Abstract

IEC 61803:2026 applies to all high-voltage direct current (HVDC) converter stations with line-commutated converters (LCC) as well with voltage-sourced converters (VSC) used for power exchange (power transmission or back-to-back installation) in utility systems. For line-commutated converters (LCC), this document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. Where VSC is referred to in this document, it is assumed to be of the MMC-type or similar, with very low harmonic generation. It is important to treat other types of VSC as appropriate. In some applications, synchronous compensators, static var compensators (SVC), or static synchronous compensator (STATCOM) are connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document. This document presents a set of standard procedures for determining the total losses of an HVDC converter station, except for VSC valves which are covered by the IEC 62751 series. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters. Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that can affect the losses, are assessed on their own merits.
This edition includes the following significant technical changes with respect to the previous edition:
a) HVDC stations with voltage-sourced converters (VSC) technology have been included;
b) to facilitate the application of this document and to ensure its quality remains consistent, 5.1.8 and 5.8 have been reviewed, taking into consideration that the present thyristor production technology provides considerably less thyristor parameters dispersion comparing with the situation in 1999 when the first edition of IEC 61803 was developed; therefore, the production records of thyristors can be used for the power losses calculation;
c) the calculation of the total station load losses (cases D1 and D2 in Annex C) has been corrected.

Status
Published
Publication Date
25-May-2026
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
26-May-2026
Due Date
08-May-2026
Completion Date
08-May-2026

Buy Documents

Standard

IEC 61803:2026 - Determination of power losses in high-voltage direct current (HVDC) converter stations

ISBN:978-2-8327-1202-3
Release Date:26-May-2026
English language (43 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 61803:2026 CMV - Determination of power losses in high-voltage direct current (HVDC) converter stations

ISBN:978-2-8327-1267-2
Release Date:26-May-2026
English language (86 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 61803:2026 - Détermination des pertes en puissance dans les stations de conversion en courant continu a haute tension (CCHT)

ISBN:978-2-8327-1202-3
Release Date:26-May-2026
French language (45 pages)
sale 15% off
Preview
sale 15% off
Preview

IEC 61803:2026 is an IEC International Standard for determining power losses in HVDC converter stations. It applies to stations with line-commutated converters (LCC) and voltage-sourced converters (VSC) used for power transmission or back-to-back operation in utility systems. The document gives a common calculation method so suppliers and purchasers can compare, verify and document losses on the same basis.

What does IEC 61803:2026 specify?

IEC 61803:2026 specifies standard procedures for calculating the total losses of an HVDC converter station. It covers no-load operation losses and operating losses, using measured parameters wherever practical.

The scope includes LCC stations, assumed to use 12-pulse thyristor converters, and VSC stations, assumed to be MMC-type or similar with very low harmonic generation. It does not include loss determination for synchronous compensators, SVC or STATCOM connected to the AC bus, and VSC valve losses are covered by the IEC 62751 series. Station designs with novel components or unusual auxiliary circuits are to be assessed on their own merits.

AnnexWhat it covers
Annex ACalculation of harmonic currents and voltages for LCC only
Annex BTypical station losses
Annex CHVDC converter station loss evaluation, with an illustration

The document is organized into clauses on scope, normative references, terms and symbols, overview, and detailed loss determination for each major item of equipment.

What are the key requirements of IEC 61803:2026?

IEC 61803:2026 requires losses to be evaluated under defined ambient and operating conditions, then summed by equipment item. That matters in practice because the result is meant to be repeatable for bids, guarantees and performance checks, not a rough site estimate.

  • Use standard reference ambient conditions in Clause 4.2. The document sets an outdoor dry-bulb temperature of 20 °C, uses the purchaser’s wet-bulb value where needed, and applies standard atmospheric pressure corrected for altitude above 1 000 m. In practice, the same station can give different losses at different temperatures, so the reference conditions keep comparisons fair.
  • Calculate losses for defined load levels in Clause 4.3. LCC load level is defined by direct current, direct voltage, firing angle, AC system voltage and transformer tap position; VSC load level is defined by direct current, direct voltage, AC system voltage, transformer tap position where relevant, converter AC voltage, converter AC current and phase angle. If no load levels are specified, the document uses rated load.
  • Separate operating losses from no-load operation losses in Clause 3 and Clause 4.3. No-load operation means the converter is blocked, the transformer is energised, and only the equipment needed for immediate pickup is connected; operating losses apply when the converter is in service. This distinction matters because many projects price standby losses differently from load-dependent losses.
  • Determine LCC thyristor valve losses item by item in Clause 5.1. The valve loss calculation covers conduction, spreading, other conduction, DC voltage-dependent loss, damping loss, turn-off loss, reactor loss, temperature effects and no-load operation loss. The document relies on measured valve data and production records where appropriate, which means the supplier must assemble test results and device data rather than use one generic value.
  • Treat transformers according to operating mode in Clause 5.2. No-load losses follow IEC 60076-1, while load losses include harmonic effects and are calculated from fundamental-frequency and higher-frequency measurements. For VSC, harmonic losses may be treated like conventional AC transformers when current THD is below 5 %; otherwise the harmonic spectrum has to be calculated and stated.
  • Evaluate filters and reactive equipment by their actual components in Clauses 5.3 to 5.7. AC filters, shunt capacitor banks, shunt reactors, DC smoothing reactors and DC filters are all calculated from measured component values and harmonic currents or voltages. That means the station design team must know which branches are energised at each load level and what harmonic content reaches each branch.
  • Use the VSC reactor rules where applicable in Clauses 5.10 and 5.11. Phase reactor losses and valve reactor losses are calculated from measured impedance, quality factor and winding temperature. This is relevant for VSC topologies that use phase reactors, valve reactors or both.
  • Include auxiliaries and only relevant special equipment in Clauses 5.8 and 5.12. Station service loads are averaged over normal operation, while special-purpose loads used only for outages or transient events are excluded. Other equipment losses are normally neglected unless the station includes special equipment not covered by the typical configuration.

What terms does IEC 61803:2026 define?

IEC 61803:2026 defines the terms it uses for station-loss accounting so that the same words mean the same thing across suppliers and purchasers.

  • Auxiliary losses - electric power needed to feed converter-station auxiliary loads.
  • Equipment no-load operation losses - losses in an item of equipment when the station is energised but the converters are blocked.
  • Load level - the set of AC system and converter operating conditions at which the station operates.
  • Equipment operating losses - losses in an item of equipment at a given load level when the converters are operating.
  • Rated load - the load corresponding to nominal operating conditions.
  • Total station no-load operation losses - the sum of all equipment no-load operation losses and the corresponding auxiliary losses.
  • Total station operating losses - the sum of all equipment operating losses and the corresponding auxiliary losses at a particular load level.
  • Total station load losses - the difference between total station operating losses and total station no-load operation losses.
  • Station essential auxiliary load - a load whose failure affects conversion capability, or which remains working after complete loss of AC power supply.

Who uses IEC 61803:2026?

IEC 61803:2026 is used by HVDC suppliers, purchasers, owners, utilities and engineering teams involved in power transmission or back-to-back installations. It is especially relevant when comparing bids, setting guaranteed loss figures, planning factory tests, or documenting loss evaluation for a project.

Manufacturers and test teams use it to calculate equipment losses from measured data on valves, transformers, filters and reactors. Buyers and quality managers use it to compare proposals on a common basis and to check that claimed performance is based on a recognized calculation method.

What changed in IEC 61803:2026 from the previous edition?

IEC 61803:2026 is the third edition and cancels and replaces the second edition published in 2020. The foreword states three significant technical changes.

  • HVDC stations with VSC technology have been included.
  • Clauses 5.1.8 and 5.8 were reviewed so that thyristor production records can be used for power-loss calculation, reflecting lower parameter dispersion in current production.
  • The calculation of total station load losses in Annex C, cases D1 and D2, was corrected.

Which standards are used with IEC 61803:2026?

IEC 61803:2026 cites the following standards as normative references, and they support the loss calculations in specific parts of the document.

  • IEC 60076-1 - transformer no-load and load loss determination and reference-temperature treatment.
  • IEC 60076-6 - reactor testing and loss determination.
  • IEC 60633 - HVDC vocabulary used for common terminology.
  • IEC 60700-1:2015 and IEC 60700-1:2015/AMD1:2021 - electrical testing of thyristor valves used for valve-loss measurements.
  • IEC 60871-1 - capacitor-loss determination for shunt capacitor banks and AC filter capacitors.
  • IEC 62747 - terminology for VSC in HVDC systems.

The document also refers to IEC 62751 (all parts) for VSC valve power losses, and cites IEC TR 62001-5 and IEC/IEEE 60076-57-129:2017 as related technical references for VSC harmonics and HVDC transformers.

What does the IEC 61803:2026 document contain?

IEC 61803:2026 contains calculation methods, supporting figures and illustrative annexes rather than a test report template. Clause 4 explains why direct power subtraction is not a reliable loss-measurement method at HVDC power levels, and it introduces the ambient and operating conditions used throughout the standard.

Clause 5 gives the item-by-item loss determination for thyristor valves, transformers, AC filters, shunt capacitors, shunt reactors, smoothing reactors, DC filters, auxiliaries, series filters and VSC reactors. The figures show typical LCC and VSC pole equipment, a simplified 12-pulse converter, a representative thyristor valve circuit, valve waveforms, and a typical phase-reactor and valve-reactor arrangement.

Annex A provides harmonic-current and harmonic-voltage calculations for LCC stations. Annex B gives typical loss shares for LCC and VSC MMC stations. Annex C shows how to evaluate station losses over different loading patterns, including standby and load-loss cases, for project-level loss capitalization and bid comparison.

Relations

Effective Date
22-Dec-2023

Buy Documents

Standard

IEC 61803:2026 - Determination of power losses in high-voltage direct current (HVDC) converter stations

ISBN:978-2-8327-1202-3
Release Date:26-May-2026
English language (43 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 61803:2026 CMV - Determination of power losses in high-voltage direct current (HVDC) converter stations

ISBN:978-2-8327-1267-2
Release Date:26-May-2026
English language (86 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 61803:2026 - Détermination des pertes en puissance dans les stations de conversion en courant continu a haute tension (CCHT)

ISBN:978-2-8327-1202-3
Release Date:26-May-2026
French language (45 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC 61803:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Determination of power losses in high-voltage direct current (HVDC) converter stations". This standard covers: IEC 61803:2026 applies to all high-voltage direct current (HVDC) converter stations with line-commutated converters (LCC) as well with voltage-sourced converters (VSC) used for power exchange (power transmission or back-to-back installation) in utility systems. For line-commutated converters (LCC), this document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. Where VSC is referred to in this document, it is assumed to be of the MMC-type or similar, with very low harmonic generation. It is important to treat other types of VSC as appropriate. In some applications, synchronous compensators, static var compensators (SVC), or static synchronous compensator (STATCOM) are connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document. This document presents a set of standard procedures for determining the total losses of an HVDC converter station, except for VSC valves which are covered by the IEC 62751 series. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters. Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that can affect the losses, are assessed on their own merits. This edition includes the following significant technical changes with respect to the previous edition: a) HVDC stations with voltage-sourced converters (VSC) technology have been included; b) to facilitate the application of this document and to ensure its quality remains consistent, 5.1.8 and 5.8 have been reviewed, taking into consideration that the present thyristor production technology provides considerably less thyristor parameters dispersion comparing with the situation in 1999 when the first edition of IEC 61803 was developed; therefore, the production records of thyristors can be used for the power losses calculation; c) the calculation of the total station load losses (cases D1 and D2 in Annex C) has been corrected.

IEC 61803:2026 applies to all high-voltage direct current (HVDC) converter stations with line-commutated converters (LCC) as well with voltage-sourced converters (VSC) used for power exchange (power transmission or back-to-back installation) in utility systems. For line-commutated converters (LCC), this document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. Where VSC is referred to in this document, it is assumed to be of the MMC-type or similar, with very low harmonic generation. It is important to treat other types of VSC as appropriate. In some applications, synchronous compensators, static var compensators (SVC), or static synchronous compensator (STATCOM) are connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document. This document presents a set of standard procedures for determining the total losses of an HVDC converter station, except for VSC valves which are covered by the IEC 62751 series. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters. Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that can affect the losses, are assessed on their own merits. This edition includes the following significant technical changes with respect to the previous edition: a) HVDC stations with voltage-sourced converters (VSC) technology have been included; b) to facilitate the application of this document and to ensure its quality remains consistent, 5.1.8 and 5.8 have been reviewed, taking into consideration that the present thyristor production technology provides considerably less thyristor parameters dispersion comparing with the situation in 1999 when the first edition of IEC 61803 was developed; therefore, the production records of thyristors can be used for the power losses calculation; c) the calculation of the total station load losses (cases D1 and D2 in Annex C) has been corrected.

IEC 61803:2026 is classified under the following ICS (International Classification for Standards) categories: 29.200 - Rectifiers. Converters. Stabilized power supply. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61803:2026 has the following relationships with other standards: It is inter standard links to IEC 61803:2020. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 61803:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and symbols
  • 3.1 Terms and definitions
  • 3.2 Symbols
  • 4 Overview
  • 4.1 General
  • 1 AC switchyard 9 DC smoothing reactor
  • 4 AC filter bank 12 DC filter
  • 6 PLC filter 14 pole line
  • 4.2 Ambient conditions
  • 4.3 Operating parameters
  • 5 Determination of equipment losses
  • 5.1 Thyristor valve losses (LCC only)
  • 5.2 Transformer losses
  • 5.3 AC filter losses
  • 5.4 Shunt capacitor bank losses
  • 5.5 Shunt reactor losses
  • 5.6 DC smoothing reactor losses
  • 5.7 DC filter losses
  • 5.8 Auxiliaries and station service losses
  • 5.9 Series filter losses
  • 5.10 Phase reactor losses (VSC only)
  • 5.11 Valve reactor losses (VSC only)
  • 5.12 Other equipment losses
  • Annex A
  • 6 ××IF
  • 6 ××IF U
  • Annex B
  • Annex C
  • Annex C provides an illustration of the basic concept behind the loss evaluation of HVDC
  • Bibliography

1 Scope

This document applies to all high-voltage direct current (HVDC) converter stations with linecommutated converters (LCC) as well with voltage-sourced converters (VSC) used for power exchange (power transmission or back-to-back installation) in utility systems. For linecommutated converters (LCC), this document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. Where VSC is referred to in this document, it is assumed to be of the MMC-type or similar, with very low harmonic generation. It is important to treat other types of VSC as appropriate. In some applications, synchronous compensators, static var compensators (SVC), or static synchronous compensator (STATCOM) are connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document.

This document presents a set of standard procedures for determining the total losses of an HVDC converter station, except for VSC valves which are covered by the IEC 62751 series. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters.

Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that can affect the losses, are assessed on their own merits.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60076-1, Power transformers - Part 1: General IEC 60076-6, Power transformers - Part 6: Reactors IEC 60633, High-voltage direct current (HVDC) transmission - Vocabulary IEC 60700-1:2015, Thyristor valves for high voltage direct current (HVDC) power transmission - Part 1: Electrical testing IEC 60700-1:2015/AMD1:2021 IEC 60871-1, Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V - Part 1: General IEC 62747, Terminology for voltage-sourced converters (VSC) for high-voltage direct current (HVDC) systems

3 Terms, definitions and symbols

For the purposes of this document, the terms and definition given in IEC 60633, IEC 62747 and the following apply.

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

  • IEC Electropedia: available at http://www.electropedia.org/
  • ISO Online browsing platform: available at http://www.iso.org/obp

3.1 Terms and definitions

3.1.1   auxiliary losses electric power required to feed the converter station auxiliary loads Note 1 to entry: The auxiliary losses depend on the number of converter units used and whether the station is in no-load operation or carrying load, in which case the auxiliary losses depend on the load level. 3.1.2   equipment no-load operation losses losses produced in an item of equipment with the converter station energised but with the converters blocked and all station service loads and auxiliary equipment connected as required for immediate pick-up of load to specified minimum power 3.1.3   load level set of AC system and converter operating conditions at which the converter station is operating Note 1 to entry: For LCC schemes, the load level is defined by the direct current, direct voltage, firing angle, AC system voltage and converter transformer tap-changer position. Note 2 to entry: For VSC schemes, the load level is defined by the direct current, direct voltage, AC system voltage, interface transformer tap-changer position (where appropriate), converter AC voltage, converter AC current and the phase angle between converter AC voltage and current.

3.1.4   equipment operating losses losses produced in an item of equipment at a given load level with the converter station energised and the converters operating 3.1.5   rated load load corresponding to operation at nominal values of the operating conditions defined in 3.1.3 Note 1 to entry: The AC system shall be assumed to be at nominal frequency, and its 3-phase voltages are nominal and balanced. The position of the tap-changer of the converter/interface transformer and the number of AC filters and shunt reactive elements, if any connected, shall be consistent with operation at rated load, coincident with nominal conditions.

3.1.6   total station no-load operation losses sum of all equipment no-load operation losses (3.1.2) and corresponding auxiliary losses (3.1.1)

3.1.7   total station operating losses sum of all equipment operating losses (3.1.4) and corresponding auxiliary losses (3.1.1) at a particular load level Note 1 to entry: An illustrative example using total station operating losses and corresponding loss evaluation is given in Annex C, case D1.

3.1.8   total station load losses difference between total station operating losses (3.1.7) and total station no-load operation losses (3.1.6) Note 1 to entry: Such calculated total station load losses are considered as being quantitatively equivalent to load losses as in conventional AC substation practice.

Note 2 to entry: It is recognized that some purchasers evaluate total station no-load operation losses (3.1.6) and total station load losses individually instead of the evaluating total station operating losses (3.1.7). Note 3 to entry: An illustrative example to derive load losses, equivalent load losses and corresponding loss evaluation is given in Annex C, case D2.

3.1.9   station essential auxiliary load load whose failure affects the conversion capability of the HVDC converter station (e.g. valve cooling), as well as load that remains working in case of complete loss of AC power supply (e.g. battery chargers, operating mechanisms)

3.2 Symbols

3.2.1 Common

f AC system frequency, in hertz (Hz) I direct current, in amperes (A) d I harmonic RMS current of order n, in amperes (A) n n harmonic order P power loss in an item of equipment, in watts (W) Q quality factor of a reactor at harmonic order n n R resistance value, in ohms (Ω) U direct voltage, in volts (V) d U harmonic RMS voltage of order n, in volts (V) n X inductive reactance at harmonic order n, in ohms (Ω) n

3.2.2 Line-commutated converters

α (trigger/firing) delay angle, in radians (rad) γ extinction angle, in radians (rad) µ overlap angle, in radians (rad) L inductance, in henrys (H), referred to the valve winding, between the commutating

voltage source and the point of common coupling between star- and delta-connected windings; L shall include any external inductance between the transformer line-

winding terminals and the point of connection of the AC harmonic filters L inductance, in henrys (H), referred to the valve winding, between the point of common

coupling between star- and delta-connected windings; the valve L shall include the

saturated inductance of the valve reactors m electromagnetic notch coupling factor, m = L /(L + L ) 1 1 2 N number of series-connected thyristors per valve t U RMS value of the phase-to-phase no-load voltage on the valve side of the converter vo transformer excluding harmonics, in volts (V)

4 Overview

4.1 General

It is important for suppliers to know in detail how and where losses are generated, since this affects component and equipment ratings. Purchasers are interested in a verifiable loss figure which allows equitable bid comparison and in a procedure which can objectively verify the guaranteed performance requirements of the supplier after delivery. The main purpose of this document is to serve the purchasers this specific interest.

As a general principle, it would be desirable to determine the efficiency of an HVDC converter station by a direct measurement of its energy losses. However, attempts to determine the station losses by subtracting the measured output power from the measured input power should recognize that such measurements have an inherent inaccuracy, especially if performed at high voltage. The losses of an HVDC converter station at full load are generally less than 1 % of the transmitted power. Therefore, the loss measured as a small difference between two large quantities is not likely to be a sufficiently accurate indication of the actual losses. In some special circumstances, it can be possible, for example, to arrange a temporary test connection in which two converters are operated from the same AC source and also connected together via their DC terminals. In this connection, the power drawn from the AC source equals the losses in the circuit though in most cases this does not represent a normal operating design mode. However, the AC source shall also provide var support and commutating voltage to the two converters. Once again, there are practical measurement difficulties, and it is still important that the losses are recalculated/corrected for nominal parameters and ambient/operating conditions.

In order to avoid the problems described above since these practical measurements are unreliable and also will depend on the type of HVDC solution, it is recommended to use this document which standardizes a method of calculating the HVDC converter station losses by summing the losses calculated for each item of equipment. The standardized calculation method will help the purchaser to meaningfully compare the competing bids. It will also allow an easy generation of performance curves for the wide range of operating conditions in which the performance has to be known. In the absence of an inexpensive experimental method which could be employed for an objective verification of losses during type tests, the calculation method is the next best alternative as it uses, wherever possible, experimental data obtained from measurements on individual equipment and components under conditions equivalent to those encountered in real operation.

Typical high-voltage direct current (HVDC) equipment for one pole of an LCC HVDC substation is shown in Figure 1 and for one pole of a VSC HVDC substation in Figure 2. The calculation of harmonic currents and voltages in HVDC equipment for line-commutated converter stations is described in Annex A.

Key

1 AC switchyard 9 DC smoothing reactor

2 shunt reactor bank 10 voltage divider 3 shunt capacitor bank 11 PLC filter

4 AC filter bank 12 DC filter

5 capacitor voltage transformer 13 DC current measuring device

6 PLC filter 14 pole line

7 converter transformer 15 ground electrode 8 valve hall Figure 1 – Typical high-voltage direct current (HVDC) equipment for one pole of an LCC scheme

Key

1 circuit breaker 9 VSC unit 2 pre-Insertion resistor 10 VSC DC capacitor

3 line side harmonic filter 11 DC harmonic filter 4 line side high frequency filter 12 dynamic braking system

5 interface transformer 13 neutral point grounding branch 6 converter side harmonic filter 14 DC reactor 7 + 8 converter side high frequency filter 15 DC cable or overhead transmission line 8 phase reactor a In some designs of VSC based on VSC switch type valves, the harmonic filters may not be required. b In some designs of VSC, the phase reactor may fulfill part of the function of the converter-side high frequency filter.

In some VSC topologies, each valve of the VSC unit may include a "valve reactor", which can be built into the valve or provided as a separate component.

d In some designs of VSC, the VSC DC capacitor may be partly or entirely distributed amongst the three phase units of the VSC Unit, where it is referred to as the DC submodule capacitors. e The philosophy and location of the neutral point grounding branch can be different depending on the design of the VSC unit.

f In some designs of VSC, the interface transformer can fulfill part of the function of the line-side high frequency filter.

g Optional.

h Optional, if phase reactors or valve reactors are located on the DC side of the converter. Figure 2 – Typical high-voltage direct current (HVDC) equipment for one pole of a VSC scheme Compared with LCCs, VSCs for HVDC systems generate a much less distorted AC side current waveform. Depending on the converter topology and the control methods employed for VSC, the network side voltage generated by the converter can approach a clean fundamental frequency sinusoid. The VSC converter can be considered as a harmonic voltage source behind an internal impedance, rather than a current source as for LCCs, as it is the generated harmonic voltage which remains independent of load. The harmonic levels can be extremely low compared to LCCs, but due to the adopted switching regime have a significant frequency range much higher than for LCCs, and can contain inter-harmonics, which are a result of the control strategy adopted. Refer to the IEC TR 62001-5 for harmonics generation of VSC converters. NOTE In this document, where the term "harmonic" is used for VSC converters, it is considered to mean the "harmonic group" according to IEC 61000-4-7, which includes the integer harmonic and the spectral bins from h – 0,5 to h + 0,5, instead of "harmonic number n".

It is important to note that the power loss in each item of equipment will depend on the ambient conditions under which it operates, as well as on the operating conditions or duty cycles to which it is subjected. Therefore, the ambient and operating conditions shall be defined for each item of equipment, based on the ambient and operating conditions of the entire HVDC converter station.

It is recognized that, for AC and DC side filter equipment, the specified notional requirements do not represent the actual losses to be expected in service; however, the simplified approach specified in this document is considered acceptable to estimate losses and compare different bids.

4.2 Ambient conditions

4.2.1 General

A set of standard reference ambient conditions shall be used for determining the power losses in HVDC converter stations.

4.2.2 Outdoor standard reference temperature

An outdoor ambient dry bulb temperature of 20 °C shall be used as the standard reference temperature for determining the total converter station losses. The corresponding valve hall temperature can be defined by the supplier if necessary. The equivalent wet-bulb temperature (where necessary) shall be defined by the purchaser.

If not defined, the wet-bulb temperature is recommended to be 14 °C, which corresponds to approximately 50 % RH at 20 °C dry bulb temperature.

4.2.3 Coolant standard reference temperature

Where forced cooling is used for equipment, the flow rate and temperature of the coolant can influence the temperature rise and associated losses of that equipment. Therefore, the coolant temperatures and flow rates established by the purchaser and the supplier shall be used as a basis for determining the losses.

4.2.4 Standard reference air pressure

The reference air pressure to be used for the evaluation of total converter station power losses shall be the standard atmospheric pressure (101,3 kPa) corrected to the altitude of the installation in question when station is located above 1 000 m above sea level.

4.3 Operating parameters

The losses of an HVDC converter station depend on its operating parameters. The losses of HVDC converter stations are classified into two categories, referred to as operating losses (3.1.4 and 3.1.7) and no-load operation losses (3.1.2 and 3.1.6). The operating losses and auxiliary losses are affected by the load level of the station because the numbers of certain types of energised equipment (for example harmonic filters and cooling equipment) can depend upon the load level and because losses in individual items of equipment themselves vary with the load level.

HVDC converter station losses shall be determined for nominal (balanced) AC system voltage and frequency, symmetrical impedances of the transformer (between phases, and for LCC schemes, between the star and delta-connected bridges) and, for LCC schemes, symmetrical firing angles. The transformer tap-changer shall be assumed to be in the position corresponding to nominal AC system voltage or as decided by the control system for the defined operating condition.

The operating losses shall be determined for the load levels specified by the purchaser, or at rated load if no such conditions are specified. For each load level, the converter operating conditions defined in 3.1.3, shunt compensation and harmonic filtering equipment shall be consistent with the respective load level and other specified performance requirements, relating, for example, to harmonic distortion and minimum reactive power exchange with the connected ac network. Cooling and other auxiliary equipment, as appropriate to the standard reference temperature (see 4.2.2 and 4.2.3), shall be assumed to be connected to support the respective load level. Unless specifically specified, reactive power shall be assumed zero for a VSC station.

For the no-load operation mode, transformers shall be energised and the converters blocked. All filters and reactive power compensation equipment shall be assumed to be disconnected except for those which are required to sustain operation at zero load in order, for example, to meet the specified reactive power requirements. Station service loads and auxiliary equipment (e.g. cooling-water pumps) shall be assumed to be connected as required for immediate pickup of load for the converter station (without waiting for tap changer movement) to specified minimum power.

NOTE For some MMC VSC valves, it can be impracticable to keep the converter blocked with AC circuit breaker closed for a while, due to a need for balancing the submodule capacitor voltages. The operating state generally known as "idling operating state" will also have an additional contribution of valve losses. However, for the purpose of guaranteeing loss calculation, it is sufficient to compare losses for no-load operation losses as defined in 3.1.2 at zero active and reactive power.

5 Determination of equipment losses

5.1 Thyristor valve losses (LCC only)

5.1.1 General

The loss production mechanisms applicable when the valves are blocked (no-load operation losses) are different from those applicable in normal operation (operating losses). Operating losses are dealt with in 5.1.2 to 5.1.11, and no-load operation losses are dealt with in 5.1.12. Auxiliary losses are dealt with in 5.8.

A simplified three-phase diagram of an HVDC 12-pulse converter is shown in Figure 3. Individual valves are marked in the order of their conduction sequence.

...

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and symbols
  • 3.1 Terms and definitions
  • 3.2 Symbols
  • 4 Overview
  • 4.1 General
  • 1 AC switchyard 9 DC smoothing reactor
  • 4 AC filter bank 12 DC filter
  • 6 PLC filter 14 pole line
  • 4.2 Ambient conditions
  • 4.3 Operating parameters
  • 5 Determination of equipment losses
  • 5.1 Thyristor valve losses (LCC only)
  • 5.2 Converter Transformer losses
  • 5.3 AC filter losses
  • 5.4 Shunt capacitor bank losses
  • 5.5 Shunt reactor losses
  • 5.6 DC smoothing reactor losses
  • 5.7 DC filter losses
  • 5.8 Auxiliaries and station service losses
  • 5.9 Series filter losses
  • 5.12 Other equipment losses
  • Annex A
  • 6 ××IF
  • 6 ××IF U
  • Annex B
  • Annex C
  • Annex C provides an illustration of the basic concept behind the loss evaluation of HVDC
  • Bibliography
  • 1 This new edition of IEC 61803 extends the application scope to both LCC and VSC HVDC
  • 2 Most recent VSC schemes are of the MMC type; therefore, the focus of this standard
  • 3 For VSC valves, the specific IEC 62751 standard exists; for other components in the VSC
  • 4 Notes are introduced to differentiate the definition of the load level for LCC and VSC
  • 7 The text is introduced to explain the differences in harmonic generation behaviour between
  • 9 The text and the note are introduced to highlight the harmonic behaviour of VSC schemes
  • 10 Guidelines on how to handle harmonic losses of transformers in VSC schemes are provided
  • 11 The text is introduced for VSC schemes and accordingly applies loss calculation for any
  • 16 Subclause 5.10 is introduced to clarify the possible locations of reactors used in VSC
  • 17 Subclause 5.11 is introduced because VSC valves have specific valve reactors, which shall
  • 18 Typical loss values for VSC MMC stations are added for informational purposes as a
  • 19 The note is added with a specific explanation for VSC schemes, with a cross-reference to
  • FOREWORD
  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and symbols
  • 3.1 Terms and definitions
  • 3.2 Symbols
  • 4 Overview
  • 4.1 General
  • 1 AC switchyard 9 DC smoothing reactor
  • 4 AC filter bank 12 DC filter
  • 6 PLC filter 14 pole line
  • 4.2 Ambient conditions
  • 4.3 Operating parameters
  • 5 Determination of equipment losses
  • 5.1 Thyristor valve losses (LCC only)
  • 5.2 Transformer losses
  • 5.3 AC filter losses
  • 5.4 Shunt capacitor bank losses
  • 5.5 Shunt reactor losses
  • 5.6 DC smoothing reactor losses
  • 5.7 DC filter losses
  • 5.8 Auxiliaries and station service losses
  • 5.9 Series filter losses
  • 5.10 Phase reactor losses (VSC only)
  • 5.11 Valve reactor losses (VSC only)
  • 5.12 Other equipment losses
  • Annex A
  • 6 ××IF
  • 6 ××IF U
  • Annex B
  • Annex C
  • Annex C provides an illustration of the basic concept behind the loss evaluation of HVDC
  • Bibliography

1 Scope

This document applies to all line-commutated high-voltage direct current (HVDC) converter stations with line-commutated converters (LCC) as well with voltage-sourced converters (VSC) used for power exchange (power transmission or back-to-back installation) in utility systems. For line-commutated converters (LCC), this document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. Where VSC is referred to in this document, it is assumed to be of the MMC-type or similar, with very low harmonic generation. It is important to treat other types of VSC as appropriate. 2 In some applications, synchronous compensators, static var compensators (SVC), or static synchronous compensator (STATCOM) may be are connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document.

This document presents a set of standard procedures for determining the total losses of an HVDC converter station, except for VSC valves which are covered by the IEC 62751 series 3. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters.

Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that could can affect the losses, are assessed on their own merits.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60076-1, Power transformers - Part 1: General IEC 60076-6, Power transformers - Part 6: Reactors IEC 60633, High-voltage direct current (HVDC) transmission - Vocabulary IEC 60700-1:2015, Thyristor valves for high voltage direct current (HVDC) power transmission - Part 1: Electrical testing IEC 60700-1:2015/AMD1:2021 IEC 60871-1, Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V - Part 1: General IEC 62747, Terminology for voltage-sourced converters (VSC) for high-voltage direct current (HVDC) systems

3 Terms, definitions and symbols

For the purposes of this document, the terms and definition given in IEC 60633, IEC 62747 and the following apply.

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

  • IEC Electropedia: available at http://www.electropedia.org/
  • ISO Online browsing platform: available at http://www.iso.org/obp

3.1 Terms and definitions

3.1.1   auxiliary losses electric power required to feed the converter station auxiliary loads Note 1 to entry: The auxiliary losses depend on the number of converter units used and whether the station is in no-load operation or carrying load, in which case the auxiliary losses depend on the load level. 3.1.2   equipment no-load operation losses losses produced in an item of equipment with the converter station energised but with the converters blocked and all station service loads and auxiliary equipment connected as required for immediate pick-up of load to specified minimum power 3.1.3   load level direct current, direct voltage, firing angle, AC voltage, and converter transformer tap-changer position at which the converter station is operating set of AC system and converter operating conditions at which the converter station is operating Note 1 to entry: For LCC schemes, the load level is defined by the direct current, direct voltage, firing angle, AC system voltage and converter transformer tap-changer position. Note 2 to entry: For VSC schemes, the load level is defined by the direct current, direct voltage, AC system voltage, interface transformer tap-changer position (where appropriate), converter AC voltage, converter AC current and the phase angle between converter AC voltage and current. 4 3.1.4   equipment operating losses losses produced in an item of equipment at a given load level with the converter station energised and the converters operating 3.1.5   rated load load related to operation at nominal values of DC current, DC voltage, AC voltage and converter firing angle load corresponding to operation at nominal values of the operating conditions defined in 3.1.3 Note 1 to entry: The AC system shall be assumed to be at nominal frequency, and its 3-phase voltages are nominal and balanced. The position of the tap-changer of the converter/interface transformer and the number of AC filters and shunt reactive elements, if any connected, shall be consistent with operation at rated load, coincident with nominal conditions.

3.1.6   total station no-load operation losses sum of all equipment no-load operation losses (3.1.2) and corresponding auxiliary losses (3.1.1)

3.1.7   total station operating losses sum of all equipment operating losses (3.1.4) and corresponding auxiliary losses (3.1.1) at a particular load level Note 1 to entry: An illustrative example using total station operating losses and corresponding loss evaluation is given in Annex C, case D1.

3.1.8   total station load losses difference between total station operating losses (3.1.7) and total station no-load operation losses (3.1.6) Note 1 to entry: Such calculated total station load losses are considered as being quantitatively equivalent to load losses as in conventional AC substation practice.

Note 2 to entry: It is recognized that some purchasers evaluate total station no-load operation losses (3.1.6) and total station load losses individually instead of the evaluating total station operating losses (3.1.7). Note 3 to entry: An illustrative example to derive load losses, equivalent load losses and corresponding loss evaluation is given in Annex C, case D2.

3.1.9   station essential auxiliary load load whose failure affects the conversion capability of the HVDC converter station (e.g. valve cooling), as well as load that shall remain remains working in case of complete loss of AC power supply (e.g. battery chargers, operating mechanisms)

3.2 Symbols

3.2.1 Common

f AC system frequency, in hertz (Hz) I direct current, in amperes (A) d I harmonic RMS current of order n, in amperes (A) n n harmonic order P power loss in an item of equipment, in watts (W) Q quality factor of a reactor at harmonic order n n R resistance value, in ohms (Ω) U direct voltage, in volts (V) d U harmonic RMS voltage of order n, in volts (V) n X inductive reactance at harmonic order n, in ohms (Ω) n

3.2.2 Line-commutated converters

α (trigger/firing) delay angle, in radians (rad) γ extinction angle, in radians (rad) µ overlap angle, in radians (rad) L inductance, in henrys (H), referred to the valve winding, between the commutating

voltage source and the point of common coupling between star- and delta-connected windings; L shall include any external inductance between the transformer line-

winding terminals and the point of connection of the AC harmonic filters L inductance, in henrys (H), referred to the valve winding, between the point of common

coupling between star- and delta-connected windings; the valve L shall include the

saturated inductance of the valve reactors

m electromagnetic notch coupling factor, m = L /(L + L ) 1 1 2 N number of series-connected thyristors per valve t U RMS value of the phase-to-phase no-load voltage on the valve side of the converter vo transformer excluding harmonics, in volts (V)

4 Overview

4.1 General

It is important for suppliers to know in detail how and where losses are generated, since this affects component and equipment ratings. Purchasers are interested in a verifiable loss figure which allows equitable bid comparison and in a procedure which can objectively verify the guaranteed performance requirements of the supplier after delivery. The main purpose of this document is to serve the purchasers this specific interest.

As a general principle, it would be desirable to determine the efficiency of an HVDC converter station by a direct measurement of its energy losses. However, attempts to determine the station losses by subtracting the measured output power from the measured input power should recognize that such measurements have an inherent inaccuracy, especially if performed at high voltage. The losses of an HVDC converter station at full load are generally less than 1 % of the transmitted power. Therefore, the loss measured as a small difference between two large quantities is not likely to be a sufficiently accurate indication of the actual losses. In some special circumstances, it may can be possible, for example, to arrange a temporary test connection in which two converters are operated from the same AC source and also connected together via their DC terminals. In this connection, the power drawn from the AC source equals the losses in the circuit though in most cases this does not represent a normal operating design mode. However, the AC source shall also provide var support and commutating voltage to the two converters. Once again, there are practical measurement difficulties, and it is still important that the losses are recalculated/corrected for nominal parameters and ambient/operating conditions. 5 In order to avoid the problems described above since these practical measurements are unreliable and also will depend on the type of HVDC solution, it is recommended to use this document which standardizes a method of calculating the HVDC converter station losses by summing the losses calculated for each item of equipment. The standardized calculation method will help the purchaser to meaningfully compare the competing bids. It will also allow an easy generation of performance curves for the wide range of operating conditions in which the performance has to be known. In the absence of an inexpensive experimental method which could be employed for an objective verification of losses during type tests, the calculation method is the next best alternative as it uses, wherever possible, experimental data obtained from measurements on individual equipment and components under conditions equivalent to those encountered in real operation.

Typical high-voltage direct current (HVDC) equipment for one pole of an LCC HVDC substation is shown in Figure 1 and for one pole of a VSC HVDC substation in Figure 2 6. The calculation of harmonic currents and voltages in HVDC equipment for line-commutated converter stations is described in Annex A.

Key

1 AC switchyard 9 DC smoothing reactor

2 shunt reactor bank 10 voltage divider 3 shunt capacitor bank 11 PLC filter

4 AC filter bank 12 DC filter

5 capacitor voltage transformer 13 DC current measuring device

6 PLC filter 14 pole line

7 converter transformer 15 ground electrode 8 valve hall Figure 1 – Typical high-voltage direct current (HVDC) equipment for one pole of an LCC scheme

Key

1 circuit breaker 9 VSC unit 2 pre-Insertion resistor 10 VSC DC capacitor

3 line side harmonic filter 11 DC harmonic filter 4 line side high frequency filter 12 dynamic braking system

5 interface transformer 13 neutral point grounding branch 6 converter side harmonic filter 14 DC reactor 7 + 8 converter side high frequency filter 15 DC cable or overhead transmission line 8 phase reactor a In some designs of VSC based on VSC switch type valves, the harmonic filters may not be required. b In some designs of VSC, the phase reactor may fulfill part of the function of the converter-side high frequency filter.

In some VSC topologies, each valve of the VSC unit may include a "valve reactor", which can be built into the valve or provided as a separate component.

d In some designs of VSC, the VSC DC capacitor may be partly or entirely distributed amongst the three phase units of the VSC Unit, where it is referred to as the DC submodule capacitors. e The philosophy and location of the neutral point grounding branch can be different depending on the design of the VSC unit.

f In some designs of VSC, the interface transformer can fulfill part of the function of the line-side high frequency filter.

g Optional.

h Optional, if phase reactors or valve reactors are located on the DC side of the converter. Figure 2 – Typical high-voltage direct current (HVDC) equipment for one pole of a VSC scheme Compared with LCCs, VSCs for HVDC systems generate a much less distorted AC side current waveform. Depending on the converter topology and the control methods employed for VSC, the network side voltage generated by the converter can approach a clean fundamental frequency sinusoid. The VSC converter can be considered as a harmonic voltage source behind an internal impedance, rather than a current source as for LCCs, as it is the generated harmonic voltage which remains independent of load. The harmonic levels can be extremely low compared to LCCs, but due to the adopted switching regime have a significant frequency range much higher than for LCCs, and can contain inter-harmonics, which are a result of the control strategy adopted. Refer to the IEC TR 62001-5 for harmonics generation of VSC converters. 7 NOTE In this document, where the term "harmonic" is used for VSC converters, it is considered to mean the "harmonic group" according to IEC 61000-4-7, which includes the integer harmonic and the spectral bins from h – 0,5 to h + 0,5, instead of "harmonic number n".

It is important to note that the power loss in each item of equipment will depend on the ambient conditions under which it operates, as well as on the operating conditions or duty cycles to which it is subjected. Therefore, the ambient and operating conditions shall be defined for each item of equipment, based on the ambient and operating conditions of the entire HVDC converter station.

It is recognized that, for AC and DC side filter equipment, the specified notional requirements do not represent the actual losses to be expected in service; however, the simplified approach specified in this document is considered acceptable to estimate losses and compare different bids.

4.2 Ambient conditions

4.2.1 General

A set of standard reference ambient conditions shall be used for determining the power losses in HVDC converter stations.

4.2.2 Outdoor standard reference temperature

An outdoor ambient dry bulb temperature of 20 °C shall be used as the standard reference temperature for determining the total converter station losses. The corresponding valve hall temperature may can be defined by the supplier if necessary. The equivalent wet-bulb temperature (where necessary) shall be defined by the purchaser. If not defined, the wet-bulb temperature is recommended to be 14 °C, which corresponds to approximately 50 % RH at 20 °C dry bulb temperature.

4.2.3 Coolant standard reference temperature

Where forced cooling is used for equipment, the flow rate and temperature of the coolant can influence the temperature rise and associated losses of that equipment. Therefore, the coolant temperatures and flow rates established by the purchaser and the supplier shall be used as a basis for determining the losses.

4.2.4 Standard reference air pressure

The reference air pressure to be used for the evaluation of total converter station power losses shall be the standard atmospheric pressure (101,3 kPa) corrected to the altitude of the installation in question when station is located above 1 000 m above sea level.

4.3 Operating parameters

The losses of an HVDC converter station depend on its operating parameters. The losses of HVDC converter stations are classified into two categories, referred to as operating losses (3.1.4 and 3.1.7) and no-load operation losses (3.1.2 and 3.1.6). The operating losses and auxiliary losses are affected by the load level of the station because the numbers of certain types of energised equipment (for example harmonic filters and cooling equipment) may can depend upon the load level and because losses in individual items of equipment themselves vary with the load level.

HVDC converter station losses shall be determined for nominal (balanced) AC system voltage and frequency, symmetrical impedances of the converter transformer (between phases, and for LCC schemes, between the star and delta-connected bridges) and, for LCC schemes, symmetrical firing angles. The transformer tap-changer shall be assumed to be in the position corresponding to nominal AC system voltage or as decided by the control system for the defined operating condition.

The operating losses shall be determined for the load levels specified by the purchaser, or at rated load if no such conditions are specified. For each load level, the valve-winding AC voltage, DC current, converter firing angle, the converter operating conditions defined in 3.1.3, shunt compensation and harmonic filtering equipment shall be consistent with the respective load level and other specified performance requirements, relating, for example, to harmonic distortion and minimum reactive power exchange with the connected ac network. Cooling and other auxiliary equipment, as appropriate to the standard reference temperature (see 4.2.2 and 4.2.3), shall be assumed to be connected to support the respective load level. Unless specifically specified, reactive power shall be assumed zero for a VSC station. For the no-load operation mode, converter transformers shall be energised and the converters blocked. All filters and reactive power compensation equipment shall be assumed to be disconnected except for those which are required to sustain operation at zero load in order, for example, to meet the specified reactive power requirements. Station service loads and auxiliary equipment (e.g. cooling-water pumps) shall be assumed to be connected as required for immediate pick-up of load for the converter station (without waiting for tap changer movement) to specified minimum power.

NOTE For some MMC VSC valves, it can be impracticable to keep the converter blocked with AC circuit breaker closed for a while, due to a need for balancing the submodule capacitor voltages. The operating state generally known as "idling operating state" will also have an additional contribution of valve losses. However, for the purpose of guaranteeing loss calculation, it is sufficient to compare losses for no-load operation losses as defined in 3.1.2 at zero active and reactive power. 8

5 Determination of equipment losses

5.1 Thyristor valve losses (LCC only)

5.1.1 General

The loss production mechanisms applicable when the valves are blocked (no-load operation losses) are different from those applicable in normal operation (operating losses). Operating losses are dealt with in 5.1.2 to 5.1.11, and no-load operation losses are dealt with in 5.1.12. Auxiliary losses are dealt with in 5.8.

Typical high-voltage direct current (HVDC) equipment for one pole of a HVDC substation is shown in Figure 1.

A simplified three-phase diagram of an HVDC 12-pulse converter is shown in Figure 3. Individual valves are marked in the order of their conduction sequence.

...

Contents

  • 1 Domaine d'application
  • 2 Références normatives
  • 3 Termes, définitions et symboles
  • 3.1 Termes et définitions
  • 3.2 Symboles
  • 4 Vue d'ensemble
  • 4.1 Généralités
  • 4.2 Conditions ambiantes
  • 4.3 Paramètres de fonctionnement
  • 5 Détermination des pertes du matériel
  • 5.1 Pertes de valves à thyristor (LCC uniquement)
  • 5.2 Pertes d'un transformateur
  • 5.3 Pertes par filtres côté alternatif
  • 5.4 Pertes au niveau d'une batterie de condensateurs shunt
  • 5.5 Pertes au niveau d'une bobine d'inductance shunt
  • 5.6 Pertes au niveau d'une bobine d'inductance de lissage en courant continu
  • 5.7 Pertes au niveau d'un filtre côté continu
  • 5.8 Pertes du matériel auxiliaire et de la station en service
  • 5.9 Pertes au niveau d'un filtre en série
  • 5.10 Pertes au niveau de l'inductance de phase (VSC uniquement)
  • 5.11 Pertes au niveau de l'inductance de valve (VSC uniquement)
  • 5.12 Autres pertes au niveau du matériel
  • Annexe A
  • 6 ××IF
  • 6 ××IF U
  • Annexe B
  • Annexe C
  • Bibliographie

1 Domaine d'application

Le présent document s'applique à toutes les stations de conversion en courant continu à haute tension (CCHT) avec convertisseurs commutés par le réseau (LCC, Line-Commutated Converters) et avec convertisseurs de source de tension (VSC, Voltage-Sourced Converters), utilisées pour l'échange de puissance (transmission de puissance ou installation dos à dos) dans des systèmes de distribution d'énergie. Pour les convertisseurs commutés par le réseau (LCC), le présent document présuppose l'utilisation de convertisseurs à thyristors à 12 pulsations, mais peut également, en prenant les précautions appropriées, s'appliquer à des convertisseurs à thyristors à 6 pulsations.

Lorsqu'il est fait référence à un VSC dans le présent document, il est admis par hypothèse qu'il s'agit d'un VSC de type MMC ou similaire, avec une très faible génération d'harmoniques. Il est important de traiter d'autres types de VSC selon le cas.

Dans certaines applications, des compensateurs synchrones, des compensateurs var statiques (CVS) ou des compensateurs statiques synchrones (STATCOM) sont connectés au bus en courant alternatif de la station de conversion en courant continu à haute tension (CCHT). Les procédures de détermination de pertes pour ce type de matériel ne figurent pas dans le présent document.

Le présent document décrit un ensemble de procédures types qui permettent de déterminer l'ensemble des pertes d'une station de conversion CCHT, à l'exception des valves VSC qui sont couvertes par la série IEC 62751. Les procédures s'appliquent à toutes les pièces, à l'exception de celles susmentionnées, et prennent en compte les pertes en fonctionnement à vide et les pertes en fonctionnement ainsi que leurs méthodes de calcul qui utilisent, dans la mesure du possible, des paramètres mesurés.

Les conceptions de station de conversion qui utilisent des composants ou des configurations de circuit originaux par rapport à la conception type prise pour hypothèse dans le présent document, ou des conceptions équipées de circuits auxiliaires inhabituels susceptibles de modifier les pertes, sont évaluées selon leurs propres mérites.

2 Références normatives

Les documents suivants sont cités dans le texte de sorte qu'ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition du document de référence s'applique (y compris les éventuels amendements).

IEC 60076-1, Transformateurs de puissance - Partie 1: Généralités IEC 60076-6, Transformateurs de puissance - Partie 6: Bobines d'inductance IEC 60633, Transport d'énergie en courant continu à haute tension (CCHT) - Vocabulaire IEC 60700-1:2015, Valves à thyristors pour le transport d'énergie en courant continu à haute tension (CCHT) - Partie 1: Essais électriques IEC 60700-1:2015/AMD1:2021 IEC 60871-1, Condensateurs shunt pour réseaux à courant alternatif de tension assignée supérieure à 1 000 V - Partie 1: Généralités IEC 62747, Terminologie relative aux convertisseurs de source de tension (VSC) des systèmes en courant continu à haute tension (CCHT)

3 Termes, définitions et symboles

Pour les besoins du présent document, les termes et définitions de l'IEC 60633 et de l'IEC 62747 ainsi que les suivants s'appliquent.

L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:

  • IEC Electropedia: disponible à l'adresse http://www.electropedia.org/
  • ISO Online browsing platform: disponible à l'adresse http://www.iso.org/obp

3.1 Termes et définitions

3.1.1   pertes auxiliaires puissance électrique exigée pour alimenter les charges auxiliaires des stations de conversion Note 1 à l'article: Les pertes auxiliaires dépendent du nombre d'unités de conversion utilisées et varient selon que la station fonctionne à vide ou en charge, auquel cas les pertes auxiliaires dépendent du niveau de charge. 3.1.2   pertes en fonctionnement à vide du matériel pertes produites dans un élément de matériel tandis que la station de conversion est sous tension, mais que les convertisseurs sont bloqués et que toutes les charges de station en service et le matériel auxiliaire sont connectés comme cela est exigé pour la captation immédiate d'une charge à la puissance minimale spécifiée 3.1.3   niveau de charge ensemble des conditions de fonctionnement du réseau à courant alternatif et du convertisseur dans lesquelles la station de conversion fonctionne Note 1 à l'article: Pour les systèmes LCC, le niveau de charge est défini par le courant continu, la tension continue, l'angle d'allumage, la tension du réseau à courant alternatif et la position du changeur de prises du transformateur de conversion.

Note 2 à l'article: Pour les systèmes VSC, le niveau de charge est défini par le courant continu, la tension continue, la tension du réseau à courant alternatif, la position du changeur de prises du transformateur d'interface (le cas échéant), la tension alternative du convertisseur, le courant alternatif du convertisseur et l'angle de phase entre la tension alternative et le courant alternatif du convertisseur. 3.1.4   pertes en fonctionnement du matériel pertes produites dans un élément de matériel à un niveau de charge donné, tandis que la station de conversion est sous tension et que les convertisseurs sont en fonctionnement 3.1.5   charge assignée charge qui correspond au fonctionnement aux valeurs nominales des conditions de fonctionnement définies au 3.1.3 Note 1 à l'article: Par hypothèse, le réseau à courant alternatif doit être à la fréquence nominale et ses tensions triphasées sont nominales et équilibrées. La position du changeur de prises du transformateur de conversion/d'interface et le nombre de filtres à courant alternatif et d'éléments d'inductance shunt éventuellement connectés doivent être cohérents avec un fonctionnement sous une charge assignée, qui coïncide avec des conditions nominales.

3.1.6   pertes totales en fonctionnement à vide d'une station somme de toutes les pertes en fonctionnement à vide du matériel (3.1.2) et des pertes auxiliaires correspondantes (3.1.1)

3.1.7   pertes totales en fonctionnement d'une station somme de toutes les pertes en fonctionnement du matériel (3.1.4) et des pertes auxiliaires correspondantes (3.1.1) à un niveau de charge particulier Note 1 à l'article: L'Annexe C, cas D1, illustre ceci par un exemple utilisant les pertes totales en fonctionnement d'une station et l'évaluation des pertes correspondante. 3.1.8   pertes totales d'une station en charge différence entre les pertes totales en fonctionnement d'une station (3.1.7) et les pertes totales en fonctionnement à vide d'une station (3.1.6) Note 1 à l'article: Les pertes totales d'une station en charge ainsi calculées sont considérées comme équivalentes, sur un plan quantitatif, aux pertes dues à la charge telles que celles de la pratique conventionnelle pour une station en courant alternatif.

Note 2 à l'article: Il est admis que certains acheteurs évaluent les pertes totales en fonctionnement à vide d'une station (3.1.6) et les pertes totales d'une station en charge de manière individuelle plutôt que d'évaluer les pertes totales en fonctionnement d'une station (3.1.7).

Note 3 à l'article: L'Annexe C, cas D2, illustre ceci par un exemple permettant d'extraire les pertes dues à la charge, les pertes dues à la charge équivalentes et l'évaluation des pertes correspondante. 3.1.9   charge auxiliaire essentielle à la station charge dont la défaillance compromet la capacité de conversion de la station de conversion CCHT (par exemple, le refroidissement des valves), ou charge qui continue à fonctionner en cas de coupure totale de l'alimentation en courant alternatif (par exemple, les chargeurs de batterie, les mécanismes de fonctionnement)

3.2 Symboles

3.2.1 Communs

f fréquence du réseau à courant alternatif, en hertz (Hz) I courant continu, en ampères (A) d I courant efficace harmonique de rang n, en ampères (A) n n rang de l'harmonique P perte en puissance dans un élément de matériel, en watts (W) facteur de qualité d'une bobine d'inductance pour un rang d'harmonique n Q n R valeur de la résistance, en ohms (Ω) U tension continue, en volts (V) d U tension efficace harmonique de rang n, en volts (V) n X réactance inductive pour un rang d'harmonique n, en ohms (Ω) n

3.2.2 Convertisseurs commutés par le réseau

α angle de retard (d'amorçage/allumage), en radians (rad) γ angle d'extinction, en radians (rad) µ angle d'empiétement, en radians (rad) L inductance, en henrys (H), se rapportant à l'enroulement de la valve, entre la source

de tension de commutation et le point de couplage commun des enroulements en étoile et en triangle; L doit inclure toute inductance externe entre les bornes d'enroulement

de ligne du transformateur et le point de connexion des filtres d'harmoniques à courant alternatif L inductance, en henrys (H), se rapportant à l'enroulement de la valve, entre le point de

couplage commun des enroulements en étoile et en triangle; la valve L doit inclure

l'inductance saturée des bobines d'inductance de la valve m facteur de couplage électromagnétique à bande étroite, m = L /(L + L ) 1 1 2 N nombre de thyristors connectés en série par valve t U valeur efficace de la tension à vide entre phases sur le côté valve du transformateur vo de conversion à l'exclusion des harmoniques, en volts (V)

4 Vue d'ensemble

4.1 Généralités

Il est important que les fournisseurs sachent précisément comment et où sont générées les pertes, en raison de l'influence de ces dernières sur les valeurs assignées des composants et matériels. Les acheteurs souhaitent disposer d'une valeur de perte vérifiable qui permet une comparaison équitable des offres et d'une procédure qui permet de vérifier objectivement les exigences de caractéristiques fonctionnelles garanties par le fournisseur après la livraison. L'objet principal du présent document est de servir spécifiquement cet intérêt des acheteurs.

En règle générale, il est souhaitable de déterminer l'efficacité d'une station de conversion CCHT en mesurant directement ses pertes d'énergie. Cependant, d'après les tentatives effectuées pour déterminer les pertes de station en soustrayant la puissance mesurée en sortie de la puissance mesurée en entrée, il convient de reconnaître que ces mesurages présentent une inexactitude inhérente, particulièrement lorsqu'ils sont réalisés à haute tension. Les pertes de station de conversion CCHT à pleine charge sont généralement inférieures à 1 % de la puissance transmise. Par conséquent, il est probable que les pertes mesurées, qui représentent une faible différence entre deux grandes quantités, ne fournissent pas une indication suffisamment exacte des pertes réelles.

Dans certaines circonstances particulières, il peut être possible, par exemple, de réaliser un montage d'essai temporaire dans lequel deux convertisseurs fonctionnent à partir de la même source de courant alternatif et sont également raccordés par l'intermédiaire de leurs bornes en courant continu. Dans ce raccordement, la puissance issue de la source de courant alternatif est égale aux pertes dans le circuit, même si dans la plupart des cas cela ne représente pas un mode nominal de fonctionnement normal. Cependant, la source de courant alternatif doit également fournir un support var et une tension de commutation aux deux convertisseurs. Là encore, des difficultés liées au mesurage pratique sont rencontrées, et il est toujours important de recalculer/corriger les pertes pour les paramètres nominaux et les conditions ambiantes/de fonctionnement.

Pour éviter les problèmes décrits ci-dessus, puisque ces mesurages pratiques ne sont pas fiables et dépendent également du type de solution CCHT, il est recommandé d'utiliser le présent document qui normalise une méthode de calcul des pertes de station de conversion CCHT en additionnant les pertes calculées pour chaque élément de matériel. La méthode de calcul normalisée aide l'acheteur à réaliser une comparaison significative des offres concurrentes. Elle permet également de créer facilement des courbes qui représentent les caractéristiques fonctionnelles pour un large éventail de conditions de fonctionnement dans lesquelles ces caractéristiques doivent être connues. En l'absence de méthode expérimentale peu coûteuse permettant une vérification objective des pertes au cours d'essais de type, la méthode de calcul constitue la meilleure solution de remplacement, car elle utilise, dans la mesure du possible, des données expérimentales obtenues à partir des mesurages réalisés sur un matériel et des composants individuels dans des conditions équivalentes à celles rencontrées en fonctionnement réel.

La Figure 1 et la Figure 2 représentent le matériel type en courant continu à haute tension (CCHT) pour un pôle d'une station CCHT LCC et pour un pôle d'une station CCHT VSC, respectivement. Le calcul des courants et tensions harmoniques dans le matériel CCHT pour les stations à convertisseurs commutés par le réseau est décrit à l'Annexe A.

Légende 1 poste de manœuvres courant alternatif 9 bobine d'inductance de lissage en courant continu 2 batterie d'inductances shunt 10 diviseur de tension 3 batterie de condensateurs shunt 11 filtre PLC 4 batterie de filtres côté courant alternatif 12 filtre côté continu 5 transformateur capacitif de tension 13 dispositif de mesure de courant continu 6 filtre PLC 14 ligne des pôles 7 transformateur de conversion 15 électrode de terre 8 salle des valves Figure 1 – Matériel type en courant continu à haute tension (CCHT) pour un pôle d'un système LCC

Légende

1 disjoncteur 9 unité VSC 2 résistance de préinsertion 10 condensateur à courant continu à VSC

3 filtre d'harmonique côté réseau 11 filtre d'harmonique à courant continu 4 filtre haute fréquence côté réseau 12 système de freinage dynamique

5 transformateur d'interface 13 branche de mise à la terre du point neutre 6 filtre d'harmonique côté convertisseur 14 inductance à courant continu 7 + 8 filtre haute fréquence côté convertisseur 15 câble à courant continu ou ligne de transport aérienne 8 inductance de phase a Dans certaines conceptions de VSC fondées sur des valves de type commutateur VSC, les filtres harmoniques

peuvent ne pas être exigés.

b Dans certaines conceptions de VSC, l'inductance de phase peut remplir une partie de la fonction du filtre haute fréquence côté convertisseur.

Dans certaines topologies de VSC, chaque valve de l'unité VSC peut contenir une "inductance de valve", qui peut être intégrée dans la valve ou fournie comme un composant séparé. d Dans certaines conceptions de VSC, le condensateur à courant continu à VSC peut être en partie ou en totalité réparti entre les trois unités de phase de l'unité VSC, auquel cas il est appelé condensateur de sous-module à courant continu.

e La philosophie et l'emplacement de la branche de mise à la terre du point neutre peuvent être différents selon la conception de l'unité VSC.

f Dans certaines conceptions de VSC, le transformateur d'interface peut remplir une partie de la fonction du filtre haute fréquence côté ligne.

g Facultatif.

h Facultatif, si les inductances de phase ou les inductances de valve sont situées du côté continu du convertisseur. Figure 2 – Matériel type en courant continu à haute tension (CCHT) pour un pôle d'un système VSC Par rapport aux LCC, les VSC pour systèmes CCHT produisent une forme d'onde de courant coté alternatif beaucoup moins déformée. Selon la topologie du convertisseur et les méthodes de commande employées pour les VSC, la tension côté réseau générée par le convertisseur peut s'approcher d'une sinusoïde propre de fréquence fondamentale. Le convertisseur VSC peut être considéré comme une source de tension harmonique derrière une impédance interne, plutôt que comme une source de courant comme pour les LCC, car c'est la tension harmonique générée qui reste indépendante de la charge. Les niveaux d'harmoniques peuvent être extrêmement faibles par rapport aux LCC, mais en raison du régime de commutation adopté, ils ont une plage de fréquences significatives beaucoup plus élevée que pour les LCC et ils peuvent contenir des interharmoniques, qui sont un résultat de la stratégie de commande adoptée. Se référer à l'IEC TR 62001-5 pour la génération d'harmoniques des convertisseurs VSC.

NOTE Dans le présent document, lorsque le terme "harmonique" est utilisé pour les convertisseurs VSC, il est considéré qu'il s'agit du "groupe d'harmoniques" selon l'IEC 61000-4-7, qui comprend l'harmonique entier et les classes spectrales de h – 0,5 à h + 0,5, plutôt que du "rang d'harmonique n". Il est important de noter que la perte en puissance dans chaque élément de matériel dépend des conditions ambiantes dans lesquels il fonctionne, ainsi que des conditions de fonctionnement ou des cycles de service auxquels il est soumis. Par conséquent, les conditions ambiantes et de fonctionnement doivent être définies pour chaque élément de matériel à partir des conditions ambiantes et de fonctionnement de l'ensemble de la station de conversion CCHT.

Il est reconnu que, pour les matériels de filtrage côté alternatif et continu, les exigences théoriques spécifiées ne représentent pas les pertes réelles à prévoir en service, mais l'approche simplifiée spécifiée dans le présent document est considérée comme acceptable pour estimer les pertes et comparer les différentes offres.

4.2 Conditions ambiantes

4.2.1 Généralités

Un ensemble de conditions ambiantes de référence doit être utilisé pour déterminer les pertes en puissance des stations de conversion CCHT.

4.2.2 Température extérieure de référence normalisée

Une température extérieure ambiante sèche de 20 °C doit être utilisée comme température de référence normalisée pour déterminer les pertes totales de station de conversion. La température correspondante de la salle des valves peut être définie par le fournisseur si nécessaire. La température humide équivalente (si nécessaire) doit être définie par l'acheteur. Lorsqu'elle n'est pas définie, il est recommandé que la température humide soit de 14 °C, ce qui correspond approximativement à 50 % d'humidité relative pour une température sèche de 20 °C.

4.2.3 Température de référence normalisée de l'agent de refroidissement

Lorsqu'un refroidissement forcé est utilisé pour le matériel, le débit et la température de l'agent de refroidissement peuvent influencer la hausse de température et les pertes associées de ce matériel. Par conséquent, les températures et les débits de l'agent de refroidissement établis par l'acheteur et le fournisseur doivent servir de base pour déterminer les pertes.

4.2.4 Pression de l'air de référence normalisée

La pression de l'air de référence à utiliser pour l'évaluation des pertes totales en puissance d'une station de conversion doit correspondre à la pression atmosphérique normalisée (101,3 kPa) corrigée en fonction de l'altitude de l'installation en question lorsque la station est située à plus de 1 000 m au-dessus du niveau de la mer.

4.3 Paramètres de fonctionnement

Les pertes d'une station de conversion CCHT dépendent de ses paramètres de fonctionnement. Les pertes des stations de conversion CCHT sont classées en deux catégories désignées comme suit: pertes en fonctionnement (3.1.4 et 3.1.7) et pertes en fonctionnement à vide (3.1.2 et 3.1.6).

Les pertes en fonctionnement et les pertes auxiliaires sont influencées par le niveau de charge de la station, car le nombre de certains types de matériels sous tension (par exemple, filtres d'harmoniques et matériel de refroidissement) peut dépendre du niveau de charge et les pertes au niveau des éléments individuels de matériel eux-mêmes varient avec le niveau de charge.

...