IEC 61241-11:2005
(Main)Electrical apparatus for use in the presence of combustible dust - Part 11: Protection by intrinsic safety 'iD'
Electrical apparatus for use in the presence of combustible dust - Part 11: Protection by intrinsic safety 'iD'
This part of IEC 61241 specifies requirements for the construction and testing of intrinsically safe apparatus intended for use in potentially explosive dust cloud or dust layer environments and for associated apparatus that is intended for connection to intrinsically safe circuits which enter such environments. The contents of the corrigendum of February 2006 have been included in this copy.
Matériels électriques pour utilisation en présence de poussières combustibles - Partie 11: Protection par sécurité intrinsèque "iD"
Cette partie de la CEI 61241 spécifie les exigences relatives à la construction et aux essais des matériels à sécurité intrinsèque destinés à être utilisés dans des environnements de nuage ou de couches de poussières combustibles, et des matériels associés destinés à être connectés à des matériels à sécurité intrinsèque qui entrent dans de tels environnements. Le contenu du corrigendum de février 2006 a été pris en considération dans cet exemplaire.
General Information
- Status
- Replaced
- Publication Date
- 23-Oct-2005
- Technical Committee
- SC 31G - Intrinsically-safe apparatus
- Current Stage
- DELPUB - Deleted Publication
- Start Date
- 30-Jun-2011
- Completion Date
- 13-Feb-2026
Relations
- Replaced By
IEC 60079-11:2011 - Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i" - Effective Date
- 05-Sep-2023
- Effective Date
- 05-Sep-2023
Get Certified
Connect with accredited certification bodies for this standard

Intertek Testing Services NA Inc.
Intertek certification services in North America.

UL Solutions
Global safety science company with testing, inspection and certification.

ANCE
Mexican certification and testing association.
Sponsored listings
Frequently Asked Questions
IEC 61241-11:2005 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Electrical apparatus for use in the presence of combustible dust - Part 11: Protection by intrinsic safety 'iD'". This standard covers: This part of IEC 61241 specifies requirements for the construction and testing of intrinsically safe apparatus intended for use in potentially explosive dust cloud or dust layer environments and for associated apparatus that is intended for connection to intrinsically safe circuits which enter such environments. The contents of the corrigendum of February 2006 have been included in this copy.
This part of IEC 61241 specifies requirements for the construction and testing of intrinsically safe apparatus intended for use in potentially explosive dust cloud or dust layer environments and for associated apparatus that is intended for connection to intrinsically safe circuits which enter such environments. The contents of the corrigendum of February 2006 have been included in this copy.
IEC 61241-11:2005 is classified under the following ICS (International Classification for Standards) categories: 29.260.20 - Electrical apparatus for explosive atmospheres. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 61241-11:2005 has the following relationships with other standards: It is inter standard links to IEC 60079-11:2011, IEC 61241-11:2005/COR1:2006. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
IEC 61241-11:2005 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
NORME CEI
INTERNATIONALE
IEC
61241-11
INTERNATIONAL
Première édition
STANDARD
First edition
2005-10
Matériels électriques pour utilisation
en présence de poussières combustibles –
Partie 11:
Protection par sécurité intrinsèque «iD»
Electrical apparatus for use in the presence
of combustible dust –
Part 11:
Protection by intrinsic safety 'iD'
Numéro de référence
Reference number
CEI/IEC 61241-11:2005
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE
IEC
61241-11
INTERNATIONAL
Première édition
STANDARD
First edition
2005-10
Matériels électriques pour utilisation
en présence de poussières combustibles –
Partie 11:
Protection par sécurité intrinsèque «iD»
Electrical apparatus for use in the presence
of combustible dust –
Part 11:
Protection by intrinsic safety 'iD'
IEC 2005 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
Q
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61241-11 CEI:2005
SOMMAIRE
AVANT-PROPOS.4
INTRODUCTION.10
1 Domaine d’application.14
2 Références normatives.18
3 Termes et définitions .18
4 Groupement et classification des matériels à sécurité intrinsèque
et des matériels associés .18
5 Catégories de matériels électriques.18
6 Construction du matériel.20
6.1 Enveloppes.20
6.2 Températures des matériels immergés dans la poussière.20
6.3 Equipements pour la connexion des circuits externes.22
6.4 Distances de séparation.24
6.5 Protection contre les inversions de polarité .24
6.6 Conducteurs de mise à la terre, connexions et raccordements .24
6.7 Encapsulage utilisé pour l’exclusion des atmosphères potentiellement
explosives .24
7 Composants intervenant dans la sécurité intrinsèque .24
7.1 Caractéristiques assignées d’un composant .24
7.2 Connecteurs pour connexions internes, cartes enfichables et composants .24
7.3 Fusibles.24
7.4 Accumulateurs et piles, primaires et secondaires .24
7.5 Semiconducteurs.24
7.6 Défaillances de composants et de connexions.24
7.7 Composants piézo-électriques.24
8 Composants infaillibles, assemblages infaillibles de composants
et connexions infaillibles .24
9 Barrières de sécurité à diodes .26
10 Vérification de type, essais de vérification et de type.26
10.1 Vérification de l’inflammation par étincelle.26
10.2 Essais de température.26
10.3 Essai de tension.26
10.4 Essai d’inflammation des composants de petite taille .26
10.5 Détermination des paramètres des composants mal définis.26
10.6 Essais pour piles et accumulateurs .26
10.7 Essais mécaniques.26
10.8 Essais pour les matériels comportant des dispositifs piézo-électriques.28
10.9 Essais de type des barrières de sécurité à diodes et des shunts de sécurité .28
10.10 Essai de traction des câbles.28
11 Vérifications et essais individuels .28
12 Marquage.28
12.1 Généralités.28
12.2 Marquage des équipements de raccordement.30
13 Documentation.32
Annexe A (normative) Voir Annexe B de la CEI 60079-11 .34
Annexe B (informative) Voir Annexe C de la CEI 60079-11 .34
Annexe C (normative) Voir Annexe D de la CEI 60079-11.34
61241-11 IEC:2005 – 3 –
CONTENTS
FOREWORD.5
INTRODUCTION.11
1 Scope.15
2 Normative references.19
3 Terms and definitions .19
4 Grouping and classification of intrinsically safe apparatus and associated apparatus .19
5 Categories of electrical apparatus .19
6 Apparatus construction.21
6.1 Enclosures.21
6.2 Temperatures of apparatus immersed in dust. .21
6.3 Facilities for connection of external circuits .23
6.4 Separation distances.25
6.5 Protection against polarity reversal.25
6.6 Earth conductors, connections and terminals.25
6.7 Encapsulation used for exclusion of potentially explosive atmosphere.25
7 Components on which intrinsic safety depends.25
7.1 Rating of components.25
7.2 Connectors for internal connections, plug-in cards and components .25
7.3 Fuses.25
7.4 Primary and secondary cells and batteries .25
7.5 Semiconductors.25
7.6 Failure of components and connections.25
7.7 Piezo-electric devices.25
8 Infallible components, infallible assemblies of components and infallible connections .25
9 Diode safety barriers.27
10 Type verifications, assessments and type tests .27
10.1 Spark ignition assessment.27
10.2 Temperature tests.27
10.3 Voltage tests.27
10.4 Small component ignition test.27
10.5 Determination of parameters of loosely specified components.27
10.6 Tests for cells and batteries .27
10.7 Mechanical test .27
10.8 Tests for apparatus containing piezoelectric devices .29
10.9 Type tests for diode safety barriers and safety shunts .29
10.10 Cable pull test .29
11 Routine verifications and tests.29
12 Marking.29
12.1 General.29
12.2 Marking of connection facilities.31
13 Documentation.33
Annex A (normative) See Annex B of IEC 60079-11.35
Annex B (informative) See Annex C of IEC 60079-11.35
Annex C (normative) See Annex D of IEC 60079-11 .35
– 4 – 61241-11 © CEI:2005
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
MATÉRIELS ÉLECTRIQUES POUR UTILISATION
EN PRÉSENCE DE POUSSIÈRES COMBUSTIBLES –
Partie 11: Protection par sécurité intrinsèque «iD»
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés «Publication(s) de la CEI»). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de la CEI. La CEI n'est responsable d'aucun des services effectués par les organismes de
certification indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 61241-11 a été établie par le sous-comité 31H: Matériels
destinés à être utilisés en présence de poussières inflammables, du comité d'études 31 de la
CEI: Matériels électriques pour atmosphères explosives.
Le texte de cette norme est basé sur les documents suivants:
FDIS Rapport de vote
31H/194/FDIS 31H/198/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
61241-11 © IEC:2005 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
___________
ELECTRICAL APPARATUS FOR USE IN THE
PRESENCE OF COMBUSTIBLE DUST –
Part 11: Protection by intrinsic safety ‘iD’
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61241-11 has been prepared by subcommittee 31H: Apparatus for
use in the presence of combustible dusts, of IEC technical committee 31: Electrical apparatus
for explosive atmospheres.
The text of this standard is based on the following documents:
FDIS Report on voting
31H/194/FDIS 31H/198/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
– 6 – 61241-11 CEI:2005
La présente partie de la CEI 61241 est à lire conjointement avec la CEI 61241-0.
La CEI 61241 comprend les parties suivantes, sous le titre général Matériels électriques pour
utilisation en présence de poussières combustibles:
Partie 0: Exigences générales
Partie 1: Protection par enveloppes «tD»
Partie 2: Protection par pressurisation «pD»
Partie 10: Classification des zones où les poussières combustibles sont ou peuvent être
présentes
Partie 11: Protection par sécurité intrinsèque «iD»
Partie 14: Sélection et installation
Partie 17: Inspection et maintenance des installations électriques situées en emplacements
dangereux (autres que les mines)
Partie 18: Protection par encapsulage «mD»
Partie 20: Méthodes d'essai
Partie 20-1: Méthodes de détermination des températures minimales d'inflammation des
poussières
Partie 20-2: Méthode de détermination de la résistivité électrique des couches de poussière
Partie 20-3: Méthode de détermination de l'énergie minimale d'inflammation des mélanges
air/poussières
NOTE Dans ce document, toutes les références à la série CEI 61241 suivent la renumérotation proposée pour les
normes de poussière convenue par le SC31H et le CE31. Il peut être nécessaire de modifier ces numéros si les
normes en question ne sont pas encore publiées.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous "http://webstore.iec.ch" dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.
Le contenu du corrigendum de février 2006 a été pris en considération dans cet exemplaire.
61241-11 IEC:2005 – 7 –
This part of IEC 61241 is to be read in conjunction with IEC 61241-0.
IEC 61241 consists of the following parts under the general title Electrical apparatus for use in
the presence of combustible dust:
Part 0: General requirements
Part 1: Protection by enclosures “tD”
Part 2: Protection by pressurization “pD”
Part 10: Classification of areas where combustible dusts are or may be present
Part 11: Protection by intrinsic safety “iD”
Part 14: Selection and installation
Part 17: Inspection and maintenance of electrical installations in hazardous areas (other
than mines)
Part 18: Protection by encapsulation “mD”
Part 20: Test methods
Part 20-1: Methods for determining the minimum ignition temperatures of dust
Part 20-2: Method for determining the electrical resistivity of dust in layers
Part 20-3: Method for determining minimum ignition energy of dust/air mixtures
NOTE All references in this standard to the IEC 61241 series follow the proposed re-numbering of the dust
standards agreed by SC31H and TC31. It may be necessary to alter these numbers if the relevant standards are
not yet published.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of February 2006 have been included in this copy.
– 8 – 61241-11 CEI:2005
TABLEAU DE RÉFÉRENCES
Date de
Nouveau numéro
Norme existante Sujet changement
assigné
prévue
CEI 61241-0 Exigences générales 2004
CEI 61241-1-1
CEI 61241-1 Protection par enveloppes 2004
CEI 61241-1-2 CEI 61241-14 Sélection et installation 2004
CEI 61241-2-1 CEI 61241-20-1 Méthodes d'essai 2005
CEI 61241-2-2 CEI 61241-20-2 Méthodes d'essai 2005
CEI 61241-2-3 CEI 61241-20-3 Méthodes d'essai 2005
CEI 61241-3 CEI 61241-10 Classification 2004
CEI 61241-4 CEI 61241-2 Protection par surpression interne 2005
CEI 61241-11 Protection par sécurité intrinsèque 2005
CEI 61241-17 Inspection et maintenance 2004
CEI 61241-18 Protection par encapsulage 2004
61241-11 IEC:2005 – 9 –
REFERENCE TABLE
Anticipated
New number
Existing standard Subject date of
assigned
change
IEC 61241-0 General requirements 2004
IEC 61241-1-1
IEC 61241-1 Protection by enclosure 2004
IEC 61241-1-2 IEC 61241-14 Selection and installation 2004
IEC 61241-2-1 IEC 61241-20-1 Test methods 2005
IEC 61241-2-2 IEC 61241-20-2 Test methods 2005
IEC 61241-2-3 IEC 61241-20-3 Test methods 2005
IEC 61241-3 IEC 61241-10 Classification 2004
IEC 61241-4 IEC 61241-2 Protection by pressurization 2005
IEC 61241-11 Protection by intrinsic safety 2005
IEC 61241-17 Inspection and maintenance 2004
IEC 61241-18 Protection by encapsulation 2004
– 10 – 61241-11 CEI:2005
INTRODUCTION
De nombreuses poussières qui sont générées, traitées, manipulées et stockées, sont
combustibles. Une fois enflammées, elles peuvent brûler rapidement et avec un pouvoir
explosif considérable si elles sont mélangées à l'air, dans les proportions appropriées. Il est
souvent nécessaire d'utiliser du matériel électrique dans des lieux où de tels matériaux
combustibles sont présents et il faut donc que des précautions adéquates soient prises pour
s'assurer que tous ces matériels soient protégés correctement afin de réduire la probabilité
d'inflammation de l'atmosphère explosive externe. Dans un matériel électrique, les sources
d’inflammation potentielles sont les arcs, les étincelles électriques, les surfaces chaudes et
les étincelles provoquées par les frictions.
Les emplacements où des poussières, des particules en suspension et des fibres sont
contenues dans l'air en quantités dangereuses, sont classés comme des emplacements à
risques et divisés en trois zones selon le niveau de risque.
En général, la sécurité électrique est assurée par la mise en œuvre de l’une des deux
considérations suivantes: le matériel électrique est situé à l'extérieur des zones à risques
lorsque cela est raisonnablement réalisable ou bien le matériel électrique est conçu, installé
et maintenu selon les prescriptions recommandées pour la zone dans laquelle il est situé.
Les poussières combustibles peuvent être enflammées par le matériel électrique
principalement de plusieurs manières:
– par les surfaces du matériel dont la température est supérieure à la température
d'inflammation de la poussière considérée. La température à laquelle une poussière
s'enflamme varie en fonction de ces propriétés, qu'elle se présente sous forme de nuage
ou en couche, de l'épaisseur de la couche, ainsi que de la géométrie de la source de
chaleur;
– par la formation d'arcs ou d'étincelles engendrés par des éléments électriques tels que
des interrupteurs, des contacts, des commutateurs, des balais ou autres;
– par la décharge de charges électrostatiques accumulées;
– par de l'énergie rayonnée (par exemple des rayonnements électromagnétiques);
– par des étincelles dues à des phénomènes mécaniques, des frictions ou un échauffement
provenant du matériel.
Pour éviter les risques d'inflammation, il est nécessaire que:
– la température des surfaces sur lesquelles la poussière peut se déposer ou qui peuvent
entrer en contact avec un nuage de poussière, soit maintenue à un niveau inférieur à la
limite de température spécifiée dans la présente norme;
– tous les éléments pouvant être à l'origine d'étincelles électriques, ou dont la température
dépasse la température limite spécifiée par la CEI 61241-14:
- soient contenus dans une enveloppe qui protège de manière appropriée contre la
pénétration de poussières, ou bien
- que l'énergie dans les circuits électriques soit limitée pour éviter la formation d'arcs,
d'étincelles ou de températures susceptibles d'enflammer des poussières
combustibles;
– toutes autres sources d'inflammation soient évitées.
Plusieurs techniques sont disponibles pour la protection contre l'explosion des matériels
électriques dans les emplacements dangereux. Cette norme décrit les caractéristiques de
sécurité de ces techniques de protection contre l'explosion et spécifie les exigences
d'installation à adopter. Il est de la plus grande importance que les procédures correctes de
choix et d'installation soient suivies pour assurer une utilisation du matériel électrique en
toute sécurité dans les emplacements dangereux.
61241-11 IEC:2005 – 11 –
INTRODUCTION
Many dusts which are generated, processed, handled and stored, are combustible. When
ignited they can burn rapidly and with considerable explosive force if mixed with air in the
appropriate proportions. It is often necessary to use electrical apparatus in locations where
such combustible materials are present, and suitable precautions must therefore be taken to
ensure that all such apparatus is adequately protected so as to reduce the likelihood of
ignition of the external explosive atmosphere. In electrical apparatus, potential ignition
sources include electrical arcs and sparks, hot surfaces and frictional sparks.
Areas where dusts, flyings and fibres in air occur in dangerous quantities are classified as
hazardous and are divided into three zones according to the level of risk.
Generally, electrical safety is ensured by the implementation of one of two considerations, i.e.
that electrical apparatus be located where reasonably practicable outside hazardous areas
and that electrical apparatus be designed, installed and maintained in accordance with
measures recommended for the area in which the apparatus is located.
Combustible dust can be ignited by electrical apparatus in several main ways:
– by surfaces of the apparatus that are above the minimum ignition temperature of the dust
concerned. The temperature at which a type of dust ignites is a function of the properties
of the dust, whether the dust is in a cloud or layer, the thickness of the layer and the
geometry of the heat source;
– by arcing or sparking of electrical parts such as switches, contacts, commutators, brushes,
or the like;
– by discharge of an accumulated electrostatic charge;
– by radiated energy (e.g. electromagnetic radiation);
– by mechanical sparking or frictional sparking or heating associated with the apparatus.
In order to avoid ignition hazards it is necessary that:
– the temperature of surfaces, on which dust can be deposited, or which would be in contact
with a dust cloud, is kept below the temperature limitation specified in this standard;
– any electrical sparking parts, or parts having a temperature above the temperature limit
specified in IEC 61241-14
- are contained in an enclosure which adequately prevents the ingress of dust, or
- the energy of electrical circuits is limited so as to avoid arcs, sparks or temperatures
capable to ignite combustible dust;
– any other ignition sources are avoided.
Several techniques are available for explosion protection of electrical apparatus in hazardous
areas. This standard describes the safety features of this type of explosion-protection
technique and specifies the requirements to be adopted. It is most important that the correct
selection and installation procedures be followed to ensure the safe use of electrical
apparatus in hazardous areas.
– 12 – 61241-11 CEI:2005
La conformité à la présente partie de la CEI 61241 n’assurera le niveau de sécurité prescrit,
que si le matériel électrique est utilisé dans les limites de ses caractéristiques assignées,
installé et entretenu conformément aux codes de bonnes pratiques ou exigences
correspondantes: par exemple pour ce qui concerne la protection contre des surintensités, les
courts-circuits internes et autres défaillances électriques. Il est notamment essentiel que la
gravité et la durée d'une défaillance interne ou externe soient limitées à des valeurs que le
matériel électrique est en mesure de supporter sans subir de dommage: par exemple, installé
dans un système conçu en conformité avec les règles de la CEI 60079-25 et installé en
conformité avec la CEI 61241-14.
Il convient que les principes suivants soient respectés:
– afin d’éviter tout risque d'étincelle, il faut que les circuits électroniques répondent à toutes
les exigences du groupe IIB conformément à la CEI 60079-11;
– une protection de niveau IP 6X ou un encapsulage est normalement requis pour s’assurer
qu’aucune poussière ne vienne altérer les lignes de fuites et les distances d’isolement.
Cependant, le rôle et la longévité de l’intégrité de l’enveloppe ou de l’encapsulage sont
largement plus importants que ceux requis par la CEI 60079-11;
– la puissance des matériels ou de leurs composants non protégés par une enveloppe ou un
encapsulage (par exemple un capteur non isolé) est limitée pour éviter l’inflammation
directe d’une couche de poussière par dissipation en son sein (échauffement provoqué
dans la poussière elle-même par des courants de fuite entre matériels) et pour limiter
l’inflammation d’origine thermique à la surface des composants;
– la température de toutes les surfaces exposées des matériels ou composants excédant
les limitations de puissance est limitée en accord avec la CEI 61241-0. La surface peut
être celle de l’enveloppe ou celle de l’encapsulage.
61241-11 IEC:2005 – 13 –
Compliance with this part of IEC 61241 will only provide the required level of safety if the
electrical apparatus is operated within its rating and is installed and maintained according to
the relevant codes of practice or requirements, for example in respect of protection against
over-currents, internal short-circuits, and other electrical faults. In particular, it is essential
that the severity and duration of an internal or external fault be limited to values that can be
sustained by the electrical apparatus without damage, for example, installed in a system
designed in accordance with the principles of IEC 60079-25 and installed in accordance with
IEC 61241-14.
The following principles should be followed:
– the electronic circuits must fulfil Group IIB requirements according to IEC 60079-11 to
avoid spark ignition;
– IP 6X or encapsulation is normally required to ensure that creepage and clearance
distances are not compromised by dust. Therefore the importance and the durability of the
integrity of the enclosure or encapsulation are much higher than required by IEC 60079-
11;
– There should be power limitation for apparatus or parts of apparatus not protected by an
enclosure or encapsulation (e.g. uninsulated sensor) to avoid ignition of a dust layer by
power dissipation directly into the dust (power matching by conductive dusts) and to avoid
thermal ignition on the surface of components;
– limitation of the temperature of all exposed surfaces of all apparatus or parts of apparatus
exceeding the power limitation limits in accordance with IEC 61241-0. The surface can be
the surface of the enclosure or of the encapsulation.
– 14 – 61241-11 CEI:2005
MATÉRIELS ÉLECTRIQUES POUR UTILISATION
EN PRÉSENCE DE POUSSIÈRES COMBUSTIBLES –
Partie 11: Protection par sécurité intrinsèque «iD»
1 Domaine d’application
Cette partie de la CEI 61241 spécifie les exigences relatives à la construction et aux essais
des matériels à sécurité intrinsèque destinés à être utilisés dans des environnements de
nuage ou de couches de poussières combustibles, et des matériels associés destinés à être
connectés à des matériels à sécurité intrinsèque qui entrent dans de tels environnements.
Les exigences de cette norme s’ajoutent à celles de la CEI 61241-0 à l’exception des cas
indiqués dans la liste ci-dessous.
Les matériels utilisés dans les systèmes seront construits en accord avec la CEI 60079-25.
Lorsque des appareils associés sont protégés par un type de protection inclus dans la
CEI 61241-0 ou dans la CEI 60079-0, les exigences de ces méthodes de protection ainsi que
les parties pertinentes de la CEI 61241 et de la CEI 60079 s’appliquent aussi à ces matériels
associés. La liste suivante des exclusions est directement applicable aux matériels associés
destinés à être utilisés dans des cas où il n’y a pas d’atmosphère potentiellement dangereuse
et qui en d’autres circonstances, seraient utilisés en combinaison avec les exigences d’autres
méthodes de protection.
Matériels en
Article ou paragraphe de la CEI 61241-0 Matériels associés
sécurité intrinsèque
4.1 Généralités S'applique S'applique
4.2 Principes de conception et d'essai du matériel S'applique Exclu
utilisé dans la Zone 20
4.3 Enveloppes à ouverture S'applique Exclu
4.4 Conditions d’environnement S'applique Exclu
5.1 Température maximale de surface S'applique Exclu
5.2 Température maximale de surface par rapport aux S'applique Exclu
couches de poussières supérieures à 50 mm
5.3 Température ambiante S'applique S'applique
6.1 Enveloppes non métalliques et parties non S'applique Exclu
métalliques des enveloppes
6.1.1 Spécification du matériau S'applique Exclu
6.1.2 Matériaux plastiques S'applique Exclu
6.1.3 Vérification de conformité S'applique Exclu
6.1.4 Endurance thermique S'applique Exclu
6.1.5 Charges électrostatiques S'applique Exclu
6.2 Enveloppes contenant des métaux légers S'applique Exclu
6.2.1 Composition S'applique Exclu
6.2.2
Trous taraudés Exclu Exclu
7 Fermetures Exclu Exclu
8 Dispositifs de verrouillage Exclu Exclu
9 Traversées Exclu Exclu
61241-11 IEC:2005 – 15 –
ELECTRICAL APPARATUS FOR USE IN THE
PRESENCE OF COMBUSTIBLE DUST –
Part 11: Protection by intrinsic safety ‘iD’
1 Scope
This part of IEC 61241 specifies requirements for the construction and testing of intrinsically
safe apparatus intended for use in potentially explosive dust cloud or dust layer environments
and for associated apparatus that is intended for connection to intrinsically safe circuits which
enter such environments.
This standard supplements the general requirements of IEC 61241-0: except as indicated in
the following list.
Apparatus utilized in systems will meet the requirements of IEC 60079-25.
If associated apparatus is protected by a type of protection listed in IEC 61241-0 or
IEC 60079-0 then the requirements of that method of protection together with the relevant
parts of IEC 61241 or IEC 60079 also apply to the associated apparatus. The list of
exclusions which follows is directly applicable to associated apparatus intended for use in
situations where there is no potentially hazardous atmosphere and in other circumstances
should be used in combination with the requirements of the other methods of protection.
Intrinsically safe
Clause or subclause of IEC 61241-0 Associated apparatus
apparatus
4.1 General Applies Applies
4.2 Principles for design and testing of apparatus for Applies Excluded
use in Zone 20
4.3 Opening enclosures Applies Excluded
4.4 Environmental conditions Applies Excluded
5.1 Maximum surface temperature Applies Excluded
Maximum surface temperature with respect to
5.2 Applies Excluded
dust layers above 50 mm
5.3 Ambient temperature Applies Applies
6.1 Non-metallic enc
...




Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...