Protection against lightning - Part 4: Electrical and electronic systems within structures

IEC 62305-4:2010(E) provides information for the design, installation, inspection, maintenance and testing of electrical and electronic system protection (LPM) to reduce the risk of permanent failures due to lightning electromagnetic impulse (LEMP) within a structure. This second edition cancels and replaces the first edition, published in 2006, and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: 1) Isolating interfaces capable of reducing conducted surges on lines entering the structure are introduced. 2) Minimum cross-sections for bonding components are slightly modified. 3) First negative impulse current is introduced for calculation purposes as electromagnetic source of harm to the internal systems. 4) Selection of SPD with regard to voltage protection level is improved to take into account oscillation and induction phenomena in the circuit downstream of SPD. 5) Annex C dealing with SPD coordination is withdrawn and referred back to SC 37A. 6) A new informative Annex D is introduced giving information on factors to be considered in the selection of SPDs.

Blitzschutz --Teil 4: Elektrische und elektronische Systeme in baulichen Anlagen

Protection contre la foudre - Partie 4: Réseaux de puissance et de communication dans les structures

La CEI 62305-4:2010 fournit des informations relatives à la conception, à l'installation, à l'inspection, à la maintenance et aux essais d'une installation de protection de réseau de puissance et de communication (MPF) visant à réduire le risque de défaillances permanentes dû aux impulsions électromagnétiques de foudre (IEMF) dans une structure. Cette seconde édition annule et remplace la première édition, publiée en 2006, dont elle constitue une révision technique. La présente édition comprend les modifications techniques importantes suivantes par rapport à la précédente édition: 1) Introduction d'interfaces d'isolement capables de réduire les chocs conduits sur les services pénétrant dans la structure. 2) Légère modification des sections minimales des composants de liaison. 3) Introduction d'un premier courant pulsé négatif à des fins de calcul, comme source électromagnétique de dégradation des réseaux internes. 4) Amélioration du choix du parafoudre par rapport au niveau de protection contre les surtensions, afin de tenir compte de l'existence de phénomènes d'oscillation et d'induction dans le circuit en aval du parafoudre. 5) Suppression de l'Annexe C traitant de la coordination des parafoudres avec renvoi au SC 37A. 6) Introduction d'une nouvelle Annexe informative D fournissant des informations sur les facteurs à prendre en compte dans le choix des parafoudres. La présente version bilingue (2012-06) correspond à la version anglaise monolingue publiée en 2010-12.

Zaščita pred delovanjem strele - 4. del: Električni in elektronski sistemi v zgradbah (IEC 62305-4:2010, spremenjen)

Ta mednarodni standard zagotavlja informacije za projektiranje, namestitev, nadzor, vzdrževanje in preskušanje zaščite električnih in elektronskih sistemov (ESP) in ukrepov za zmanjšanje tveganja za trajne okvare zaradi elektromagnetnih impulzov strele (LEMP) v zgradbi. Ne zajema zaščite pred elektromagnetnimi motnjami zaradi delovanja strele, ki lahko povzročijo okvaro elektronskega sistema. Informacije, navedene v dodatku A, pa se lahko kljub temu uporabijo za vrednotenje takih motenj. Ta osnutek mednarodnega standarda ne obravnava podrobnosti projektiranja samih električnih in elektronskih sistemov.

General Information

Status
Published
Publication Date
24-Feb-2011
Withdrawal Date
12-Jan-2014
Drafting Committee
Parallel Committee
Current Stage
6060 - Document made available - Publishing
Start Date
25-Feb-2011
Completion Date
25-Feb-2011

Relations

Buy Standard

Standard
EN 62305-4:2011
English language
91 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2011
1DGRPHãþD
SIST EN 62305-4:2006
=DãþLWDSUHGGHORYDQMHPVWUHOHGHO(OHNWULþQLLQHOHNWURQVNLVLVWHPLY]JUDGEDK
,(&VSUHPHQMHQ
Protection against lightning - Part 4: Electrical and electronic systems within structures
Blitzschutz - Teil 4: Elektrische und elektronische Systeme in baulichen Anlagen
Protection contre la foudre - Partie 4: Réseaux de puissance et de communication dans
les structures
Ta slovenski standard je istoveten z: EN 62305-4:2011
ICS:
91.120.40 =DãþLWDSUHGVWUHOR Lightning protection
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 62305-4
NORME EUROPÉENNE
February 2011
EUROPÄISCHE NORM
ICS 29.020; 91.120.40 Supersedes EN 62305-4:2006 + corr. Nov.2006

English version
Protection against lightning -
Part 4: Electrical and electronic systems within structures
(IEC 62305-4:2010, modified)
Protection contre la foudre -  Blitzschutz - Teil 4: Elektrische und
Partie 4: Réseaux de puissance et de elektronische Systeme in baulichen
communication dans les structures Anlagen
(CEI 62305-4:2010, modifiée) (IEC 62305-4:2010, modifiziert)

This European Standard was approved by CENELEC on 2011-01-13. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62305-4:2011 E
Foreword
The text of document 81/373/FDIS, future edition 2 of IEC 62305-4, prepared by IEC TC 81, Lightning
protection, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as
EN 62305-4 on 2011-01-13.
This European Standard supersedes EN 62305-4:2006 + corr. Nov.2006.
This EN 62305-4:2011 includes the following significant technical changes with respect to
EN 62305-4:2006 + corr. Nov.2006:
1) Isolating interfaces capable of reducing conducted surges on lines entering the structure are
introduced.
2) Minimum cross-sections for bonding components are slightly modified.
3) First negative impulse current is introduced for calculation purposes as electromagnetic source of
harm to the internal systems.
4) Selection of SPD with regard to voltage protection level is improved to take into account oscillation
and induction phenomena in the circuit downstream of SPD.
5) Annex C dealing with SPD coordination is withdrawn and referred back to SC 37A.
6) A new informative Annex D is introduced giving information on factors to be considered in the
selection of SPDs.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2011-10-13
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-13
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 62305-4:2010 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
[2] IEC 61000 series NOTE  Harmonized in EN 61000 series (partially modified).
[8] IEC 61643-11 NOTE  Harmonized as EN 61643-11.
__________
- 3 - EN 62305-4:2011
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year

IEC 60364-5-53 2001 Electrical installations of buildings - - -
Part 5-53: Selection and erection of electrical
equipment - Isolation, switching and control

IEC 60664-1 2007 Insulation coordination for equipment within EN 60664-1 2007
low-voltage systems -
Part 1: Principles, requirements and tests

IEC 61000-4-5 2005 Electromagnetic compatibility (EMC) - EN 61000-4-5 2006
Part 4-5: Testing and measurement
techniques - Surge immunity test

IEC 61000-4-9 1993 Electromagnetic compatibility (EMC) - EN 61000-4-9 1993
Part 4-9: Testing and measurement
techniques - Pulse magnetic field immunity
test
IEC 61000-4-10 1993 Electromagnetic compatibility (EMC) - EN 61000-4-10 1993
Part 4-10: Testing and measurement
techniques - Damped oscillatory magnetic
field immunity test
IEC 61643-1 2005 Low-voltage surge protective devices - - -
Part 1: Surge protective devices connected to
low-voltage power distribution systems -
Requirements and tests
IEC 61643-12 (mod) 2008 Low-voltage surge protective devices - CLC/TS 61643-12 2009
Part 12: Surge protective devices connected
to low-voltage power distribution systems -
Selection and application principles

IEC 61643-21 - Low voltage surge protective devices - EN 61643-21 -
Part 21: Surge protective devices connected
to telecommunications and signalling
networks - Performance requirements and
testing methods
IEC 61643-22 (mod) - Low-voltage surge protective devices - CLC/TS 61643-22 -
Part 22: Surge protective devices connected
to telecommunications and signalling
networks - Selection and application principles

IEC 62305-1 2010 Protection against lightning - EN 62305-1 2011
Part 1: General principles
IEC 62305-2 2010 Protection against lightning - EN 62305-2 2011
Part 2: Risk management
Publication Year Title EN/HD Year

IEC 62305-3 2010 Protection against lightning - EN 62305-3 2011
Part 3: Physical damage to structures and life
hazard
IEC 62305-4 ®
Edition 2.0 2010-12
INTERNATIONAL
STANDARD
Protection against lightning –
Part 4: Electrical and electronic systems within structures

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
PRICE CODE
XC
ICS 29.020; 91.120.40 ISBN 978-2-88912-283-7
– 2 – 62305-4 Ó IEC:2010(E)
CONTENTS
FOREW ORD . 5
INTRODUCTION . 7
1 Sc o pe . 9
2 Normative references . 9
3 Terms and definitions . 10
4 Design and installation of SPM. 13
4.1 General . 13
4.2 Design of SPM . 16
4.3 Lightning protection zones (LPZ) . 17
4.4 Basic SPM . 20
5 Earthing and bonding . 21
5.1 General . 21
5.2 Earth-termination system . 22
5.3 Bonding network . 24
5.4 Bonding bars . 28
5.5 Bonding at the boundary of an LPZ . 29
5.6 Material and dimensions of bonding components . 29
6 Magnetic shielding and line routing . 30
6.1 Spatial shielding . 30
6.2 Shielding of internal lines . 30
6.3 Routing of internal lines . 30
6.4 Shielding of external lines . 31
6.5 Material and dimensions of magnetic shields . 31
7 Coordinated SPD system . 31
8 Isolating interfaces . 32
9 SPM management . 32
9.1 General . 32
9.2 SPM management plan . 32
9.3 Inspection of SPM . 33
9.3.1 Inspection procedure . 34
9.3.2 Inspection documentation . 34
9.4 Maintenance . 35
Annex A (informative) Basis of electromagnetic environment evaluation in an LPZ . 36
Annex B (informative) Implementation of SPM for an existing structure . 60
Annex C (informative) Selection and installation of a coordinated SPD system . 76
Annex D (informative) Factors to be considered in the selection of SPDs . 82
Bibliography . 87

Figure 1 – General principle for the division into different LPZ . 13
Figure 2 – Examples of possible SPM (LEMP protection measures) . 15
Figure 3 – Examples for interconnected LPZ . 19
Figure 4 – Examples for extended lightning protection zones . 20
Figure 5 – Example of a three-dimensional earthing system consisting of the bonding
network interconnected with the earth-termination system . 22
Figure 6 – Meshed earth-termination system of a plant . 23

62305-4 Ó IEC:2010(E) – 3 –
Figure 7 – Utilization of reinforcing rods of a structure for equipotential bonding . 25
Figure 8 – Equipotential bonding in a structure with steel reinforcement . 26
Figure 9 – Integration of conductive parts of internal systems into the bonding network . 27
Figure 10 – Combinations of integration methods of conductive parts of internal
systems into the bonding network . 28
Figure A.1 – LEMP situation due to lightning strike . 37
Figure A.2 – Simulation of the rise of magnetic field by damped oscillations . 40
Figure A.3 – Large volume shield built by metal reinforcement and metal frames . 41
Figure A.4 – Volume for electrical and electronic systems inside an inner LPZ n . 42
Figure A.5 – Reducing induction effects by line routing and shielding measures . 43
Figure A.6 – Example of SPM for an office building . 45
Figure A.7 – Evaluation of the magnetic field values in case of a direct lightning strike . 46
Figure A.8 – Evaluation of the magnetic field values in case of a nearby lightning strike . 48
Figure A.9 – Distance s depending o
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.