Protection against lightning - Part 3: Physical damage to structures and life hazard

IEC 62305-3:2010(E) provides the requirements for protection of a structure against physical damage by means of a lightning protection system (LPS), and for protection against injury to living beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1). This second edition cancels and replaces the first edition, published in 2006, and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: 1) Minimum thicknesses of metal sheets or metal pipes given in Table 3 for air-termination systems are assumed as not able to prevent hot-spot problems. 2) Steel with electro-deposited copper is introduced as material suitable for LPS. 3) Some cross-sectional areas of LPS conductors were slightly modified. 4) For bonding purposes, isolating spark gaps are used for metal installations and SPD for internal systems. 5) Two methods - simplified and detailed - are provided for evaluation of separation distance. 6) Protection measures against injuries of living beings due to electric shock are considered also inside the structure. 7) Improved information for LPS in the case of structures with a risk of explosion are given in Annex D (normative).

Blitzschutz - Teil 3: Schutz von baulichen Anlagen und Personen

Protection contre la foudre - Partie 3: Dommages physiques sur les structures et risques humains

La CEI 62305-3:2010 spécifie les exigences pour la protection d'une structure contre les dommages physiques par un système de protection contre la foudre (SPF) et pour la protection contre les blessures d'êtres vivants dues aux tensions de contact et de pas à proximité d'un SPF (voir la CEI 62305-1). Cette deuxième édition annule et remplace la première édition, parue en 2006, dont elle constitue une révision technique. La présente édition comprend les modifications techniques importantes suivantes par rapport à la précédente édition: 1) Les épaisseurs minimales des tôles ou canalisations métalliques indiquées dans le Tableau 3 pour les dispositifs de capture sont supposées comme non capables d'éviter les problèmes de points chauds. 2) L'acier comportant un dépôt électrolytique de cuivre est introduit comme matériau adapté aux SPF. 3) Certaines surfaces de section des conducteurs du système de protection ont été légèrement modifiées. 4) A des fins de liaison, des éclateurs sont utilisés pour les installations métalliques, tandis que le parafoudre est utilisé pour les réseaux internes. 5) Deux méthodes simplifiée et détaillée sont fournies pour l'évaluation de la distance de séparation. 6) Les mesures de protection contre les blessures d'êtres vivants dues à un choc électrique sont également prises en compte à l'intérieur de la structure. 7) Une information plus complète concernant le système de protection contre la foudre (SPF) dans le cas de structures présentant un risque d'explosion est fournie à l'Annexe D (normative). La présente version bilingue (2012-06) correspond à la version anglaise monolingue publiée en 2010-12.

Zaščita pred delovanjem strele - 3. del: Fizična škoda na zgradbah in nevarnost za živa bitja (IEC 62305-3:2010, spremenjen)

IEC 62305-3 podaja zahteve za zaščito zgradb pred fizično škodo s sistemom za zaščito pred delovanjem strele (LPS) in za zaščito pred poškodbami živih bitij zaradi napetosti dotika in napetosti koraka v bližini LPS (glej IEC 62305-1). Ta standard velja za projektiranje, namestitev, nadzor in vzdrževanje sistema LPS za zgradbe brez omejitve glede višine in za vzpostavitev ukrepov za zaščito pred poškodbami živih bitij zaradi napetosti dotika in koraka.

General Information

Status
Published
Publication Date
03-Mar-2011
Withdrawal Date
01-Jan-2014
Drafting Committee
Parallel Committee
Current Stage
6060 - Document made available - Publishing
Start Date
04-Mar-2011
Completion Date
04-Mar-2011

Relations

Standard
EN 62305-3:2011 - BARVE
English language
161 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard – translation
EN 62305-3:2011 - BARVE
Slovenian language
152 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2011
1DGRPHãþD
SIST EN 62305-3:2006
SIST EN 62305-3:2006/A11:2009
=DãþLWDSUHGGHORYDQMHPVWUHOHGHO)L]LþQDãNRGDQD]JUDGEDKLQQHYDUQRVW]D
åLYDELWMD ,(&VSUHPHQMHQ
Protection against lightning - Part 3: Physical damages to structures and life hazard
Blitzschutz - Teil 3: Schutz von baulichen Anlagen und Personen
Protection contre la foudre - Partie 3: Dommages physiques sur les structures et risques
humains
Ta slovenski standard je istoveten z: EN 62305-3:2011
ICS:
91.120.40 =DãþLWDSUHGVWUHOR Lightning protection
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 62305-3
NORME EUROPÉENNE
March 2011
EUROPÄISCHE NORM
ICS 29.020; 91.120.40 Supersedes EN 62305-3:2006 + corr. Nov.2006 + corr. Sep.2008 + A11:2009

English version
Protection against lightning -
Part 3: Physical damage to structures and life hazard
(IEC 62305-3:2010, modified)
Protection contre la foudre -  Blitzschutz -
Partie 3: Dommages physiques sur les Teil 3: Schutz von baulichen Anlagen und
structures et risques humains Personen
(CEI 62305-3:2010, modifiée) (IEC 62305-3:2010, modifiziert)

This European Standard was approved by CENELEC on 2011-01-02. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62305-3:2011 E
Foreword
The text of the International Standard IEC 62305-3:2010, prepared by IEC TC 81, Lightning protection,
together with common modifications prepared by the Technical Committee CENELEC TC 81X, Lightning
protection, was submitted to the formal vote and was approved by CENELEC as EN 62305-3 on
2011-01-02.
This European Standard supersedes EN 62305-3:2006 + corr. Nov.2006 + corr. Sep.2008 + A11:2009.
This EN 62305-3:2011 includes the following significant technical changes with respect to
EN 62305-3:2006 + corr. Nov.2006 + corr. Sep.2008 + A11:2009:
1) Minimum thicknesses of metal sheets or metal pipes given in Table 3 for air-termination systems are
assumed as not able to prevent hot-spot problems.
2) Steel with electro-deposited copper is introduced as material suitable for LPS.
3) Some cross-sectional areas of LPS conductors were slightly modified.
4) For bonding purposes, isolating spark gaps are used for metal installations and SPD for internal
systems.
5) Two methods – simplified and detailed – are provided for evaluation of separation distance.
6) Protection measures against injuries of living beings due to electric shock are considered also inside
the structure.
7) Improved information for LPS in the case of structures with a risk of explosion are given in Annex D
(normative).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-01-02
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2014-01-02
__________
Endorsement notice
The text of the International Standard IEC 62305-3:2010 was approved by CENELEC as a European
Standard with agreed common modifications as given below.
In the official version, for Bibliography, the following note has to be added for the standard indicated:
[2] IEC 61400-24 NOTE  Harmonized as EN 61400-24.

COMMON MODIFICATIONS
Through the complete document:
Replace all references to IEC 62305 by references to EN 62305.

- 3 - EN 62305-3:2011
Replace all references to IEC 62561 by references to EN 50164.
2 Normative references
Replace this subclause by:
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 50164-1 Lightning Protection Components (LPC) – Part 1: Requirements for connection
components
EN 50164-2 Lightning Protection Components (LPC) – Part 2: Requirements for conductors
and earth electrodes
EN 50164-3 Lightning Protection Components (LPC) – Part 3: Requirements for isolating
spark gaps
EN 50164-4 Lightning Protection Components (LPC) – Part 4: Requirements for conductor
fasteners
EN 50164-5 Lightning Protection Components (LPC) – Part 5: Requirements for earth
electrode inspection housings and earth electrode seals
EN 50164-6 Lightning Protection Components (LPC) – Part 6: Requirements for lightning
strike counters
EN 50164-7 Lightning Protection Components (LPC) – Part 7: Requirements for earthing
enhancing compounds
NOTE  The above mentioned standards EN 50164 series will ultimately be replaced by EN 62561 series. EN 50164 series will still
be valid for 72 months from the issuing date of each part of the EN 50164 series.
EN 60079-10-1:2009 Explosive atmospheres – Part 10-1: Classification of areas – Explosive gas
atmospheres (IEC 60079-10-1:2008)
EN 60079-10-2:2009 Explosive atmospheres – Part 10-2: Classification of areas – Combustible dust
atmospheres (IEC 60079-10-2:2009)
EN 60079-14:2008 Explosive atmospheres – Part 14: Electrical installations design, selection and
erection (IEC 60079-14:2007)
EN 61557-4 Electrical safety in low voltage distribution systems up to 1 000 V a.c. and
1 500 V d.c. – Equipment for testing, measuring or monitoring of protective
measures – Part 4: Resistance of earth connection and equipotential bonding
(IEC 61557-4)
EN 61643-11 Low-voltage surge protective devices – Part 1: Surge protective devices
connected to low-voltage power distribution systems – Requirements and tests
(IEC 61643-1)
EN 61643-21 Low voltage surge protective devices – Part 21: Surge protective devices
connected to telecommunications and signalling networks – Performance
requirements and testing methods (IEC 61643-21)
EN 62305-1:2011 Protection against lightning – Part 1: General principles (IEC 62305-1:2010,
modified)
EN 62305-2:2011 Protection against lightning – Part 2: Risk management (IEC 62305-2:2010,
modified)
EN 62305-4:2011 Protection against lightning – Part 4: Electrical and electronic systems within
structures (IEC 62305-4:2010, modified)

1)
EN 62561 series Lightning Protection System Components (LPSC) (IEC 62561 series)
2)
EN 62561-1 Lightning Protection System Components (LPSC) – Part 1: Requirements for
connection components (IEC 62561)
2)
EN 62561-3 Lightning Protection System Components (LPSC) – Part 3: Requirements for
isolating spark gaps (IEC 62561-3)
ISO 3864-1 Graphical symbols – Safety colours and safety signs – Part 1: Design principles
for safety signs in workplaces and public areas
3 Terms and definitions
Definition 3.16
Add at the end of the paragraph: “… as defined in the EN 50164 series.”
Definition 3.17
Add at the end of the paragraph: “… as defined in the EN 50164 series.”
4 Lightning protection system (LPS)
4.3 Continuity of steelwork in reinforced concrete structures
Replace NOTE 2 by:
NOTE 2  When the continuity of steelwork in reinforced concrete is intended to be established by clamping, specifically designed
clamps complying with and tested according to EN 50164-1, should be used.
5 External lightning protection system
5.5.1 General
After the first paragraph, add the following paragraph:
All components shall comply with the EN 50164 series.
5.5.3 Connections
nd
In the 2 paragraph, replace “the future IEC 62561-1” with “EN 50164-1”.
5.6.2 Dimensions
Replace the first paragraph by:
Materials, configurations and minimum cross-sectional areas of air-termination conductors, air-termination
rods, down-conductors and earth lead-in rods are given in Table 6 and shall comply with the requirements
and tests according to the EN 50164 series.
Add at the beginning of the second paragraph “Materials, …” and replace at the end of the paragraph
“IEC 62561 series” with “EN 50164 series”.
In Table 7, delete the NOTE “f”.

1)
In preparation.
2)
At draft stage.
- 5 - EN 62305-3:2011
Annex E (informative) Guidelines for the design, construction, maintenance and
inspection of lightning protection systems
E.4.2.3.2 Mechanical design
In the first sentence of the NOTE, replace “may” with “should” and “IEC 62561” with “EN 50164”.
In the last paragraph, replace “could” with “should” and “IEC 62561” with “EN 50164”.
E.4.3.3 Welding or clamping to the steel-reinforcing rods
In the NOTE, replace “IEC 62561 series of standards are suitable” with “EN 50164 series of standards
should be used”.
E.4.3.7 Down-conductors
th
Replace the 12 paragraph (i.e. after Figure E.9) by:
“If steel structures are used as down-conductors, every steel column should be connected to the steel
reinforcing rods of the concrete foundation according to Figure E.7 by purposely designed bonding points
complying with EN 50164 series.”
E.5.2.4.1 General information
Replace the first paragraph by:
“The maximum permissible temperature for a conductor will not be exceeded if its cross-section complies
with Table 6 and the EN 50164 series.”
E.5.2.4.2 Non-isolated air-termination
nd
After the 2 paragraph, add the following NOTE:
NOTE  For more details see EN 50164 series.
E.5.5 Components
st
Replace the 1 paragraph by:
“Components of LPS should withstand the electromagnetic effects of lightning current and predictable
accidental stresses without being damaged. This can be achieved by choosing components that have
successfully been tested in accordance with the EN 50164 series.
All components shall comply with the EN 50164 series.”
E.5.6.1 Mechanical design
th
At the end of the 6 paragraph, add the following:
“…according to the EN 50164 series.”
E.5.6.2.1 Materials
st
At the end of the 1 line, add the following:
“and the EN 50164 series”
E.5.6.2.2.1 Metals in soil and air
Replace the NOTE by:
NOTE  Isolating spark gaps having a protection level U of 2,5 kV and a minimum I of 50 kA (10/350 µs) complying with
p imp
EN 50164-3 are suitable.
IEC 62305-3 ®
Edition 2.0 2010-12
INTERNATIONAL
STANDARD
colour
inside
Protection against lightning –
Part 3: Physical damage to structures and life hazard

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
PRICE CODE
XG
ICS 29.020; 91.120.40 ISBN 978-2-88912-282-0
– 2 – 62305-3 Ó IEC:2010(E)
CONTENTS
FOREW ORD . 7
INTRODUCTION . 10
1 Scope . 11
2 Normative references . 11
3 Terms and definitions . 12
4 Lightning protection system (LPS) . 15
4.1 Class of LPS . 15
4.2 Design of the LPS . 16
4.3 Continuity of steelwork in reinforced concrete structures . 16
5 External lightning protection system . 17
5.1 General . 17
5.1.1 Application of an external LPS . 17
5.1.2 Choice of external LPS . 17
5.1.3 Use of natural components . 17
5.2 Air-termination systems . 18
5.2.1 General . 18
5.2.2 Positioning . 18
5.2.3 Air-terminations against flashes to the side of tall structures . 19
5.2.4 Construction . 20
5.2.5 Natural components . 20
5.3 Down-conductor systems . 21
5.3.1 General . 21
5.3.2 Positioning for an isolated LPS . 22
5.3.3 Positioning for a non-isolated LPS . 22
5.3.4 Construction . 23
5.3.5 Natural components . 23
5.3.6 Test joints . 24
5.4 Earth-termination system . 24
5.4.1 General . 24
5.4.2 Earthing arrangement in general conditions . 25
5.4.3 Installation of earth electrodes . 26
5.4.4 Natural earth electrodes. 27
5.5 Components . 27
5.5.1 General . 27
5.5.2 Fixing. 28
5.5.3 Connections . 28
5.6 Materials and dimensions. 29
5.6.1 Materials . 29
5.6.2 Dimensions . 29
6 Internal lightning protection system . 31
6.1 General . 31
6.2 Lightning equipotential bonding . 32
6.2.1 General . 32
6.2.2 Lightning equipotential bonding for metal installations . 32
6.2.3 Lightning equipotential bonding for external conductive parts. 33
6.2.4 Lightning equipotential bonding for internal systems . 34

62305-3 Ó IEC:2010(E) – 3 –
6.2.5 Lightning equipotential bonding for lines connected to the structure to
be protected . 34
6.3 Electrical insulation of the external LPS . 35
6.3.1 General . 35
6.3.2 Simplified approach . 36
6.3.3 Detailed approach . 36
7 Maintenance and inspection of an LPS . 37
7.1 General . 37
7.2 Application of inspections . 37
7.3 Order of inspections . 37
7.4 Maintenance . 37
8 Protection measures against injury to living beings due to touch and step voltages . 37
8.1 Protection measures against touch voltages . 37
8.2 Protection measures against step voltages . 38
Annex A (normative) Positioning the air-termination system . 39
Annex B (normative) Minimum cross-section of the entering cable screen in order to
avoid dangerous sparking. 45
Annex C (informative) Evaluation of the separation distance s. 46
Annex D (normative) Additional information for LPS in the case of structures with a
risk of explosion . 52
Annex E (informative) Guidelines for the design, construction, maintenance and
inspection of lightning protection systems . 59
Bibliography . 156

Figure 1 – Protection angle corresponding to the class of LPS . 19
Figure 2 – Loop in a down-conductor . 23
Figure 3 – Minimum length l of each earth electrode according to the class of LPS . 25
Figure A.1 – Volume protected by a vertical air-termination rod . 39
Figure A.2 – Volume protected by a vertical air-termination rod . 40
Figure A.3 – Volume protected by a wire air-termination system . 40
Figure A.4 – Volume protected by isolated wires combined in a mesh according to the
protection angle method and rolling sphere method . 41
Figure A.5 – Volume protected by non-isolated wires combined in a mesh according to
the mesh method and the protection angle method . 42
Figure A.6 – Design of an air-termination system according to the rolling sphere
method . 43
Figure C.1 – Values of coefficient k in the case of a wire air-termination system . 46
c
Figure C.2 – Values of coefficient k in the case of multiple down-conductors system . 47
c
Figure C.3 – Values of coefficient k in the case of a sloped roof with air-termination on
c
the ridge . 49
Figure C.4 – Examples of calculation of the separation distance in the case of multiple
down-conductors with an interconnecting ring of the down-conductors at each level . 50
Figure C.5 – Values of coefficient k in the case of a meshed air-termination system,
c
with a multiple down-conductors system . 51
Figure E.1 – LPS design flow diagram . 61
Figure E.2 – LPS design for a cantilevered part of a structure . 67
Figure E.3 – Measuring the overall electrical resistance . 68

– 4 – 62305-3 Ó IEC:2010(E)
Figure E.4 – Equipotential bonding in a structure with a steel reinforcement . 70
Figure E.5 – Typical methods of joining reinforcing rods in concrete (where permitted) . 71
Figure E.6 – Example of clamps used as joints between reinforcing rods and
conductors . 72
Figure E.7 – Examples for connection points to the reinforcement in a reinforced
concrete wall. 73
Figure E.8 – Use of metallic facade as natural down-conductor system and connection
of facade supports . 77
Figure E.9 – Connection of the continuous strip windows to a metal facade covering . 78
Figure E.10 – Internal down-conductors in industrial structures . 81
Figure E.11 – Installation of bonding conductors in reinforced concrete structures and
flexible bonds between two reinforced concrete parts . 83
Figure E.12 – Protection angle method air-termination design for different heights
according to Table 2 . 87
Figure E.13 – Isolated external LPS using two isolated air-termination masts designed
according to the protection angle air-termination design method . 88
Figure E.14 – Isolated external LPS using two isolated air-termination masts,
interconnected by horizontal catenary wire . 89
Figure E.15 – Example of design of an air-termination of a non-isolated LPS by air-
termination rods . 90
Figure E.16 – Example of design of an air-termination of a non isolated LPS by a
horizontal wire according to the protection angle air-termination design method . 91
Figure E.17 – Protected volume of an air- termination rod on a sloped surface using
the protection angle design method . 92
Figure E.18 – Design of an LPS air-termination conductor network on a structure with
complicated shape . 93
Figure E.19 – Design of an LPS air-termination according to the protection angle
method, mesh method and general arrangement of air-termination elements . 94
Figure E.20 – Space protected by two parallel air-termination horizontal wires or two
air-termination rods (r > h ) . 95
t
Figure E.21 – Three examples of design of non-isolated LPS air-termination according
to the mesh method air-termination design . 98
Figure E.22 – Four examples of details of an LPS on a structure with sloped tiled roofs . 100
Figure E.23 – Air-termination and visually concealed conductors for buildings less
than 20 m high, with sloping roofs . 101
Figure E.24 – Construction of an LPS using natural components on the roof of the
structure . 103
Figure E.25 – Positioning of the external LPS on a structure made of isolating material
e.g. wood or bricks with a height up to 60 m with flat roof and with roof fixtures . 104
Figure E.26 – Construction of air-termination network on a roof with conductive
covering where puncturing of the covering is not acceptable . 105
Figure E.27 – Construction of external LPS on a structure of steel-reinforced concrete
using the reinforcement of the outer walls as natural components . 106
Figure E.28 – Example of an air-termination stud used on car park roofs . 107
Figure E.29 – Air-termination rod used for protection of a metallic roof fixture with
electric power installations which are not bonded to the air-termination system . 108
Figure E.30 – Method of achieving electrical continuity on metallic parapet capping . 109
Figure E.31 – Metallic roof fixture protected against direct lightning interception,
connected to air-termination system . 112

62305-3 Ó IEC:2010(E) – 5 –
Figure E.32 – Examplesof lightning protection of a house with a TV antenna . 115
Figure E.33 – Installation of lightning protection of metallic equipment on a roof against
a direct lightning flash . 116
Figure E.34 – Connection of natural air-termination rod to air-termination conductor . 118
Figure E.35 – Construction of the bridging between the segments of the metallic
facade plates . 119
Figure E.36 – Installation of external LPS on a structure of insulating material with
different roof levels . 122
Figure E.37 – Five examples of geometry of LPS conductors . 123
Figure E.38 – Construction of an LPS using only two down-conductors and foundation
earth electrodes . 124
Figure E.39 – Four examples of connection of earth-termination to the LPS of
structures using natural down-conductors (girders) and detail of a test joint. 128
Figure E.40 – Construction of foundation earth ring for structures of different
foundation design . 132
Figure E.41 – Two examples of vertical electrodes in type A earthing arrangement . 134
Figure E.42 – Meshed earth-termination system of a plant . 137
Figure E.43 – Example of an equipotential bonding arrangement . 144
Figure E.44 – Example of bonding arrangement in a structure with multiple point
entries of external conductive parts using a ring electrode for interconnection of
bonding bars . 145
Figure E.45 – Example of bonding in the case of multiple point entries of external
conductive parts and an electric power or communication line using an internal ring
conductor for interconnection of the bonding bars . 146
Figure E.46 – Example of bonding arrangement in a structure with multiple point
entries of external conductive parts entering the structure above ground level . 147
Figure E.47 – Directions for calculations of the separation distance, s, for a worst case
lightning interception point at a distance l from the reference point according to 6.3 . 149

Table 1 – Relation between lightning protection levels (LPL) and class of LPS (see
IEC 62305-1) . 16
Table 2 – Maximum values of rolling sphere radius, mesh size and protection angle
corresponding to the class of LPS . 19
Table 3 – Minimum thickness of metal sheets or metal pipes in air-termination systems . 21
Table 4 – Typical preferred values of the distance between down-conductors
according to the class of LPS . 22
Table 5 – LPS materials and conditions of use . 28
Table 6 – Material, configuration and minimum cross-sectional area of air-termination
conductors, air-termination rods, earth lead-in rods and down-conductors . 30
Table 7 – Material, configuration and minimum dimensions of earth electrodes . 31
Table 8 – Minimum dimensions of conductors connecting different bonding bars or
connecting bonding bars to the earth-termination system . 33
Table 9 – Minimum dimensions of conductors connecting internal metal installations to
the bonding bar . 33
Table 10 – Isolation of external LPS – Values of coefficient k . 35
i
Table 11 – Isolation of external LPS – Values of coefficient k . 35
m
Table 12 – Isolation of external LPS – Approximated values of coefficient k . 36
c
Table B.1 – Cable length to be considered according to the condition of the screen . 45
Table E.1 – Suggested fixing centres. 99

– 6 – 62305-3 Ó IEC:2010(E)
Table E.2 – Maximum period between inspections of an LPS . 151

62305-3 Ó IEC:2010(E) – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
_____________
PROTECTION AGAINST LIGHTNING –

Part 3: Physical damage to structures and life hazard

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62305-3 has been prepared by IEC technical committee 81:
Lightning protection.
This second edition cancels and replaces the first edition, published in 2006, and constitutes
a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
1) Minimum thicknesses of metal sheets or metal pipes given in Table 3 for air-termination
systems are assumed as not able to prevent hot-spot problems.
2) Steel with electro-deposited copper is introduced as material suitable for LPS.
3) Some cross-sectional areas of LPS conductors were slightly modified.
4) For bonding purposes, isolating spark gaps are used for metal installations and SPD for
internal systems.
– 8 – 62305-3 Ó IEC:2010(E)
5) Two methods – simplified and detailed – are provided for evaluation of separation
distance.
6) Protection measures against injuries of living beings due to electric shock are considered
also inside the structure.
7) Improved information for LPS in the case of structures with a risk of explosion are given in
Annex D (normative).
The text of this standard is based on the following documents:
FDIS Report on voting
81/372/FDIS 81/382/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted, as closely as possible, in accordance with the ISO/IEC
Directives, Part 2.
A list of all the parts in the IEC 62305 series, under the general title Protection against
lightning, can be found on the IEC website.

62305-3 Ó IEC:2010(E) – 9 –
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
 reconfirmed,
 withdrawn,
 replaced by a revised edition, or
 amended.
In the United States, based on the requirements of NFPA 780: Standard for the Installation of Lightning Protection
[1]
Systems:2008 and practical experience in the use of horizontal earth electrodes, the minimum length of
horizontal earth electrodes is not required to be twice that required for vertical electrodes.
In France and Portugal:
– natural components cannot substitute as lightning protection components but may be used to
complete/enhance the LPS;
– aluminium solid round diameters should be increased from 8 mm to 10 mm;
– stranded conductors cannot be used as down-conductors;
– diameter of solid round conductors should be increased from 16 mm to 18 mm;
– hot dip galvanized steel solid tape thickness should be increased from 2 mm to 3,5 mm.
In Russia the use of piping carrying and tanks containing readily-combustible or explosive materials as air-
termination natural components or down-conductor natural components are not allowed in any case.
In Japan the minimum values of the cross-section are reduced from:

2 2 2 2
– 16 mm to 14 mm for copper and 25 mm to 22 mm for aluminium, for bonding conductors connecting
different bonding bars and conductors connecting the bars to the earth-termination system;

2 2 2 2 2 2
– 6 mm to 5 mm for copper, 10 mm to 8 mm for aluminium and 16 mm to 14 mm for steel, for bonding
conductors connecting internal metal installations to the bonding bars.
A bilingual version of this publication may be issued at a later date.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
———————
References in square brackets refer to the bibliography.

– 10 – 62305-3 Ó IEC:2010(E)
INTRODUCTION
This part of IEC 62305 deals with the protection, in and around a structure, against physical
damage and injury to living beings due to touch and step voltages.
The main and most effective measure for protection of structures against physical damage is
considered to be the lightning protection system (LPS). It usually consists of both external
and internal lightning protection systems.
An external LPS is intended to
a) intercept a lightning flash to the structure (with an air-termination system),
b) conduct the lightning current safely towards earth (using a down-conductor system),
c) disperse the lightning current into the earth (using an earth-termination system).
An internal LPS prevents dangerous sparking within the structure using either equipotential
bonding or a separation distance (and hence electrical insulation) between the external LPS
(as defined in 3.2) components and other electrically conducting elements internal to the
structure.
Main protection measures against injury to living beings due to touch and step voltages are
intended to:
1) reduce the dangerous current flowing through bodies by insulating exposed conductive
parts, and/or by increasing the surface soil resistivity,
2) reduce the occurrence of dangerous touch and step voltages by physical restrictions
and/or warning notices.
The type and location of an LPS should be carefully considered in the initial design of a new
structure, thereby enabling maximum advantage to be taken of the electrically conductive
parts of the structure. By doing so, design and construction of an integrated installation is
made easier, the overall aesthetic aspects can be improved, and the effectiveness of the LPS
can be increased at minimum cost and effort.
Access to the ground and the proper use of foundation steelwork for the purpose of forming
an effective earth-termination may well be impossible once construction work on a site has
commenced. Therefore, soil resistivity and the nature of the earth should be considered at the
earliest possible stage of a project. This information is fundamental to the design of an earth-
termination system and may influence the foundation design work for the structure.
Regular consultation between LPS designers and installers, architects and builders is
essential in order to achieve the best result at minimum cost.
If lightning protection is to be added to an existing structure, every effort should be made to
ensure that it conforms to the principles of this standard. The design of the type and location
of an LPS should take into account the features of the existing structure.

62305-3 Ó IEC:2010(E) – 11 –
PROTECTION AGAINST LIGHTNING –

Part 3: Physical damage to structures and life hazard

1 Scope
This part of IEC 62305 provides the requirements for protection of a structure against physical
damage by means of a lightning protection system (LPS), and for protection against injury to
living beings due to touch and step voltages in the vicinity of an LPS (see IEC 62305-1).
This standard is applicable to:
a) design, installation, inspection and maintenance of an LPS for structures without limitation
of their height,
b) establishment of measures for protection against injury to living beings due to touch and
step voltages.
NOTE 1 Specific requirements for an LPS in structures dangerous to their surroundings due to the risk of explosion are
under consideration. Additional information is provided in Annex D for use in the interim.
NOTE 2 This part of IEC 62305 is not intended to provide protection against failures of electrical and electronic
systems due to overvoltages. Specific requirements for such cases are provided in IEC 62305-4.
[2]
NOTE 3 Specific requirements for protection against lightning of wind turbines are reported in IEC 61400-24 .
2 Normative references
The following referenced documents are indispensable for the application of this
...


SLOVENSKI SIST EN 62305-3
STANDARD
maj 2011
Zaščita pred delovanjem strele – 3. del: Fizična škoda na zgradbah in
nevarnost za živa bitja (IEC 62305-3:2010, spremenjen)

Protection against lightning – Part 3: Physical damages to structures and life
hazard (IEC 62305-3:2010, modified)

Protection contre la foudre – Partie 3: Dommages physiques sur les structures et
risques humains (CEI 62305-3:2010, modifieé)

Blitzschutz – Teil 3: Schutz von baulichen Anlagen und Personen (IEC 62305-
2:2010, modifiziert)
Referenčna oznaka
ICS 91.120.40 SIST EN 62305-3:2011 (sl)

Nadaljevanje na straneh II in III ter od 1 do 150

© 2013-03. Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov ni dovoljeno.

SIST EN 62305-3 : 2011
NACIONALNI UVOD
Standard SIST EN 62305-3 (sl), Zaščita pred delovanjem strele – 3. del: Fizična škoda na zgradbah in
nevarnost za živa bitja (IEC 62305-3:2010, spremenjen), 2011, ima status slovenskega standarda in je
enakovreden evropskemu standardu EN 62305-3 (en), Protection against lightning – Part 3: Physical
damages to structures and life hazard (IEC 62305-3:2010, modified), 2011.

NACIONALNI PREDGOVOR
Evropski standard EN 62305-3:2011 je pripravil tehnični odbor Evropskega komiteja za
standardizacijo v elektrotehniki CLC/TC 81X Zaščita pred delovanjem strele.

Slovenski standard SIST EN 62305-3:2011 je prevod evropskega standarda EN 62305-3:2011. V
primeru spora glede besedila slovenskega prevoda v tem standardu je odločilen izvirni mednarodni
standard v angleškem jeziku. Slovensko izdajo standarda je pripravil tehnični odbor SIST/TC STZ
Zaščita pred delovanjem strele.

Odločitev za izdajo tega standarda je dne 4. maja 2011 sprejel SIST/TC STZ Zaščita pred delovanjem
strele.
ZVEZA Z NACIONALNIMI STANDARDI
S privzemom tega mednarodnega standarda veljajo za omenjeni namen referenčnih standardov vsi
standardi, navedeni v izvirniku, razen tistih, ki so že sprejeti v nacionalno standardizacijo:

SIST EN 50164-1:2008 Elementi za zaščito pred strelo (LPC) – 1. del: Zahteve za povezovalne
elemente
SIST EN 50164-2:2008 Elementi za zaščito pred strelo (LPC) – 2. del: Zahteve za vodnike in
ozemljila
SIST EN 50164-3:2006 Elementi za zaščito pred strelo (LPC) – 3. del: Zahteve za iskrišča
SIST EN 50164-4:2008 Elementi za zaščito pred strelo (LPC) – 4. del: Zahteve za pritrdilne
elemente
SIST EN 50164-5:2009 Elementi za zaščito pred strelo (LPC) – 5. del: Zahteve za merilne
omarice ozemljil in tesnjenje izolacije pri ozemljilih
SIST EN 50164-6:2009 Elementi za zaščito pred strelo (LPC) – 6. del: Zahteve za števce udarov
strele
SIST EN 50164-7:2008 Elementi za zaščito pred strelo (LPC) – 7. del: Zahteve za spojine, ki
izboljšajo ozemljitev
SIST EN 60079-10-1:2009 Eksplozivne atmosfere – 10-1. del: Razvrstitev prostorov – Eksplozivne
plinske atmosfere (IEC 60079-10-1:2008)
SIST EN 60079-10-2:2009 Eksplozivne atmosfere – 10-2. del: Razdelitev eksplozijsko ogroženih
prostorov - Eksplozivne prašne atmosfere (IEC 60079-10-2:2009)
SIST EN 60079-14:2009 Eksplozivne atmosfere – 14. del: Načrtovanje, izbira in namestitev
električnih inštalacij (IEC 60079-14:2007)
SIST EN 61557-4:2007 Električna varnost v nizkonapetostnih razdelilnih sistemih izmenične
napetosti do 1 kV in enosmerne napetosti do 1,5 kV – Oprema za
preskušanje, merjenje ali nadzorovanje zaščitnih ukrepov – 4. del:
Upornost ozemljitvenega priključka in izenačitev potencialov (IEC 61557-
4:2007)
II
SIST EN 62305-3 : 2011
SIST EN 61643-11:2012 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari – 11. del:
Naprave za zaščito pred prenapetostnimi udari za nizkonapetostne
napajalne sisteme - Zahteve in preskusi (IEC 61643-11:2011,
spremenjen)
SIST EN 61643-21:2002 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari – 21. del:
Naprave priključene na telekomunikacijska in signalna omrežja-
Zahtevane lastnosti in preskusne metode (IEC 61643-21:2000 +
popravek mar. 2001)
SIST EN 62305-1:2011 Zaščita pred delovanjem strele – 1. del: Splošna načela (IEC 62305-
1:2010, spremenjen)
SIST EN 62305-2:2012 Zaščita pred delovanjem strele – 2. del: Vodenje rizika (IEC 62305-
2:2010, spremenjen)
SIST EN 62305-4:2011 Zaščita pred delovanjem strele – 4. del: Električni in elektronski sistemi v
zgradbah (IEC 62305-4:2010, spremenjen)
SIST EN 62561 (skupina) Zahteve za elemente sistema za zaščito pred strelo (LPSC)
SIST ISO 3864-1:2012 Grafični simboli – Opozorilne barve in opozorilni znaki – 1. del: Načela
načrtovanja opozorilnih znakov in opozorilnih oznak

OSNOVA ZA IZDAJO STANDARDA
– privzem standarda EN 62305-3:2011
PREDHODNA IZDAJA
– SIST EN 62305-3:2006
– SIST EN 62305-3:2006/A11:2009
OPOMBE
– Povsod, kjer se v besedilu standarda uporablja izraz “evropski standard”, v
– Nacionalni uvod in nacionalni predgovor nista sestavni del standarda
– Ta nacionalni dokument je enakovreden EN 62305-3:2011 in je objavljen z dovoljenjem
CENELEC
Avenue Marnix 17
B - 1000 Brussels
Belgija
This national document is identical with EN 62305-3:2011 and is published with the permission of

CENELEC
Avenue Marnix 17
B - 1000 Brussels
Belgium
III
SIST EN 62305-3 : 2011

IV
EVROPSKI STANDARD EN 62305-3
EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄISCHE NORM marec 2011
ICS: 29.020; 91.120.40 Nadomešča EN 62305-3:2006 +
popravek September 2008 + A11:2009

Slovenska izdaja
Zaščita pred delovanjem strele – 3. del: Fizična škoda na zgradbah in
nevarnost za živa bitja (IEC 62305-3:2010, spremenjen)

Protection against lightning – Protection contre la foudre – Blitzschutz – Teil 3: Schutz von
Part 3: Physical damages to Partie 3: Dommages physiques sur les baulichen Anlagen und
structures and life hazard structures et risques humains Personen
(IEC 62305-3:2010, modified) (CEI 62305-3:2010, modifieé) (IEC 62305-2:2010, modifiziert)

Ta evropski standard je CENELEC sprejel 2. januarja 2011. Člani CENELEC morajo izpolnjevati
notranje predpise CEN/CENELEC, s katerimi je predpisano, da mora biti ta standard brez kakršnih koli
sprememb sprejet kot nacionalni standard.

Najnovejši seznami teh nacionalnih standardov z njihovimi bibliografskimi podatki se na zahtevo lahko
dobijo pri Centralnem sekretariatu ali katerem koli članu CENELEC.

Ta evropski standard obstaja v treh izvirnih izdajah (angleški, francoski in nemški). Izdaje v drugih
jezikih, ki jih članice CENELEC na lastno odgovornost prevedejo in izdajo ter prijavijo pri Centralnem
sekretariatu CEN, veljajo kot uradne izdaje.

Člani CENELEC so nacionalni elektrotehniški komiteji Avstrije, Belgije, Bolgarije, Cipra, Češke
republike, Danske, Estonije, Finske, Francije, Grčije, Hrvaške, Irske, Islandije, Italije, Latvije, Litve,
Luksemburga, Malte, Madžarske, Nemčije, Nizozemske, Norveške, Poljske, Portugalske, Romunije,
Slovaške, Slovenije, Španije, Švedske, Švice in Združenega kraljestva.

CENELEC
Evropski komite za standardizacijo v elektrotehniki
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Upravni center: Avenue Marnix 17, B - 1000 Bruselj

© 2011 CENELEC. Lastnice avtorskih pravic so vse države članice CENELEC. Ref. oznaka EN 62305-3:2011 E

SIST EN 62305-3 : 2011
VSEBINA Stran
Predgovor k evropskemu standardu .6
Predgovor k mednarodnemu standardu.11
Uvod .13
1 Področje uporabe .14
2 Zveze s standardi .14
3 Izrazi in definicije .15
4 Sistem zaščite pred delovanjem strele (LPS).18
4.1 Vrsta LPS .18
4.2 Načrtovanje LPS.19
4.3 Neprekinjenost jeklene armature v armiranobetonskih zgradbah.19
5 Zunanji sistem zaščite pred delovanjem strele .19
5.1 Splošno.19
5.2 Lovilni sistemi .20
5.3 Odvodni sistemi.23
5.4 Ozemljitveni sistem.26
5.5 Sestavni deli .29
5.6 Materiali in mere.30
6 Notranji sistem zaščite pred delovanjem strele.32
6.1 Splošno.32
6.2 Izenačitev potencialov .33
6.3 Električna izolacija zunanjega LPS .36
7 Vzdrževanje in pregledovanje LPS .37
7.1 Splošno.37
7.2 Izvajanje pregledov.37
7.3 Vrste pregledov .38
7.4 Vzdrževanje.38
8 Ukrepi za zaščito pred poškodbami živih bitij zaradi napetosti dotika in koraka.38
8.1 Ukrepi za zaščito pred napetostjo dotika.38
8.2 Ukrepi za zaščito pred napetostjo koraka .38
Dodatek A (normativni): Nameščanje lovilnega sistema.40
Dodatek B (normativni): Najmanjši prerez kabelskega zaslona vstopajočega kabla za preprečitev
nevarnega iskrenja.45
Dodatek C (informativni): Določitev ločilne razdalje s .46
Dodatek D (informativni): Dodatne informacije za LPS za zgradbe s tveganjem eksplozije .52
Dodatek E (informativni): Smernice za načrtovanje, namestitev, vzdrževanje in pregledovanje
sistemov za zaščito pred delovanjem strele .59

Slika 1: Zaščitni kot glede na vrsto LPS.21
Slika 2: Zanka v odvodu .25
SIST EN 62305-3 : 2011
Slika 3: Najmanjša dolžina l vsakega ozemljila glede na vrsto LPS.27
Slika A.1: Prostor, ščiten z navpično lovilno palico .40
Slika A.2: Prostor, ščiten z navpično lovilno palico .41
Slika A.3: Prostor, ščiten z lovilno vrvjo.41
Slika A.4: Prostor, ščiten z izoliranimi vrvmi, povezanimi v mrežo, skladno z metodo
zaščitnega kota in metodo kotaleče krogle .42
Slika A.5: Prostor, ščiten z neizoliranimi vrvmi, povezanimi v mrežo, skladno z metodo
mreže in metodo zaščitnega kota .43
Slika A.6: Načrt lovilnega sistema po metodi kotaleče krogle.44
Slika C.1: Vrednosti koeficienta k pri lovilnem sistemu iz vrvi.46
c
Slika C.2: Vrednosti koeficienta k pri odvodnem sistemu z več odvodi .47
c
Slika C.3: Vrednosti koeficienta k pri poševni strehi z lovilniki na slemenu .49
c
Slika C.4: Primeri izračunavanja ločilne razdalje pri več odvodih in
medsebojno povezanem obroču odvodov na vsakem nivoju .50
Slika C.5: Vrednosti koeficienta k pri mrežnem lovilnem sistemu z odvodnim sistemom
c
z več odvodi .51
Slika E.1: Diagram poteka načrtovanja LPS .60
Slika E.2: Načrtovanje LPS pri zgradbah z napuščem.65
Slika E.3: Meritev celotne upornosti.66
Slika E.4: Primer izenačitve potencialov v zgradbi z jekleno armaturo.68
Slika E.5: Tipične metode za povezavo armaturnih palic v betonu (kjer je dovoljeno) .69
Slika E.6: Primer spojk, ki se uporabljajo kot spoji med armaturnimi palicami in vodniki .70
Slika E.7: Primeri povezovalnih točk na armaturo v armiranobetonski steni .71
Slika E.8: Uporaba kovinske fasade kot pomožni odvodni sistem in povezava fasadnih nosilcev.75
Slika E.9: Povezovanje neprekinjenih oken na kovinsko fasadno prekritje .76
Slika E.10: Notranji odvodi v industrijskih zgradbah .78
Slika E.11: Namestitev povezovalnih vodnikov v armiranobetonskih zgradbah in
pregibnih povezav med dvema armiranobetonskima deloma .80
Slika E.12: Načrtovanje lovilnika po metodi zaščitnega kota za različne višine
glede na preglednico 2.83
Slika E.13: Izolirani zunanji LPS z uporabljenima dvema izoliranima lovilnima stebroma,
načrtovan po načrtovalni metodi zaščitnega kota.84
Slika E.14: Izolirani zunanji LPS, sestavljen iz dveh izoliranih lovilnih stebrov, med seboj
povezanih z vodoravno obešeno vrvjo.85
Slika E.15: Primer načrtovanja lovilnika neizoliranega LPS z lovilnimi palicami.86
Slika E.16: Primer načrtovanja lovilnika neizoliranega LPS z vodoravnim vodnikom
skladno z načrtovalno metodo zaščitnega kota .87
Slika E.17: Ščiteni prostor lovilne palice na poševni površini z uporabo načrtovalne metode
zaščitnega kota .88
Slika E.18: Načrtovanje mreže lovilnikov LPS na zgradbi z zapleteno obliko.89
Slika E.19: Načrtovanje lovilnika LPS skladno z metodo zaščitnega kota in metodo zanke ter
splošna razporeditev lovilnih sestavnih delov .90
Slika E.20: Prostor, ščiten z dvema vzporednima vodoravnima lovilnima vrvema
ali dvema lovilnima palicama (r > h ) .91
t
SIST EN 62305-3 : 2011
Slika E.21: Trije primeri načrtovanja lovilnika neizoliranega LPS z uporabo
načrtovalne metode mreže.94
Slika E.22: Štirje primeri detajlov LPS na zgradbi s poševno streho z opečno kritino.96
Slika E.23: Lovilni in vizualno nevidni vodniki za stavbe, nižje od 20 m in s poševno streho.97
Slika E.24: Namestitev LPS z uporabo pomožnih sestavnih delov na strehi zgradbe.98
Slika E.25: Namestitev zunanjega LPS na zgradbi iz izolacijskega materiala (npr. les, opeka),
visoki do 60 m, z ravno streho in s strešnimi pritiklinami .99
Slika E.26: Konstrukcija lovilnika na strehi s prevodnim prekritjem, kjer ni dovoljeno
preluknjanje prekritja . 100
Slika E.27: Namestitev zunanjega LPS na armiranobetonsko zgradbo, kjer je armatura
zunanjih sten uporabljena kot pomožni sestavni del. 101
Slika E.28: Primer lovilne gobice na strehi garažne hiše . 102
Slika E.29: Uporaba lovilne palice za zaščito kovinskih pritiklin na strehi z električnimi
napajalnimi inštalacijami, ki niso povezane z lovilnim sistemom . 103
Slika E.30: Metoda za doseganje električne prevodnosti na kovinski prekrivni oblogi . 104
Slika E.31: Kovinska strešna pritiklina, zaščitena pred direktnim udarom strele in povezana
z lovilnim sistemom . 107
Slika E.32: Primer zaščite pred delovanjem strele na zgradbi s TV anteno . 110
Slika E.33: Namestitev strelovodne zaščite pred direktnim udarom strele za kovinsko opremo
na strehi. 111
Slika E.34: Povezovanje pomožne lovilne palice z lovilniki. 113
Slika E.35: Povezovanje med segmenti kovinskih fasadnih plošč. 114
Slika E.36: Namestitev zunanjega LPS na zgradbi iz izolacijskega materiala in
z različnimi nivoji strehe . 116
Slika E.37: Pet primerov geometrije vodnikov LPS. 117
Slika E.38: Konstrukcija LPS ob uporabi samo dveh odvodov in temeljskega ozemljila . 118
Slika E.39: Štirje primeri povezovanja ozemljila na LPS zgradbe s pomožnimi odvodi (nosilci)
in detajl preskusnega spoja. 122
Slika E.40: Konstrukcija temeljskega obročastega ozemljila pri zgradbah z različno
načrtovanimi temelji. 126
Slika E.41: Dva primera navpičnih ozemljil pri razporeditvi ozemljil tipa A . 128
Slika E.42: Mrežni ozemljitveni sistem industrijskega kompleksa. 131
Slika E.43: Primeri izenačitve potencialov. 137
Slika E.44: Primer razporeditve povezav v zgradbi z več vhodnimi mesti zunanjih prevodnih
delov z uporabo obročastega ozemljila za medsebojno povezavo zbiralk . 139
Slika E.45: Primer povezovanja pri več vhodnih mestih zunanjih prevodnih delov in električne
napajalne ali komunikacijske napeljave z uporabo notranjega obročastega vodnika za
medsebojno povezavo zbiralk . 140
Slika E.46: Primer razporeditve povezav v zgradbi z več vhodnimi mesti zunanjih prevodnih delov,
ki vstopajo v zgradbo nad zemljo. 141
Slika E.47: Napotki za izračun ločilne razdalje s za najslabši primer točke udara strele
pri razdalji l od referenčne točke glede na točko 6.3. 143

SIST EN 62305-3 : 2011
Preglednica 1: Odnos med zaščitnimi nivoji (LPL) in vrstami LPS (glej IEC 62305-1) .18
Preglednica 2: Največje vrednosti polmera kotaleče krogle, velikosti mreže in zaščitnega kota
glede na vrsto LPS.21
Preglednica 3: Najmanjša debelina kovinskih kritin ali kovinskih cevi v lovilnih sistemih .23
Preglednica 4: Značilne priporočljive razdalje med odvodi glede na vrsto LPS.24
Preglednica 5: Materiali LPS in pogoji uporabe .29
Preglednica 6: Material, oblika in najmanjši prerez lovilnikov, lovilnih palic, paličnih ozemljil
in odvodov.31
Preglednica 7: Material, oblika in najmanjše mere ozemljil.32
Preglednica 8: Najmanjše mere vodnikov, ki povezujejo različne zbiralke za izenačitev potencialov
ali povezujejo zbiralke za izenačitev potencialov na ozemljitveni sistem .34
Preglednica 9: Najmanjše mere vodnikov, ki povezujejo notranje kovinske inštalacije na zbiralke
za izenačitev potencialov .34
Preglednica 10: Izolacija zunanjega LPS – vrednosti koeficienta k .36
i
Preglednica 11: Izolacija zunanjega LPS – vrednosti koeficienta k .36
m
Preglednica 12: Izolacija zunanjega LPS – približne vrednosti koeficienta k .37
c
Preglednica B.1: Dolžina kabla, ki se upošteva glede na stanje zaslona .45
Preglednica E.1: Predlagana mesta pritrditev.95
Preglednica E.2: Najdaljše obdobje med pregledi LPS. 145
SIST EN 62305-3 : 2011
Predgovor k evropskemu standardu
Besedilo mednarodnega standarda IEC 62305-3:2010, ki ga je pripravil tehnični odbor IEC/TC 81
Strelovodna zaščita, skupaj s skupnimi spremembami, ki jih je pripravil tehnični odbor CENELEC/TC
81X Strelovodna zaščita, je bilo dano na glasovanje in ga je CENELEC 2. januarja 2011 sprejel kot
EN 62305-3.
Ta evropski standard nadomešča EN 62305-3:2006 + popr. nov. 2006 + popr. sep. 2008 + A11:2009.

Standard 62305-3:2011 vključuje naslednje bistvene tehnične spremembe glede na EN 62305-3:2006
+ popr. nov. 2006 + popr. sep. 2008 + A11:2009:
1) Najmanjše debeline kovinskih plošč ali kovinskih cevi za lovilne sisteme v preglednici 3 ne morejo
preprečiti toplotnih poškodb.
2) Z bakrom galvanizirano jeklo je primerno kot material za LPS.
3) Nekateri prerezi vodnikov LPS so bili nekoliko spremenjeni.
4) Za izenačitev potencialov se pri kovinskih inštalacijah uporabljajo iskrišča, pri notranjih sistemih
pa SPD.
5) Za ovrednotenje ločilne razdalje se lahko uporabita dve metodi – poenostavljena in zahtevnejša.
6) Ukrepi za zaščito pred poškodbami živih bitij zaradi električnega udara so obravnavani tudi za
notranjost zgradbe.
7) Dodatne informacije za LPS pri zgradbah, kjer obstaja tveganje eksplozije, so podane v dodatku
D (normativni).
Opozarjamo na možnost, da bi lahko bil kateri od elementov tega standarda predmet patentnih pravic.
CEN in CENELEC ne odgovarjata za identifikacijo nobene od teh patentnih pravic.
Določena sta bila naslednja datuma:
– zadnji datum, do katerega mora EN dobiti status
nacionalnega standarda bodisi z objavo istovetnega besedila
ali z razglasitvijo                                                    (dop) 2012-01-02
– zadnji datum, ko je treba razveljaviti nacionalne standarde,
ki so z EN v nasprotju (dow) 2014-01-02

Razglasitvena objava
Besedilo mednarodnega standarda IEC 62305-3:2010 je CENELEC odobril kot evropski standard s
sprejetimi skupnimi spremembami, kot so navedene spodaj.

V uradni verziji je treba v Literaturi dodati naslednjo opombo za navedeni standard:

[2] IEC 61400-24 OPOMBA: Harmoniziran kot EN 61400-24

SIST EN 62305-3 : 2011
SKUPNE SPREMEMBE
V celotnem dokumentu:
Zamenjajo se vsa sklicevanja na IEC 62305 s sklicevanji na EN 62305.

Zamenjajo se vsa sklicevanja na IEC 62561 s sklicevanji na EN 50164.

2 Zveze s standardi
To točka se zamenja z:
Spodaj navedeni standardi so nujno potrebni pri uporabi tega dokumenta. Pri datiranem sklicevanju se
upoštevajo samo navedene izdaje. Pri nedatiranem sklicevanju se upoštevajo zadnje izdaje navedenih
dokumentov (vključno s popravki in dopolnili).

EN 50164-1 Elementi za zaščito pred strelo (LPC) – 1. del: Zahteve za povezovalne
elemente
EN 50164-2 Elementi za zaščito pred strelo (LPC) – 2. del: Zahteve za vodnike in
ozemljila
EN 50164-3 Elementi za zaščito pred strelo (LPC) – 3. del: Zahteve za iskrišča
EN 50164-4 Elementi za zaščito pred strelo (LPC) – 4. del: Zahteve za pritrdilne
elemente
EN 50164-5 Elementi za zaščito pred strelo (LPC) – 5. del: Zahteve za merilne
omarice ozemljil in tesnjenje izolacije pri ozemljilih
EN 50164-6 Elementi za zaščito pred strelo (LPC) – 6. del: Zahteve za števce udarov
strele
EN 50164-7 Elementi za zaščito pred strelo (LPC) - 7. del: Zahteve za spojine, ki
izboljšajo ozemljitev
OPOMBA: Zgoraj navedeni standardi skupine 50164 bodo na koncu zamenjani s skupino EN 62561. Skupina standardov
EN 50164 bo še vedno v veljavi 72 mesecev po izdaji posameznega standarda iz skupine EN 50164.

EN 60079-10-1:2009 Eksplozivne atmosfere – 10-1. del: Razvrstitev prostorov – Eksplozivne
plinske atmosfere (IEC 60079-10-1:2008)
EN 60079-10-2:2009 Eksplozivne atmosfere – 10-2. del: Razvrstitev prostorov – Eksplozivne
prašne atmosfere (IEC 60079-10-2:2009)
EN 60079-14:2008 Eksplozivne atmosfere – 14. del: Načrtovanje, izbira in namestitev
električnih inštalacij (IEC 60079-14:2007)
EN 61557-4 Električna varnost v nizkonapetostnih razdelilnih sistemih izmenične
napetosti do 1 kV in enosmerne napetosti do 1,5 kV – Oprema za
preskušanje, merjenje ali nadzorovanje zaščitnih ukrepov – 4. del:
Upornost ozemljitvenega priključka in izenačitev potencialov (IEC
61557-4)
EN 61643-11 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari – 1. del:
Naprave za zaščito pred prenapetostnimi udari za nizkonapetostne
razdelilne sisteme – Zahteve in preskusi (IEC 61643-1)
EN 61643-21 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari –
21. del: Naprave priključene na telekomunikacijska in signalna omrežja-
Zahtevane lastnosti in preskusne metode (IEC 61643-21)
EN 62305-1:2011 Zaščita pred delovanjem strele – 1. del: Splošna načela (IEC 62305-
1:2010, spremenjen)
SIST EN 62305-3 : 2011
EN 62305-2:2011 Zaščita pred delovanjem strele – 2. del: Vodenje rizika (IEC 62305-
2:2010, spremenjen)
EN 62305-4:2011 Zaščita pred delovanjem strele – 4. del: Električni in elektronski sistemi v
zgradbah (IEC 62305-4:2010, spremenjen)
1)
EN 62561 (skupina) Zahteve za elemente sistema za zaščito pred strelo (LPSC) (skupina IEC
62561)
2)2)
EN 62561-1 Zahteve za elemente sistema za zaščito pred strelo (LPSC) ) – 1. del:
Zahteve za povezovalne elemente (IEC 62561)
2)
EN 62561-3 Zahteve za elemente sistema za zaščito pred strelo (LPSC) – 3. del:
Zahteve za iskrišča (IEC 62561-3)
ISO 3864-1 Grafični simboli – Opozorilne barve in opozorilni znaki – 1. del: Načela
načrtovanja opozorilnih znakov na delovnem mestu in na javnih površinah
3 Izrazi in definicije
definicija 3.16
na koncu odstavka se doda: "kot je določen v skupini standardov EN 50164"

definicija 3.17
na koncu odstavka se doda: "kot je določen v skupini standardov EN 50164"

4 Sistem zaščite pred delovanjem strele (LPS)
4.3 Neprekinjenost jeklene armature v armiranobetonskih zgradbah

OPOMBA 2 se zamenja z:
OPOMBA 2: Če se neprekinjenost jeklene armature v armiranem betonu zagotovi s spajanjem, naj bodo uporabljene
posebne spojke, ki so izdelane in preskušene v skladu z EN 50164-1.

5 Zunanji sistem zaščite pred delovanjem strele

5.5.1 Splošno
Za prvim odstavkom se doda naslednji odstavek:

Vsi sestavni deli morajo biti v skladu s skupino standardov EN 50164.

5.5.3 Povezave
V drugem odstavku se zamenja "bodoči IEC 62561-1" z "EN 50164-1".

5.6.2 Mere
Prvi odstavek se zamenja z:
Materiali, oblike in najmanjši prerezi lovilnikov, lovilnih palic, odvodov in paličnih ozemljil so podani v
preglednici 6 in morajo ustrezati zahtevam in preskusom v skladu s skupino standardov EN 50164.

Na začetku drugega odstavka se doda "Materiali," in na koncu odstavka se zamenja "skupina
standardov IEC 62561" s "skupina standardov EN 50164".

V preglednici 7 se zbriše OPOMBA "f".

1)
V pripravi.
2)
Osnutek.
SIST EN 62305-3 : 2011
Dodatek E (informativni) Smernice za načrtovanje, namestitev, vzdrževanje in
pregledovanje sistemov za zaščito pred delovanjem strele

E.4.2.3.2 Mehansko načrtovanje

V prvem stavku OPOMBE se zamenjata "lahko" z "naj" in "IEC 62561" z "EN 50164".

V zadnjem odstavku se zamenjata "lahko" z "naj" in "IEC 62561" z "EN 50164".

E.4.3.3 Varjenje ali spajanje na jeklene armaturne palice

V OPOMBI se zamenja "skupino standardov IEC 62561, se štejejo za primerne" s "skupino
standardov EN 50164, naj se uporabijo".

E.4.3.7 Odvodi
Dvanajsti odstavek se zamenja (tj. za sliko E.9) z:

Če se jeklene konstrukcije uporabljajo kot odvodi, naj bo vsak jekleni steber povezan z jeklenimi
armaturnimi palicami betonskih temeljev, kot je prikazano na sliki E.7, v namensko načrtovanih
povezovalnih točkah v skladu s skupino standardov EN 50164.

E.5.2.4.1 Splošne informacije
Prvi odstavek se zamenja z:
Najvišja dovoljena temperatura vodnika ne bo presežena, če je prerez vodnika v skladu s preglednico
6 in skupino standardov EN 50164.

E.5.2.4.2 Neizolirani lovilnik

Za drugim odstavkom se doda naslednja OPOMBA:

OPOMBA: Za več podrobnosti glej skupino standardov EN 50164.

E.5.5 Sestavni deli
Prvi odstavek se zamenja z:
Sestavni deli LPS naj vzdržijo elektromagnetne učinke toka strele in predvidene naključne
obremenitve brez poškodb. To se lahko doseže z izbiro sestavnih delov, ki so bili uspešno preskušeni
v skladu s skupino standardov EN 50164.

Vsi sestavni deli morajo biti skladni s skupino standardov EN 50164.

E.5.6.1 Mehansko načrtovanje
Na koncu šestega odstavka se doda:

"v skladu s skupino standardov EN 50164".

E.5.6.2.1 Materiali
Na koncu prve vrstice se doda:

"in v skupini standardov EN 50164".

SIST EN 62305-3 : 2011
E.5.6.2.2.1 Kovine v zemlji in na zraku

OPOMBA se zamenja z:
OPOMBA: Ustrezna so iskrišča z zaščitnim nivojem U = 2,5 kV in najmanjšim tokom I = 50 kA (10/350 µs) ter skladna s
p imp
standardom EN 50164-3.
SIST EN 62305-3 : 2011
Predgovor k mednarodnemu standardu
1. IEC (Mednarodna elektrotehniška komisija) je svetovna organizacija za standardizacijo, ki združuje vse nacionalne
elektrotehnične komiteje (nacionalni komiteji IEC). Cilj IEC je pospeševati mednarodno sodelovanje v vseh vprašanjih
standardizacije s področja elektrotehnike in elektronike. V ta namen poleg drugih aktivnosti izdaja mednarodne standarde. Za
njihovo pripravo so odgovorni tehnični odbori (TC). Vsak nacionalni komite IEC, ki ga zanima obravnavana tema, lahko sodeluje v
tem pripravljalnem delu. Prav tako lahko v pripravi sodelujejo mednarodne organizacije ter vladne in nevladne ustanove, ki so
povezane z IEC. IEC deluje v tesni povezavi z mednarodno organizacijo za standardizacijo ISO skladno s pogoji, določenimi v
soglasju med obema organizacijama.
2. Uradne odločitve ali sporazumi IEC o tehničnih vprašanjih, pripravljeni v tehničnih odborih, kjer so prisotni vsi nacionalni
komiteji, ki jih tema zanima, izražajo, kolikor je mogoče, mednarodno soglasje o obravnavani temi.
3. Publikacije IEC imajo obliko priporočil za mednarodno uporabo ter jih kot takšne sprejmejo nacionalni komiteji IEC. Čeprav
IEC skuša zagotavljati natančnost tehničnih vsebin v publikacijah IEC, IEC ni odgovoren za način uporabe ali za možne
napačne interpretacije končnih uporabnikov.
4. Da bi se pospeševalo mednarodno poenotenje, so nacionalni komiteji IEC v svojih nacionalnih in regionalnih standardih
dolžni čim pregledneje uporabljati mednarodne standarde. Vsako odstopanje med standardom IEC in ustreznim
nacionalnim ali regionalnim standardom je treba v slednjem jasno označiti.
5. IEC ni določil nobenega postopka v zvezi z označevanjem kot znakom strinjanja in ne prevzema nikakršne odgovornosti za
opremo, ki je deklarirana, da ustreza kateremu od publikacij IEC.
6. Vsi uporabniki naj bi si zagotovili zadnjo izdajo teh publikacij.
7. IEC ali njegovi direktorji, zaposleni, uslužbenci ali agenti, vključno s samostojnimi strokovnjaki ter člani tehničnih odborov in
nacionalnih komitejev IEC, ne prevzemajo nobene odgovornosti za kakršno koli osebno poškodbo, škodo na premoženju
ali katero koli drugo škodo kakršne koli vrste, bodisi posredne ali neposredne, ali za stroške (vključno z zakonitim
lastništvom) in izdatke, povezane s publikacijo, njeno uporabo ali zanašanjem na to publikacijo IEC ali katero koli drugo
publikacijo IEC.
8. Posebno pozornost je treba posvetiti normativnim virom, na katere se sklicuje ta publikacija. Uporaba navedenih publikacij
je nujna za pravilno uporabo te publikacije.
9. Opozarjamo na možnost, da bi lahko bil kateri od elementov tega mednarodnega standarda predmet patentnih pravic. IEC
ne odgovarja za identifikacijo nobene od teh patentnih pravic.
Mednarodni standard IEC 62305-3 je pripravil tehnični odbor IEC/TC 81 Strelovodna zaščita.
Ta druga izdaja preklicuje in nadomešča prvo izdajo, ki je bila izdana leta 2006, in predstavlja tehnično
revizijo.
Ta izdaja vsebuje naslednje bistvene tehnične spremembe glede na prejšnjo izdajo:
1) Najmanjše debeline kovinskih plošč ali kovinskih cevi za lovilne sisteme v preglednici 3 ne morejo
preprečiti toplotnih poškodb.
2) Z bakrom galvanizirano jeklo je primerno kot material za LPS.
3) Nekateri prerezi vodnikov LPS so bili nekoliko spremenjeni.
4) Za izenačitev potencialov se pri kovinskih inštalacijah uporabljajo iskrišča, pri notranjih sistemih
pa SPD.
5) Za ovrednotenje ločilne razdalje se lahko uporabita dve metodi – poenostavljena in zahtevnejša.
6) Ukrepi za zaščito pred poškodbami živih bitij zaradi električnega udara so obravnavani tudi za
notranjost zgradbe.
7) Dodatne informacije za LPS pri zgradbah, kjer obstaja tveganje eksplozije, so podane v dodatku
D (normativni).
Besedilo tega standarda temelji na naslednjih dokumentih:
FDIS Poročilo o glasovanju
81/372/FDIS 81/382/RVD
SIST EN 62305-3 : 2011
Celotna informacija o glasovanju za sprejetje tega standarda je na voljo v poročilu o glasovanju,
navedenem v gornji preglednici.
Ta izdaja je bila pripravljena kolikor je mogoče v skladu z drugim delom Direktiv ISO/IEC.
Seznam vseh delov skupine standardov IEC 62305 pod skupnim naslovom Zaščita pred delovanjem
strele se lahko najde na spletni strani IEC.
Odbor se je odločil, da bo vsebina te publikacije ostala nespremenjena do datuma, ko bodo znani
rezultati pregleda vzdrževanja standarda in je objavljen na spletni strani IEC »http://webstore.iec.ch«
pod datumom v zvezi s posebnimi publikacijami. S tem datumom bo publikacija:
– ponovno potrjena,
– umaknjena,
– zamenjana z revidirano izdajo ali
– dopolnjena.
[1]1)
V Združenih državah Amerike skladno z zahtevami NFPA 780, Standard za sisteme zaščite pred delovanjem strele:2008 , in
praktičnimi izkušnjami pri uporabi vodoravnih ozemljil ne zahtevajo, da je najmanjša dolžina vodoravnih ozemljil dvakrat daljša
od navpičnih elektrod.
V Franciji in na Portugalskem:
– pomožni elementi ne morejo nadomestiti sestavnih delov sistema zaščite pred delovanjem strele, lahko pa se uporabijo
za dopolnitev oziroma povečanje LPS,
– poln, okrogel prerez aluminijastega vodnika naj se poveča z 8 mm na 10 mm,
– pramenasti vodniki se ne morejo uporabiti kot odvodi,
– premer polnih okroglih vodnikov naj se poveča s 16 mm na 18 mm,
– debelina polnega vročega pocinkanega jeklenega traku naj se poveča z 2 mm na 3,5 mm.

V Rusiji uporaba cevovodov, v katerih se prenašajo lahko gorljivi ali eksplozivni materiali, in rezervoarjev, ki jih vsebujejo, kot
pomožnih sestavnih delov lovilnega ali odvodnega sistema ni dovoljena v nobenem primeru.
Na Japonskem so najmanjše vrednosti prerezov zmanjšane s:
2 2 2 2
– 16 mm na 14 mm za baker in s 25 mm na 22 mm za aluminij za povezovalne vodnike, ki povezujejo različne zbiralke in
za vodnike, ki povezujejo zbiralke z ozemljitvenim sistemom,
2 2 2 2 2 2
– 6 mm na 5 mm za baker, 10 mm na 8 mm za aluminij in s 16 mm na 14 mm za jeklo za povezovalne vodnike, ki
povezujejo notranje kovinske inštalacije na zbiralke.
Dvojezična verzija tega standarda bo lahko objavljena pozneje.
POMEMBNO – Logo "barvna vsebina" na naslovnici tega standarda pomeni, da so uporabljene
barve, ki so koristne za pravilno razumevanje vsebine standarda. Uporabniki naj torej za

tiskanje tega standarda uporabijo barvni tiskalnik.

1)
Sklicevanja v oglatih oklepajih se nanašajo na literaturo.
SIST EN 62305-3 : 2011
Uvod
Ta del IEC 62305 se uporablja za zaščito v zgradbi in okoli nje pred fizično škodo in poškodbami živih
bitij, ki nastanejo zaradi napetosti dotika in napetosti koraka.
Glavni in najučinkovitejši ukrep za zaščito zgradb pred fizično škodo je sistem zaščite pred
delovanjem strele (LPS). Ponavadi je sestavljen tako iz zunanjega kot iz notranjega sistema zaščite
pred delovanjem strele.
Zunanji LPS je namenjen:
a) prestrezanju atmosferskih praznitev v zgradbo (s pomočjo lovilnega sistema),
b) varnemu odvajanju toka strele proti zemlji (z uporabo odvodnega sistema),
c) porazdelitvi toka strele v zemlji (z uporabo sistema ozemljil).
Notranji LPS preprečuje nevarno iskrenje v zgradbi z izenačitvijo potencialov ali z doseganjem ločilne
razdalje (in s tem električno izolacijo) med deli zunanjega LPS (kot je določeno v 3.2) in drugimi
električno prevodnimi elementi v zgradbi.
Glavni zaščitni ukrepi pred poškodbami živih bitij zaradi napetosti dotika in napetosti koraka so
namenjeni:
1) zmanjšanju nevarnih tokov, ki tečejo skozi telo, z izolacijo izpostavljenih prevodnih delov in/ali s
povečanjem površinske upornosti zemlje,
2) zmanjšanju pojava nevarnih napetosti dotika in koraka s fizičnimi omejitvami in/ali opozorilnimi
oznakami.
Vrsta in namestitev LPS naj bosta skrbno preučeni že na začetku projektiranja nove zgradbe, da se na
ta način kar najbolj izkoristijo električno prevodni deli zgradbe. S tem postaneta načrtovanje in
namestitev celotne inštalacije lažja, izboljša se lahko celotni estetski videz ter z minimalnimi stroški in
napori se poveča učinkovitost LPS.
Kadar se je gradnja že začela, lahko postaneta dostop do tal in ustrezna uporaba jeklenih konstrukcij
temeljev za oblikovanje učinkovite ozemljitve nemogoča. Zato naj se že v najzgodnejši fazi projekta
proučita upornost zemlje in narava tal. Ta informacija je podlaga za načrtovanje sistema ozemljil in
lahko vpliva na samo načrtovanje temeljev zgradbe.
Nujno je redno posvetovanje med načrtovalci LPS in inštalaterji, arhitekti in gradbinci, da bi se dosegli
najboljši rezultati z minimalnimi stroški.
Če se zaščita pred delovanjem strele namešča na obstoječo zgradbo, naj se naredi vse, da se
zagotovi skladnost z načeli tega standarda. Pri načrtovanju vrste in namestitve LPS naj se upoštevajo
značilnosti obstoječe zgradbe.

SIST EN 62305-3 : 2011
Zaščita pred delovanjem strele – 3. del: Fizična škoda na zgradbah
in nevarnost za živa bitja
1 Področje uporabe
Ta del standarda IEC 62305 določa zahteve za zaščito zgradb pred fizično škodo s pomočjo sistema
zaščite pred delovanjem strele (LPS) in za zaščito pred poškodbami živih bitij zaradi napetosti dotika
in koraka v bližini LPS (glej IEC 62305-1).
Ta standard se uporablja za:
a) načrtovanje, namestitev, pregledovanje in vzdrževanje LPS za zgradbe brez omejitve glede
njihove
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...