HD 60364-4-43:2023/FprAA:2026
(Amendment)Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent
- Abstract
IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
- Status
- Not Published
- Publication Date
- 03-Jan-2027
- Technical Committee
- CLC/TC 64 - Electrical installations and protection against electric shock
- Current Stage
- 5020 - Vote circulated - Formal Approval
- Start Date
- 04-Sep-2026
- Due Date
- 20-May-2026
- Completion Date
- 04-Sep-2026
HD 60364-4-43:2023/FprAA:2026 is a CENELEC draft amendment to the low-voltage electrical installations rules for protection against overcurrent. It updates the guidance for protecting live conductors, PEN conductors, PEM conductors and PEL conductors, and for coordinating overcurrent protective measures in electrical installations.
This draft amendment is being prepared by CLC/TC 64 and, if approved, it will modify HD 60364-4-43:2023. It is aimed at people who design, install, check or specify low-voltage installations and the overcurrent protective devices used in them.
What does HD 60364-4-43:2023/FprAA:2026 specify?
HD 60364-4-43:2023/FprAA:2026 specifies how overcurrent protection devices are positioned for overload and short-circuit protection in low-voltage installations. The amendment also adds national annex material for special national conditions and A-deviations.
The document is organized as:
- amendments to Subclause 431.4, “Protection against overload current”
- amendments to Subclause 431.5, “Protection against short-circuit currents”
- a new normative Annex G on the position of overcurrent protection devices
- annex material for special national conditions and A-deviations
| Annex | What it covers |
|---|---|
| Annex G | Position of overcurrent protection devices |
| Special national conditions | Country-specific conditions that affect harmonization |
| A-deviations | National deviations linked to local regulations |
What are the key requirements of HD 60364-4-43:2026?
HD 60364-4-43:2026 ties the placement of overload and short-circuit protective devices to Annex G. In practice, this means designers must check where a device sits in the circuit, not only which device is selected.
Overload protection
For overload protection, devices are generally placed at the origin of each circuit unless an exception applies. Annex G says a device should also be placed where the current-carrying capacity of the conductors is reduced, unless one of the stated exceptions is used. This matters when conductor size, material, insulation, installation method, external influences or grouping change along a run.
The amendment also allows some exceptions where the conductor is already effectively protected upstream, or where the distributor provides overload protection at the origin and agrees that it protects the relevant part of the installation. In IT systems without a neutral conductor, the overload protective device may be omitted in one line conductor if a residual current protective device is installed in each circuit.
Short-circuit protection
For short-circuit protection, the device is normally placed where the conductor’s let-through energy withstand capability, expressed as k2S2, is reduced. Annex G also allows alternative placement when the run section is short, has no branch circuit or socket-outlet, and is installed to minimize short-circuit and fire risk.
A protective device may also be installed on the supply side of the point of reduced k2S2 if its operating characteristic still protects the wiring downstream against short-circuit. This is important for coordination studies and for selecting devices with the right trip behavior.
Safety limits on exceptions
The special positioning exceptions in Annex G do not apply to installations in locations with a fire risk or risk of explosion. That means the more flexible placement rules cannot be used where the consequences of a fault would be more severe.
What the amendment changes in the clauses
The amendment updates Subclause 431.4.1 and Subclause 431.5.1 so that the positioning of overcurrent protective devices must meet Annex G. In practice, Annex G becomes the central reference for deciding where overload and short-circuit protection may be installed.
What terms does HD 60364-4-43:2026 define?
- Overcurrent - current above the intended value in a circuit, which the document treats as the condition that protection must manage.
- Overload current - a type of overcurrent linked to excessive load rather than a fault, so protection focuses on thermal stress.
- Short-circuit current - fault current caused by a low-impedance path, which drives fast protective disconnection.
- Current-carrying capacity - the amount of current a conductor can carry without exceeding its permitted limits.
- Let-through energy withstand capability (k2S2) - the conductor’s ability to withstand the energy from a short-circuit until the protective device operates.
- Residual current protective device - a device used in the document as part of certain overload-protection exceptions in IT systems.
- PEN conductor / PEM conductor / PEL conductor - conductor types explicitly named in the scope and included in the protection rules for live conductors.
Who uses HD 60364-4-43:2026?
HD 60364-4-43:2026 is used by electrical designers, installers, inspectors, and technical reviewers working on low-voltage electrical installations. It is also relevant to manufacturers and specifiers of fuses, circuit-breakers and other overcurrent protection devices.
It matters for building services, industrial installations and electricity supply systems where protection has to be coordinated with conductor sizing, circuit layout and fire or explosion risk. Buyers and quality managers use it to check whether a proposed installation concept places protective devices in acceptable positions.
What changed in HD 60364-4-43:2026 from the previous edition?
The underlying HD 60364-4-43:2023 is described as a technical revision of the third edition published in 2008. The scope states that the document was restructured, that automatic disconnection of supply was designated as the preferred protection measure, that other measures were moved into normative annexes, that a new terms-and-definitions clause was added, and that new requirements were added for neutral or mid-point conductors with and without triplen harmonics.
Which standards are used with HD 60364-4-43:2026?
The amendment refers to IEC 60364-5-53:2019, IEC 60364-5-53:2019/AMD1:2020, HD 60364-5-53:2015/A11:2017, and CEI 0-21. Annex ZB uses CEI 0-21 for Italy’s maximum and minimum prospective short-circuit currents at a grid supply point. The other named documents appear in the national-condition material and related cross-references.
What does the HD 60364-4-43:2026 document contain?
This amendment contains clause-by-clause wording changes, not a full rewrite of the base standard. It includes the revised text for overload and short-circuit protection, plus the new Annex G on device positioning.
It also includes annex material on special national conditions and A-deviations for national implementation. For readers, the practical value is in the placement rules, the exceptions to those rules, and the national notes that can affect application in specific countries.
Relations
- Effective Date
- 09-Apr-2024
Get Certified
Connect with accredited certification bodies for this standard
DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

IMQ S.p.A. (Certification)
Italian electrical product certification.
Sponsored listings
Frequently Asked Questions
HD 60364-4-43:2023/FprAA:2026 is a draft published by CLC. Its full title is "Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against overcurrent". This standard covers: IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
IEC 60364-4-43:2023 provides requirements for: - protection of live conductors, PEN conductors, PEM conductors, and PEL conductors against the harmful effects caused by overcurrent; - coordination of measures for protection against overcurrent. This fourth edition cancels and replaces the third edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) the standard has been restructured, see Table 1 (Correspondence between IEC 60364‑4‑43:2008 and this document) below; b) the measure "automatic disconnection of supply" has been designated as the preferred measure for protection against overcurrent; c) all measures except the measure "automatic disconnection of supply" have been transferred into new normative annexes to indicate that these measures are usable in certain applications and under certain restricted conditions only (see Annex A, Annex B and Annex E); d) a new clause "Terms and definitions" has been added; e) new requirements have been added for the protection of the neutral or mid-point conductor (with and without triplen harmonics).
HD 60364-4-43:2023/FprAA:2026 is classified under the following ICS (International Classification for Standards) categories: 29.120.50 - Fuses and other overcurrent protection devices; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
HD 60364-4-43:2023/FprAA:2026 has the following relationships with other standards: It is inter standard links to HD 60364-4-43:2023. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
HD 60364-4-43:2023/FprAA:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
SIST HD 60364-4-43:2023/oprAA:2025
01-julij-2025
Nizkonapetostne električne inštalacije - 4-43. del: Zaščitni ukrepi - Zaščita pred
nadtoki - Dopolnilo AA
Low-voltage electrical installations - Part 4-43: Protection for safety - Protection against
overcurrent
Errichten von Niederspannungsanlagen - Teil 4-43: Schutzmaßnahmen - Schutz bei
Überstrom
Installations électriques à basse tension - Partie 4-43: Protection pour assurer la sécurité
- Protection contre les surintensités
Ta slovenski standard je istoveten z: HD 60364-4-43:2023/prAA:2025
ICS:
29.120.50 Varovalke in druga Fuses and other overcurrent
nadtokovna zaščita protection devices
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
SIST HD 60364-4-43:2023/oprAA:2025 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
SIST HD 60364-4-43:2023/oprAA:2025
SIST HD 60364-4-43:2023/oprAA:2025
HARMONIZATION DOCUMENT DRAFT
HD 60364-4-43:2023
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT
prAA
June 2025
ICS 91.140.50; 29.120.50 -
English Version
Low-voltage electrical installations - Part 4-43: Protection for
safety - Protection against overcurrent
Installations électriques à basse tension - Partie 4-43: Errichten von Niederspannungsanlagen - Teil 4-43:
Protection pour assurer la sécurité - Protection contre les Schutzmaßnahmen - Schutz bei Überstrom
surintensités
This draft amendment prAA, if approved, will modify the Harmonization Document HD 60364-4-43:2023; it is submitted to CENELEC
members for enquiry.
Deadline for CENELEC: 2025-08-29.
It has been drawn up by CLC/TC 64.
If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for implementation of this amendment on a national level.
This draft amendment, was established by CENELEC in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a Harmonization Document. It is distributed for review and comments. It is subject to change without notice
and shall not be referred to as a Harmonization Document.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Project: 79835 Ref. No. HD 60364-4-43:2023/prAA:2025 E
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
Contents Page
1 European foreword . 3
2 1 Modification to Subclause 431.4, “Protection against overload current” . 4
3 2 Modification to Subclause 431.5, “Protection against short-circuit currents” . 4
4 3 Addition of Annex G, “Position of overcurrent protection devices” . 4
5 Annex G (normative) Position of overcurrent protection devices. 5
6 G.1 General . 5
7 G.2 Positioning of devices for overload protection . 5
8 G.3 Positioning of devices for short-circuit protection . 6
9 4 Addition of Annex ZB, “Special national conditions” and Annex ZC, “A-deviations” . 6
10 Annex ZA (normative) Special national conditions. 7
11 Annex ZB (informative) A-deviations . 8
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
12 European foreword
13 This document (HD 60364-4-43:2023/prAA:2025) has been prepared by CLC/TC 64 “Electrical installations
14 and protection against electric shock”.
15 This document is currently submitted to the Enquiry.
16 The following dates are proposed:
• latest date by which the existence of this (doa) dav + 6 months
document has to be announced at national
level
• latest date by which this document has to be (dop) dav + 12 months
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) dav + 36 months
conflicting with this document have to be (to be confirmed or
withdrawn modified when voting)
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
17 1 Modification to Subclause 431.4, “Protection against overload current”
18 In 431.4.1, add the following paragraph:
19 “The positioning of overcurrent protective devices for protection against overload currents shall meet the
20 requirements provided in Annex G.”
21 2 Modification to Subclause 431.5, “Protection against short-circuit currents”
22 In 431.5.1, replace Note 1 with the following paragraph:
23 “The positioning of overcurrent protective devices for protection against short-circuit currents shall meet the
24 requirements provided in Annex G.”
25 3 Addition of Annex G, “Position of overcurrent protection devices”
26 Add the following new normative Annex G:
27 “
SIST HD 60364-4-43:2023/oprAA:2025
HD 60364-4-43:2023/prAA:2025 (E)
28 Annex G
29 (normative)
31 Position of overcurrent protection devices
32 G.1 General
33 Devices for overload and/or short-circuit protection shall be installed at the origin of each circuit unless the
34 exceptions of G.2 and/or G.3 are applied.
35 G.2 Positioning of devices for overload protection
36 G.2.1 A device for protection against overload shall be placed at each point where there is a reduction in the
37 value of current-carrying capacity of the conductors except where A.2, G.2.2, G.2.3, or G.2.4 apply. The
38 requirements in G.2.2 to G.2.4 shall not be applied to installations situated in locations presenting a fire risk or
39 risk of explosion.
40 NOTE A reduc
...