Corrigendum 1 - Amendment 1 - Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers

General Information

Status
Published
Publication Date
04-May-2006
Current Stage
DELPUB - Deleted Publication
Start Date
03-Dec-2013
Completion Date
14-Feb-2026

Relations

Effective Date
05-Sep-2023
Effective Date
05-Sep-2023

Buy Documents

Standard

IEC 60335-2-40:2002/AMD1:2005/COR1:2006 - Corrigendum 1 - Amendment 1 - Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers Released:5/5/2006

English language (10 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

Institut za varilstvo d.o.o. (Welding Institute)

Slovenia's leading welding institute since 1952. ISO 3834, EN 1090, pressure equipment certification, NDT personnel, welder qualification. Only IIW Au

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

IEC 60335-2-40:2002/AMD1:2005/COR1:2006 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Corrigendum 1 - Amendment 1 - Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers". This standard covers: Corrigendum 1 - Amendment 1 - Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers

Corrigendum 1 - Amendment 1 - Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers

IEC 60335-2-40:2002/AMD1:2005/COR1:2006 is classified under the following ICS (International Classification for Standards) categories: 23.120 - Ventilators. Fans. Air-conditioners. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 60335-2-40:2002/AMD1:2005/COR1:2006 has the following relationships with other standards: It is inter standard links to IEC 60335-2-40:2002/AMD1:2005, IEC 60335-2-40:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 60335-2-40:2002/AMD1:2005/COR1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


IEC 60335-2-40 – Amendment 1
(Fourth Edition – 2002)
Household and similar electrical appliances – Safety –

Part 2-40: Particular requirements for electrical heat pumps,

air-conditioners and dehumidifiers

CORRIGENDUM 1
Page 5
7 Marking and instructions
7.1
In the third paragraph, instead of:
If a flammable refrigerant is used, the symbols for reading the user manual, the repair manual
and the installation manual (symbols 3084, 3038 and 1785 of ISO 7000) shall be placed on
the appliance in a location visible to the persons required to know the information. The
perpendicular height shall be at least 10 mm.
read:
If a flammable refrigerant is used, the symbols for “read operator’s manual”, “operator’s
manual; operating instructions” and “service indicator; read technical manual” (symbols 0790,
1641 and 1659 of ISO 7000) shall be placed on the appliance in a location visible to the
persons required to know the information. The perpendicular height shall be at least 10 mm.

7.6
In the second paragraph, instead of:
When a flammable refrigerant is employed, a symbol requiring reference to the manual
[B.3.2 of ISO 3864], including colour and format, shall be permanently placed on the
appliance.
read:
When a flammable refrigerant is employed, a symbol requiring reference to the manual
[0790 of ISO 7000], including colour and format, shall be permanently placed on the
appliance.
May 2006
Page 11
DD.3.2
In the note, instead of:
NOTE The manufacturer shall specify other potential continuously operating sources known to cause ignition of

the refrigerant used.
read:
NOTE The manufacturer should specify other potential continuously operating sources known to cause ignition of

the refrigerant used.
Page 20
FF.2.3
In the note, instead of:
NOTE If a zeotropic blend is used, the test shall be conducted maintaining the composition within a reasonable
range. Liquid phase of the blend may be extracted from the bottle then evaporated. Gas phase release with the
pressure regulator from a large mixed gas tank is the best method.
read:
NOTE If a zeotropic blend is used, the test is conducted maintaining the composition within a reasonable range.
Liquid phase of the blen
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...