ISO/FDIS 15779
(Main)Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements
Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements
ISO 15779:2011 specifies requirements and test methods for components and gives recommendations for the design, installation, testing, maintenance and safety of condensed aerosol firefighting systems in buildings, plants or other structures, and the characteristics of the extinguishants and types of fire for which they are a suitable extinguishing medium. It covers total flooding systems primarily related to buildings, plant and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by ISO 15779:2011. Any local applications require a pre-engineered and pre-designed system that shall be tested and approved for a specific application by a relevant authority.
Systèmes d'extinction d'incendie utilisant des aérosols — Exigences et méthodes d'essai pour la conception des composants et des systèmes, l'installation et l'entretien — Exigences générales
General Information
- Status
- Not Published
- Technical Committee
- ISO/TC 21/SC 8 - Gaseous media and firefighting systems using gas
- Drafting Committee
- ISO/TC 21/SC 8 - Gaseous media and firefighting systems using gas
- Current Stage
- 5020 - FDIS ballot initiated: 2 months. Proof sent to secretariat
- Start Date
- 04-Feb-2026
- Completion Date
- 04-Feb-2026
Relations
- Effective Date
- 29-Oct-2022
Overview
ISO/FDIS 15779 outlines the essential requirements and test methods for condensed aerosol fire extinguishing systems, focusing on components, as well as system design, installation, and maintenance. Developed by ISO, this international standard provides a comprehensive framework to ensure the safety, effectiveness, and reliability of total flooding aerosol firefighting systems. It is specifically tailored for applications in buildings, plants, and other structures, using electrically non-conducting condensed aerosol extinguishants for which performance data is available for validation by independent authorities.
This standard offers vital guidelines for manufacturers, designers, system integrators, and facility managers involved in fire protection solutions, ensuring systems are compliant, tested, and safely operated throughout their lifecycle.
Key Topics
ISO/FDIS 15779 addresses several critical areas to help optimize fire safety:
System Components and Extinguishants
- Specifications for condensed aerosol generators and extinguishing agents
- Description of physical and chemical properties of aerosols used
Design and Installation
- Recommendations for system layout, design, and appropriate applications
- Guidelines for determining the correct quantity and placement of extinguishing units
Activation and Safety
- Requirements for activation devices (electrical, thermal, or other methods)
- Key safety considerations: toxicity, visibility post-discharge, turbulence, thermal hazards, and precautions for electrical hazards
Testing, Commissioning, and Maintenance
- Procedures for commissioning, acceptance testing, and routine inspection
- Maintenance requirements and staff training
Environmental and Compatibility Aspects
- Consideration of environmental impacts and compatibility with other extinguishing agents
- Limitations on use with potentially explosive atmospheres or temperature extremes
Performance Validation
- Methods for verifying the performance of systems and agents
- Emphasis on third-party validation and compliance documentation
Applications
Condensed aerosol fire extinguishing systems compliant with ISO/FDIS 15779 are widely used for:
Building Fire Protection
- Effective fire suppression in offices, commercial properties, data centers, and server rooms
Industrial and Plant Facilities
- Protection of machinery spaces, electrical control rooms, manufacturing lines, and sensitive equipment areas
Critical Infrastructure
- Safeguarding telecommunications sites, power generation facilities, and other essential infrastructure requiring non-conductive fire suppression
Validation Scope
- The standard is applicable to total flooding systems, not local or spot protection. Local applications require separate pre-engineered solutions, properly tested and approved for their specific context.
Related Standards
To develop a comprehensive fire protection strategy, ISO/FDIS 15779 should be considered in conjunction with related standards and regulatory frameworks, including:
- ISO 14520 series - Gaseous fire-extinguishing systems
- ISO 7240 series - Fire detection and alarm systems
- NFPA 2010 - Standard for Fixed Aerosol Fire-Extinguishing Systems
- Regional building and fire codes - Local fire safety regulations and best practices
For organizations committed to safety, efficiency, and operational compliance, aligning with the requirements of ISO/FDIS 15779 ensures modern, reliable, and internationally recognized condensed aerosol fire extinguishing systems. This not only enhances asset protection but also supports regulatory approval and peace of mind for facility owners and occupants.
Buy Documents
ISO/FDIS 15779 - Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements Released:21. 01. 2026
REDLINE ISO/FDIS 15779 - Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements Released:21. 01. 2026
Get Certified
Connect with accredited certification bodies for this standard

NSF International
Global independent organization facilitating standards development and certification.
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
ISO/FDIS 15779 is a draft published by the International Organization for Standardization (ISO). Its full title is "Condensed aerosol fire extinguishing systems — Requirements and test methods for components and system design, installation and maintenance — General requirements". This standard covers: ISO 15779:2011 specifies requirements and test methods for components and gives recommendations for the design, installation, testing, maintenance and safety of condensed aerosol firefighting systems in buildings, plants or other structures, and the characteristics of the extinguishants and types of fire for which they are a suitable extinguishing medium. It covers total flooding systems primarily related to buildings, plant and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by ISO 15779:2011. Any local applications require a pre-engineered and pre-designed system that shall be tested and approved for a specific application by a relevant authority.
ISO 15779:2011 specifies requirements and test methods for components and gives recommendations for the design, installation, testing, maintenance and safety of condensed aerosol firefighting systems in buildings, plants or other structures, and the characteristics of the extinguishants and types of fire for which they are a suitable extinguishing medium. It covers total flooding systems primarily related to buildings, plant and other specific applications, utilizing electrically non-conducting condensed aerosol fire extinguishants for which there are sufficient data currently available to enable validation of performance characteristics by an appropriate independent authority. Local applications of condensed aerosol extinguishing systems are not covered by ISO 15779:2011. Any local applications require a pre-engineered and pre-designed system that shall be tested and approved for a specific application by a relevant authority.
ISO/FDIS 15779 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO/FDIS 15779 has the following relationships with other standards: It is inter standard links to ISO 15779:2011. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ISO/FDIS 15779 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
FINAL DRAFT
International
Standard
ISO/TC 21/SC 8
Condensed aerosol fire
Secretariat: SA
extinguishing systems —
Voting begins on:
Requirements and test methods
2026-02-04
for components and system design,
Voting terminates on:
installation and maintenance —
2026-04-01
General requirements
Systèmes d'extinction d'incendie utilisant des aérosols —
Exigences et méthodes d'essai pour la conception des composants
et des systèmes, l'installation et l'entretien — Exigences générales
RECIPIENTS OF THIS DRAFT ARE INVITED TO SUBMIT,
WITH THEIR COMMENTS, NOTIFICATION OF ANY
RELEVANT PATENT RIGHTS OF WHICH THEY ARE AWARE
AND TO PROVIDE SUPPOR TING DOCUMENTATION.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL, TECHNO
LOGICAL, COMMERCIAL AND USER PURPOSES, DRAFT
INTERNATIONAL STANDARDS MAY ON OCCASION HAVE
TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL
TO BECOME STAN DARDS TO WHICH REFERENCE MAY BE
MADE IN NATIONAL REGULATIONS.
Reference number
FINAL DRAFT
International
Standard
ISO/TC 21/SC 8
Condensed aerosol fire
Secretariat: SA
extinguishing systems —
Voting begins on:
Requirements and test methods
for components and system design,
Voting terminates on:
installation and maintenance —
General requirements
Systèmes d'extinction d'incendie utilisant des aérosols —
Exigences et méthodes d'essai pour la conception des composants
et des systèmes, l'installation et l'entretien — Exigences générales
RECIPIENTS OF THIS DRAFT ARE INVITED TO SUBMIT,
WITH THEIR COMMENTS, NOTIFICATION OF ANY
RELEVANT PATENT RIGHTS OF WHICH THEY ARE AWARE
AND TO PROVIDE SUPPOR TING DOCUMENTATION.
© ISO 2026
IN ADDITION TO THEIR EVALUATION AS
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
BEING ACCEPTABLE FOR INDUSTRIAL, TECHNO
LOGICAL, COMMERCIAL AND USER PURPOSES, DRAFT
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
INTERNATIONAL STANDARDS MAY ON OCCASION HAVE
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
TO BE CONSIDERED IN THE LIGHT OF THEIR POTENTIAL
or ISO’s member body in the country of the requester.
TO BECOME STAN DARDS TO WHICH REFERENCE MAY BE
MADE IN NATIONAL REGULATIONS.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland Reference number
ii
Contents Page
Foreword .vi
Introduction .vii
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Use and limitations . 5
4.1 General .5
4.2 Aerosol agent description .5
4.2.1 Condensed aerosol .5
4.2.2 Physical characteristics .6
4.2.3 Extinguishing mechanism .6
4.3 Application .6
4.4 Activation device .6
4.4.1 General .6
4.4.2 Electrical activation device.6
4.4.3 Thermal activation device .6
4.4.4 Other methods of activation device .6
4.5 Limitation of use .6
4.6 Electrostatic discharge .7
4.7 Potentially explosive atmosphere .7
4.8 Temperature limitations .7
4.9 Compatibility with other extinguishants .7
4.10 Environment .7
5 Safety . 8
5.1 General .8
5.2 Toxicity .8
5.2.1 General .8
5.2.2 Condensed aerosols .8
5.3 Reduced visibility .9
5.3.1 General .9
5.3.2 Safety precautions .9
5.4 Turbulence .9
5.5 Thermal hazards . .9
5.5.1 Minimum thermal clearance .9
5.5.2 Removal of discharged generators .9
5.5.3 Hot work .9
5.5.4 Casing temperatures for condensed aerosol generators .9
5.6 Safety precautions .10
5.6.1 General .10
5.6.2 Specific requirements .10
5.7 Electrical hazards .10
5.8 Electrical earthing .11
5.9 Electrostatic discharge .11
6 Extinguishant concentrations .11
6.1 General .11
6.2 Design application density requirements .11
6.2.1 Fire classification .11
6.2.2 Class B fire.11
6.2.3 Class A solid burning surface fire. 12
6.2.4 EDP (electronic data processing) rooms, telecommunication and electronic risks . 12
6.3 Aerosol generator performance requirements . 12
6.3.1 Distribution coverage . 12
6.3.2 Effective discharge . 12
iii
6.3.3 Ambient temperature and humidity operation range . 13
6.3.4 Service life . 13
6.3.5 Vibration and shock resistance . 13
6.3.6 Corrosion . 13
6.3.7 Drop impact . 13
6.3.8 Actuation element . 13
6.3.9 Exposure to fire . . 13
6.4 Marking . 13
7 Specifications, plans and approvals . 14
7.1 Specifications .14
7.2 Enclosure .14
7.2.1 Venting and structural strength .14
7.2.2 Loss of extinguishant to adjacent hazards .14
7.2.3 Forced-air ventilating systems .14
7.2.4 Venting requirements . 15
7.3 Total flooding quantity . 15
7.3.1 General . 15
7.3.2 Safety factor . 15
7.4 Design application density adjustment .16
7.4.1 Effects of altitude and temperature .16
7.4.2 Effects of ventilation .16
7.4.3 Compensation for leakage through enclosure openings .16
7.5 Unit size and quantity of aerosol generators .16
7.5.1 Maximum or minimum protected height limitations.16
7.5.2 Minimum thermal clearance .16
7.5.3 Several smaller units versus few large units .17
7.5.4 Mounting locations .17
7.5.5 Quantity of aerosol generators .17
7.5.6 Multiple generator systems .17
7.6 Operating conditions .18
7.7 Duration of protection .18
7.8 System discharge .18
7.8.1 Discharge time .18
7.8.2 Effectiveness of discharge .18
7.8.3 Thermal clearance .18
7.8.4 Extended discharge .19
7.9 Detection, actuation and control systems .19
7.9.1 General .19
7.9.2 Automatic detection .19
7.9.3 Operating devices .19
7.9.4 Electric control equipment . . 20
7.9.5 Operating alarm indicators . 20
7.9.6 System isolate switch . 20
8 Commissioning and acceptance .21
8.1 General .21
8.2 Tests .21
8.2.1 General .21
8.2.2 Enclosure check .21
8.2.3 Review of design calculations .21
8.2.4 Review of the mechanical components of condensed aerosol generators . 22
8.2.5 Review of electrical components . 22
8.2.6 Preliminary functional tests . 23
8.2.7 System functional operational test . 23
8.2.8 Remote monitoring operations .24
8.2.9 Control panel primary power source .24
8.2.10 Completion of functional tests .24
8.2.11 Completion certificate and documentation .24
iv
9 Inspection, maintenance, testing and training .24
9.1 General .24
9.2 Inspection . 25
9.2.1 General . 25
9.2.2 Enclosures . 25
9.3 Maintenance . 26
9.3.1 General . 26
9.3.2 User's programme of inspection . 26
9.3.3 Service schedule . 26
9.4 Training . 26
Annex A (normative) Documentation requirements .27
Annex B (informative) Toxicity and visibility testing .28
Annex C (normative) Test methods.34
Annex D (normative) Extinguishing density/Coverage test procedure .43
Bibliography .69
v
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire
fighting, Subcommittee SC 8, Gaseous media and firefighting systems using gas.
This second edition cancels and replaces the first edition (ISO 15779:2011), which has been technically
revised.
The main changes are as follows:
— in 6.2.2 and 7.8.1, a requirement concerning the time taken to reach minimum design density from the
beginning of discharge has been added for Class B fires
— Clause C.12, Impact test, has been removed;
— in D.6.1.3.2, Wood crib test, the total preburn time has been changed from 6 min to 2 min;
— figures have been updated to improve clarity;
— in the Bibliography, the reference to ISO 14520-1 has been removed and a reference to ATEX Directive
has been added.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
vi
Introduction
The firefighting systems covered in this document are designed to provide a supply of condensed aerosol
extinguishing medium for the extinction of fire.
Several different methods for supplying condensed aerosol extinguishant to, and applying it at, the
required point of discharge for fire extinction have been developed in recent years, and there is a need for
dissemination of information on established systems and methods. This document has been prepared to
meet this need.
The requirements of this document are made in the light of the best technical data known to the working
group at the time of writing but, since a wide field is covered, it has been impracticable to consider every
possible factor or circumstance that can potentially affect implementation of the recommendations.
It has been assumed in the preparation of this document that the execution of its provisions is entrusted to
people appropriately qualified and experienced in the specification, design, installation, testing, approval,
inspection, operation and maintenance of systems and equipment, for whose guidance it has been prepared,
and who can be expected to exercise a duty of care to avoid unnecessary release of extinguishant.
It is important that the fire protection of a building or plant be considered as a whole. Condensed aerosol
extinguishing systems form only a part, albeit an important part, of the available facilities. Their adoption
does not remove the need to consider supplementary measures, such as the provision of portable fire
extinguishers or other mobile appliances for first aid or emergency use, or to deal with special hazards.
For many years, condensed aerosol extinguishants have been a recognized effective medium for the
extinction of flammable liquid fires and fires in the presence of electrical and ordinary Class A hazards.
However, it is important to note in the planning of comprehensive schemes that there can be hazards for
which these mediums are not suitable, and in certain circumstances or situations there can be dangers in
their use requiring special precautions.
Advice on these matters can be obtained from the appropriate manufacturer of either the extinguishant
or the extinguishing system, or both. Information can also be sought from the appropriate fire authority,
the health and safety authorities and insurers. In addition, reference should be made as necessary to other
national standards and statutory regulations of the particular country.
vii
FINAL DRAFT International Standard ISO/FDIS 15779:2026(en)
Condensed aerosol fire extinguishing systems —
Requirements and test methods for components and
system design, installation and maintenance — General
requirements
1 Scope
This document specifies the requirements and test methods for components of condensed aerosol
firefighting systems. It gives recommendations for the design, installation, testing, maintenance and safety
of these systems, as well as their application in buildings, plants or other structures. The characteristics
of the extinguishants in the condensed aerosol firefighting systems are also specified, as well as the types
of fire for which they are a suitable extinguishing medium. This document covers total flooding systems
primarily related to buildings, plants and other specific applications, utilizing electrically non-conducting
condensed aerosol fire extinguishants for which there are sufficient data currently available to enable
validation of performance characteristics by an appropriate independent authority.
Local applications of condensed aerosol extinguishing systems are not covered by this document. Any local
applications require a pre-engineered and pre-designed system which has been tested and approved for a
specific application by a relevant authority.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
ISO 3941, Classification of fires
EN 60068-2-6, Environmental testing — Part 2-6: Tests — Test Fc: Vibration (sinusoidal)
EN 60068-2-30, Environmental testing — Part 2-30: Tests — Test Db and guidance: Damp heat, cyclic (12 h +
12 h cycle)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/
3.1
aerosol generator
non-pressurized container that, when activated, generates a condensed aerosol (3.7) extinguishing agent
3.2
aerosol generator assembly
aerosol generator (3.1) with its mounting bracket
3.3
approved
acceptable to a relevant authority (3.4)
Note 1 to entry: In determining the acceptability of installations or procedures, equipment or materials, the authority
can base acceptance on conformance to the appropriate standards.
3.4
authority
organization, office or individual responsible for approving equipment, installations or procedures
3.5
automatic
performing a function without the necessity of intentional human intervention
3.6
competent person
person who is suitably trained, qualified by knowledge and practical experience, and with the necessary
instructions to enable the required system design, installation and maintenance
3.7
condensed aerosol
aerosol extinguishing agent
extinguishant
extinguishing medium consisting of finely divided solid particles, generally in the order of magnitude of
microns in diameter suspended in gas which is generated and distributed by a combustion process of a solid
aerosol-forming compound
3.8
coolant
heat-absorbing medium or process
3.9
design application density
extinguishing density multiplied by the safety factor, required for system design purposes
Note 1 to entry: Extinguishing density is the actual concentration of aerosol in the test room.
Note 2 to entry: The extinguishing density and the design application density are expressed in g/m .
3.10
discharge time
time from the generator activation until the end of its discharge
Note 1 to entry: Measured in s.
Note 2 to entry: The end of discharge is determined by the drop of the temperature (primary), sound (secondary) and
visual indication if possible.
3.11
effective mass
mass of discharged extinguishant required to achieve the design application density within the protected
volume within the specified system discharge time
3.12
electrical activation device
device which automatically operates via an electrical input and is arranged to initiate the aerosol-forming
compound (3.34).
3.13
electrical clearance
unobstructed air distance between the aerosol generator (3.1) components and unenclosed or uninsulated
live electrical components not at ground potential
3.14
emergency hold device
device that prevents the electrical actuation (3.12) of aerosol generators (3.1)
3.15
extinguishing density
effective minimum mass of discharged extinguishant per unit of enclosure volume required to extinguish
fire involving a specific fuel under defined experimental conditions, using a specific aerosol generator (3.1)
type and size, excluding any safety factor
Note 1 to entry: Measured in g/m .
3.16
family of condensed aerosol generators
range of aerosol generators (3.1) designed with the same solid compound, the same kind of cooling device,
discharge outlet, ignition device, layout and internal/external architecture, with variation in the mass of the
solid compound
3.17
hold time
period of time during which an extinguishant is required to maintain at least the extinguishing density to
ensure even distribution throughout the protected volume
3.18
hot work
grinding, welding, thermal cutting, oxygen cutting, thermal heating, oxygen heating and other related heat-
producing or spark-producing operations
3.19
ignition device
device that is able to ignite the solid aerosol-forming compound (3.34)
3.20
inspection
visual examination to give reasonable assurance that the extinguishing system is fully operable and has
not been activated or tampered with, and that there is no obvious physical damage or condition to prevent
operation
3.21
listed
systems or components that are included in a list published by a listing organization
3.22
listing organization
internationally recognized fire protection system or components test and certification organization
3.23
location drawing
layout diagram of protected volume clearly indicating the as-installed location of all aerosol generator
assemblies (3.2), controls, system isolate switch (3.36), emergency hold device (3.14), and associated
components of the firefighting system
3.24
maintenance
thorough check to give maximum assurance that the extinguishing system will operate as intended
Note 1 to entry: Maintenance includes a thorough examination and any necessary repair or replacement of system
components.
3.25
manual
requiring intentional intervention to accomplish a function
3.26
manufacturer
entity that manufactures a product or has a product designed or manufactured, and markets that product
under its name or trademark
3.27
mass median aerodynamic diameter
MMAD
particle size and distribution of any aerosol statistically, based on the weight and size of the particle, along
with the geometric standard deviation
3.28
monitoring
supervision of the operating integrity of an electrical, mechanical, pneumatic or hydraulic control feature of
a system
3.29
normally occupied area
area that is occupied by persons, under normal circumstances
3.30
normally unoccupied area
area not normally occupied by people, but which may be entered occasionally for brief periods
3.31
particulate concentration
concentration of the solid fraction of the aerosol in the protected space after system discharge at the design
application density
Note 1 to entry: Measured in g/m .
Note 2 to entry: This information is necessary to assess the potential health effects of accidental exposure to the agent
and the potential degree of visibility obscuration.
3.32
release
physical discharge or emission of extinguishant as a consequence of the aerosol generator’s actuation
3.33
safety factor
multiplier of the extinguishing density to determine the aerosol design application density
3.34
solid aerosol-forming compound
mixture of oxidant, combustible component and technical admixtures producing fire-extinguishing aerosol
upon ignition
3.35
system discharge time
time from the first generator activation until the end of the last generator discharge time to achieve the
design application density within the protected volume
Note 1 to entry: This time measurement is relevant to an extinguishing system of interconnected aerosol generators
(3.1) intended to protect the same hazard.
3.36
system isolate switch
key-operated or dual mode switch manual device that prevents the electrical actuation (3.12) of aerosol
generators by electrically isolating them from the released circuit
Note 1 to entry: The actuation of this device provides an indication of system isolation and shall result in an audible
and visual alarm of system impairment at the control panel.
Note 2 to entry: The intention is to prevent the discharge of agent into the hazard area when the system isolation
switch device is activated.
3.37
thermal activation device
device which automatically operates at a rated temperature and is arranged for the activation of the solid
aerosol-forming compound (3.34)
3.38
thermal clearance
minimum air distance between both a condensed aerosol (3.1) generator surface and its discharge ports and
either personnel, any structure or components sensitive to the temperature developed by the generator
during and following discharge
3.39
total flooding system
firefighting system arranged to discharge extinguishant into an enclosed space to achieve the appropriate
design application density
3.40
unoccupiable area
area which cannot be occupied due to dimensional or other physical constrains
EXAMPLE Shallow voids or cabinets.
3.41
user
entity for whom the system is designed, and who is responsible for operation and for ensuring the consistency
of performance as described by the manufacturer and for following the legal regulation
4 Use and limitations
4.1 General
The design, installation, testing and maintenance of aerosol fire-extinguishing systems shall be performed
by persons competent in this fire extinguishing system technology.
4.2 Aerosol agent description
4.2.1 Condensed aerosol
Condensed aerosol is an extinguishant consisting of finely divided solid particles, typically based on alkali
metal salts, and gases mainly comprised of nitrogen, carbon dioxide, carbon monoxide and water vapour.
Condensed aerosol is self-generated by a combustion process of a solid aerosol-forming compound contained
in a non-pressurized can, an aerosol generator. Aerosol generators also contain one or more actuation
device(s) designed to ignite the aerosol-forming compound and can have various cooling arrangements to
cool the aerosol prior to its release into a protected volume. The aerosol generating combustion process
provides sufficient energy for a rapid discharge rate and efficient distribution of the aerosol. No store
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
ISO/DISFDIS 15779:2025(en)
Style Definition
...
ISO/TC 21/SC 8
Style Definition
...
Style Definition
...
Secretariat: SA
Style Definition
...
Style Definition
Date: 2025-12-042026-01-20 .
Style Definition
...
th
ISO TC21SC8WG10 4 Meeting Edition
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Condensed aerosol fire extinguishing systems — Requirements and
Style Definition
...
test methods for components and system design, installation and
Style Definition
...
maintenance — General requirements
Style Definition
...
Style Definition
...
Systèmes d'extinction d'incendie utilisant des aérosols — Exigences et méthodes d'essai pour la conception des
Style Definition
...
composants et des systèmes, l'installation et l'entretien — Exigences générales
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
FDIS stage
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Style Definition
...
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779:2023(E2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
Formatted: Font: Bold
Formatted: HeaderCentered
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication
Formatted: Default Paragraph Font
may be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying,
Formatted: Adjust space between Latin and Asian text,
or posting on the internet or an intranet, without prior written permission. Permission can be requested from either ISO
Adjust space between Asian text and numbers
at the address below or ISO'sISO’s member body in the country of the requester.
ISO Copyright Officecopyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Formatted: zzCopyright address, Adjust space between Latin
and Asian text, Adjust space between Asian text and numbers
Phone: + 41 22 749 01 11
Formatted: French (France)
Email: copyright@iso.org
E-mail: copyright@iso.org
Website: www.iso.orgwww.iso.org
Formatted: zzCopyright address, Adjust space between Latin
and Asian text, Adjust space between Asian text and numbers
Published in Switzerland.
Formatted: FooterPageRomanNumber
ii © ISO 2023 – All rights reserved
ii
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779.2:2025:2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
Contents Page Formatted: Font: Bold
Formatted: HeaderCentered, Left
Foreword . xii
Formatted: Adjust space between Latin and Asian text,
Adjust space between Asian text and numbers
Introduction . xiv
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Use and limitations . 6
4.1 General. 6
4.2 Aerosol agent description . 6
4.3 Application . 6
4.4 Activation device . 7
4.5 Limitation of use. 7
4.6 Electrostatic discharge. 7
4.7 Potentially explosive atmosphere . 8
4.8 Temperature limitations . 8
4.9 Compatibility with other extinguishants . 8
4.10 Environment . 8
5 Safety . 8
5.1 General. 8
5.2 Toxicity . 9
5.3 Reduced visibility . 9
5.4 Turbulence . 10
5.5 Thermal hazards . 10
5.6 Safety precautions . 11
5.7 Electrical hazards . 11
5.8 Electrical earthing . 12
5.9 Electrostatic discharge. 12
6 Extinguishant concentrations . 12
6.1 General. 12
6.2 Design application density requirements. 13
6.3 Aerosol generator performance requirements . 14
6.4 Marking . 15
7 Specifications, plans and approvals . 15
7.1 Specifications . 15
7.2 Enclosure . 16
7.3 Total flooding quantity . 16
7.4 Design application density adjustment . 17
7.5 Unit size and quantity of aerosol generators . 18
7.6 Operating conditions . 19
7.7 Duration of protection . 20
7.8 System discharge . 20
7.9 Detection, actuation and control systems . 21
8 Commissioning and acceptance . 23
Formatted: Font: 10 pt
8.1 General. 23
Formatted: Font: 10 pt
8.2 Tests . 23
Formatted: FooterCentered, Left, Line spacing: single
9 Inspection, maintenance, testing and training. 27
Formatted: Font: 11 pt
9.1 General. 27
9.2 Inspection . 27 Formatted: FooterPageRomanNumber, Left, Space After: 0
pt, Line spacing: single
iii
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779:2023(E2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
9.3 Maintenance . 28
Formatted: Font: Bold
9.4 Training . 29
Formatted: HeaderCentered
Annex A (normative) Documentation requirements . 30
Annex B (informative) Toxicity and visibility testing . 31
Annex C (normative) Test methods . 41
Annex D (normative) Extinguishing density/Coverage test procedure . 51
Bibliography . 94
Foreword . 11
Introduction . 13
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Use and limitations . 6
4.1 General. 6
4.2 Aerosol agent description . 6
4.2.1 Condensed aerosol . 6
4.2.2 Physical characteristics . 6
4.2.3 Extinguishing mechanism . 6
4.3 Application . 6
4.4 Activation device . 7
4.4.1 General. 7
4.4.2 Electrical activation device . 7
4.4.3 Thermal activation device . 7
4.4.4 Other methods of activation device . 7
4.5 Limitation of use. 7
4.6 Electrostatic discharge. 7
4.7 Potentially explosive atmosphere . 7
4.8 Temperature limitations . 8
4.9 Compatibility with other extinguishants . 8
4.10 Environment . 8
5 Safety . 8
5.1 General. 8
5.2 Toxicity . 9
5.2.1 General. 9
5.2.2 Condensed aerosols . 9
5.3 Reduced visibility . 9
5.3.1 General. 9
5.3.2 Safety precautions . 9
5.4 Turbulence . 9
5.5 Thermal hazards . 10
5.5.1 Minimum thermal clearance . 10
5.5.2 Removal of discharged generators . 10
5.5.3 Hot work . 10
5.5.4 Casing temperatures for condensed aerosol generators . 10
Formatted: FooterPageRomanNumber
iv © ISO 2023 – All rights reserved
iv
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779.2:2025:2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
5.6 Safety precautions . 10
Formatted: Font: Bold
5.6.1 General. 10
Formatted: HeaderCentered, Left
5.6.2 Specific requirements . 10
5.7 Electrical hazards . 11
Table 1 — Required electrical clearances to enable operation, inspection, cleaning, repairs,
painting and normal maintenance work to be carried out. 11
5.8 Electrical earthing . 12
5.9 Electrostatic discharge. 12
6 Extinguishant concentrations . 12
6.1 General. 12
6.2 Design application density requirements. 12
6.2.1 Fire classification . 12
6.2.2 Class B fire . 12
6.2.3 Class A solid burning surface fire . 12
6.2.4 EDP (electronic data processing) rooms, telecommunication and electronic risks . 13
6.3 Aerosol generator performance requirements . 13
6.3.1 Distribution coverage . 13
6.3.2 Effective discharge . 13
6.3.3 Ambient temperature and humidity operation range . 13
6.3.4 Service life . 14
6.3.5 Vibration and shock resistance . 14
6.3.6 Corrosion . 14
6.3.7 Drop Impact . 14
6.3.8 Actuation element . 14
6.3.9 Exposure to fire . 14
6.4 Marking . 14
7 Specifications, plans and approvals . 15
7.1 Specifications . 15
7.2 Enclosure . 15
7.2.1 Venting and structural strength . 15
7.2.2 Loss of extinguishant to adjacent hazards . 15
7.2.3 Forced-air ventilating systems . 15
7.2.4 Venting requirements . 16
7.3 Total flooding quantity . 16
7.3.1 General. 16
7.3.2 Safety factor . 16
7.4 Design application density adjustment . 17
7.4.1 Effects of altitude and temperature . 17
7.4.2 Effects of ventilation . 17
7.4.3 Compensation for leakage through enclosure openings . 17
7.5 Unit size and quantity of aerosol generators . 17
7.5.1 Maximum or minimum protected height limitations . 17
7.5.2 Minimum thermal clearance . 18
7.5.3 Several smaller units versus few large units . 18
7.5.4 Mounting locations . 18
7.5.5 Quantity of aerosol generators . 18
7.5.6 Multiple generator systems . 19
7.6 Operating conditions . 19 Formatted: Font: 10 pt
7.7 Duration of protection . 19
Formatted: Font: 10 pt
7.8 System discharge . 19
Formatted: FooterCentered, Left, Line spacing: single
7.8.1 Discharge time . 19
Formatted: Font: 11 pt
7.8.2 Effectiveness of discharge . 20
Formatted: FooterPageRomanNumber, Left, Space After: 0
7.8.3 Thermal clearance . 20
pt, Line spacing: single
v
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779:2023(E2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
7.8.4 Extended discharge . 20
Formatted: Font: Bold
7.9 Detection, actuation and control systems . 20
Formatted: HeaderCentered
7.9.1 General. 20
7.9.2 Automatic detection . 20
7.9.3 Operating devices . 20
7.9.4 Electric control equipment . 21
7.9.5 Operating alarm indicators . 21
7.9.6 System isolate switch . 22
8 Commissioning and acceptance . 22
8.1 General. 22
8.2 Tests . 22
8.2.1 General. 22
8.2.2 Enclosure check . 22
8.2.3 Review of design calculations . 23
8.2.4 Review of the mechanical components of condensed aerosol generators . 23
8.2.5 Review of electrical components . 23
8.2.6 Preliminary functional tests . 25
8.2.7 System functional operational test . 25
8.2.8 Remote monitoring operations . 25
8.2.9 Control panel primary power source . 25
8.2.10 Completion of functional tests . 26
8.2.11 Completion certificate and documentation . 26
9 Inspection, maintenance, testing and training. 26
9.1 General. 26
9.2 Inspection . 26
9.2.1 General. 26
9.2.2 Enclosures . 27
9.3 Maintenance . 27
9.3.1 General. 27
9.3.2 User's programme of inspection . 27
9.3.3 Service schedule . 28
9.4 Training . 28
Annex A (normative) Documentation requirements . 29
A.1 General. 29
A.2 Working documents . 29
Annex B (informative) Toxicity and visibility testing . 30
B.1 General. 30
B.2 Assessing toxicity: irritation and inhalation toxicity tests . 30
B.3 Assessing toxicity: literature review . 31
Figure B.1 — Flowchart of assessment of condensed aerosols . 32
B.4 Assessing visibility for a condensed aerosol: a model approach . 32
Table B.1 — Visibility as a function of particle MMAD and concentration . 32
B.5 Design of the model . 33
Figure B.2 — Particle MMAD (µm) . 34
Formatted: FooterPageRomanNumber
vi © ISO 2023 – All rights reserved
vi
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779.2:2025:2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
B.6 Potential settling rates and the effect on visibility . 34
Formatted: Font: Bold
Formatted: HeaderCentered, Left
Table B.2 — Aerosol settling velocity — Spherical particles in air . 34
B.7 Accounting for refractive index . 35
B.8 Designing the lighting and space to conform with physical properties of the condensed
aerosol . 35
B.9 Utilizing light of specific wavelengths and photoluminescent marking systems . 35
B.10 Decreasing distance to exits . 36
B.11 Training . 36
B.12 Recommended testing procedures . 36
Annex C (normative) Test methods . 37
C.1 General. 37
C.2 Conditions . 37
C.3 Samples . 37
Table C.1 — Test sequence . 38
C.4 Conformity . 38
C.5 Extinguishing density determination . 38
C.6 Temperature and humidity operation range tests . 39
C.6.1 Objective of the test . 39
C.6.2 Test procedure . 39
C.6.2.1 General. 39
C.6.2.2 Conditioning . 39
C.6.2.3 Final measurements . 39
C.6.2.4 Requirements . 39
C.6.3 Low temperature test . 39
C.7 Accelerated aging test . 39
C.7.1 General. 39
C.7.2 Objective of the test . 40
C.7.3 Performance requirements . 40
C.7.4 Aging test . 40
C.7.5 Remark . 40
C.7.6 Number of products under test. 40
C.8 Corrosion test . 40
C.9 Stress corrosion test . 41
C.10 Vibration test . 41
Formatted: Font: 10 pt
C.11 Drop impact test . 42
Formatted: Font: 10 pt
Formatted: FooterCentered, Left, Line spacing: single
C.11.1 Impact surface . 42
Formatted: Font: 11 pt
C.11.2 Procedure . 42
Formatted: FooterPageRomanNumber, Left, Space After: 0
pt, Line spacing: single
vii
Formatted: Font: 11 pt, Bold
ISO/DISFDIS 15779:2023(E2026(en)
Formatted: Font: 11 pt, Bold
Formatted: Font: 11 pt, Bold
C.11.3 Requirements . 42
Formatted: Font: Bold
Formatted: HeaderCentered
C.12 Activation performance test . 42
C.13 Function test . 42
C.13.1 Discharge time . 42
C.13.2 Aerosol flow temperatures . 43
Figure C.1 — Test configuration for the function test, side and top view . 44
C.13.3 Casing temperature test . 44
C.13.4 Efficiency . 44
C.13.5 Test procedure . 44
C.13.6 Requirements . 44
Table C.2 — Test conditions for function test C.13 . 44
C.14 Fire exposure test . 45
C.14.1 Objective of the test . 45
C.14.2 Test procedure . 45
C.14.3 Requirements . 45
Annex D (normative) Extinguishing density/Coverage test procedure . 46
D.1 General. 46
Table D.1 — Tests . 46
D.2 Principle . 46
D.3 Extinguishing system . 47
D.4 Extinguishing density .
...