Ländern unterschiedlich und werden in der vorliegenden Europäischen Norm nicht festgelegt.
Systèmes de détection et d'alarme incendie - Partie 29 : Détecteurs d'incendie multi-capteurs - Détecteurs ponctuels utilisant une combinaison de capteurs de fumée et de chaleur
La présente Norme européenne spécifie les exigences, les méthodes d'essai et les critères de performance pour les détecteurs d'incendie ponctuels multicapteurs destinés à être utilisés dans les systèmes de détection d'incendie installés dans les bâtiments (voir l'EN 54-1:2011), incorporant dans une seule enveloppe mécanique au moins un capteur de fumée optique ou à ionisation et au moins un capteur de chaleur. La performance globale de détection du feu est déterminée en utilisant la combinaison des phénomènes détectés.
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des détecteurs ponctuels utilisant une combinaison de capteurs de fumée et de chaleur, par rapport à la présente Norme européenne.
Les détecteurs ponctuels, utilisant une combinaison de capteurs de fumée et de chaleur possédant des caractéristiques particulières appropriées pour la détection de risques d'incendies spécifiques, ne sont pas couverts par la présente Norme européenne. Les exigences de performance relatives à toute autre fonction ne relèvent pas du domaine d'application de la présente Norme européenne (par exemple, des caractéristiques supplémentaires ou une fonctionnalité améliorée pour lesquelles la présente Norme européenne ne définit pas d'essai ou de méthode d'évaluation).
NOTE Certains types de détecteurs contiennent des matières radioactives. Les exigences nationales de radioprotection variant d'un pays à l'autre, celles-ci ne sont pas spécifiées dans la présente Norme européenne.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 29. del: Večsenzorski javljalniki požara - Točkovni javljalniki s senzorjema za zaznavanje dima in toplote
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2015
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO9HþVHQ]RUVNL
MDYOMDOQLNLSRåDUD7RþNRYQLMDYOMDOQLNLVVHQ]RUMHPD]D]D]QDYDQMHGLPDLQWRSORWH
Fire detection and fire alarm systems - Part 29: Multi-sensor fire detectors - Point
detectors using a combination of smoke and heat sensors
Brandmeldeanlagen - Teil 29: Mehrfachsensor-Brandmelder - Punktförmige Melder mit
kombinierten Rauch- und Wärmesensoren
Systèmes de détection et d'alarme incendie - Partie 29 : Détecteurs d'incendie multi-
capteurs - Détecteurs ponctuels utilisant une combinaison de capteurs de fumée et de
chaleur
Ta slovenski standard je istoveten z: EN 54-29:2015
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-29
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2015
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 29: Multi-sensor fire
detectors - Point detectors using a combination of smoke and
heat sensors
Systèmes de détection et d'alarme incendie - Partie 29 : Brandmeldeanlagen - Teil 29: Mehrfachsensor-
Détecteurs d'incendie multi-capteurs - Détecteurs ponctuels Brandmelder - Punktförmige Melder mit kombinierten
utilisant une combinaison de capteurs de fumée et de Rauch- und Wärmesensoren
chaleur
This European Standard was approved by CEN on 15 February 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-29:2015 E
worldwide for CEN national Members.
Contents Page
Foreword .6
Introduction .8
1 Scope .9
2 Normative references .9
3 Terms and definitions . 10
4 Requirements . 10
4.1 General . 10
4.2 Nominal activation conditions/sensitivity . 10
4.2.1 Individual alarm indication . 10
4.2.2 Response to slowly developing fires. 10
4.2.3 Repeatability of smoke response. 11
4.2.4 Directional dependence of smoke response . 11
4.2.5 Directional dependence of heat response . 11
4.2.6 Lower limit of heat response . 11
4.2.7 Reproducibility of smoke response . 11
4.2.8 Reproducibility of heat response . 11
4.2.9 Air movement . 11
4.2.10 Dazzling . 11
4.3 Operational reliability . 11
4.3.1 Connection of ancillary devices . 11
4.3.2 Monitoring of detachable detectors . 11
4.3.3 Manufacturer's adjustments . 12
4.3.4 On-site adjustment of response behaviour . 12
4.3.5 Protection against the ingress of foreign bodies . 12
4.3.6 Software controlled detectors . 12
4.4 Tolerance to supply parameters . 13
4.4.1 Variation in supply parameters . 13
4.5 Performance parameters under fire conditions . 14
4.5.1 Fire sensitivity . 14
4.6 Durability of nominal activation conditions/sensitivity . 14
4.6.1 Temperature resistance . 14
4.6.2 Humidity resistance . 14
4.6.3 Shock and vibration resistance . 14
4.6.4 Electrical stability . 15
4.6.5 Resistance to chemical agents . 15
5 Test and assessment and sampling methods . 15
5.1 General . 15
5.1.1 Atmospheric conditions for tests . 15
5.1.2 Operating conditions for tests . 15
5.1.3 Mounting arrangements . 15
5.1.4 Tolerances . 16
5.1.5 Measurement of smoke response value . 16
5.1.6 Measurement of heat response value . 16
5.1.7 Provision for tests . 17
5.1.8 Test schedule . 17
5.2 Nominal activation conditions/sensitivity . 18
5.2.1 Individual alarm indication . 18
5.2.2 Response to slowly developing fires . 19
5.2.3 Repeatability of smoke response . 19
5.2.4 Directional dependence of smoke response . 19
5.2.5 Directional dependence of heat response . 20
5.2.6 Lower limit of heat sensitivity . 20
5.2.7 Reproducibility of smoke response . 21
5.2.8 Reproducibility of heat response . 21
5.2.9 Air movement . 22
5.2.10 Dazzling . 22
5.3 Operational reliability . 23
5.3.1 Connection of ancillary devices . 23
5.3.2 Monitoring of detachable detectors . 23
5.3.3 Manufacturer's adjustments . 23
5.3.4 On-site adjustment of behaviour . 23
5.3.5 Protection against the ingress of foreign bodies . 23
5.3.6 Software controlled devices . 23
5.4 Tolerance to supply parameters . 24
5.4.1 Variation in supply parameters . 24
5.5 Performance parameters under fire conditions . 24
5.5.1 Fire sensitivity . 24
5.6 Durability of nominal activation conditions/sensitivity . 26
5.6.1 Temperature resistance . 26
5.6.2 Humidity resistance . 28
5.6.3 Shock and vibration resistance . 30
5.6.4 Electrical stability . 34
5.6.5 Resistance to chemical agents . 35
6 Assessment and verification of constancy of performance (AVCP) . 37
6.1 General . 37
6.2 Type testing . 37
6.2.1 General . 37
6.2.2 Test samples, testing and compliance criteria . 38
6.2.3 Test reports . 38
6.3 Factory production control (FPC) . 38
6.3.1 General . 38
6.3.2 Requirements . 39
6.3.3 Product specific requirements . 41
6.3.4 Initial inspection of factory and FPC . 42
6.3.5 Continuous surveillance of FPC . 42
6.3.6 Procedure for modifications . 42
6.3.7 One-off products, pre-production products, (e.g. prototypes) and products produced in
very low quantities . 43
7 Classification and designation . 43
8 Marking, Labelling and Packaging . 44
Annex A (normative) Smoke tunnel for smoke response values . 45
Annex B (normative) Test aerosol for smoke response value measurements . 46
Annex C (normative) Smoke measuring instruments . 47
C.1 Obscuration meter . 47
C.2 Measuring ionization chamber (MIC) . 47
Annex D (normative) Heat tunnel for heat response value . 51
Annex E (normative) Apparatus for dazzling test . 52
Annex F (informative) Apparatus for impact test. 54
Annex G (normative) Fire test room . 56
Annex H (normative) Open wood fire (TF1) . 58
H.1 Fuel . 58
H.2 Arrangement . 58
H.3 Method of ignition . 58
H.4 Variables . 58
H.5 End-of-test condition . 58
H.6 Test validity criteria . 59
Annex I (normative) Smouldering (pyrolysis) wood fire (TF2) . 61
I.1 Fuel . 61
I.2 Hotplate . 61
I.3 Arrangement . 61
I.4 Heating rate . 61
I.5 End-of-test condition . 61
I.6 Test validity criteria . 61
Annex J (normative) Glowing smouldering cotton fire (TF3) . 65
J.1 Fuel . 65
J.2 Arrangement . 65
J.3 Ignition . 66
J.4 End-of-test condition . 67
J.5 Test validity criteria . 67
Annex K (normative) Open plastics (polyurethane) fire (TF4) . 69
K.1 Fuel . 69
K.2 Conditioning . 69
K.3 Arrangement . 69
K.4 Ignition . 69
K.5 Method of ignition . 69
K.6 End-of-test condition . 69
K.7 Test validity criteria . 69
Annex L (normative) Liquid (heptane) fire (TF5) . 71
L.1 Fuel . 71
L.2 Arrangement . 71
L.3 Ignition . 71
L.4 End-of-test condition . 71
L.5 Test validity criteria . 71
Annex M (normative) Low temperature black smoke (decalene) liquid fire (TF8) . 73
M.1 Fuel . 73
M.2 Arrangement . 73
M.3 Ignition . 73
M.4 End-of-test condition . 73
M.5 Test validity criteria . 73
Annex N (informative) Information concerning the construction of the smoke tunnel . 75
Annex O (informative) Construction of the heat tunnel . 77
Annex P (informative) Information concerning test procedures and requirements for the response
to slowly developing fires . 80
Annex Q (informative) Information concerning the construction of the measuring ionization
chamber . 84
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Regulation . 86
ZA.1 Scope and relevant characteristics . 86
ZA.2 Procedure for assessment and verification of constancy of performance (AVCP) of point
detectors using a combination of smoke and heat sensors. 88
ZA.3 CE marking and labelling . 92
Bibliography . 96
Foreword
This document (EN 54-29:2015) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by October 2015, and conflicting national standards shall be withdrawn at
the latest by January 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports the basic requirements of Regulation (EU) 305/2011.
For relationship with EU Regulations, see informative Annex ZA which is an integral part of this document.
EN 54, Fire detection and fire alarm systems, consists of the following parts:
— Part 1: Introduction
— Part 2: Control and indicating equipment
— Part 3: Fire alarm devices – Sounders
— Part 4: Power supply equipment
— Part 5: Heat detectors – Point detectors
— Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
— Part 10: Flame detector – Point detectors
— Part 11: Manual call points
— Part 12: Smoke detectors – Line detector using an optical light beam
— Part 13: Compatibility assessment of system components
— Part 14: Technical Specification: Guidelines for planning, design, installation, commissioning, use and
maintenance
— Part 16: Voice alarm control and indicating equipment
— Part 17: Short circuit isolators
— Part 18: Input/output devices
— Part 20: Aspirating smoke detectors
— Part 21: Alarm transmission and fault warning routing equipment
— Part 22: Resettable Line-type heat detectors
— Part 23: Fire alarm devices – Visual alarms
— Part 24: Components of voice alarm systems – Loudspeakers
— Part 25: Components using radio links and system requirements
— Part 26: Point fire detectors using carbon monoxide sensors
— Part 27: Duct smoke detectors
— Part 28: Non-resettable (digital) line type heat detectors
— Part 29: Point detectors using a combination of smoke and heat sensors
— Part 30: Point detectors using a combination of carbon monoxide and heat sensors
— Part 31: Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors
— Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice
alarm systems
NOTE This list includes standards that are in preparation and other standards may be added. For current status of
published standards refer to http://www.cen.eu/Pages/default.aspx.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
Introduction
Multi-sensor fire detectors combining smoke and heat sensors complying with this document are general
purpose fire detectors. Multi-sensor fire detectors can be used to achieve
— a high stability against deceptive phenomena,
— a response to a broad range of fires.
Compared to the standards for single phenomenon detectors, additional environmental tests were included to
demonstrate a higher stability.
The response to a broad range of fires is shown by including the test fires TF1 and TF8 in addition to the test
fires TF2 to TF5 which are used for detectors complying with EN 54-7.
The performance of single sensor components of a multi-sensor fire detector need not comply with the
standards for single phenomena fire detectors (EN 54-5, EN 54-7) however the combined performance does
need to meet the requirements of this standard.
1 Scope
This European Standard specifies requirements, test methods and performance criteria for point-type multi-
sensor fire detectors for use in fire detection systems installed in buildings (see EN 54-1:2011), incorporating
in one mechanical enclosure at least one optical or ionization smoke sensor and at least one heat sensor. The
overall fire detection performance is determined utilizing the combination of the detected phenomena.
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of
point detectors using a combination of smoke and heat sensors to this European Standard.
Point detectors using a combination of smoke and heat sensors having special characteristics suitable for the
detection of specific fire risks are not covered by this European Standard. The performance requirements for
any additional functions are beyond the scope of this European Standard (e.g. additional features or
enhanced functionality for which this European Standard does not define a test or assessment method).
NOTE Certain types of detector contain radioactive materials. The national requirements for radiation protection differ
from country to country and they are not specified in this European Standard.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 54-1:2011, Fire detection and fire alarm systems - Part 1: Introduction
EN 54-5:2000, Fire detection and fire alarm systems - Part 5: Heat detectors - Point detectors
EN 54-5:2000/A1:2002, Fire detection and fire alarm systems - Part 5: Heat detectors - Point detectors
EN 50130-4:2011, Alarm systems - Part 4: Electromagnetic compatibility - Product family standard: Immunity
requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems
EN 60068-1:1994, Environmental testing - Part 1: General and guidance (IEC 60068-1:1988)
EN 60068-2-1:2007, Environmental testing - Part 2-1: Tests - Test A: Cold (IEC 60068-2-1:2007)
EN 60068-2-6:2008, Environmental testing - Part 2-6: Tests - Test Fc: Vibration (sinusoidal) (IEC 60068-2-
6:2008)
EN 60068-2-27:2009, Environmental testing - Part 2-27: Tests - Test Ea and guidance: Shock (IEC 60068-2-
27:2009)
EN 60068-2-30:2005, Environmental testing - Part 2-30: Tests - Test Db: Damp heat, cyclic (12 h + 12 h
cycle) (IEC 60068-2-30:2005)
EN 60068-2-42:2003, Environmental testing - Part 2-42: Tests - Test Kc: Sulphur dioxide test for contacts and
connections (IEC 60068-2-42:2003)
EN 60068-2-78:2013, Environmental testing - Part 2-78: Tests - Test Cab: Damp heat, steady state
(IEC 60068-2-78:2012)
ISO 209:2007, Aluminium and aluminium alloys — Chemical composition
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 54-1:2011 and the following apply.
3.1
non-volatile memory
memory element which does not require the presence of an energy source for the retention of its content
3.2
site specific data
alterable data required for the detector to operate in a defined detector configuration
3.3
smoke response value
aerosol density in the proximity of a test specimen at the moment that it generates a reference signal in a
smoke tunnel
3.4
heat response value
temperature in the proximity of a test specimen at the moment that it generates a reference signal in a heat
tunnel
3.5
sensor
transducer, which is assigned to be receptive to one fire phenomenon and converts its information into an
electrical output
4 Requirements
4.1 General
In order to comply with this standard, the detector shall meet the requirements of Clause 4, which shall be
verified by visual inspection, engineering assessment or shall be tested as described in Clause 5 and shall
meet the requirements of the tests.
4.2 Nominal activation conditions/sensitivity
4.2.1 Individual alarm indication
The detector shall be provided with an integral red visual indicator, by which the individual detector that
released an alarm, can be identified, until the alarm condition is reset. Where other conditions of the detector
can be visually indicated, they shall be clearly distinguishable from the alarm indication, except when the
detector is switched into a service mode. For detachable detectors, the indicator may be integral with the base
or the detector head. The visual indicator shall be visible from a distance of 6 m directly below the detector, in
an ambient light intensity up to 500 lux when assessed as described in 5.2.1.
NOTE The alarm condition is reset manually at the control and indicating equipment (see EN 54–2:1997 as amended
by EN 54–2:1997/A1:2006).
4.2.2 Response to slowly developing fires
The detector may incorporate provision for “drift compensation”, for example to compensate for sensor drift
due to the build up of dirt in the detector, If such drift compensation is included, then it shall not lead to a
significant reduction in the detector's sensitivity to slowly developing fires when assessed as specified in 5.2.2.
4.2.3 Repeatability of smoke response
The detector shall have stable behaviour with respect to its sensitivity to smoke after a number of alarm
conditions. To confirm this, the detector shall be assessed in accordance with 5.2.3.
4.2.4 Directional dependence of smoke response
The sensitivity of the detector to smoke shall not be unduly dependent on the direction of airflow around it. To
confirm this, the detector shall be assessed in accordance with 5.2.4.
4.2.5 Directional dependence of heat response
The heat sensitivity of the detector shall not be unduly dependent on the direction of airflow around it. To
confirm this, the detector shall be assessed in accordance with 5.2.5.
4.2.6 Lower limit of heat response
The detector shall not be more sensitive to heat alone, without the presence of smoke, than is permitted in
EN 54-5:2000 as amended by EN 54-5:2000/A1:2002. To confirm this, the detector shall be assessed in
accordance with 5.2.6.
4.2.7 Reproducibility of smoke response
The sensitivity of the detector to smoke shall not vary unduly from specimen to specimen. To confirm this, the
detector shall be assessed in accordance with 5.2.7.
4.2.8 Reproducibility of heat response
The heat sensitivity of the detector shall not vary unduly from specimen to specimen. To confirm this, the
detector shall be assessed in accordance with 5.2.8.
4.2.9 Air movement
The sensitivity of the detector shall not be unduly affected by the rate of the airflow and that it is not unduly
prone to false alarms in draughts or in short gusts. To confirm this, the detector shall be assessed in
accordance with 5.2.9.
4.2.10 Dazzling
The sensitivity of the detector shall not be unduly influenced by the close proximity of artificial light sources. To
confirm this, the detector shall be assessed in accordance with 5.2.10. This test is only applicable to detectors
using optical smoke sensors, as ionization chamber detectors are considered unlikely to be influenced.
4.3 Operational reliability
4.3.1 Connection of ancillary devices
Where the detector provides for connections to ancillary devices (e.g. remote indicators, control relays), open-
or short-circuit failures of these connections shall not prevent the correct operation of the detector.
4.3.2 Monitoring of detachable detectors
For detachable detectors, means shall be provided for a remote monitoring system (e.g. the control and
indicating equipment) to detect the removal of the head from the base, in order to give a fault signal.
4.3.3 Manufacturer's adjustments
It shall not be possible to change the manufacturer's settings except by special means (e.g. the use of a
special code or tool) or by breaking or removing a seal.
4.3.4 On-site adjustment of response behaviour
If there is provision for on-site adjustment of the response behaviour of the detector then:
a) for each setting at which the manufacturer claims compliance with this standard, the detector shall comply
with the requirements of this standard, and access to the adjustment means shall only be possible by the
use of a code or special tool or by removing the detector from its base or mounting;
b) any setting(s) at which the manufacturer does not claim compliance with this standard, shall only be
accessible by the use of a code or special tool, and it shall be clearly marked on the detector or in the
associated data, that if these setting(s) are used, the detector does not comply with the standard.
These adjustments may be carried out at the detector or at the control and indicating equipment.
4.3.5 Protection against the ingress of foreign bodies
The detector shall be so designed that a sphere of diameter (1,3 ± 0,05) mm cannot pass into the smoke
sensor chamber(s).
NOTE This requirement is intended to restrict the access of insects into the sensitive parts of the detector. It is known
that this requirement is not sufficient to prevent the access of all insects; however, it is considered that extreme restrictions
on the size of access holes may introduce the danger of clogging by dust etc. It may therefore be necessary to take other
precautions against false alarms due to the entry of small insects.
4.3.6 Software controlled detectors
4.3.6.1 General
For detectors which rely on software control in order to fulfil the requirements of this standard, the
requirements of 4.3.6.2, 4.3.6.3 and 4.3.6.4 shall be met.
4.3.6.2 Software documentation
4.3.6.2.1 Design overview
The manufacturer shall submit documentation which gives an overview of the software design. This
documentation shall be in sufficient detail for the design to be inspected for compliance with this standard and
shall include at least the following:
a) a functional description of the main program flow (e.g. as a flow diagram or structogram) including:
1) a brief description of the modules and the functions that they perform;
2) the way in which the modules interact;
3) the overall hierarchy of the program;
4) the way in which the software interacts with the hardware of the detector;
5) the way in which the modules are called, including any interrupt processing.
b) a description of which areas of memory are used for the various purposes (e.g. the program, site specific
data and running data);
c) a designation, by which the software and its version can be uniquely identified.
4.3.6.2.2 Design detail
The manufacturer shall have available detailed design documentation, which only needs to be provided if
required by the testing authority. It shall comprise at least the following:
a) an overview of the whole system configuration, including all software and hardware components;
b) a description of each module of the program, containing at least:
1) the name of the module;
2) a description of the tasks performed;
3) a description of the interfaces, including the type of data transfer, the valid data range and the
checking for valid data.
c) full source code listings, as hard copy or in machine-readable form (e.g. ASCII-code), including all global
and local variables, constants and labels used, and sufficient comment for the program flow to be
recognized;
d) details of any software tools used in the design and implementation phase (e.g. CASE-tools, compilers).
4.3.6.3 Software design
In order to ensure the reliability of the detector, the following requirements for software design shall apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data to
cause error in the program operation;
c) the software shall be designed to avoid the occurrence of deadlock of the program flow.
4.3.6.4 The storage of programs and data
The program necessary to comply with this standard and any pre-set data, such as manufacturer's settings,
shall be held in non-volatile memory. Writing to areas of memory containing this program and data shall only
be possible by the use of some special tool or code and shall not be possible during normal operation of the
detector.
Site-specific data shall be held in memory which will retain data for at least two weeks without external power
to the detector, unless provision is made for the automatic renewal of such data, following loss of power,
within 1 h of power being restored.
4.4 Tolerance to supply parameters
4.4.1 Variation in supply parameters
Within the specified range(s) of the supply parameters, the sensitivity of the detector shall not be unduly
dependent on these parameters (e.g. voltage). To confirm this, the detector shall be assessed in accordance
with 5.4.1.
4.5 Performance parameters under fire conditions
4.5.1 Fire sensitivity
The detector shall have adequate sensitivity to incipient type fires that may occur in buildings. To confirm this,
the detector shall be assessed in accordance with 5.5.1.
4.6 Durability of nominal activation conditions/sensitivity
4.6.1 Temperature resistance
4.6.1.1 Dry heat (operational)
The detector shall function correctly at high ambient temperatures. To confirm this, the detector shall be
assessed in accordance with 5.6.1.1.
4.6.1.2 Cold (operational)
The detector shall function correctly at low ambient temperatures. To confirm this, the detector shall be
assessed in accordance with 5.6.1.2.
4.6.2 Humidity resistance
4.6.2.1 Damp heat, cyclic (operational)
The detector shall function correctly at a high level of relative humidity with short period of condensation. To
confirm this, the detector shall be assessed in ac
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...