Fixed firefighting systems - Automatic sprinkler systems - Part 2: Design and installation of ESFR and CMSA sprinkler systems

This document specifies requirements for the design and installation of early suppression fast response (ESFR) and control mode specific application (CMSA) sprinklers in automatic sprinkler systems, in accordance with this standard and additionally the EN 12845 series of standards.
This document does not cover all legislative requirements.
NOTE   In certain countries, specific national regulations can apply. Attention is drawn to the applicability or non-applicability for this document as specified by national responsible authorities.

Ortsfeste Brandbekämpfungsanlagen - Automatische Sprinkleranlagen - Teil 2: Auslegung und Installation von ESFR- und CMSA-Sprinklern

Installations fixes de lutte contre l'incendie - Systèmes d'extinction automatique du type sprinkleur - Partie 2 : Conception et installation de système de sprinkleurs ESFR et CMSA

Vgrajene naprave za gašenje - Avtomatski sprinklerski sistemi - 2. del: Projektiranje in vgradnja sprinklerskih sistemov ESFR in CMSA - Dopolnilo A1

General Information

Status
Not Published
Publication Date
15-Sep-2027
Current Stage
4020 - Submission to enquiry - Enquiry
Start Date
11-Dec-2025
Due Date
29-Apr-2026
Completion Date
11-Dec-2025

Relations

Effective Date
11-Jun-2025

Overview

EN 12845-2:2024/prA1 is a draft amendment to the European standard for fixed firefighting systems, specifically focusing on automatic sprinkler systems. This part 2 of the EN 12845 series addresses the design and installation of Early Suppression Fast Response (ESFR) and Control Mode Specific Application (CMSA) sprinkler systems. Prepared by CEN Technical Committee CEN/TC 191, this standard update integrates recent technical modifications enhancing the applicability, spacing, and installation requirements for ESFR and CMSA sprinklers.

The document is intended to complement the main EN 12845 series by providing detailed requirements and guidance for these advanced sprinkler types within automatic sprinkler systems, which are crucial for rapid fire suppression and control in varied commercial and industrial settings.

Key Highlights:

  • Specification of sprinkler types, spacing, clearance, and positioning.
  • Detailed provisions for ceilings and roof conditions including slopes and skylight protection.
  • Updated requirements for obstruction scenarios and vertical clearances.
  • Enhanced installation guidance particularly for wet-pipe systems and dry-pipe or pre-action systems.
  • Modifications to terminology for clarity and consistency (e.g., replacing “head” with “sprinkler”).

Key Topics

Sprinkler System Design Requirements

  • Use of ESFR sprinklers as ceiling and in-rack sprinklers to optimize suppression capabilities.
  • CMSA sprinkler spacing and location criteria adapted to accommodate specific fire risks.
  • Defined geometric criteria including ceiling slope, vertical clearance below sprinklers, and obstruction effects.
  • Specific design methods for ensuring spray coverage under unobstructed and obstructed ceilings, including solid ceiling structural members with less than 70% open area.

Installation Practices

  • Protection measures for skylights and plastic skylights, necessitating supplemental sprinklers to maintain coverage integrity.
  • Inclusion of new design tables and formula updates for sprinkler spacing and count, ensuring enhanced fire protection density.
  • Special considerations for dry-pipe and pre-action systems reflecting changes in operational characteristics.
  • Requirements for vertical barriers and aisle widths in rack storage to support effective sprinkler deployment.

Technical Updates and Clarifications

  • Modifications to terminology and definitions to align with related standards such as EN 17451 and EN 12845 parts 2 and 3.
  • Clarification on longitudinal and transverse flue space minimum distances.
  • Removal and replacement of older clauses to improve standard coherence and eliminate redundancies.
  • New keys and legends for figures supporting spatial layouts of sprinkler arrays and obstructions.

Applications

EN 12845-2:2024/prA1 serves as an essential reference for:

  • Fire safety engineers designing automatic sprinkler systems using ESFR and CMSA sprinklers.
  • Installation professionals ensuring compliance with up-to-date European design guidelines.
  • Facility managers optimizing fire protection in warehouses, storage racks, and industrial buildings where early suppression and control mode sprinkler systems are employed.
  • Architects and consultants integrating fire suppression into building designs with complex ceiling and storage configurations.
  • Regulatory bodies and authorities setting national fire safety codes addressing automatic sprinkler installation.

Using this standard helps enhance fire safety performance by ensuring sprinkler systems are designed and installed to meet modern fire risk challenges, especially in high-challenge storage and industrial settings.

Related Standards

EN 12845-2:2024/prA1 is closely linked with several other standards essential for comprehensive fire protection system design:

  • EN 12845:2015 + A1:2019 – The core standard for fixed firefighting systems and automatic sprinkler system requirements, forming the basis for this amendment.
  • EN 17451 – Specifies testing and maintenance requirements applicable to fire sprinkler systems.
  • EN 12845-3 – Covers installation and design aspects complementary to part 2, offering broader guidance for automatic sprinkler systems.

Additionally, national standards and regulations may supplement or modify requirements in EN 12845-2 depending on country-specific fire safety legislation. Practitioners must consider those in conjunction with this European standard to ensure full compliance.


Keywords: EN 12845-2, ESFR sprinkler systems, CMSA sprinkler systems, automatic sprinkler design, firefighting systems, fire suppression, sprinkler installation, fire safety standards, fixed firefighting, sprinkler spacing, ceiling sprinkler requirements, fire protection design, CEN standards.

Draft

EN 12845-2:2025/oprA1:2026 - BARVE

English language
31 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

EN 12845-2:2024/prA1 is a draft published by the European Committee for Standardization (CEN). Its full title is "Fixed firefighting systems - Automatic sprinkler systems - Part 2: Design and installation of ESFR and CMSA sprinkler systems". This standard covers: This document specifies requirements for the design and installation of early suppression fast response (ESFR) and control mode specific application (CMSA) sprinklers in automatic sprinkler systems, in accordance with this standard and additionally the EN 12845 series of standards. This document does not cover all legislative requirements. NOTE In certain countries, specific national regulations can apply. Attention is drawn to the applicability or non-applicability for this document as specified by national responsible authorities.

This document specifies requirements for the design and installation of early suppression fast response (ESFR) and control mode specific application (CMSA) sprinklers in automatic sprinkler systems, in accordance with this standard and additionally the EN 12845 series of standards. This document does not cover all legislative requirements. NOTE In certain countries, specific national regulations can apply. Attention is drawn to the applicability or non-applicability for this document as specified by national responsible authorities.

EN 12845-2:2024/prA1 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 12845-2:2024/prA1 has the following relationships with other standards: It is inter standard links to EN 12845-2:2024. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase EN 12845-2:2024/prA1 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2026
Vgrajene naprave za gašenje - Avtomatski sprinklerski sistemi - 2. del:
Projektiranje in vgradnja sprinklerskih sistemov ESFR in CMSA - Dopolnilo A1
Fixed firefighting systems - Automatic sprinkler systems - Part 2: Design and installation
of ESFR and CMSA sprinkler systems
Ortsfeste Brandbekämpfungsanlagen - Automatische Sprinkleranlagen - Teil 2:
Auslegung und Installation von ESFR- und CMSA-Sprinklern
Installations fixes de lutte contre l'incendie - Systèmes d'extinction automatique du type
sprinkleur - Partie 2 : Conception et installation de système de sprinkleurs ESFR et
CMSA
Ta slovenski standard je istoveten z: EN 12845-2:2024/prA1
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

DRAFT
EUROPEAN STANDARD
EN 12845-2:2024
NORME EUROPÉENNE
EUROPÄISCHE NORM
prA1
December 2025
ICS 13.220.20
English Version
Fixed firefighting systems - Automatic sprinkler systems -
Part 2: Design and installation of ESFR and CMSA sprinkler
systems
Installations fixes de lutte contre l'incendie - Systèmes Ortsfeste Brandbekämpfungsanlagen - Automatische
d'extinction automatique du type sprinkleur - Partie 2 : Sprinkleranlagen - Teil 2: Auslegung und Installation
Conception et installation de système de sprinkleurs von ESFR- und CMSA-Sprinklern
ESFR et CMSA
This draft amendment is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 191.

This draft amendment A1, if approved, will modify the European Standard EN 12845-2:2024. If this draft becomes an
amendment, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for
inclusion of this amendment into the relevant national standard without any alteration.

This draft amendment was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12845-2:2024/prA1:2025 E
worldwide for CEN national Members.

Contents Page
European foreword . 4
1 Modification to the Introduction . 5
2 Modification to 3.1.1 “open-top containers” . 5
3 Modification to 3.1.6 “ceiling structural member” . 5
4 Modification to 5.1 “Sprinkler type, spacing, clearance and nominal operating
temperature” . 5
5 Modification to 5.1.1 “Sprinkler type” . 5
6 Modification to 5.1.3 “Sprinkler spacing, location and positioning relative to roof and
ceilings” . 5
7 Modification to 5.1.3.3 “CMSA sprinkler spacing and location” . 5
8 Modification to 5.1.3.5.3 “Unobstructed ceiling” . 5
9 Modification to 5.1.3.5.4 “Obstructed ceiling – Location of sprinkler in channels
ceiling” . 6
10 Modification to 5.1.3.7 “Vertical clearance below sprinklers” . 6
11 Modification to 5.2.1 . 6
12 Modification to 5.2.3 . 6
13 Modification to 5.2.4 . 6
14 Modification to 5.2.6.1. 6
15 Modification to 5.2.6.2. 7
16 Modification to 5.3.2 . 7
17 Modification to 5.3.3.1. 7
18 Modification to 5.3.3.2.1 . 7
19 Modification to 5.3.3.2.3 . 8
20 Modification to 5.3.3.2.4 . 8
21 Deletion of 5.4 . 9
22 Modification to 6.1 . 9
23 Modification to 6.4 . 9
24 Modification to 6.5 . 9
25 Modification to 6.6.1.1. 10
26 Modification to 6.6.1.2. 10
27 Modification to 6.6.2.1.1 . 11
28 Modification to 6.6.2.2.3 . 11
29 Modification to 6.6.2.2.5 . 11
30 Modification to 6.7.2 . 11
31 Modification to 6.8 . 12
32 Modification to Annex A . 12
European foreword
This document (EN 12845-2:2024/prA:2025) has been prepared by Technical Committee CEN/TC 191
“Fixed firefighting systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
1 Modification to the Introduction
Replace all instances of “head” or “heads” with “sprinkler” or “sprinklers”.
In the first subclause, in the third bracket, delete the word “sprinkler” after “although ESFR protection
schemes utilizing in-rack” to avoid a duplication of the word “sprinklers”.
“In comparison with EN 12845:2015+A1:2019, technical modifications have been made to integrate
references and usage of EN 17451, EN 12845-2 and EN 12845-3 into this document.”.
2 Modification to 3.1.1 “open-top containers”
Split Note 2 to entry after the first sentence. The second sentence shall become Note to entry 3. Renumber
the following Note to entry.
3 Modification to 3.1.6 “ceiling structural member”
Add the following new definition:
“3.1.6
ceiling structural member
solid ceiling structural member is one where its cross-sectional area in a vertical plane is less than 70 %
open”.
4 Modification to 5.1 “Sprinkler type, spacing, clearance and nominal operating
temperature”
In the heading of the clause delete the word “nominal”.
5 Modification to 5.1.1 “Sprinkler type”
Add after the first sentence the following:
“ESFR ceiling sprinklers may be used as in-rack sprinklers in accordance with 6.6.2.2.”.
In the third paragraph add “category of” before goods and storage type.
In the fourth paragraph, after Note 1, delete the word “nominal”.
In Note 2 delete all instances of “nominal”.
6 Modification to 5.1.3 “Sprinkler spacing, location and positioning relative to
roof and ceilings”
Delete “roof and” in the headline.
7 Modification to 5.1.3.3 “CMSA sprinkler spacing and location”
Replace in the second paragraph “the following” with “to any of the following”.
8 Modification to 5.1.3.5.3 “Unobstructed ceiling”
Add “any of” after “For ESFR and CMSA installation,”.
In the second line of the list add “ceiling” after “solid”.
Delete the third line of the list.
In the last two lines of the list replace “if solid” with “if all solid ceiling”.
9 Modification to 5.1.3.5.4 “Obstructed ceiling – Location of sprinkler in
channels ceiling”
In the first line of the first list add “ceiling” after “solid”.
In the second line of the first list add “ceiling” after “of the”.
In the title for Figure 2 add “ceiling” after “solid”.
In the second list update all instances of “solid structural member” to “solid ceiling structural member”.
In the last sentence of the clause add “ceiling” after “solid”.
10 Modification to 5.1.3.7 “Vertical clearance below sprinklers”
Add “the level of” after “space between”.
11 Modification to 5.2.1
Change title to “Ceiling slope”.
12 Modification to 5.2.3
Change the second sentence to:
“Skylights with a surface greater than 3 m or height above 0,5 m measured above the normal ceiling
level shall be sprinkler protected.”.
Replace the second paragraph with:
“If plastic skylights will be installed, Figure 3 or Figure 4 shall be applied for acceptable ceiling-level
sprinkler arrangements.”.
For Figure 3, change Key 1 to “ceiling level sprinklers in elevation view”, Key 4 to “Supplemental sprinklers
under plastic skylights in elevation view”, Key 6 to “Ceiling level sprinklers in plan view” and Key 7 to
“Supplemental sprinklers under plastic skylights in plan view”.
Update the sentence above Figure 3 title and below Keys for Figure 3 by adding “under plastic skylights”
after “The supplemental sprinklers”.
For Figure 4, change Key 2 to “Ceiling level sprinkler in elevation view”, Key 6 to “Supplemental sprinklers
under plastic skylights at the same elevation as ceiling sprinklers in elevation view”, Key 7 to “Ceiling level
sprinklers in plan view” and Key 8 to “Supplemental sprinklers under plastic skylights at the same
elevation as ceiling sprinklers in plan view”.
Update the sentence above Figure 4 title and below Keys for Figure 4 by adding “under plastic skylights”
after “Supplemental sprinkler”.
13 Modification to 5.2.4
nd
In the list delete “nominal” in the 2 entry. Change also “; or” to “.”.
Delete the third entry of the list.
14 Modification to 5.2.6.1
th
Delete “nominal” in the 5 paragraph.
In the formula replace “1/2” with “0,5 ×”.
Replace Figure 7 with the following:

”.
Change Key 3 of Figure 7 to “Ceiling sprinkler”.
15 Modification to 5.2.6.2
rd
Change in the list the 3 line to the following:
“Option 3: For a wet sprinkler system, the design shall increase the number of sprinklers by 30 % rounded
up for uneven results.”.
16 Modification to 5.3.2
Add to the title of Figure 11 “ceiling” before “structural members”.
In the last paragraph of the clause add “ceiling” before “structural member”.
17 Modification to 5.3.3.1
Replace the second sentence with the following:
“Under these conditions the width of the grouped obstruction shall be considered the width of both
objects’ and the smallest of the two widths used plus the horizontal distance between them (see
Figure 12).”.
rd
In the 3 sentence add “smallest” before “objects least dimension”. Delete also “least” in the same instance.
18 Modification to 5.3.3.2.1
In the keys for Figure 13 delete “head” in the entry for X. In the title for Figure 13 replace “ESFR” with “ESFR
and CMSA”.
19 Modification to 5.3.3.2.3
Replace Figure 15 a) with the following:

”.
20 Modification to 5.3.3.2.4
Replace Figure 16 with the following:

”.
Above Figure 17 add the following text:
“For flat, solid, grouped objects that fulfils the requirement H < (3 x A); A + B > 0,6 m (see Figure 17 and
18), additional sprinklers shall be installed under the objects in accordance with Figure 17 and or
Figure 18.”.
For the keys of Figure 17 update Key 3 to “width of object A” and Key 4 to “width of object B”. Delete the
formula below the keys of Figure 17 and above the title of Figure 17.
For the keys of Figure 18 update Key 3 to “width of object A” and Key 4 to “width of object B”. Delete the
formula below the keys of Figure 18 and above the title of Figure 18.
21 Deletion of 5.4
Delete the whole clause.
22 Modification to 6.1
After the first paragraph add the following:
“Designs given in this document shall only be applied for STC1, STC3 and STC4 unless specified differently
in the corresponding clauses. The additional design requirements given in Table A.2 for the specific STC’s
shall be applied.”.
Update the second paragraph to:
“All required longitudinal flue spaces shall be no less than 150 mm. All required transverse flue spaces
shall be no less than 100 mm.”.
rd
In the 3 paragraph delete the word “loading”.
th
Update the 6 paragraph to:
“The design criteria for a given k-factor at a specific ceiling and storage height may be applied to a lower
ceiling and/or storage height, provided no other parameters changed.”.
23 Modification to 6.4
In Table 6 replace the shape of design for 10 ceiling sprinklers to “3 × 3+ 1 × 1”.
In Table 6 replace the current entry for 15 ceiling sprinklers with “14” and update the shape of design to
“4 × 3+2 × 1”.
In Table 6 replace the current entry for 16 ceiling sprinklers with “15” and update the shape of design to
“5 × 3”.
In Table 6 add a new line before 20 ceiling sprinklers with the following entries for the line “16”, “90” and
“5 × 3+1 × 1”.
24 Modification to 6.5
st
In the last paragraph in the 1 sentence add “in the water discharged from the sprinkler” at the end of the
sentence.
25 Modification to 6.6.1.1
st
In the 1 paragraph replace the word “heads” with “sprinklers”.
Change all instances of “18 kg” to “18 kg/100 m ”.
nd th
In the heading of Table 7 delete “/ roof” in the 2 column and “for 12 sprinklers in operation” in the 4 .
d th
In Table 7, in the line for HHS5 add footnote behind 4,1 in the 7 column.
In Table 7 in footnote d replace “deflector” with “thermal element”.
Replace all text after Table 7 and before Table 8 with the following:
“For HHS5 with 12 sprinkler design the following requirements shall be applied. Sprinklers shall be
intermediate temperature rated (79 °C to 107 °C) ESFR pendent sprinklers with a k-factor of K360. The
maximum sprinkler thermal element distance below the ceiling shall be 325 mm.
The minimum aisle width between two adjacent racks shall be 2,4 m. The rack shall have a solid vertical
barrier of 10 mm plywood or particleboard, or 0,8 mm sheet metal, or equivalent, from face of rack to
face of rack, spaced at a maximum of 5,0 m intervals. The vertical barrier shall extend from a maximum
of 100 mm above the floor to the maximum storage height. The plan area of storage between vertical
barriers and aisles shall not exceed 12 m2. The vertical barrier shall extend across the longitudinal flue.
The commodity shall be permitted to extend a 100 mm beyond the vertical barrier at the aisle.”.
th
In the heading of Table 8 and Table 9 delete “Nominal” in the 4 column.
26 Modification to 6.6.1.2
nd
Replace the 2 sentence with:
“The requirements given in 5.2.6.1 shall be applied for all designs given in this clause.”.
rd
In the 3 sentence change the reference to “5.3.3.2.3”.
Replace Figure 23 with the following:

”.
In the list below Figure 23 in b) add “ceiling” after “solid”. In c), d) and f) add in all cases “ceiling” after
“solid”.
27 Modification to 6.6.2.1.1
For Figure 25 update Key 3 to “Face of rack”.
28 Modification to 6.6.2.2.3
st rd
In the 1 sentence delete the word “nominal”. In the 3 sentence add “ceiling” before “structural”.
29 Modification to 6.6.2.2.5
st
In the 1 sentence delete all brackets and their content.
30 Modification to 6.7.2
Change heading to “Special consideration to be used for dry-pipe and pre-action systems”.
st
In the 1 sentence delete the word “nominal”.
nd
In the 2 paragraph delete “or interlocked systems”.
Above Figure 32 add “ceiling” after “solid” in both instances.
31 Modification to 6.8
Add the following new clause:
“6.8 Special designs
6.8.1 General
The following special designs provide alternative protection solutions for specific storage configurations
and conditions.
6.8.2 Ceiling only sprinkler protection for mini load
If Mini load systems are installed with existing ceiling protection no additional in-rack sprinklers are
needed, if the following conditions are met:
— storage height is less than 3 m;
— ceiling height is less than 6,0 m;
— commodity class of the boxes and its content is max. HHS4;
— block storage area shall be limited to 25 m separated by aisle 1,5 m;
— only wet systems shall be used.
Table 21 — Allowable ceiling only designs for mini loads without in-rack sprinkler protection
Maximum Pendent ESFR 74 °C for 60 min water
Maximum CMSA
ceiling supply duration
storage
height in
height in m
K200 K240 K320 K360 K240
m
12 @ 12 @1,7 12 @ 12 @ 25 @
3 4,5
2,4 bar bar 1,0 bar 1,0 bar 1,5 bar
12 @ 12 @ 12 @ 12 @
3 6,0 -
3,4 bar 2,4 bar 1,4 bar 1,4 bar
”.
32 Modification to Annex A
st
Replace the 1 sentence with the following:
“Table A.3 shall be used to determine the HHS classes. If not covered by Table A.3, Figure A.1, which taken
from prEN 12845-1 and updated to give information about evaluating the HHS classes, shall be used.”.
Add the following new Table A.2 after Table A.1:

Table A.2 — Description and requirements of storage types and configurations 1 to 4
Similar ST class
Desig- Storage Additional
Description from
nation configuration requirement
EN 12845:2015
On-floor storage, When using Table 10
without pallets or other storage block area
material handling shall be limited to
devices. Unit loads are
150 m .
Solid pile
placed on top of each
When necessary to
other, leaving no
extend above 150 m
horizontal spaces
up to 250 m , the
between unit loads.
area of operation in
Table 10 shall be
STC1 ST1
increased
A storage arrangement
proportionally (e.g.
that consists of product
30 % increased block
stored on pallets. Pallet
area requires 30 %
Palletized
loads are placed one on
larger area of
storage
top of another with the
opera
...