C01.11 - Masonry Cement
Masonry Cement
General Information
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Section 15. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.2)
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of masonry cement for use where mortar for masonry is required. Masonry cement shall conform to the applicable physical property requirements prescribed. The masonry cement shall be sampled in accordance with practice C 183. The temperature and relative humidity of the air in the vicinity of the mixing slab and dry materials, molds, base plates, and mixing bowl shall conform to the requirements of test method C 109/C 109M. Determine normal consistency by the Vicat apparatus in accordance with test method C 187. Determine autoclave expansion in accordance with test method C 151. Determine the time of setting by the Gillmore needle method in accordance with test method C 266. Determine the density of the masonry cement in accordance with test method C 188, using kerosene as the liquid. The sand shall be a blend of equal parts by weight of graded standard sand and standard 20-30 sand conforming to specification C 778. The compressive testing procedures for mortars are presented. Water retention shall be determined in accordance with the procedures in test method C 1506.
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 15 and 16 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)2
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers plastic cements for use in Portland cement-based plasters for exterior (stucco) and interior applications. All the materials should be tested and conform to the required values of fineness, autoclave expansion, time of setting, compressive strength, air content of mortar, and water retention. The cement should be stored in a way that permits easy access and inside a suitable weathertight building.
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 13 and 14. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)2
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers plastic cements for use in Portland cement-based plasters for exterior (stucco) and interior applications. All the materials should be tested and conform to the required values of fineness, autoclave expansion, time of setting, compressive strength, air content of mortar, and water retention. The cement should be stored in a way that permits easy access and inside a suitable weathertight building.
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 14 and 15. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. (Warning— Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)2
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of masonry cement for use where mortar for masonry is required. Masonry cement shall conform to the applicable physical property requirements prescribed. The masonry cement shall be sampled in accordance with practice C 183. The temperature and relative humidity of the air in the vicinity of the mixing slab and dry materials, molds, base plates, and mixing bowl shall conform to the requirements of test method C 109/C 109M. Determine normal consistency by the Vicat apparatus in accordance with test method C 187. Determine autoclave expansion in accordance with test method C 151. Determine the time of setting by the Gillmore needle method in accordance with test method C 266. Determine the density of the masonry cement in accordance with test method C 188, using kerosene as the liquid. The sand shall be a blend of equal parts by weight of graded standard sand and standard 20-30 sand conforming to specification C 778. The compressive testing procedures for mortars are presented. Water retention shall be determined in accordance with the procedures in test method C 1506.
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 16 and 17 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)2
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Section 16. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.2)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Section 16. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.2)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Section 16. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.2)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers plastic cements for use in Portland cement-based plasters for exterior (stucco) and interior applications. All the materials should be tested and conform to the required values of fineness, autoclave expansion, time of setting, compressive strength, air content of mortar, and water retention. The cement should be stored in a way that permits easy access and inside a suitable weathertight building.
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard , of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 14 and 15. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (WarningFresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard , of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Section 16. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (WarningFresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure. )
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of masonry cement for use where mortar for masonry is required. Masonry cement shall conform to the applicable physical property requirements prescribed. The masonry cement shall be sampled in accordance with practice C 183. The temperature and relative humidity of the air in the vicinity of the mixing slab and dry materials, molds, base plates, and mixing bowl shall conform to the requirements of test method C 109/C 109M. Determine normal consistency by the Vicat apparatus in accordance with test method C 187. Determine autoclave expansion in accordance with test method C 151. Determine the time of setting by the Gillmore needle method in accordance with test method C 266. Determine the density of the masonry cement in accordance with test method C 188, using kerosene as the liquid. The sand shall be a blend of equal parts by weight of graded standard sand and standard 20-30 sand conforming to specification C 778. The compressive testing procedures for mortars are presented. Water retention shall be determined in accordance with the procedures in test method C 1506.
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 Units—The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in Standard , of measurements made in other units. Values are stated in only SI units when inch-pound units are not used in practice.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 16 and 17 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (WarningFresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers plastic cements for use in Portland cement-based plasters for exterior (stucco) and interior applications. All the materials should be tested and conform to the required values of fineness, autoclave expansion, time of setting, compressive strength, air content of mortar, and water retention. The cement should be stored in a way that permits easy access and inside a suitable weathertight building.
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 14 and 15. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of masonry cement for use where mortar for masonry is required. Masonry cement shall conform to the applicable physical property requirements prescribed. The masonry cement shall be sampled in accordance with practice C 183. The temperature and relative humidity of the air in the vicinity of the mixing slab and dry materials, molds, base plates, and mixing bowl shall conform to the requirements of test method C 109/C 109M. Determine normal consistency by the Vicat apparatus in accordance with test method C 187. Determine autoclave expansion in accordance with test method C 151. Determine the time of setting by the Gillmore needle method in accordance with test method C 266. Determine the density of the masonry cement in accordance with test method C 188, using kerosene as the liquid. The sand shall be a blend of equal parts by weight of graded standard sand and standard 20-30 sand conforming to specification C 778. The compressive testing procedures for mortars are presented. Water retention shall be determined in accordance with the procedures in test method C 1506.
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion of measurements made in other units, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 16 and 17 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.(Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
ABSTRACT
This specification covers three types of mortar cement for use where mortar for masonry is required. Mortar cements are classified as Type N, S, or M, according to the prescribed physical requirements. Mortar cement shall conform to the prescribed requirements such as fineness, autoclave expansion, time of setting, compressive strength, flexural bond strength, air content of mortar, and water retention. Test specimens shall undergo molding and storage before conducting the procedures in the required test methods.
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Annex A1. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Annex A1. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 14 and 15. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion of measurements made in other units, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 16 and 17 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.(Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Annex A1. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification7 pagesEnglish language
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Annex A1. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.²)
- Technical specification7 pagesEnglish language
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion of measurements made in other units, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 17 and 18 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning-—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10, of measurements made in other units.
1.3 The text of this standard refers to notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 15 and 16. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Warning—Fresh hydraulic cementitious mixtures are caustic and may cause chemical burns to skin and tissue upon prolonged exposure.)²
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion of measurements made in other units, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 17 and 18 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Technical specification6 pagesEnglish language
SCOPE
1.1 This specification covers three types of masonry cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion of measurements made in other units, using the Rules for Conversion and Rounding given in IEEE/ASTM SI 10.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.4 The following safety hazards caveat pertains only to Sections 17 and 18 of this specification. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Technical specification6 pagesEnglish language
SCOPE
1.1 This specification covers two types of plastic cement for use in portland cement-based plasters for exterior (stucco) and interior application.
1.2 The values stated in SI units are to be regarded as the standard.
1.3 The text of this standard refers to notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of this standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Technical specification4 pagesEnglish language
SCOPE
1.1 This specification covers three types of mortar cement for use where mortar for masonry is required.
1.2 The values stated in SI units are to be regarded as the standard.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
- Technical specification7 pagesEnglish language
Frequently Asked Questions
C01.11 is a Technical Committee within ASTM International. It is named "Masonry Cement". This committee has published 25 standards.
C01.11 develops ASTM standards in the area of Information technology. Currently, there are 25 published standards from this technical committee.
ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.
A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.