SIST HD 60364-4-43:2023/kFprAA:2026
(Amendment)Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
- Abstract
IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
- Status
- Not Published
- Public Enquiry End Date
- 30-Jul-2025
- Technical Committee
- ELI - Electrical and communication installations
- Current Stage
- 5020 - Formal vote (FV) (Adopted Project)
- Start Date
- 10-Sep-2026
- Due Date
- 29-Oct-2026
- Completion Date
- 10-Sep-2026
SIST HD 60364-4-43:2023/kFprAA:2026 is a draft amendment to the CENELEC Harmonization Document HD 60364-4-43:2023 for low-voltage electrical installations. It specifies how to protect live conductors, PEN conductors, PEM conductors and PEL conductors against overcurrent, and it adds rules for where overload and short-circuit protective devices are installed.
What does SIST HD 60364-4-43:2023/kFprAA:2026 specify?
SIST HD 60364-4-43:2023/kFprAA:2026 modifies the overcurrent protection part of Low-voltage electrical installations. It focuses on protection against overload current and short-circuit currents, and on how those protective measures are coordinated in practice.
The amendment is organized as:
- a change to Subclause 431.4 on overload current,
- a change to Subclause 431.5 on short-circuit currents,
- a new normative Annex G on the position of overcurrent protection devices,
- special national conditions and A-deviations in the national annexes.
| Annex | What it covers |
|---|---|
| G (normative) | Position of overcurrent protection devices for overload and short-circuit protection |
| ZB (normative) | Special national conditions |
| ZC (informative) | A-deviations |
What are the key requirements of SIST HD 60364-4-43:2026?
SIST HD 60364-4-43:2023/kFprAA:2026 makes the location of overcurrent protective devices part of the requirement, not just their presence. In practice, designers have to check where the conductor changes, where the risk changes, and whether an exception is allowed.
Overload protection follows Annex G
Subclause 431.4 now points to Annex G for the positioning of devices that protect against overload current. This means the device location has to be checked against the conductor route, not chosen only by convenience.
Short-circuit protection also follows Annex G
Subclause 431.5 now points to Annex G for the positioning of short-circuit protective devices. In practice, the short-circuit protective device has to match the conductor’s withstand capability along the circuit.
Devices are normally placed at the origin of each circuit
Annex G starts from the rule that overload and/or short-circuit protective devices are installed at the origin of each circuit unless an exception applies. This gives a clear default for circuit design and panel layout.
Changes in current-carrying capacity trigger overload protection
Where the current-carrying capacity of conductors decreases, overload protection is required at that point unless one of the allowed exceptions applies. The document gives examples such as changes in conductor size, material, insulation, installation method, external influences, or grouping of conductors.
Short-circuit protection follows changes in withstand capability
Annex G requires short-circuit protection at the point where the conductor’s let through energy withstand capability (k2S2) is reduced, unless an exception applies. This helps prevent damage when a conductor segment has lower short-circuit tolerance than the rest of the circuit.
Exceptions are tightly limited
The annex allows exceptions only under defined conditions, such as short protected runs, no branch circuits or socket-outlets in the affected section, and reduced risk of short-circuit, fire, or injury. The text also excludes these exceptions in locations presenting a fire risk or risk of explosion.
Special cases are covered for some systems and supply arrangements
Annex G includes cases where overload or short-circuit devices may be omitted because protection is already provided on the supply side, because the distributor accepts the arrangement, or, in IT systems without a neutral conductor, because a residual current protective device is installed in each circuit. For an engineer, this means the protection concept has to be checked as a whole, not device by device.
What terms does SIST HD 60364-4-43:2023/kFprAA:2026 define?
- Current-carrying capacity - the conductor capability that drives where overload protection must be placed.
- Overload current - current that can heat conductors and create harmful effects over time.
- Short-circuit current - fault current that can create severe thermal and mechanical stress.
- Let through energy withstand capability (k2S2) - the conductor’s ability to withstand short-circuit energy before the protective device clears the fault.
- Special national conditions - national characteristics or practices that cannot be changed even over a long period.
- A-deviations - national deviations due to regulations outside the competence of the CENELEC national member.
- IT systems - a supply arrangement specifically treated in the overload protection exceptions.
- Residual current protective device - a device used in one of the IT system exceptions for overload protection.
Who uses SIST HD 60364-4-43:2023/kFprAA:2026?
This document is used by electrical designers, installers, panel builders, inspectors, quality managers and buyers who need to specify or check low-voltage protection arrangements. It is relevant in buildings, industrial installations and electricity supply systems where conductor protection and device placement must be coordinated.
It is especially useful when deciding:
- where to locate protective devices in a circuit,
- whether a conductor segment needs separate overload or short-circuit protection,
- whether an exception is allowed,
- how national conditions affect the design.
What changed in SIST HD 60364-4-43:2023/kFprAA:2026 from the previous edition?
The underlying HD 60364-4-43:2023 is described as a technical revision that cancels and replaces the 2008 third edition. The scope identifies these main changes:
- the document was restructured,
- automatic disconnection of supply was designated as the preferred overcurrent measure,
- other overcurrent measures were moved to normative annexes for restricted applications,
- a new terms and definitions clause was added,
- new requirements were added for neutral or mid-point conductors, including cases with triplen harmonics.
Which standards are used with SIST HD 60364-4-43:2026?
The national condition for Germany refers to IEC 60364-5-53:2019/AMD1:2020 and HD 60364-5-53:2015/A11:2017. These references matter because they affect how related protection requirements are applied in the German special national condition.
The Italian national condition refers to CEI 0-21 for prospective short-circuit currents at a grid supply point.
What does the SIST HD 60364-4-43:2026 document contain?
The amendment text contains the European foreword, the two modified subclauses on overload and short-circuit currents, and the new normative Annex G. Annex G is the practical core of the document: it gives the general rule, the overload-protection positioning rules, and the short-circuit-protection positioning rules.
It also contains annexes on special national conditions and A-deviations, with country-specific notes. In practice, those annexes are used when applying the document in national implementations and when checking whether a local rule changes the default harmonized requirement.
Relations
- Effective Date
- 09-Apr-2024
Get Certified
Connect with accredited certification bodies for this standard
DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

IMQ S.p.A. (Certification)
Italian electrical product certification.
Sponsored listings
Frequently Asked Questions
SIST HD 60364-4-43:2023/kFprAA:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent". This standard covers: IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
SIST HD 60364-4-43:2023/kFprAA:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST HD 60364-4-43:2023/kFprAA:2026 has the following relationships with other standards: It is inter standard links to SIST HD 60364-4-43:2023. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
SIST HD 60364-4-43:2023/kFprAA:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
SIST HD 60364-4-43:2023/oprAA:2025
01-julij-2025
Nizkonapetostne električne inštalacije - 4-43. del: Zaščitni ukrepi - Zaščita pred
nadtoki - Dopolnilo AA
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against
overcurrent
Errichten von Niederspannungsanlagen - Teil 4-43: Schutzmaßnahmen - Schutz bei
Überstrom
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité
- Protection contre les surintensités
Ta slovenski standard je istoveten z: HD 60364-4-43:2023/prAA:2025
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
SIST HD 60364-4-43:2023/oprAA:2025 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
SIST HD 60364-4-43:2023/oprAA:2025
SIST HD 60364-4-43:2023/oprAA:2025
HARMONIZATION DOCUMENT DRAFT
HD 60364-4-43:2023
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT
prAA
June 2025
ICS 91.140.50; 29.120.50 -
English Version
Low-voltage electrical installations - Part 4-43: Protection for
safety - Protection against overcurrent
Installations électriques à basse tension - Partie 4-43: Errichten von Niederspannungsanlagen - Teil 4-43:
Protection pour assurer la sécurité - Protection contre les Schutzmaßnahmen - Schutz bei Überstrom
surintensités
This draft amendment prAA, if approved, will modify the Harmonization Document HD 60364-4-43:2023; it is submitted to CENELEC
members for enquiry.
Deadline for CENELEC: 2025-08-29.
It has been drawn up by CLC/TC 64.
If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for implementation of this amendment on a national level.
This draft amendment, was established by CENELEC in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a Harmonization Document. It is distributed for review and comments. It is subject to change without notice
and shall not be referred to as a Harmonization Document.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 79835 Ref. No. HD 60364-4-43:2023/prAA:2025 E
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
Contents Page
1 European foreword . 3
2 1 Modification to Subclause 431.4, “Protection against overload current” . 4
3 2 Modification to Subclause 431.5, “Protection against short-circuit currents” . 4
4 3 Addition of Annex G, “Position of overcurrent protection devices” . 4
5 Annex G (normative) Position of overcurrent protection devices. 5
6 G.1 General . 5
7 G.2 Positioning of devices for overload protection . 5
8 G.3 Positioning of devices for short-circuit protection . 6
9 4 Addition of Annex ZB, “Special national conditions” and Annex ZC, “A-deviations” . 6
10 Annex ZA (normative) Special national conditions. 7
11 Annex ZB (informative) A-deviations . 8
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
12 European foreword
13 This document (HD 60364-4-43:2023/prAA:2025) has been prepared by CLC/TC 64 “Electrical installations
14 and protection against electric shock”.
15 This document is currently submitted to the Enquiry.
16 The following dates are proposed:
• latest date by which the existence of this (doa) dav + 6 months
document has to be announced at national
level
• latest date by which this document has to be (dop) dav + 12 months
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) dav + 36 months
conflicting with this document have to be (to be confirmed or
withdrawn modified when voting)
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
17 1 Modification to Subclause 431.4, “Protection against overload current”
18 In 431.4.1, add the following paragraph:
19 “The positioning of overcurrent protective devices for protection against overload currents shall meet the
20 requirements provided in Annex G.”
21 2 Modification to Subclause 431.5, “Protection against short-circuit currents”
22 In 431.5.1, replace Note 1 with the following paragraph:
23 “The positioning of overcurrent protective devices for protection against short-circuit currents shall meet the
24 requirements provided in Annex G.”
25 3 Addition of Annex G, “Position of overcurrent protection devices”
26 Add the following new normative Annex G:
27 “
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
28 Annex G
29 (normative)
31 Position of overcurrent protection devices
32 G.1 General
33 Devices for overload and/or short-circuit protection shall be installed at the origin of each circuit unless the
34 exceptions of G.2 and/or G.3 are applied.
35 G.2 Positioning of devices for overload protection
36 G.2.1 A device for protection against overload shall be placed at each point where there is a reduction in the
37 value of current-carrying capacity of the conductors except where A.2, G.2.2, G.2.3, or G.2.4 apply. The
38 requirements in G.2.2 to G.2.4 shall not be applied to installations situated in locations presenting a fire risk or
39 risk of explosion.
40 NOTE A reduc
...