Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders

This European Standard specifies the requirements, test methods and performance criteria for fire alarm sounders, including voice sounders, in a fixed installation intended to signal an audible warning between the fire detection and fire alarm systems and the occupants of a building (see EN 54-1:2011).
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of fire alarm sounders to this EN.
This European Standard is not intended to cover:
a) loudspeaker type devices primarily intended for emitting emergency voice messages that are generated from an external audio source;
b) supervisory sounders, for example, within the control and indicating equipment.

Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen Akustische Signalgeber

Systèmes de détection et d'alarme incendie - Partie 3 : Dispositifs sonores d'alarme feu

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 3. del: Naprave za alarmiranje - Zvočne naprave - Dopolnilo A1

General Information

Status
Not Published
Current Stage
5060 - Closure of Vote - Formal Approval
Start Date
13-Sep-2018
Completion Date
13-Sep-2018

Relations

Buy Standard

Draft
EN 54-3:2014/kFprA1:2018
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2018
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO1DSUDYH]D
DODUPLUDQMH=YRþQHQDSUDYH'RSROQLOR$
Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen Akustische Signalgeber
Systèmes de détection et d'alarme incendie - Partie 3: Dispositifs sonores d'alarme feu
Ta slovenski standard je istoveten z: EN 54-3:2014/FprA1
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

FINAL DRAFT
EUROPEAN STANDARD
EN 54-3:2014
NORME EUROPÉENNE
EUROPÄISCHE NORM
FprA1
June 2018
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 3: Fire alarm
devices - Sounders
Systèmes de détection et d'alarme incendie - Partie 3 : Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen
Dispositifs sonores d'alarme feu Akustische Signalgeber
This draft amendment is submitted to CEN members for unique acceptance procedure. It has been drawn up by the Technical
Committee CEN/TC 72.
This draft amendment A1, if approved, will modify the European Standard EN 54-3:2014. If this draft becomes an amendment,
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of
this amendment into the relevant national standard without any alteration.

This draft amendment was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-3:2014/FprA1:2018 E
worldwide for CEN national Members.

Contents Page
European foreword . 4
1 Modification to the Foreword . 5
2 Modification to Clause 2, Normative references . 5
3 Modifications to cross references to EN 60529:1991 . 5
4 Modification to 3.1.1, A-weighted sound pressure level . 5
5 Modification to 4.2.1, Duration of operation . 5
6 Modification to 4.2.3, Flammability of materials . 5
7 Modification to 4.2.7, On-site adjustment of the operation mode . 5
8 Modification to 4.2.8.4, The storage of program and data . 6
9 Modification to 4.3.1, Sound pressure level . 6
10 Modification to 4.3.2, Frequencies and sound pattern . 6
11 Modification to 4.3.5, Voice sounders sequence timing . 6
12 Modification to 5.1.2, Operating conditions for tests . 6
13 Modification to 5.1.6, Test schedule . 6
14 Modification to 5.2.4.2.2, State of the specimen during conditioning . 8
15 Modification to 5.2.4.3, Test requirements. 8
16 Modification to 5.3.1.2, Test procedure . 8
17 Modification to 5.3.1.3, Test requirements. 8
18 Modification to 5.3.2, Frequencies and sound patterns . 8
19 Modification to 5.3.3.1, Object of the test . 8
20 Modification to 5.3.4.2, Test procedure . 8
21 Modification to 5.4.1.1.2.3, Conditioning . 9
22 Modification to 5.4.1.1.3, Test requirements . 9
23 Modification to 5.4.1.2.2.3, Conditioning . 9
24 Modification to 5.4.1.3.2.3, Conditioning . 9
25 Modification to 5.4.2.1.2.1, Reference . 9
26 Modification to 5.4.2.1.2.2, State of the specimen during conditioning . 9
27 Modification to 5.4.2.1.2.3, Conditioning . 9
28 Modification to 5.4.2.1.2.4, Measurements during conditioning . 9
29 Modification to 5.4.3.1.1, Object of the test. 9
30 Modification to 5.4.3.3.2.2, State of the specimen during conditioning . 10
31 Modification to 5.4.5.1.2.1, Reference . 10
32 Modification to 6.2.1, General . 10
33 Modification to 6.2.3, Test reports . 10
34 Modification to 6.3.2.1, General . 10
35 Modification to 6.3.2.7, Non-complying products . 10
36 Modification to 6.3.7, One-off products, pre-production products, (e.g. prototypes)
and products produced in very low quantities . 10
37 Modification to Clause 8, Marking, labelling and packaging . 10
38 Modification to Annex A, Title . 11
39 Modifications to Annex A, Figure A.2 . 11
40 Modification to Annex A, Figure A.3 . 11
41 Modification to Annex B, B.1.1 . 11
42 Modification to Annex B, B.1.2 . 11
43 Modification to Annex B, B.6.2 Measurement of sound pressure level . 12
44 Modification to Annex D, Figure D.1 . 12
45 Modification to Annex D, Figure D.2 . 12
46 Modification to Annex D, Figure D.3 . 12
47 Modification to Annex D, Figure D.4 . 13
48 Modification to Annex D, Figure D.5 . 13
49 Modification to Annex D, Figure D.6 . 14
50 Modification to Annex E (informative), Comparison of flammability test
requirements in various standards . 14
Annex A (informative) Comparison of flammability test requirements in various standards. 15
A.1 Introduction. 15
A.2 Relevant standards . 15
A.3 Vertical burning tests . 15
A.4 Horizontal burning tests . 16
51 Modification to Annex ZA (informative) Clauses of this European Standard
addressing the provisions of the EU Construction Products Regulation . 17
Annex ZA (informative) Relationship of this European Standard with Regulation (EU)
No.305/2011 . 18
ZA.1 Scope and relevant characteristics . 18
ZA.1.1 System of Assessment and Verification of Constancy of Performance (AVCP) . 19
ZA.2 Assignment of AVCP tasks . 20

European foreword
This document (EN 54-3:2014/FprA1:2018) has been prepared by Technical Committee CEN/TC 72
“Fire detection and fire alarm systems”, the secretariat of which is held by BSI.
This document is currently submitted to the Unique Acceptance Procedure.
This document has been prepared under a standardization request given to CEN-CENELEC by the
European Commission and the European Free Trade Association, and supports basic work
requirements of Regulation (EU) 305/2011.
For relationship with EU Regulation, see informative Annex ZA, which is an integral part of this
document.
1 Modification to the Foreword
Insert the following text before the list of standards:
"Amendment 1 to EN 54-3:2014 corrects some of the errors and clarifies some of the points.".
2 Modification to Clause 2, Normative references
Add the following amendment to reference EN 60529:1991:
"EN 60529:1991/A2:2013, Degrees of protection provided by enclosures (IP Code) (IEC 60529/A2:2013)".
Replace reference to EN 60695-11-20:1999 including its amendment with:
"EN 60695-11-20:2015, Fire hazard testing — Part 11-20: Test flames — 500 W flame test method (IEC
60695-11-20:2015)".
Add the following reference:
"EN 54-25, Fire detection and fire alarm systems — Part 25: Components using radio links".
3 Modifications to cross references to EN 60529:1991
st st
In 4.2.4, a) and b) (twice); 5.2.4.2.1, 1 paragraph; 5.2.4.2.2, last paragraph; 5.2.4.2.3, 1 paragraph;
5.2.4.3 a) (update of 5.2.4.3 b) is covered by modification 15); Annex C, e); replace "as amended by EN
60529:1991/A1:2000" with "as amended by EN 60529:1991/A1:2000 and EN 60529:1991/A2:2013".
4 Modification to 3.1.1, A-weighted sound pressure level
Replace the definition with:
"sound pressure level, expressed in dB(A), which is 20 times the logarithm to base ten of the ratio of the
A-weighted sound pressure to the reference pressure of 20 μPa at 1 kHz".
5 Modification to 4.2.1, Duration of operation
Replace the second paragraph with:
"This requirement does not apply to the capacity of batteries that may be used within sounders as a
means of local storage of operating power. The capacity and charging requirements of such batteries
need to meet the requirement of the system.".
6 Modification to 4.2.3, Flammability of materials
In b), replace "EN 60695-11-20:1999 and EN 60695-11-20:1999/A1:2003 Class 5VB" with "EN 60
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.