SIST EN 15116:2008
(Main)Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams
Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams
This European Standard specifies methods for measuring the cooling capacity of chilled beams with forced air flow. The evaluation of aerodynamic air performance should be based on the requirements of WI 00156113 and the requirements set out in this standard.
The purpose of the standard is to give comparable and repeatable product data.
The test method applies to all types of convector cooling systems with forced air supply using any medium as energy transport medium. This standard only applies to situations where induced air only passes through the heat exchanger (primary air does not pass through the heat exchanger).
NOTE The result is valid only for the specified test set up. For other conditions, (i.e. different positions of heat loads, inactive ceiling elements around the test objects), the producer should give guidance based on full scale tests.
This standard refers to water as the main cooling medium, with the possibility of additional cooling from the primary air. Wherever water is written, any other cooling medium can also be used in the test.
Lüftung von Gebäuden - Kühlbalken - Prüfung und Bewertung von aktiven Kühlbalken
Diese Europäische Norm legt Verfahren zur Messung der Kühlleistung von Kühlbalken mit Zwangsbelüftung fest. Die Beurteilung der aerodynamischen Luftleistung ist nicht Bestandteil dieser Norm. Die Beurteilung der aerodynamischen Luftleistung wird in der Zukunft in einer neuen Norm mit dem Titel "Lüftung von Gebäuden — Luftdurchlässe — Strömungstechnische Prüfung und Bewertung von Mischlüftungs¬anwendungen im anisothermen Betrieb — Teil 1: Kaltluftstrahlen" behandelt.
Zweck dieser Norm ist es, vergleichbare und reproduzierbare Produktkennwerte zur Verfügung zu stellen.
Das Prüfverfahren gilt für sämtliche Bauarten von konvektiven Kühlsystemen mit Zwangsbelüftung unter Verwendung eines beliebigen Mediums als Medium für den Energietransport. Diese Norm gilt nur dann, wenn lediglich die induzierte Luft durch den Wärmeübertrager strömt (die Primärluft strömt nicht durch den Wärmeübertrager).
ANMERKUNG Das Ergebnis gilt nur für den festgelegten Prüfaufbau. Bei anderen Bedingungen (d. h. bei einer anderen Anordnung der Wärmelasten, inaktiven Deckenelementen in der Umgebung der Prüfgegenstände) sollte der Hersteller Richtlinien auf Grundlage von maßstabsgetreuen Prüfungen zur Verfügung stellen.
Diese Norm bezieht sich auf Wasser als hauptsächliches Kühlmedium, mit der Möglichkeit einer zusätzlichen Kühlung durch die Primärluft. Bei Prüfungen, für die Wasser als Kühlmedium genannt ist, kann auch jedes andere Kühlmedium verwendet werden.
Ventilation des bâtiments - Poutres froides - Essai et évaluation des poutres froides actives
La présente Norme européenne spécifie les méthodes de mesure de la puissance frigorifique des poutres froides à ventilation forcée. L'évaluation de la performance aérodynamique de l'air ne fait pas partie de la présente norme. Ceci fera l'objet d'une future norme intitulée "Unités terminales - Essais aérodynamiques et étalonnage pour applications de fluides mixtes pour les essais non-isothermes - Jets froids".
La norme vise à attribuer aux produits des données comparables et répétables.
La méthode d’essai s’applique à tous les types de systèmes de refroidissement convectif à ventilation forcée quel que soit le milieu utilisé pour véhiculer l’énergie. La présente norme ne s'applique qu'aux situations où l'air induit ne passe que par l'échangeur de chaleur (l'air primaire ne passe pas par l'échangeur de chaleur).
NOTE Le résultat n’est valable que pour l’installation d’essai spécifiée. Pour d’autres conditions (c’est-à-dire positions différentes des sources de chaleur, éléments de plafond inactifs autour des dispositifs soumis à l’essai), il y a lieu pour le fournisseur de donner des indications basées sur des essais en vraie grandeur.
Dans l’ensemble de la présente norme le fluide froid de référence est l’eau, avec la possibilité d'un refroidissement complémentaire par l'air primaire. Toutefois, chaque fois qu’il est question d’eau, tout autre fluide de refroidissement est également utilisable pour l’essai.
Prezračevanje stavb - Hladilne grede - Preskušanje in razvrstitev aktivnih hladilnih gred
General Information
Relations
Overview
EN 15116:2008 (CEN) - "Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams" - specifies methods for measuring the cooling capacity of active chilled beams with forced air supply. The standard defines repeatable, comparable product data by describing test-room conditions, two alternative heat-supply methods, measurement principles and result expression. It targets convector cooling systems where induced air passes only through the heat exchanger (primary air does not pass through the coil). Water is treated as the main cooling medium, although other media may be used in the prescribed test procedures.
Key topics
- Purpose: Provide comparable and repeatable product data for active chilled beams (water-side cooling capacity and specific ratings).
- Measurement principle: Water-side cooling capacity calculated from measured cooling-water flow rate and temperature rise (steady state).
- Test methods: Two allowed approaches:
- Internal heat supply method - room heated by electric dummies (person simulators) inside an insulated test room.
- External heat supply method - heat supplied via walls/floor with controlled inner-surface temperatures.
- Test-room requirements: Recommended room ~4 m × 4 m × 3 m (floor area 10–21 m²; height 2.7–3.0 m). Airtightness and controlled inner-surface temperatures are specified (limits on heat flow through surfaces and uniformity).
- Key parameters and definitions: primary/induced/exhaust air flow rates, reference air temperature, mean cooling-water temperature, temperature difference Δθ (reference air – water mean), nominal Δθ = 8 K, nominal water flow definition (2 K ± 0.2 K temperature rise).
- Result expression: Water-side cooling capacity as function of primary air flow and Δθ; specific cooling capacity per unit length, nominal capacities and uncertainty reporting.
- Limitations: Aerodynamic air performance (mixed-flow jet behavior) is excluded and addressed in a separate/new standard; test results apply only to the specified test setup - manufacturers should provide guidance or full-scale tests for other installation conditions.
Applications
- Manufacturers: product development, performance declarations and datasheets for active chilled beams.
- Testing laboratories: standardized test procedures for certification and comparative testing.
- HVAC consultants and designers: verify chilled beam cooling capacity for selection and system design, and interpret manufacturer data correctly for building simulations.
- Specifiers and building owners: compare products on a like-for-like basis when assessing cooling performance and capacity.
Related standards
- EN 14240:2004 - Chilled ceilings - Testing and rating (test-room and dummy guidance referenced).
- EN 12792:2003 - Ventilation terminology and symbols.
- EN ISO 5167-1, EN ISO 7726, ISO 5221 - flow and measurement instrumentation and methods referenced by EN 15116.
Keywords: EN 15116:2008, active chilled beams, testing and rating of chilled beams, cooling capacity measurement, chilled beam test method, primary air, induced air, water-side cooling capacity, CEN standard.
Standards Content (Sample)
SLOVENSKI STANDARD
01-oktober-2008
3UH]UDþHYDQMHVWDYE+ODGLOQHJUHGH3UHVNXãDQMHLQUD]YUVWLWHYDNWLYQLKKODGLOQLK
JUHG
Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams
Lüftung von Gebäuden - Kühlbalken - Prüfung und Bewertung von aktiven Kühlbalken
Ventilation des bâtiments - Poutres froides - Essai et évaluation des poutres froides
actives
Ta slovenski standard je istoveten z: EN 15116:2008
ICS:
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 15116
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2008
ICS 91.140.30
English Version
Ventilation in buildings - Chilled beams - Testing and rating of
active chilled beams
Ventilation des bâtiments - Poutres froides - Essai et Lüftung von Gebäuden - Kühlbalken - Prüfung und
évaluation des poutres froides actives Berechnung von aktiven Kühlbalken
This European Standard was approved by CEN on 28 February 2008.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2008 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15116:2008: E
worldwide for CEN national Members.
Contents Page
Foreword .3
1 Scope.4
2 Normative references.4
3 Terms, definitions and symbols.4
3.1 Terms and definitions .4
3.2 Symbols and units.7
4 Test method.9
4.1 Principle.9
4.1.1 General.9
4.1.2 The internal heat supply method .9
4.1.3 The external heat supply method .9
4.2 Test room.9
4.3 Instrumentation.10
4.3.1 The internal heat supply method .10
4.3.2 The external heat supply method .10
4.3.3 Other instrumentation.10
4.4 Test procedure.11
4.4.1 Test set up.11
4.4.2 Steady state condition.11
4.4.3 Measurements.12
4.4.4 Expression of results.13
5 Uncertainty.14
6 Test report.14
Bibliography.20
Foreword
This document (EN 15116:2008) has been prepared by Technical Committee CEN/TC 156 “Ventilation
for buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by October 2008, and conflicting national standards shall be
withdrawn at the latest by October 2008.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus,
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia,
Slovenia, Spain, Sweden, Switzerland and the United Kingdom.
1 Scope
This European Standard specifies methods for measuring the cooling capacity of chilled beams with
forced air flow. The evaluation of aerodynamic air performance is not part of this standard. It will be dealt
with in the future in a new standard entitled "Air terminal devices - Aerodynamic testing and rating for
mixed flow applications for non isothermal testing - Cold jets".
The purpose of the standard is to give comparable and repeatable product data.
The test method applies to all types of convector cooling systems with forced air supply using any
medium as energy transport medium. This standard only applies to situations where induced air only
passes through the heat exchanger (primary air does not pass through the heat exchanger).
NOTE The result is valid only for the specified test set up. For other conditions, (i.e. different positions of heat
loads, inactive ceiling elements around the test objects), the producer should give guidance based on full scale tests.
This standard refers to water as the main cooling medium, with the possibility of additional cooling from
the primary air. Wherever water is written, any other cooling medium can also be used in the test.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 12792:2003, Ventilation for buildings - Symbols, terminology and graphical symbols
EN 14240:2004, Ventilation for buildings — Chilled ceilings — Testing and rating
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular
cross-section conduits running full – Part 1: General principles and requirements (ISO 5167-1:2003)
EN ISO 7726, Ergonomics of the thermal environment - Instruments for measuring physical quantities (ISO
7726:1998)
ISO 5221, Air distribution and air diffusion - Rules to methods of measuring air flow rate in an air handling
duct
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792:2003 and the following apply.
3.1.1
active chilled beam
convector with integrated air supply where the induced air only passes through the cooling coil(s). The
cooling medium in the coil is water
NOTE For the purpose of this standard primary air does not pass through the cooling coil.
3.1.2
test room
room in which the test object is mounted
3.1.3
primary air flow rate (q )
p
airflow supplied to the test object through a duct from outside of the test room or with primary air fan and
ducting inside the test room
3.1.4
induced air flow rate (q )
i
secondary airflow from the test room induced into the test object by the primary air
3.1.5
exhaust air flow rate (q )
e
airflow discharged from the test room or return air if the primary air fan is located in the test room. The
exhaust air flow rate is the same as the primary air flow rate
3.1.6
primary air pressure drop (∆p )
a
pressure drop across induction nozzle plus discharge loss
3.1.7
cooling water flow rate (q )
w
the average of the measured water flow rates during the test period
3.1.8
nominal cooling water flow rate (q )
wN
flow rate that gives a cooling water temperature rise (θ − θ ) of 2 K ± 0,2 K at nominal temperature
w2 w1
difference (∆θ = 8 K) and at nominal air flow rate
N
3.1.9
water side pressure drop (∆p )
w
internal pressure drop across coil plus beam internal pipes
3.1.10
room air temperature (θθθθ )
a
average of air temperatures measured with radiation shielded sensors in 1,1 m height in positions out of
the main air current from the test object
3.1.11
globe temperature (θθθθ )
g
temperature measured with a temperature sensor placed in the centre of the globe. The globe is placed in
1,1 m height in a position out of the main air current from the test object
3.1.12
reference air temperature (θθ )
θθ
r
reference air temperature equals average air temperature of the induced air on the inlet side of the
cooling coil(s), measured with radiation shielded sensors in three positions in the induced air opening, two
centrally at the quarter points and one at the central point of the opening
3.1.13
cooling water inlet temperature (θθθθ )
w1
average of the measured water temperature into the test object during the test period
3.1.14
cooling water outlet temperature (θθθθ )
w2
average of the measured water temperature out of the test object during the test period
3.1.15
mean cooling water temperature (θθθθ )
w
mean value of the cooling water inlet and outlet temperatures, [θ =0,5·(θ + θ )]
w w1 w2
3.1.16
primary air temperature (θθ )
θθ
p
average of the primary air temperature during the test period
3.1.17
temperature difference (∆∆θ∆∆θθθ)
difference between reference air temperature and mean cooling water temperature, ∆θ=θ - θ
r w
3.1.18
nominal temperature difference (∆∆∆∆θθθθ )
N
nominal temperature difference (8 K) between the reference air temperature and the mean cooling water
temperature (∆θ =θ - θ =8 K)
N r w
3.1.19
primary air temperature difference (∆∆∆∆θθθθ )
p
temperature difference between the reference air temperature and the primary air temperature
3.1.20
specific heat capacity (c )
p
heat required to raise the temperature of a unit mass of the cooling medium by 1K
-1 -1 -1 -1
NOTE c for water = 4,187 kJ·kg ·K and c for air = 1,005 kJ·kg ·K , at 15 °C.
p p
3.1.21
cooling length (L)
active length of the cooling section
3.1.22
total length (L )
t
total installed length of the cooling section including casing
3.1.23
water side cooling capacity (P )
w
cooling capacity of the test object calculated from the measured cooling water flow rate and the cooling
water temperature rise P =c q (θ - θ )
w p m w2 w1
3.1.24
primary air cooling capacity (P )
a
cooling capacity calculated from the primary air flow rate and primary air temperature difference
P = c q ρ (θ - θ )
a p p p r p
3.1.25
specific cooling capacity per unit length (P )
L
water side cooling capacity divided by the (active) cooling section length
3.1.26
specific cooling capacity (P )
K
cooling capacity divided by the difference between reference air temperature and mean cooling water
m
temperature, ∆θ=θ - θ raised to the exponent m i.e. P = P /∆θ
r w K w
3.1.27
nominal cooling capacity (P ) or nominal specific cooling capacity (P )
N LN
water side cooling capacity calculated from the curve of best fit for the nominal cooling water flow rate at
nominal temperature difference (∆θ = 8 K) and at nominal air flow rate
N
3.2 Symbols and units
For the purposes of this document the symbols given in EN 12792:2003 apply together with those given
in Table 1.
Table 1 — Symbols and units
Symbol Quantity Unit
n
A Constant in P = Aq
K p
At Test room floor area m
m
k
1 Constant in P = k1 ∆θ
w
n
k
2 Constant in P = k2 qp
w
n
n Exponent used in P = Aq
K p
m
m Exponent used in P = P /∆θ
K w
L Cooling length (active length) m
L Total length of a chilled beam, including casing m
t
-1 -1
c Specific heat capacity kJ·kg ·K
p
h Height from floor to underside of active chilled beam m
P Total cooling capacity P = P + P W
w a
-1
P Specific cooling capacity per unit active length W m
L
P W
N Nominal cooling capacity (at ∆θ = 8 K)
N
-1
P W·m
Nominal specific cooling capacity per unit active length (at ∆θ = 8 K)
LN
N
-m
m
P W K
K Specific cooling capacity (P = P /∆θ )
K w
P Primary air cooling capacity W
a
P Water side cooling capacity W
w
-2
P Specific cooling capacity per unit floor area Wm
t
P Heating capacity of dummies W
s
P Heat transfer test room periphery W
TR
-1
q Cooling medium flow rate l(litre)·s
w
-1
q Nominal cooling water flow rate l(litre)·s
wN
∆p Water pressure drop kPa
w
-1
q Cooling medium mass flow rate (q = ρ q ) kg·s
m
m w w
-1
q Nominal primary air flow rate l(litre)··s
pN
-1
q Primary air flow rate l(litre)··s
p
-1
q Induced air flow rate l(litre)··s
i
-1
q Exhaust air flow rate (if appropriate) l(litre)··s
e
∆p Primary air pressure drop Pa
a
Room air temperature °C
θ
a
Room exhaust air temperature (if appropriate) °C
θ
e
θ Globe temperature °C
g
Reference air temperature °C
θ
r
θ Surface wall temperature °C
sw
Primary air temperature °C
θ
p
Cooling water inlet temperature °C
θ
w1
θ Cooling water outlet temperature °C
w2
Mean cooling water temperature °C
θ
w
-3
ρ Density of primary air at θ kg·m
p p
-1
kg·l (litre)
ρ Density of cooling medium at θ
w w
Temperature difference K
∆θ
reference air temperature-water mean
Nominal temperature difference (=8K) K
∆θ
N
∆θp Temperature difference reference air temperature
-primary air temperature K
4 Test method
4.1 Principle
4.1.1 General
The water side cooling capacity of the test object shall be determined from measurements of the cooling
water flow rate and cooling water temperature rise under steady state condition. The water side cooling
capacity shall be presented as a function of the primary air flow rate and the temperature difference
between the reference air temperature and the mean cooling water temperature.
The measurements shall be performed in an airtight room, to the requirements of 4.2, with controlled
temperatures on the inside surfaces. Two alternative methods are allowed:
4.1.2 The internal heat supply method
The perimeter of the room shall be insulated and have negligible heat flow through it. The perimeters
shall be insulated in such a way that during the test the average heat flow through these surfaces is less
-2
than 0,40 W·m .
To balance the cooling capacity of the test object, heating is supplied in the test room by means of a
number of electric heated person simulators, dummies, as described in 4.3 of EN 14240:2004. The
dummies are placed on the floor inside the test room. To get reproducible results the dummies shall be
placed in determined positions as described in 4.4.1 of EN 14240:2004. For location of beam(s) relative
to the dummies, see 4.4.1 of this standard.
NOTE This method uses the same test room and heating supply to the room as specified in EN 14240 for
testing and rating of chilled ceilings.
4.1.3 The external heat supply method
To balance the cooling capacity of the test object, heating is supplied to the test room evenly distributed
through the walls and the floor. The ceiling shall be insulated in such a way that during the test the heat
-2
flow through the ceiling is less than 0,40 W·m . The temperature of the inner walls and floor of the test
room shall be controlled and maintained uniform at any level necessary to keep the desired room
temperature. The maximum temperature difference between any point of the inner walls and floor during
the test shall be less than 1 K.
4.2 Test room
2 2
The floor area of the test room shall be between 10 m and 21 m .
The ratio of width to length of the test room shall be not less than 0,5; and the inside height shall be
between 2,7 m and 3 m.
The recommended inside dimensions are a length of 4 m, a width of 4 m and a height of 3 m.
NOTE 1 The test room specification enables the use of test rooms in accordance with EN 442 for the testing of
chilled beams. The dimensions of the test room are given as a recommendation. It is permitted for the test room
dimensions to deviate from the recommended dimensions.
The test room shall be sufficiently tight to minimise flow from the ambient air outside which shall not
-1 -2
exceed 0,8 ls m of the perimeter surface at a pressure difference of 50 Pa (note includes floor walls and
ceiling).
The outside of the room or outer room as appropriate should be insulated. The heat loss to the outside
should be determined by preliminary calibration (without test object cooling) to demonstrate compliance
with either 4.1.2 or 4.1.3 as appropriate.
It is recommende
...
Frequently Asked Questions
SIST EN 15116:2008 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Ventilation in buildings - Chilled beams - Testing and rating of active chilled beams". This standard covers: This European Standard specifies methods for measuring the cooling capacity of chilled beams with forced air flow. The evaluation of aerodynamic air performance should be based on the requirements of WI 00156113 and the requirements set out in this standard. The purpose of the standard is to give comparable and repeatable product data. The test method applies to all types of convector cooling systems with forced air supply using any medium as energy transport medium. This standard only applies to situations where induced air only passes through the heat exchanger (primary air does not pass through the heat exchanger). NOTE The result is valid only for the specified test set up. For other conditions, (i.e. different positions of heat loads, inactive ceiling elements around the test objects), the producer should give guidance based on full scale tests. This standard refers to water as the main cooling medium, with the possibility of additional cooling from the primary air. Wherever water is written, any other cooling medium can also be used in the test.
This European Standard specifies methods for measuring the cooling capacity of chilled beams with forced air flow. The evaluation of aerodynamic air performance should be based on the requirements of WI 00156113 and the requirements set out in this standard. The purpose of the standard is to give comparable and repeatable product data. The test method applies to all types of convector cooling systems with forced air supply using any medium as energy transport medium. This standard only applies to situations where induced air only passes through the heat exchanger (primary air does not pass through the heat exchanger). NOTE The result is valid only for the specified test set up. For other conditions, (i.e. different positions of heat loads, inactive ceiling elements around the test objects), the producer should give guidance based on full scale tests. This standard refers to water as the main cooling medium, with the possibility of additional cooling from the primary air. Wherever water is written, any other cooling medium can also be used in the test.
SIST EN 15116:2008 is classified under the following ICS (International Classification for Standards) categories: 91.140.30 - Ventilation and air-conditioning systems. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN 15116:2008 has the following relationships with other standards: It is inter standard links to oSIST prEN 15116:2005. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase SIST EN 15116:2008 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
The SIST EN 15116:2008 standard provides comprehensive guidelines for the testing and rating of active chilled beams in building ventilation systems, focusing specifically on the measurement of their cooling capacity with forced air flow. Its scope encompasses all types of convector cooling systems that use forced air supply, thereby ensuring a broad applicability across various building environments. One of the significant strengths of this standard is its emphasis on delivering comparable and repeatable product data, which is paramount for manufacturers and consumers alike. By specifying methods for evaluating aerodynamic air performance, the standard not only increases the reliability of the data generated but also facilitates informed decision-making regarding chilled beam systems. Furthermore, the stipulation that induced air should only pass through the heat exchanger reinforces the standard’s intention to create precise testing conditions. This aspect ensures that the results obtained are valid only under specified test setups, reducing ambiguities related to varying operational environments. The note concerning the need for producers to provide guidance for alternative conditions highlights the standard's flexibility and adaptability, encouraging best practices in the industry. Moreover, the standard’s primary focus on water as the main cooling medium, while allowing for other cooling mediums, opens up opportunities for innovation and adaptability within various cooling applications. This inclusion broadens the scope of the standard, making it relevant not just for traditional water-based systems, but also for newer technologies that may utilize different energy transport mediums. Overall, SIST EN 15116:2008 stands out as a crucial standard in the field of building ventilation, providing essential methodologies that enhance the performance and evaluation of chilled beam systems, thereby contributing to more efficient building designs. Its relevance in today’s energy-conscious environment cannot be understated, as it aids in promoting more sustainable cooling solutions.
SIST EN 15116:2008は、建物内の換気システムにおけるアクティブチルドビームの試験および評価に関する欧州標準です。この標準の範囲は、強制空気流を用いたチルドビームの冷却能力を測定する方法を明確に定義しており、システムの空力的な空気性能評価を行うための基準を提供します。 この標準の強みは、製品データを比較可能かつ再現可能にするための確固たるテストメソッドにあります。すべてのタイプの強制供給を使用するコンベクター冷却システムに適用可能であり、あらゆる冷媒をエネルギー輸送媒体として利用できる柔軟性を持っています。特に、受動的な空気の取り込みは熱交換器を経由しない条件下でのみ適用されるため、使用条件についても明確な指針を示しています。 さらに、この標準は主に水を冷却媒体として指定していますが、他の冷却媒体を使用することも可能であり、業界全体での適用性と現実的なニーズに応えています。これは、実際の運用環境において発生するさまざまな条件に対しても適用できるように配慮されていることを示しています。 SIST EN 15116:2008は、冷却システム評価の信頼性を高めるうえで重要な役割を果たしており、換気システムの設計者やエンジニアがこの標準に従うことで、高性能かつ効率的な換気設計を実現できることが期待されます。この標準は、特に持続可能な建物におけるエネルギー効率を向上させるための基盤を提供し、業界内でのベストプラクティスを促進します。
SIST EN 15116:2008는 건물의 환기 시스템에서 액티브 칠드 빔의 성능을 시험하고 평가하는 데 중요한 기준을 제공합니다. 이 표준은 강제 공기 흐름을 사용하는 칠드 빔의 냉각 용량을 측정하는 방법을 명시하며, 공기 역학적 성능 평가를 위한 요구 사항을 포함하고 있습니다. 이 표준의 강점 중 하나는 제품 데이터의 비교 가능성과 반복 가능성을 제공합니다. 이는 제조업체가 제품의 신뢰성을 확보할 수 있도록 돕는 중요한 요소입니다. 또한, 모든 유형의 강제 공기 공급을 사용하는 컨벡터 냉각 시스템에 적용될 수 있는 시험 방법을 제공하여 범위가 넓고 유연성을 갖추고 있습니다. SIST EN 15116:2008은 기본적으로 물을 주요 냉각 매체로 지정하고 있으며, 추가적인 냉각이 필요할 경우 기본 공기에서 수득할 수 있는 가능성을 인지하고 있습니다. 이 표준은 특정 시험 설정에 대해서만 유효하며, 다른 조건에서는 제조업체가 전면적인 테스트를 기반으로 한 지침을 제공해야 함을 유의해야 합니다. 이러한 측면에서, 표준은 실제 적용 상황에 맞춰 필요한 조정이 이루어질 수 있도록 구성되어 있습니다. 요약하자면, SIST EN 15116:2008는 액티브 칠드 빔의 공기 역학적 성능 시험을 위해 설계된 핵심 표준으로, 사용자에게 실질적인 지침과 함께 동일한 환경에서 제품 성능을 비교할 수 있는 유용한 정보를 제공합니다. 해당 표준은 건물의 에너지 효율성을 높이고 효과적인 환기 시스템을 구현하는 데 중요한 역할을 할 것입니다.
Le document SIST EN 15116:2008 est une norme européenne qui se concentre sur la ventilation dans les bâtiments, spécifiquement sur les systèmes de poutres froides actives. Cette norme a pour objectif de spécifier des méthodes précises pour mesurer la capacité de refroidissement des poutres froides avec un flux d'air forcé, garantissant ainsi des données comparables et répétables sur les produits. L'une des forces majeures de cette norme réside dans son approche rigoureuse pour l'évaluation des performances aérodynamiques de l'air, reposant sur les exigences de la WI 00156113. En définissant des méthodes de test cohérentes, cette norme assure que les résultats obtenus peuvent être fiables et uniformes, ce qui est essentiel pour les fabricants et les utilisateurs finaux cherchant à comparer différentes solutions de systèmes de refroidissement. En outre, la norme SIST EN 15116:2008 s'applique à tous les types de systèmes de refroidissement par convecteurs avec une alimentation d'air forcé, indépendamment du moyen utilisé pour le transport d'énergie. Cela inclut l'eau comme principal moyen de refroidissement, tout en permettant la flexibilité d'utiliser d'autres fluides de refroidissement lors des essais, élargissant ainsi la pertinence de la norme à divers contextes et technologies. Le rappel que les résultats ne sont valides que pour le montage de test spécifié souligne l'importance d'une méthode d'essai contrôlée. Les recommandations pour des tests à grande échelle en cas de conditions différentes garantissent que les producteurs peuvent fournir des conseils pertinents, adaptant ainsi les résultats à des situations variées. En résumé, la norme SIST EN 15116:2008 est un outil crucial pour le secteur de la construction, en offrant un cadre fiable pour l'évaluation des systèmes de poutres froides actives, tout en veillant à répondre aux exigences de performance du marché.
Die SIST EN 15116:2008 ist eine entscheidende Norm für die Ventilation in Gebäuden, die speziell die Anforderungen und Prüfmethoden für aktive Kühldecken behandelt. Die Norm legt umfassende Methoden zur Messung der Kühlkapazität von Kühldecken mit Zwangsluftströmung fest, und bezieht sich dabei auf die Anforderungen des WI 00156113 sowie auf die in der Norm festgelegten Kriterien. Sie bietet eine robuste Grundlage zur Evaluierung der aerodynamischen Luftleistung von Kühlsystemen und stellt sicher, dass die produktbezogenen Daten vergleichbar und reproduzierbar sind. Ein herausragendes Merkmal dieser Norm ist ihre Vielseitigkeit. Sie gilt für alle Arten von Konvektor-Kühlsystemen, die mit Zwangsluftversorgung arbeiten und verschiedene Medien als Energieträger nutzen. Dies ermöglicht eine breite Anwendung in der Praxis und stellt sicher, dass Hersteller und Prüfinstitutionen eine einheitliche Grundlage für die Durchführung von Tests haben. Ein weiterer wichtiger Aspekt ist die klare Definition des Testaufbaus. Es wird hervorgehoben, dass die Ergebnisse ausschließlich für den spezifischen Testaufbau gültig sind, was eine genaue und präzise Bewertung der Kühlleistung ermöglicht. Dies ist besonders wichtig, da unterschiedliche Bedingungen (wie Variationen der Wärmebelastungen oder der Position der inaktiven Deckenelemente) die Ergebnisse beeinflussen können. Hersteller wird nahegelegt, auf Basis von Tests im Vollmaßstab weitergehende Hinweise zu geben, um die Relevanz der Testergebnisse in unterschiedlichen Kontexten sicherzustellen. Ein bedeutendes Merkmal der Norm ist die Fokussierung auf Wasser als Hauptkühlmedium, wobei die Möglichkeit zusätzlicher Kühlung durch die Primärluft vorgesehen ist. Dies erleichtert die Implementierung in bestehenden Systemen und bietet Flexibilität bei der Auswahl des Kühlmediums. Zusammenfassend lässt sich sagen, dass die SIST EN 15116:2008 eine wesentliche Ressource für Fachleute im Bereich der Gebäudetechnik darstellt. Sie definiert klar die Anforderungen und Prüfmethoden, sorgt für die Vergleichbarkeit der Produktdaten und trägt somit zur Effizienz und Nachhaltigkeit von Kühlsystemen in modernen Gebäuden bei.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...