High-voltage switchgear and controlgear - Part 101: Synthetic testing (IEC 62271-101:2021)

IEC 62271-101:2021 mainly applies to AC circuit-breakers within the scope of IEC 62271-100. It provides the general rules for testing AC circuit-breakers, for making and breaking capacities over the range of test duties described in 7.102 to 7.111 of IEC 62271-100:2021, by synthetic methods.
It has been proven that synthetic testing is an economical and technically correct way to test high-voltage AC circuit-breakers according to the requirements of IEC 62271-100 and that it is equivalent to direct testing.
The methods and techniques described are those in general use. The purpose of this document is to establish criteria for synthetic testing and for the proper evaluation of results. Such criteria will establish the validity of the test method without imposing restraints on innovation of test circuitry.
This third edition cancels and replaces the second edition published in 2012 and Amendment 1:2017. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the second edition:
a) alignment with the third edition of IEC 62271-100:2021;
b) update this document with the last methods and techniques used for synthetic tests.

Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 101: Synthetische Prüfung (IEC 62271-101:2021)

Appareillage à haute tension - Partie 101: Essais synthétiques (IEC 62271-101:2021)

L’IEC 62271-101:2021 s’applique principalement aux disjoncteurs à courant alternatif définis dans le domaine d’application de l’IEC 62271-100. Elle donne les règles générales d’essais de ces disjoncteurs, pour les pouvoirs de fermeture et de coupure dans la plage des séquences d’essais décrites de 7.102 à 7.111 de l’IEC 62271-100:2021, à l'aide de méthodes d'essais synthétiques.
Il a été démontré que l'essai synthétique est un moyen économique et techniquement valable pour soumettre à l’essai les disjoncteurs à courant alternatif à haute tension selon les exigences de l’IEC 62271-100, et qu’il est équivalent à un essai direct.
Les méthodes et techniques décrites sont celles d’usage courant. L’objet du présent document est d'établir des critères pour les essais synthétiques et pour l'évaluation correcte des résultats. Ces critères établissent la validité de la méthode d'essai sans limiter l'invention de nouveaux circuits d'essais.
Cette troisième édition annule et remplace la deuxième édition parue en 2012 et l’Amendement 1:2017. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à la deuxième édition:
a) alignement sur la troisième édition de l’IEC 62271-100:2021;
b) mise à jour du présent document avec les méthodes et techniques récentes utilisées pour les essais synthétiques.

Visokonapetostne stikalne in krmilne naprave - 101. del: Sintetično preskušanje (IEC 62271-101:2021)

Ta del standarda IEC 62271 se uporablja za trifazne izmenične odklopnike za notranjo in zunanjo namestitev, ki delujejo na frekvencah 50 Hz in/ali 60 Hz v sistemih z napetostjo nad 1000 V. Ta dokument vključuje samo neposredne preskusne metode za preskuse vklopne in izklopne zmogljivosti. Za sintetične preskusne metode glej standard IEC 62271-101.
OPOMBA: Pri neposredni preskusni metodi se za dovajanje napetosti in toka med preskusi vklopne ter izklopne zmogljivosti uporablja en vir.
Ta del standarda IEC 62271 se ne uporablja za:
– odklopnike z zapiralnim mehanizmom za odvisno ročno upravljanje;
– odklopnike, namenjene za uporabo na motornih garniturah opreme za električno vleko; ti so zajeti v standardu IEC 60077 (vsi deli) [1]1;
– generatorske odklopnike, nameščene med generatorjem in blokovnim transformatorjem; ti so zajeti v standardu IEC 62271-37-013 [2];
– samosprožilne odklopnike s sprožilnimi napravami, katerih delovanja med preskušanjem ni mogoče prekiniti. Preskusi naprav za avtomatski ponovni vklop so zajeti v standardu IEC 62271-111 [3];
– o preskusih za dokazovanje zmogljivosti pod določenimi pogoji v izrednih razmerah, ki niso opisani v tem dokumentu, se dogovorita proizvajalec in uporabnik. Take izredne razmere so na primer stanje, ko je napetost višja od nazivne napetosti odklopnika, do česar lahko pride zaradi nenadne izgube obremenitve dolgih vodov ali kablov.

General Information

Status
Published
Publication Date
07-Oct-2021
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
23-Sep-2021
Due Date
28-Nov-2021
Completion Date
08-Oct-2021

Relations

Standard
SIST EN IEC 62271-101:2021 - BARVE
English language
158 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard
SIST EN IEC 62271-101:2021 - BARVE. Vodni pretisk prestavljen na PDF-str 233-240, 264-266
English language
299 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2021
Nadomešča:
SIST EN 62271-101:2013
SIST EN 62271-101:2013/A1:2018
Visokonapetostne stikalne in krmilne naprave - 101. del: Sintetično preskušanje
(IEC 62271-101:2021)
High-voltage switchgear and controlgear - Part 101: Synthetic testing (IEC 62271-
101:2021)
Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 101: Synthetische Prüfung (IEC
62271-101:2021)
Appareillage à haute tension - Partie 101: Essais synthétiques (IEC 62271-101:2021)
Ta slovenski standard je istoveten z: EN IEC 62271-101:2021
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 62271-101

NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2021
ICS 29.130.10 Supersedes EN 62271-101:2013 and all of its
amendments and corrigenda (if any)
English Version
High-voltage switchgear and controlgear - Part 101: Synthetic
testing
(IEC 62271-101:2021)
Appareillage à haute tension - Partie 101: Essais Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil
synthétiques 101: Synthetische Prüfung
(IEC 62271-101:2021) (IEC 62271-101:2021)
This European Standard was approved by CENELEC on 2021-08-31. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 62271-101:2021 E

European foreword
The text of document 17A/1312/FDIS, future edition 3 of IEC 62271-101, prepared by SC 17A
“Switching devices” of IEC/TC 17 “High-voltage switchgear and controlgear” was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN IEC 62271-101:2021.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022-05-31
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2024-08-31
document have to be withdrawn
This document supersedes EN 62271-101:2013 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 62271-101:2021 was approved by CENELEC as a
European Standard without any modification.
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 62271-100 2021 High-voltage switchgear and controlgear - EN IEC 62271-100 2021
Part 100: Alternating-current circuit-
breakers
IEC 62271-101 ®
Edition 3.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
High-voltage switchgear and controlgear –

Part 101: Synthetic testing
Appareillage à haute tension –

Partie 101: Essais synthétiques

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.130.10 ISBN 978-2-8322-1004-6

– 2 – IEC 62271-101:2021 © IEC 2021
CONTENTS
FOREWORD . 9
1 Scope . 11
2 Normative references. 11
3 Terms and definitions . 11
4 Synthetic testing techniques and methods for short-circuit breaking tests . 13
4.1 Basic principles and general requirements for synthetic breaking test
methods . 13
4.1.1 General . 13
4.1.2 High-current interval . 14
4.1.3 Interaction interval . 15
4.1.4 High-voltage interval . 15
4.2 Synthetic test circuits and related specific requirements for breaking tests . 18
4.2.1 Current injection methods . 18
4.2.2 Voltage injection method . 19
4.2.3 Duplicate circuit method (transformer or Skeats circuit) . 20
4.2.4 Other synthetic test methods . 20
4.3 Three-phase synthetic test methods . 20
5 Synthetic testing techniques and methods for short-circuit making tests . 24
5.1 Basic principles and general requirements for synthetic making test methods . 24
5.1.1 General . 24
5.1.2 High-voltage interval . 27
5.1.3 Pre-arcing interval . 27
5.1.4 Latching interval and fully closed position . 27
5.2 Synthetic test circuit and related specific requirements for making tests . 27
5.2.1 General . 27
5.2.2 Test circuit and test requirements . 27
5.2.3 Alternative test method with reduced voltage . 32
7 Type tests . 33
7.102 General . 33
7.104 Demonstration of arcing times . 34
7.107 Terminal fault tests . 45
7.109 Short-line fault tests . 49
7.110 Out-of-phase making and breaking tests . 50
7.111 Capacitive current tests . 50
Annex A (normative) Correction of di/dt and TRV for test duty T100a . 53
A.1 General . 53
A.2 Reduction in di/dt . 53
A.3 Corrected TRV for the first-pole-to-clear with required asymmetry . 53
A.4 Correction of the di/dt and TRV of the first-pole-to-clear for tests with
intermediate asymmetry . 60
A.5 Correction of the di/dt and TRV of the second- or last-pole-to-clear with
major extended loop with required asymmetry during three-phase tests . 61
A.6 Correction of the di/dt and TRV during tests with a subsequent minor loop . 61
A.7 Calculation of the di/dt and TRV of the first-pole-to-clear . 61
A.7.1 General . 61
A.7.2 Calculation of di/dt . 61

IEC 62271-101:2021 © IEC 2021 – 3 –
A.7.3 Calculation of TRV . 62
A.7.4 Examples of calculation of di/dt and TRV . 64
Annex B (normative) Tolerances on test quantities for type tests . 66
Annex C (normative) Information to be given and results to be recorded for synthetic
tests . 69
C.1 General . 69
C.2 Auxiliary circuit-breaker . 69
C.3 Test conditions . 69
C.4 Quantities to be recorded . 69
C.4.1 General . 69
C.4.2 Voltages . 69
C.4.3 Currents . 69
Annex D (normative) Test procedure using a three-phase current circuit and one
voltage circuit . 70
D.1 Test circuit . 70
D.2 Test method . 71
D.2.1 General . 71
D.2.2 Test duty T100s(b) . 71
D.2.3 Test duty T100a . 80
D.2.4 Combination of first-pole-to-clear factors 1,3 and 1,5 . 89
Annex E (normative) Splitting of test duties in test series taking into account the
associated TRV for each pole-to-clear . 92
E.1 General . 92
E.2 Test-duties T10, T30, T60, T100s(b), OP1 and OP2(b). 92
E.2.1 Test procedure for first-pole-to-clear factors 1,5 and 2,5 . 92
E.2.2 Test procedure for first-pole-to-clear factors 1,3 and 2,0 . 93
E.2.3 Test procedure for first-pole-to-clear factor 1,2 . 94
E.3 Test duty T100a . 95
E.3.1 General . 95
E.3.2 Test procedure for first-pole-to-clear factor 1,5 . 96
E.3.3 Test procedure for first-pole-to-clear factor 1,3 . 97
E.3.4 Test procedure for first-pole-to-clear factor 1,2 . 99
E.4 Combination of first-pole-to-clear factors . 100
E.4.1 General . 100
E.4.2 Combination of first-pole-to-clear factors 1,3 and 1,5 for test duties T10,
T30, T60 and T100s(b) . 100
E.4.3 Combination of first-pole-to-clear factors 2,0 and 2,5 for test duties OP1
and OP2(b) . 101
E.4.4 Combination of first-pole-to-clear factors 1,3 and 1,5 for test duty T100a . 102
Annex F (informative) Three-phase synthetic test circuits . 114
F.1 General . 114
F.2 Three-phase synthetic combined circuit . 114
F.3 Three-phase synthetic circuit with injection in all phases . 117
F.4 Three-phase synthetic circuit with injection in two phases . 118
Annex G (informative) Examples of test circuits for metal-enclosed and dead tank
circuit-breakers . 122
Annex H (informative) Step-by-step method to prolong arcing . 133
Annex I (informative) Synthetic methods for capacitive current tests . 135
I.1 General . 135

– 4 – IEC 62271-101:2021 © IEC 2021
I.2 Recovery voltage . 135
I.3 Combined current and voltage circuits . 135
I.4 Making tests . 136
I.5 Current chopping . 136
I.6 Examples test circuits . 136
Annex J (normative) Synthetic test methods for circuit-breakers with opening resistors . 145
J.1 General . 145
J.2 Conditions. 145
J.2.1 General . 145
J.2.2 Transient recovery voltage interval . 145
J.2.3 Power-frequency recovery voltage interval . 145
J.3 Multiple step test procedure . 145
J.3.1 General . 145
J.3.2 Test to verify the re-ignition behaviour of the making and breaking unit . 146
J.3.3 Test to verify the re-ignition behaviour of the making and breaking unit
during short circuit test duties with any test method . 147
J.3.4 Tests on resistor switch(s) . 148
J.4 Test requirements . 149
J.4.1 General . 149
J.4.2 Testing of the making and breaking unit . 150
J.4.3 Testing of the resistor switch . 151
J.4.4 Test of the resistor stack . 151
Annex K (informative) Combination of current injection and voltage injection methods . 152
K.1 Current injection methods . 152
K.2 Voltage injection methods . 152
K.3 Combined current and voltage injection circuits. 152
K.3.1 General . 152
K.3.2 Combined current and voltage injection circuit with application of full
test voltage to earth . 152
K.3.3 Combined current and voltage injection circuit with separated
application of test voltage . 152
Bibliography . 155

Figure 1 – Interrupting process – Basic time intervals . 14
Figure 2 – Examples of evaluation of initial recovery voltage . 17
Figure 3 – Equivalent surge impedance of the voltage circuit for the current injection
method . 19
Figure 4 – Reference lines of TRV with four-parameter for k = 1,5 . 22
pp
Figure 5 – Reference lines of TRV with four-parameter for k = 1,3 . 23
pp
Figure 6 – Reference lines of TRV with four-parameter for k = 1,2 . 24
pp
Figure 7 – Making process – Basic time intervals . 26
Figure 8 – Example of synthetic making circuit for single-phase tests . 29
Figure 9 – Example of synthetic making circuit for out-of-phase tests . 30
Figure 10 – Example of synthetic making circuit for three-phase tests (k = 1,5) . 31
pp
Figure 11 – Comparison of arcing time settings during three-phase direct tests (left)
and three-phase synthetic (right) for T100s with k = 1,5 . 37
pp
IEC 62271-101:2021 © IEC 2021 – 5 –
Figure 12 – Comparison of arcing time settings during three-phase direct tests (left)
and three-phase synthetic (right) for T100s with k = 1,3 . 38
pp
Figure 13 – Comparison of arcing time settings during three-phase direct tests (left)
and three-phase synthetic tests (right) for T100a with k = 1,5 . 41
pp
Figure 14 – Comparison of arcing time settings during three-phase direct tests (left)
and three-phase synthetic tests (right) for T100a with k = 1,3 . 42
pp
Figure 15 – Evaluation of recovery voltage during synthetic capacitive current
switching testing . 52
Figure D.1 – Example of a three-phase current circuit with single-phase synthetic
injection . 71
Figure D.2 – Representation of the testing conditions of Table D.1. 73
Figure D.3 – Representation of the testing conditions of Table D.2. 75
Figure D.4 – Representation of the testing conditions of Table D.3. 77
Figure D.5 – Representation of the testing conditions of Table D.4. 79
Figure D.6 – Representation of the testing conditions of Table D.5. 82
Figure D.7 – Representation of the testing conditions of Table D.6. 84
Figure D.8 – Representation of the testing conditions of Table D.7. 86
Figure D.9 – Representation of the testing conditions of Table D.8. 88
Figure E.1 – Example of graphical representation of the tests shown in Table E.6 . 97
Figure E.2 – Example of graphical representation of the tests shown in Table E.7 and
Table E.8 . 99
Figure F.1 – Three-phase synthetic combined circuit . 115
Figure F.2 – Waveshapes of currents, phase-to-ground and phase-to phase voltages
during a three-phase synthetic test (T100s; k = 1,5) performed according to the
pp
three-phase synthetic combined circuit . 116
Figure F.3 – Three-phase synthetic circuit with injection in all phases for k = 1,5 . 117
pp
Figure F.4 – Waveshapes of currents and phase-to-ground voltages during a three-
phase synthetic test (T100s; k = 1,5) performed according to the three-phase
pp
synthetic circuit with injection in all phases . 118
Figure F.5 – Three-phase synthetic circuit for terminal fault tests with k = 1,3
pp
(current injection method) . 119
Figure F.6 – Waveshapes of currents and phase-to-ground voltages during a
three-phase synthetic test (T100s; k = 1,3 ) performed according to the three-phase
pp
synthetic circuit shown in Figure F.5 . 120
Figure F.7 – TRV voltages waveshapes of the test circuit described in Figure F.5 . 121
Figure G.1 – Example of a test circuit for unit testing (circuit-breaker with interaction
due to gas circulation) . 123
Figure G.2 – Oscillogram corresponding to Figure G.1 – Example of the required TRVs
to be applied between the terminals of the unit(s) under test and between the live parts
and the insulated enclosure . 124
Figure G.3 – Example of test circuit using two voltage circuits for breaking tests . 125
Figure G.4 – Example of test circuit using two voltage circuits for breaking tests . 126
Figure G.5 – Example of a synthetic test circuit for unit testing (if unit testing is allowed

as per 7.102.4.2 of IEC 62271-100:2021) . 127
Figure G.6 – Oscillogram corresponding to Figure G.3 – Example of the required TRVs
to be applied between the terminals of the unit(s) under test and between the live parts
and the insulated enclosure . 128

– 6 – IEC 62271-101:2021 © IEC 2021
Figure G.7 – Example of a capacitive current injection circuit with enclosure of the
circuit-breaker energized . 129
Figure G.8 – Example of a capacitive synthetic circuit using two power-frequency
circuits and with the enclosure of the circuit-breaker energized . 130
Figure G.9 – Example of a capacitive synthetic current injection circuit – Unit testing on
half a pole of a circuit-breaker with two units per pole – Enclosure energized with DC
voltage . 131
Figure G.10 – Example of a synthetic making circuit for out-of-phase tests . 132
Figure H.1 – Example of a re-ignition circuit diagram for prolonging arc-duration . 133
Figure H.2 – Example of waveforms obtained during a symmetrical test using the
circuit in Figure H.1. 134
Figure I.1 – Power-frequency circuits in parallel. 138
Figure I.2 – Current injection circuit . 139
Figure I.3 – Power-frequency current injection circuit . 140
Figure I.4 – Current injection circuit, recovery voltage applied to both terminals of the
circuit-breaker . 141
Figure I.5 – Current injection circuit with decay compensation. 142
Figure I.6 – LC oscillating circuit . 143
Figure I.7 – Inrush making current test circuit . 144
Figure J.1 – Test circuit to verify re-ignition behaviour of the making and breaking unit
using current injection method. 147
Figure J.2 – Test circuit to verify re-ignition behaviour of the making and breaking unit . 148
Figure J.3 – Test circuit on the resistor switch . 149
Figure J.4 – Example of test circuit for capacitive current switching tests on the making
and breaking unit . 150
Figure J.5 – Example of test circuit for capacitive current switching tests on the resistor
switch . 151
Figure K.1 – Example of combined current and voltage injection circuit with application
of full test voltage to earth . 153
Figure K.2 – Example of combined current and voltage injection circuit with separated
application of test voltage . 154

Table 1 – Tolerances and limits required during the high-current interval . 15
Table 2 – Test circuits for test duties T100s and T100a . 21
Table 3 – Test parameters during three-phase interruption for test-duties T10, T30,
T60 and T100s, k = 1,5 . 21
pp
Table 4 – Test parameters during three-phase interruption for test-duties T10, T30,
T60 and T100s, k = 1,3 . 22
pp
Table 5 – Test parameters during three phase interruption for test-duties T10, T30,

T60 and T100s, k = 1,2 . 23
pp
Table 6 – Symbols and abbreviated terms used for operation during synthetic tests . 33
Table 7 – Synthetic test methods for test duties T10, T30, T60, T100s, T100a, SP,
DEF, OP and SLF . 46
Table A.1 – Corrected TRV values for the first-pole-to-clear for k = 1,3 and
pp
f = 50 Hz . 54
r
Table A.2 – Corrected TRV values for the first-pole-to-clear for k = 1,3 and
pp
f = 60 Hz . 55
r
IEC 62271-101:2021 © IEC 2021 – 7 –
Table A.3 – Corrected TRV values for the first-pole-to-clear for k = 1,5 and
pp
f = 50 Hz . 57
r
Table A.4 – Corrected TRV values for the first-pole-to-clear for k = 1,5 and
pp
f = 60 Hz . 58
r
Table A.5 – Corrected TRV values for the first-pole-to-clear for k = 1,2 and
pp
f = 50 Hz . 58
r
Table A.6 – Corrected TRV values for the first-pole-to-clear for k = 1,2 and
pp
f = 60 Hz . 59
r
Table A.7 – Percentage of DC component and di/dt at current zero for first-pole-to-
clear for f = 50 Hz . 59
r
Table A.8 – Percentage of DC component and di/dt at current zero for first-pole-to-
clear for f = 60 Hz . 60
r
Table B.1 – Tolerances on test quantities for type tests . 67
Table D.1 – Demonstration of arcing times for k = 1,5 . 72
pp
Table D.2 – Alternative demonstration of arcing times for k = 1,5 . 74
pp
Table D.3 – Demonstration of arcing times for k = 1,3 . 76
pp
Table D.4 – Alternative demonstration of arcing times for k = 1,3 . 78
pp
Table D.5 – Demonstration of arcing times for k = 1,5 . 81
pp
Table D.6 – Alternative demonstration of arcing times for k = 1,5 . 83
pp
Table D.7 – Demonstration of arcing times for k = 1,3 . 85
pp
Table D.8 – Alternative demonstration of arcing times for k = 1,3 . 87
pp
Table D.9 – Procedure for combining k = 1,5 and 1,3 during test-duties T10, T30,
pp
T60 and T100s(b) . 89
Table D.10 – Procedure for combining k = 1,5 and 1,3 during test-duty T100a . 90
pp
Table E.1 – Test procedure for k = 1,5 and 2,5 . 92
pp
Table E.2 – Test procedure for k = 1,3 and 2,0 . 93
pp
Table E.3 – Simplified test procedure for k = 1,3 and 2,0 . 94
pp
Table E.4 – Test procedure for k = 1,2 . 95
pp
Table E.5 – Simplified test procedure for k = 1,2 . 95
pp
Table E.6 – Test procedure for asymmetrical currents for k = 1,5 . 96
pp
Table E.7 – Test procedure for asymmetrical currents for k = 1,3 . 98
pp
Table E.8 – Test procedure for asymmetrical currents for k = 1,2 . 100
pp
Table E.9 – Procedure for combining k = 1,3 and 1,5 for test-duties T10, T30, T60
pp
and T100s(b) . 101
Table E.10 – Procedure for combining k = 2,0 and 2,5 for test-duties OP1 and
pp
OP2(b) . 102
Table E.11 – Procedure for combining k = 1,5 and 1,3 for test-duty T100a . 103
pp
Table E.12 – Required test parameters for different asymmetrical conditions in the
case of k = 1,5, f = 50 Hz . 104
pp r
– 8 – IEC 62271-101:2021 © IEC 2021
Table E.13 – Required test parameters for different asymmetrical conditions in the
case of a k = 1,3, f = 50 Hz . 106
pp r
Table E.14 – Required test parameters for different asymmetrical conditions in the
case of k = 1,2, f = 50 Hz . 108
pp r
Table E.15 – Required test parameters for different asymmetrical conditions in the
case of k = 1,5, f = 60 Hz . 109
pp r
Table E.16 – Required test parameters for different asymmetrical conditions in the
case of k = 1,3, f = 60 Hz . 111
pp r
Table E.17 – Required test parameters for different asymmetrical conditions in the
case of k = 1,2, f = 60 Hz . 113
pp r
IEC 62271-101:2021 © IEC 2021 – 9 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR –

Part 101: Synthetic testing
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62271-101 has been prepared by subcommittee 17A: Switching
devices, of IEC technical committee 17: High-voltage switchgear and controlgear.
This third edition cancels and replaces the second edition published in 2012 and
Amendment 1:2017. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the second
edition:
a) alignment with the third edition of IEC 62271-100:2021;
b) update this document with the last methods and techniques used for synthetic tests;

– 10 – IEC 62271-101:2021 © IEC 2021
The text of this document is based on the following documents:
FDIS Report on voting
17A/1312/FDIS 17A/1315/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/standardsdev/publications.
This publication shall be read in conjunction with IEC 62271-100:2021, to which it refers. The
numbering of the subclauses of Clause 7 is the same as in IEC 62271‑100. However, not all
subclauses of IEC 62271-100 are addressed; merely those where synthetic testing has
introduced changes.
A list of all the parts in the IEC 62271 series, under the general title High-voltage switchgear
and controlgear, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of October 2021 have been included in this copy.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates that it
contains colours which are considered to be useful for the correct understanding of its
contents. Users should therefore print this document using a colour printer.

IEC 62271-101:2021 © IEC 2021 – 11 –
HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR –

Part 101: Synthetic testing
1 Scope
This part of IEC 62271 mainly applies to AC circuit-breakers within the scope of IEC 62271-100.
It provides the general rules for testing AC circuit-breakers, for making and breaking capacities
over the range of test duties described in 7.102 to 7.111 of IEC 62271-100:2021, by synthetic
methods.
It has been proven that synthetic testing is an economical and technically correct way to test
high-voltage AC circuit-breakers according to the requirements of IEC 62271-100 and that it is
equivalent to direct testing.
The methods an
...


SLOVENSKI STANDARD
01-november-2021
Nadomešča:
SIST EN 62271-101:2013
SIST EN 62271-101:2013/A1:2018
Visokonapetostne stikalne in krmilne naprave - 101. del: Sintetično preskušanje
(IEC 62271-100:2021)
High-voltage switchgear and controlgear - Part 101: Synthetic testing (IEC 62271-
100:2021)
Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 101: Synthetische Prüfung (IEC
62271-100:2021)
Appareillage à haute tension - Partie 101: Essais synthétiques (IEC 62271-100:2021)
Ta slovenski standard je istoveten z: EN IEC 62271-101:2021
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 62271-100

NORME EUROPÉENNE
EUROPÄISCHE NORM
August 2021
ICS 29.130.10 Supersedes EN 62271-100:2009 and all of its
amendments and corrigenda (if any)
English Version
High-voltage switchgear and controlgear - Part 100: Alternating
current circuit-breakers
(IEC 62271-100:2021)
Appareillage à haute tension - Partie 100: Disjoncteurs à Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil
courant alternatif 100: Wechselstrom-Leistungsschalter
(IEC 62271-100:2021) (IEC 62271-100:2021)
This European Standard was approved by CENELEC on 2021-08-11. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 62271-100:2021 E

EN IEC 62271-100:2021 (E)
European foreword
The text of document 17A/1299/FDIS, future edition 3 of IEC 62271-100, prepared by SC 17A
“Switching devices” of IEC/TC 17 “High-voltage switchgear and controlgear” was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN IEC 62271-100:2021.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022–05–11
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2024–08–11
document have to be withdrawn
This document supersedes EN 62271-100:2009 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 62271-100:2021 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 60137:2017 NOTE Harmonized as EN 60137:2017 (not modified)
IEC 62271-110 NOTE Harmonized as EN IEC 62271-110
IEC 60296 NOTE Harmonized as EN IEC 60296
IEC 60376 NOTE Harmonized as EN IEC 60376
IEC 60480 NOTE Harmonized as EN IEC 60480
EN IEC 62271-100:2021 (E)
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60050-151 2001 International Electrotechnical Vocabulary - -
(IEV) - Part 151: Electrical and magnetic
devices
+A1 2013
+A2 2014
+A3 2019
+A4 2020
IEC 60050-441 1984 International Electrotechnical Vocabulary - -
(IEV) - Part 441: Switchgear, controlgear
and fuses
+A1 2000
IEC 60050-442 1998 International Electrotechnical Vocabulary - -
(IEV) - Part 442: Electrical accessories
+A1 2015
+A2 2015
+A3 2019
IEC 60050-461 2008 International Electrotechnical Vocabulary - -
(IEV) - Part 461: Electric cables
IEC 60050-601 1985 International Electrotechnical Vocabulary - -
(IEV) - Part 601: Generation, transmission
and distribution of electricity - General
+A1 1998
+A2 2020
IEC 60050-614 2016 International Electrotechnical Vocabulary - -
(IEV) - Part 614: Generation, transmission
and distribution of electricity - Operation
IEC 60059 - IEC standard current ratings EN 60059 -
IEC 60060-1 - High-voltage test techniques - Part 1: EN 60060-1 -
General definitions and test requirements
EN IEC 62271-100:2021 (E)
IEC 60255-151 2009 Measuring relays and protection equipment EN 60255-151 2009
- Part 151: Functional requirements for
over/under current protection
IEC 60270 - High-voltage test techniques - Partial EN 60270 -
discharge measurements
IEC 62271-1 2017 High-voltage switchgear and controlgear - EN 62271-1 2017
Part 1: Common specifications for
alternating current switchgear and
controlgear
IEC 62271-101 - High-voltage switchgear and controlgear - EN 62271-101 -
Part 101: Synthetic testing
IEC 62271-102 2018 High-voltage switchgear and controlgear - EN IEC 62271-102 2018
Part 102: Alternating current disconnectors
and earthing switches
IEC 62271-200 2021 High-voltage switchgear and controlgear - EN IEC 62271-200 2021
Part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above
1 kV and up to and including 52 kV
IEC 62271-203 - High-voltage switchgear and controlgear - EN 62271-203 -
Part 203: Gas-insulated metal-enclosed
switchgear for rated voltages above 52 kV

IEC 62271-100 ®
Edition 3.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
High-voltage switchgear and controlgear –

Part 100: Alternating-current circuit-breakers

Appareillage à haute tension –

Partie 100: Disjoncteurs à courant alternatif

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.130.10 ISBN 978-2-8322-9885-5

– 2 – IEC 62271-100:2021  IEC 2021
CONTENTS
FOREWORD . 11
1 Scope . 13
2 Normative references . 13
3 Terms and definitions . 14
3.1 General terms and definitions . 15
3.2 Assemblies . 19
3.3 Parts of assemblies . 19
3.4 Switching devices . 19
3.5 Parts of circuit-breakers . 21
3.6 Operational characteristics . 25
3.7 Characteristic quantities . 27
3.8 Index of definitions . 43
4 Normal and special service conditions . 47
5 Ratings . 47
5.1 General . 47
5.2 Rated voltage (U ) . 48
r
5.3 Rated insulation level (U , U , U ) . 48
d p s
5.4 Rated frequency (f ) . 48
r
5.5 Rated continuous current (I ) . 48
r
5.6 Rated short-time withstand current (I ) . 48
k
5.7 Rated peak withstand current (I ) . 48
p
5.8 Rated duration of short-circuit (t ) . 48
k
5.9 Rated supply voltage of auxiliary and control circuits (U ) . 48
a
5.10 Rated supply frequency of auxiliary and control circuits . 48
5.11 Rated pressure of compressed gas supply for controlled pressure systems . 48
5.101 Rated short-circuit breaking current (I ) . 49
sc
5.102 Rated first-pole-to-clear factor (k ) for terminal fault . 52
pp
5.103 Rated short-circuit making current . 52
5.104 Rated operating sequence . 52
5.105 Rated out-of-phase making and breaking current . 52
5.106 Rated capacitive currents. 53
6 Design and construction . 55
6.1 Requirements for liquids . 55
6.2 Requirements for gases . 55
6.3 Earthing . 55
6.4 Auxiliary and control equipment and circuits . 56
6.5 Dependent power operation . 56
6.6 Stored energy operation . 56
6.7 Independent unlatched operation (independent manual or power operation) . 56
6.8 Manually operated actuators . 56
6.9 Operation of releases . 56
6.10 Pressure/level indication . 57
6.11 Nameplates. 58

IEC 62271-100:2021  IEC 2021 – 3 –
6.12 Locking devices . 60
6.13 Position indication . 60
6.14 Degrees of protection provided by enclosures . 60
6.15 Creepage distances for outdoor insulators . 60
6.16 Gas and vacuum tightness . 60
6.17 Tightness for liquid systems . 60
6.18 Fire hazard (flammability) . 60
6.19 Electromagnetic compatibility (EMC) . 60
6.20 X-ray emission . 60
6.21 Corrosion . 60
6.22 Filling levels for insulation, switching and/or operation . 61
6.101 Requirements for simultaneity of poles during single closing and single
opening operations . 61
6.102 General requirement for operation . 61
6.103 Pressure limits of fluids for operation . 61
6.104 Vent outlets . 62
6.105 Time quantities . 62
6.106 Mechanical loads . 62
6.107 Circuit-breaker classification . 63
7 Type tests . 65
7.1 General . 65
7.2 Dielectric tests . 67
7.3 Radio interference voltage (RIV) test . 72
7.4 Resistance measurement . 72
7.5 Continuous current tests . 73
7.6 Short-time withstand current and peak withstand current tests . 74
7.7 Verification of the protection . 74
7.8 Tightness tests . 74
7.9 Electromagnetic compatibility tests (EMC) . 74
7.10 Additional tests on auxiliary and control circuits . 75
7.11 X-radiation test procedure for vacuum interrupters . 75
7.101 Mechanical and environmental tests . 75
7.102 Miscellaneous provisions for making and breaking tests . 88
7.103 General considerations for making and breaking tests . 106
7.104 Demonstration of arcing times . 113
7.105 Short-circuit test quantities . 132
7.106 Short-circuit test procedure . 155
7.107 Terminal fault tests . 157
7.108 Additional short-circuit tests . 161
7.109 Short-line fault tests . 164
7.110 Out-of-phase making and breaking tests . 175
7.111 Capacitive current tests . 177
7.112 Requirements for making and breaking tests on class E2 circuit-breakers
having a rated voltage above 1 kV up to and including 52 kV . 191
8 Routine tests . 192
8.1 General . 192
8.2 Dielectric test on the main circuit . 193
8.3 Tests on auxiliary and control circuits . 195

– 4 – IEC 62271-100:2021  IEC 2021
8.4 Measurement of the resistance of the main circuit . 195
8.5 Tightness test . 195
8.6 Design and visual checks . 195
8.101 Mechanical operating tests . 195
9 Guide to the selection of switchgear and controlgear (informative) . 197
9.101 General . 197
9.102 Selection of rated values for service conditions . 199
9.103 Selection of rated values for fault conditions . 201
9.104 Selection for electrical endurance in networks of rated voltage above 1 kV

and up to and including 52 kV . 205
9.105 Selection for switching of capacitive loads . 205
10 Information to be given with enquiries, tenders and orders (informative) . 205
10.1 General . 205
10.2 Information with enquiries and orders . 205
10.3 Information to be given with tenders. 206
11 Transport, storage, installation, operation instructions and maintenance. 208
11.1 General . 208
11.2 Conditions during transport, storage and installation . 208
11.3 Installation . 208
11.4 Operating instructions . 214
11.5 Maintenance . 214
11.101 Resistors and capacitors . 215
12 Safety . 215
13 Influence of the product on the environment . 215
Annex A (normative) Calculation of TRVs for short-line faults from rated

characteristics . 216
A.1 Basic approach . 216
A.2 Transient voltage on line side . 219
A.3 Transient voltage on source side . 219
A.4 Examples of calculations . 223
Annex B (normative) Tolerances on test quantities during type tests . 226
Annex C (normative) Records and reports of type tests. 235
C.1 Information and results to be recorded . 235
C.2 Information to be included in type test reports . 235
Annex D (normative) Method of determination of the prospective TRV . 239
D.1 General . 239
D.2 Drawing the envelope . 239
D.3 Determination of parameters . 240
Annex E (normative) Methods of determining prospective TRV waves . 243
E.1 General . 243
E.2 General summary of the recommended methods . 245
E.3 Detailed consideration of the recommended methods . 246
E.4 Comparison of methods . 257
Annex F (informative) Requirements for breaking of transformer-limited faults by
circuit-breakers with rated voltage higher than 1 kV . 261
F.1 General . 261
F.2 Circuit-breakers with rated voltage less than 100 kV . 262

IEC 62271-100:2021  IEC 2021 – 5 –
F.3 Circuit-breakers with rated voltage from 100 kV to 800 kV . 264
F.4 Circuit-breakers with rated voltage higher than 800 kV . 264
Annex G (normative) Use of mechanical characteristics and related requirements . 265
Annex H (normative) Requirements for making and breaking test procedures for
metal-enclosed and dead tank circuit-breakers . 266
H.1 General . 266
H.2 Reduced number of making and breaking units for testing purposes . 266
H.3 Tests for single pole in one enclosure . 267
H.4 Tests for three poles in one enclosure . 270
Annex I (normative) Requirements for circuit-breakers with opening resistors . 272
I.1 General . 272
I.2 Switching performance to be verified . 272
I.3 Insertion time of the resistor. 285
I.4 Current carrying performance . 285
I.5 Dielectric performance . 285
I.6 Mechanical performance . 285
I.7 Requirements for the specification of opening resistors. 285
I.8 Examples of recovery voltage waveshapes . 285
Annex J (normative) Verification of capacitive current breaking in presence of single
or two-phase earth faults . 292
J.1 General . 292
J.2 Test voltage . 292
J.3 Test current . 292
J.4 Test-duty . 293
J.5 Criteria to pass the tests . 293
Bibliography . 294

Figure 1 – Typical oscillogram of a three-phase short-circuit make-break cycle. 29
Figure 2 – Circuit-breaker without switching resistors – Opening and closing operations . 30
Figure 3 – Circuit breaker without switching resistors – Close-open cycle . 31
Figure 4 – Circuit-breaker without switching resistors – Reclosing (auto-reclosing) . 32
Figure 5 – Circuit-breaker with switching resistors – Opening and closing operations . 33
Figure 6 – Circuit-breaker with switching resistors – Close-open cycle . 34
Figure 7 – Circuit-breaker with switching resistors – Reclosing (auto-reclosing) . 35
Figure 8 – Determination of short-circuit making and breaking currents, and of
percentage DC component . 50
Figure 9 – Percentage DC component in relation to the time interval from the initiation

of the short-circuit for the different time constants . 51
Figure 10 – Example of wind velocity measurement . 82
Figure 11 – Test sequence for low temperature test . 84
Figure 12 – Test sequence for high temperature test . 85
Figure 13 – Humidity test . 87
Figure 14 – Example of reference mechanical characteristics (idealised curve) . 91
Figure 15 – Reference mechanical characteristics of Figure 14 with the envelopes
centred over the reference curve (+5 %, –5 %) . 92

– 6 – IEC 62271-100:2021  IEC 2021
Figure 16 – Reference mechanical characteristics of Figure 14 with the envelope fully
displaced upward from the reference curve (+10 %, –0 %) . 93
Figure 17 – Reference mechanical characteristics of Figure 14 with the envelope fully

displaced downward from the reference curve (+0 %, –10 %) . 93
Figure 18 – Equivalent testing set-up for unit testing of circuit-breakers with more than
one separate making and breaking units . 95
Figure 19 – Earthing of test circuits for single-phase short-circuit tests, k = 1,5 . 96
pp
Figure 20 – Earthing of test circuits for single-phase short-circuit tests, k = 1,3 . 97
pp
Figure 21 – Test circuit for single-phase out-of-phase tests . 97
Figure 22 – Test circuit for out-of-phase tests using two voltages separated by 120
electrical degrees . 98
Figure 23 – Test circuit for out-of-phase tests with one terminal of the circuit-breaker
earthed (subject to agreement of the manufacturer) . 98
Figure 24 – Example of prospective test TRV with four-parameter envelope which
satisfies the conditions to be met during type test – Case of specified TRV with four-
parameter reference line . 99
Figure 25 – Example of prospective test TRV with two-parameter envelope which
satisfies the conditions to be met during type test: case of specified TRV with two-
parameter reference line . 100
Figure 26 – Example of prospective test TRV-waves and their combined envelope in
two-part test. 101
Figure 27 – Earthing of test circuits for three-phase short-circuit tests, k = 1,5 . 108
pp
Figure 28 – Earthing of test circuits for three-phase short-circuit tests, k = 1,3 . 109
pp
Figure 29 – Determination of power frequency recovery voltage . 111
Figure 30 – Graphical representation of the time parameters for the demonstration of

arcing times in three-phase tests of test-duty T100a . 114
Figure 31 – Graphical representation of an example of the three valid symmetrical
breaking operations for k = 1,5 . 115
pp
Figure 32 – Graphical representation of the three valid symmetrical breaking
operations for k = 1,2 or 1,3 . 116
pp
Figure 33 – Graphical representation of an example of the three valid asymmetrical

breaking operations for k = 1,5 . 120
pp
Figure 34 – Graphical representation of an example of the three valid asymmetrical
breaking operations for k = 1,2 or 1,3 . 121
pp
Figure 35 – Example of a graphical representation of the three valid symmetrical
breaking operations for single-phase tests in substitution of three-phase conditions for
k = 1,5 . 125
pp
Figure 36 – Example of a graphical representation of an example of the three valid
symmetrical breaking operations for single-phase tests in substitution of three-phase
conditions for k = 1,2 or 1,3 . 126
pp
Figure 37 – Example of a graphical representation of an example of the three valid
asymmetrical breaking operations for single-phase tests in substitution of three-phase
conditions for k = 1,5 . 128
pp
Figure 38 – Example of a graphical representation of an example of the three valid
asymmetrical breaking operations for single-phase tests in substitution of three-phase

for k = 1,2 and 1,3 . 129
pp
IEC 62271-100:2021  IEC 2021 – 7 –
Figure 39 – Graphical representation of the arcing window and the pole factor k ,
p
determining the TRV of the individual pole, for systems with a k of 1,2 . 131
pp
Figure 40 – Graphical representation of the arcing window and the pole factor k ,
p
determining the TRV of the individual pole, for systems with a k of 1,3 . 131
pp
Figure 41 – Graphical representation of the arcing window and the pole factor k ,
p
determining the TRV of the individual pole, for systems with a k of 1,5 . 132
pp
Figure 42 – Representation of a specified TRV by a 4-parameter reference line and a
delay line . 135
Figure 43 – Representation of a specified TRV by a two-parameter reference line and

a delay line . 136
Figure 44 – Basic circuit for terminal fault with ITRV . 136
Figure 45 – Representation of ITRV in relationship to TRV . 137
Figure 46 – Example of line transient voltage with time delay with non-linear rate of rise . 151
Figure 47 – Necessity of additional single-phase tests and requirements for testing. 162
Figure 48 – Basic circuit arrangement for short-line fault testing and prospective TRV-
circuit-type a) according to 7.109.3: Source side and line side with time delay . 166
Figure 49 – Basic circuit arrangement for short-line fault testing – circuit type b1)
according to 7.109.3: Source side with ITRV and line side with time delay . 167
Figure 50 – Basic circuit arrangement for short-line fault testing – circuit type b2)

according to 7.109.3: Source side with time delay and line side without time delay . 168
Figure 51 – Example of a line side transient voltage with time delay . 169
Figure 52 – Flow chart for the choice of short-line fault test circuits . 170
Figure 53 – Compensation of deficiency of the source side time delay by an increase
of the excursion of the line side voltage . 172
Figure 54 – Recovery voltage for capacitive current breaking tests . 188
Figure 55 – Reclassification procedure for line and cable-charging current tests . 190
Figure 56 – Reclassification procedure for capacitor bank current tests . 191
Figure A.1 – Typical graph of line and source side TRV parameters – Line side and
source side with time delay . 218
Figure A.2 – Actual course of the source side TRV for short-line fault L , L and L . 221
90 75 60
Figure A.3 – Typical graph of line and source side TRV parameters – Line side and

source side with time delay, source side with ITRV . 222
Figure D.1 – Representation by four parameters of a prospective TRV of a circuit –
Case D.2 c) 1) . 241
Figure D.2 – Representation by four parameters of a prospective TRV of a circuit –
Case D.2 c) 2) . 241
Figure D.3 – Representation by four parameters of a prospective TRV of a circuit –

Case D.2 c) 3) i) . 242
Figure D.4 – Representation by two parameters of a prospective TRV of a circuit –
Case D.2 c) 3) ii) . 242
Figure E.1 – Effect of depression on the peak value of the TRV . 244
Figure E.2 – Breaking with arc-voltage present . 246
Figure E.3 – TRV in case of ideal breaking . 247
Figure E.4 – Breaking with pronounced premature current-zero . 247
Figure E.5 – Relationship between the values of current and TRV occurring in test and
those prospective to the system . 248

– 8 – IEC 62271-100:2021  IEC 2021
Figure E.6 – Breaking with post-arc current . 249
Figure E.7 – Schematic diagram of power-frequency current injection apparatus . 250
Figure E.8 – Sequence of operation of power-frequency current injection apparatus . 251
Figure E.9 – Schematic diagram of capacitance injection apparatus . 253
Figure E.10 – Sequence of operation of capacitor-injection apparatus . 254
Figure F.1 – First example of transformer-limited fault (also called transformer-fed fault) . 261
Figure F.2 – Second example of transformer-limited fault (also called transformer-
secondary fault) . 262
Figure H.1 – Test configuration considered in Table H.1, Table H.2 and Table H.3 . 268
Figure I.1 – Typical system configuration for breaking by a circuit-breaker with opening
resistors . 272
Figure I.2 – Test circuit for test-duties T60 and T100 . 274
Figure I.3 – Test circuit for test-duties T10, T30 and OP2 . 275
Figure I.4 – Example of an underdamped TRV for T100s(b), U = 1 100 kV I = 50 kA,
r sc
f = 50 Hz . 277
r
Figure I.5 – Example of an overdamped TRV for T10, U = 1 100 kV I = 50 kA, f =
r sc r
50 Hz . 278
Figure I.6 – Example of a test circuit for short-line fault test-duty L . 279
Figure I.7 – Example of real line simulation for short-line fault test-duty L based on
U = 1 100 kV, I = 50 kA and f = 50 Hz . 280
r sc r
Figure I.8 – Typical recovery voltage waveshape of capacitive current breaking on a
circuit-breaker equipped with opening resistors. 282
Figure I.9 – Typical recovery voltage waveshape of T10 (based on U = 1 100 kV, I =
r sc
50 kA and f = 50 Hz) on the resistor switch of a circuit-breaker equipped with opening
r
resistors . 283
Figure I.10 – TRV waveshapes for high short-circuit current breaking operation . 286
Figure I.11 – Currents in case of high short-circuit current breaking operation . 287
Figure I.12 – TRV shapes for low short-circuit current breaking operation . 288
Figure I.13 – Currents in case of low short-circuit current breaking operation . 289
Figure I.14 – Voltage waveshapes for line-charging current breaking operation . 290
Figure I.15 – Current waveshapes for line-charging current breaking operation . 291

Table 1 – Preferred values of rated capacitive currents . 54
Table 2 – Nameplate information . 59
Table 3 – Examples of static horizontal and vertical forces for static terminal load . 63
Table 4 – Number of mechanical operations . 64
Table 5 – Type tests . 66
Table 6 – Invalid tests . 67
Table 7 – Test requirements for voltage tests as condition check for metal-enclosed
circuit-breakers . 70
Table 8 – Number of operating sequences . 79
Table 9 – Standard values of ITRV –
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...