Abstract

EN 50525-3-41 applies to non-sheathed single core cables insulated with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1  Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 450/750 V. NOTE 2  Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. The cables are intended for fixed wiring applications. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 3  HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-41 should be read in conjunction with EN 50525-1, which specifies general requirements.

Status
Published
Public Enquiry End Date
28-Feb-2009
Publication Date
12-Jun-2011
Technical Committee
IEKA - Electric cables
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
08-Jun-2011
Due Date
13-Aug-2011
Completion Date
13-Jun-2011

Buy Documents

Standard

SIST EN 50525-3-41:2011

English language (11 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 50525-3-41:2011 is the Slovenian adoption of EN 50525-3-41:2011 from CENELEC. It specifies single-core, non-sheathed low-voltage energy cables with halogen-free crosslinked insulation, low smoke emission and low corrosive gas release for fixed wiring and internal wiring applications. The document is written for cable manufacturers, test laboratories, specifiers, installers and buyers who need to identify the right cable family and verify its performance.

What does SIST EN 50525-3-41:2011 specify?

SIST EN 50525-3-41:2011 applies to non-sheathed single-core cables insulated with halogen-free crosslinked compound and intended to give low smoke and low corrosive gas release in fire conditions. The cable family is rated up to and including 450/750 V (U0/U), is intended for fixed wiring applications, and has a maximum conductor operating temperature of 90 °C.

The document is organized into four clauses, two normative annexes and a bibliography.

AnnexWhat it covers
Annex ATests for cables to EN 50525-3-41, with applicability by cable type
Annex BGeneral data, including dimensions and minimum insulation resistance

Clause 4 divides the cable family into fixed-wiring and internal-wiring versions:

  • H07Z-U and H07Z-R for fixed wiring
  • H07Z-K for fixed wiring
  • H05Z-U and H05Z-K for internal wiring

What are the key requirements of SIST EN 50525-3-41:2011?

SIST EN 50525-3-41:2011 sets out the conductor class, insulation type, cable designation, dimensions and fire-performance checks for each cable variant. In practice, this tells the user what construction to specify and which tests to use to confirm the cable meets the part.

Cable construction and designation

Clause 4 requires each version to use the conductor class linked to its CENELEC code in EN 60228. H07Z-U and H05Z-U use class 1 conductors, H07Z-R uses class 2 conductors, and H07Z-K and H05Z-K use class 5 conductors. For the reader, this means the cable designation itself tells you whether you are selecting a rigid or flexible conductor construction.

Clause 4 also requires polyolefin cross-linked insulation of Type EI 5 to EN 50363-5. That matters because the insulation material is part of the fire and temperature performance, not just the cable size.

Size ranges and marking

Clause 4 gives separate size ranges for each cable family and links the cable dimensions to Tables B.1 to B.4. It also requires the CENELEC code marking to comply with Clause 6 of EN 50525-1. In practice, this is what a purchaser, inspector or installer checks on the cable sheath marking and in the datasheet.

Electrical, dimensional and fire-related performance

Clause 4 requires each cable to comply with EN 50525-1 plus the particular requirements of this part. Annex A then ties those requirements to the test programme: conductor resistance, voltage tests, insulation resistance at 90 °C, insulation fault checks, constructional inspection, thickness and diameter measurements, insulation material tests, low-temperature impact, flame propagation, smoke emission, and halogen assessment.

For fire performance, the document requires compliance with EN 60332-1-2 for vertical flame propagation and EN 61034-2 for smoke density. For the reader, that means the cable family is intended where reduced smoke and fire spread are important, and the test evidence must support that claim.

Smoke performance

Clause 4 requires all sizes to exceed 60 % light transmittance during the EN 61034-2 test. That is the practical acceptance point for low smoke emission and is often the key result needed in specification review or compliance testing.

What terms does SIST EN 50525-3-41:2011 define?

  • H07Z-U - CENELEC code for a fixed-wiring cable with a class 1 conductor.
  • H07Z-R - CENELEC code for a fixed-wiring cable with a class 2 conductor.
  • H07Z-K - CENELEC code for a fixed-wiring cable with a class 5 conductor.
  • H05Z-U - CENELEC code for an internal-wiring cable with a class 1 conductor.
  • H05Z-K - CENELEC code for an internal-wiring cable with a class 5 conductor.
  • Class 1, class 2 and class 5 conductors - conductor constructions defined in EN 60228 and used here to separate rigid and flexible versions.
  • Type EI 5 - the halogen-free crosslinked polyolefin insulation material specified in EN 50363-5.
  • U0/U - the rated voltage designation used for this cable family, up to and including 450/750 V.

Who uses SIST EN 50525-3-41:2011?

Cable manufacturers use SIST EN 50525-3-41:2011 to design the cable construction, choose the conductor class, select the insulation material and apply the correct code marking. Test laboratories and certification bodies use it to run the required electrical, dimensional, flame, smoke and halogen-related tests.

Engineers, quality managers and buyers use it when specifying cables for fixed wiring, internal wiring, switchgear and control gear, especially where low smoke and halogen-free performance are required. Installers and panel builders use it to confirm they are fitting the right H07Z or H05Z variant for the application and voltage level.

What changed in SIST EN 50525-3-41:2011 from the previous edition?

SIST EN 50525-3-41:2011 supersedes HD 22.9 S3:2007.

Which standards are used with SIST EN 50525-3-41:2011?

StandardWhat it contributes
EN 50525-1General requirements, marking rules, terms and the halogen assessment reference
EN 50363-5Halogen-free crosslinked insulating compounds, including Type EI 5
EN 50395Electrical test methods used in Annex A
EN 50396Non-electrical test methods, including thickness and diameter measurements
EN 60228Conductor classes for rigid and flexible conductors
EN 60332-1-2Vertical flame propagation test under fire conditions
EN 60811-1-4Low-temperature impact test for insulation materials
EN 61034-2Smoke density measurement for cables burning under defined conditions
EN 60719Calculation of lower and upper limits for average outer dimensions
HD 516Guidance on the safe use of these cables

What does the SIST EN 50525-3-41:2011 document contain?

Annex A provides the test matrix for each cable variant, so users can see which tests apply to H07Z-U, H07Z-R, H07Z-K, H05Z-U and H05Z-K. Annex B provides general data tables for rigid and flexible conductors, including insulation thickness, mean overall diameter and minimum insulation resistance at 90 °C.

The main clause 4 is structured by use case, first fixed wiring and then internal wiring, which makes it easy to match a cable code to a job. The bibliography points readers to EN 60719 for dimension calculations and HD 516 for guidance on safe use.

Relations

Effective Date
28-Jan-2023
Effective Date
09-Feb-2026
Effective Date
09-Feb-2026
Effective Date
03-Feb-2026
Effective Date
06-Jan-2009

Buy Documents

Standard

SIST EN 50525-3-41:2011

English language (11 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

SIST EN 50525-3-41:2011 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-41: Cables with special fire performance - Single core non-sheathed cables with halogen-free crosslinked insulation, and low emission of smoke". This standard covers: EN 50525-3-41 applies to non-sheathed single core cables insulated with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 450/750 V. NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. The cables are intended for fixed wiring applications. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-41 should be read in conjunction with EN 50525-1, which specifies general requirements.

EN 50525-3-41 applies to non-sheathed single core cables insulated with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 450/750 V. NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. The cables are intended for fixed wiring applications. The maximum conductor operating temperature for each of the cables in this standard is 90 °C. NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-41 should be read in conjunction with EN 50525-1, which specifies general requirements.

SIST EN 50525-3-41:2011 is classified under the following ICS (International Classification for Standards) categories: 29.060.20 - Cables. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 50525-3-41:2011 has the following relationships with other standards: It is inter standard links to SIST HD 22.9 S3:2007, SIST EN 1648-1:2018, SIST EN 1648-2:2018, SIST EN 60335-1:2012/A13:2017, SIST HD 22.9 S3:2007. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN 50525-3-41:2011 is associated with the following European legislation: EU Directives/Regulations: 2006/95/EC, 2014/35/EU. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

SIST EN 50525-3-41:2011 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 4 Heat resistant cables (90 °C)
  • 4.1 Cables for fixed wiring – H07Z-U and H07Z-R
  • 4.2 Cables for fixed wiring – H07Z-K
  • 4.3 Cables for internal wiring – H05Z-U
  • 4.4 Cables for internal wiring – H05Z-K
  • Annex A
  • 1 Electrical tests
  • 1.1 Resistance of conductors T, S 50395 5 X X X X
  • 1.3 Insulation resistance at 90 °C T 50395 8.1 X X X X
  • 1.4 Absence of faults in insulation R 50395 10 X X X X
  • 2 Constructional and dimensional
  • 2.1 Checking of compliance with T, S 50525-1 Inspection X X X X
  • 2.2 Measurement of thickness of T, S 50396 4.1 X X X X
  • 2.3 Measurement of overall diameter T, S 50396 4.4 X X X X
  • 3 Insulation material tests
  • 4 Impact test at - 5 °C T 60811-1-4 8.5 X X X X
  • 5 Tests under fire conditions
  • 5.1 Test on single vertical cable T 60332-1-2 - X X X X
  • 5.2 Smoke emission T 61034-2 - X X X X
  • 6 Assessment of halogens for all non-
  • Annex B
  • Bibliography

1 Scope

EN 50525-3-41 applies to non-sheathed single core cables insulated with halogen-free crosslinked compound and having low emission of smoke and corrosive gases when exposed to fire.

NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U /U up to and including 450/750 V.

NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. The cables are intended for fixed wiring applications.

The maximum conductor operating temperature for each of the cables in this standard is 90 °C.

NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-41 should be read in conjunction with EN 50525-1, which specifies general requirements.

2 Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE One or more references to the standards below are in respect of a specific sub-division of that standard, for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times, the latest version applies.

EN 50363-5 Insulating, sheathing and covering materials for low voltage energy cables - Part 5: Halogen-free, cross-linked insulating compounds EN 50395 Electrical test methods for low voltage energy cables EN 50396 Non electrical test methods for low voltage energy cables EN 50525-1 Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U /U) - Part 1: General requirements

EN 60228 Conductors of insulated cables (IEC 60228) EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame (IEC 60332-1-2) EN 60811-1-4 Insulating and sheathing materials of electric and optical cables - Common test methods - Part 1-4: General application - Tests at low temperature (IEC 60811-1-4) EN 61034-2 Measurement of smoke density of cables burning under defined conditions - Part 2: Test procedure and requirements (IEC 61034-2)

SIST EN 50525-3-41:2011 - 5 - EN 50525-3-41:2011

3 Terms and definitions

For the purposes of this document the terms and definitions given in Clause 3 of EN 50525-1 apply.

4 Heat resistant cables (90 °C)

4.1 Cables for fixed wiring – H07Z-U and H07Z-R

4.1.1 Construction
4.1.1.1 Conductor

The conductor shall be class 1 or class 2, according to EN 60228.

4.1.1.2 Sizes of cable

The sizes of cable shall be:

2 2 - class 1 – 1,5 mm to 10 mm ; 2 2 - class 2 – 1,5 mm to 630 mm .

4.1.1.3 Insulation

The insulation shall be a polyolefin cross-linked material of Type EI 5 to EN 50363-5 applied around the conductor.

4.1.1.4 Marking

The cable shall be marked with the CENELEC code H07Z-U for cables with class 1 conductor, or H07Z-R for cables with class 2 conductor. The marking shall comply with Clause 6 of EN 50525-1.

4.1.2 Requirements

Each cable shall comply with the appropriate requirements given in EN 50525-1, and the particular requirements of this Part.

Testing shall be in accordance with Annex A, and the relevant tests indicated in column 6. The dimensions of the cables shall conform to Table B.1 for the relevant size. When tested in accordance with the method and procedure given in EN 61034-2, all sizes of cable shall exceed 60 % light transmittance throughout the test.

...