EN 12259-2:1999/A1:2001
(Amendment)Fixed firefighting systems - Components for sprinkler and water spray systems - Part 2: Wet alarm valve assemblies
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 2: Wet alarm valve assemblies
This standard specifies requirements for constructions and performance of wet alarm valve assemblies and retard chambers used in automatic sprinkler systems Auxiliary components and attachments to wet alarm valve assemblies and retard chambers are not covered by this standard. NOTE: All pressure data in this European standard are given as guage pressure in bar (bar=100.000 Pa).
Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 2: Nassalarmventil mit Zubehör
Installations fixes de lutte contre l'incendie - Composants des systèmes d'extinction du type sprinkleur et à pulvérisation d'eau - Partie 2: Systèmes de soupape d'alarme hydraulique
Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s pršečo vodo - 2. del: Mokri alarmni ventili
General Information
- Status
- Published
- Publication Date
- 20-Mar-2001
- Withdrawal Date
- 30-Dec-2002
- Technical Committee
- CEN/TC 191 - Fixed firefighting systems
- Drafting Committee
- CEN/TC 191/WG 5 - Sprinkler systems
- Current Stage
- 6060 - Definitive text made available (DAV) - Publishing
- Start Date
- 21-Mar-2001
- Completion Date
- 21-Mar-2001
- Directive
- 89/106/EEC - Construction products
Relations
- Effective Date
- 22-Dec-2008
Overview
EN 12259-2:1999/A1:2001 (CEN) specifies requirements for the construction and performance of wet alarm valve assemblies and retard chambers used in automatic sprinkler and water spray systems. It is an amendment (A1, 2001) to EN 12259-2:1999 and forms part of the EN 12259 series covering components for fixed firefighting systems. Pressure data in this standard are expressed as gauge pressure in bar (bar = 100 000 Pa). Auxiliary components and attachments to wet alarm valve assemblies and retard chambers are not covered.
Key topics and requirements
- Scope and intended use: Wet alarm valve assemblies for sprinkler and water spray systems in land-based buildings and structures.
- Design and performance: Minimum requirements addressing construction, clearances and dimensional criteria (illustrated in the standard), operational reliability and response characteristics.
- Retard chambers: Specific clauses for valves fitted with retard chambers including response delay and durability of that delay under service and fire exposure.
- Testing and conformity assessment:
- Initial type testing of all characteristics when first applying the standard or at changes in production method.
- Factory production control (FPC) obligations for manufacturers: documented procedures, inspections, testing and record keeping. An FPC system conforming to relevant parts of EN ISO 9000 / EN ISO 9001 is considered acceptable.
- CE marking and Construction Products Directive (CPD): Annex ZA maps clauses to CPD essential requirements. Wet alarm valve assemblies follow attestation system 1 (product certification), and CE marking must include information such as standard reference (EN 12259-2), product type, rated working pressure (bar), nominal size and pressure loss if > 0.2 bar.
- Documentation: Manufacturer declaration of conformity and certificate details required for CE marking.
Applications and users
This standard is intended for:
- Manufacturers of wet alarm valve assemblies and retard chambers (design, production, FPC).
- Specifiers, consultants and system designers who select components for sprinkler and water spray installations.
- Installers and commissioning engineers verifying conformity and documentation.
- Notified bodies and testing laboratories carrying out initial type testing and conformity assessment.
- Building owners and authorities needing assurance of product performance and CE compliance.
Related standards
- EN 12259 series (Parts 1–12) covering other sprinkler system components (sprinklers, dry alarm valves, water motor alarms, etc.)
- EN ISO 9001 (quality management and factory production control)
Keywords: EN 12259-2, wet alarm valve assemblies, retard chambers, sprinkler systems, CE marking, factory production control, initial type testing, Construction Products Directive.
Frequently Asked Questions
EN 12259-2:1999/A1:2001 is a amendment published by the European Committee for Standardization (CEN). Its full title is "Fixed firefighting systems - Components for sprinkler and water spray systems - Part 2: Wet alarm valve assemblies". This standard covers: This standard specifies requirements for constructions and performance of wet alarm valve assemblies and retard chambers used in automatic sprinkler systems Auxiliary components and attachments to wet alarm valve assemblies and retard chambers are not covered by this standard. NOTE: All pressure data in this European standard are given as guage pressure in bar (bar=100.000 Pa).
This standard specifies requirements for constructions and performance of wet alarm valve assemblies and retard chambers used in automatic sprinkler systems Auxiliary components and attachments to wet alarm valve assemblies and retard chambers are not covered by this standard. NOTE: All pressure data in this European standard are given as guage pressure in bar (bar=100.000 Pa).
EN 12259-2:1999/A1:2001 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 12259-2:1999/A1:2001 has the following relationships with other standards: It is inter standard links to EN 12259-2:1999. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 12259-2:1999/A1:2001 is associated with the following European legislation: EU Directives/Regulations: 305/2011, 89/106/EEC; Standardization Mandates: M/109. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
You can purchase EN 12259-2:1999/A1:2001 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.
Standards Content (Sample)
SLOVENSKI STANDARD
01-oktober-2001
9JUDMHQHQDSUDYH]DJDãHQMH6HVWDYQLGHOLVSULQNOHUVNLKVLVWHPRYLQVLVWHPRYV
SUãHþRYRGRGHO0RNULDODUPQLYHQWLOL
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 2:
Wet alarm valve assemblies
Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 2:
Nassalarmventil mit Zubehör
Installations fixes de lutte contre l'incendie - Composants des systemes d'extinction du
type sprinkleur et a pulvérisation d'eau - Partie 2: Systemes de soupape d'alarme
hydraulique
Ta slovenski standard je istoveten z: EN 12259-2:1999/A1:2001
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 12259-2:1999/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2001
ICS 13.220.20
English version
Fixed firefighting systems - Components for sprinkler and water
spray systems - Part 2: Wet alarm valve assemblies
Installations fixes de lutte contre l'incendie - Composants Ortsfeste Löschanlagen - Bauteile für Sprinkler- und
des systèmes d'extinction du type sprinkleur et à Sprühwasseranlagen - Teil 2: Nassalarmventil mit Zubehör
pulvérisation d'eau - Partie 2: Systèmes de soupape
d'alarme hydraulique
This amendment A1 modifies the European Standard EN 12259-2:1999; it was approved by CEN on 20 January 2001.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Management Centre or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2001 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12259-2:1999/A1:2001 E
worldwide for CEN national Members.
Page 2
Foreword
This European Standard has been prepared by Technical Committee CEN/TC 191 "Fixed fire fighting
systems", the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by September 2001, and conflicting national standards shall
be withdrawn at the latest by December 2002.
This European Standard has been prepared under a mandate given to CEN by the European Commission
and the European Free Trade Association, and supports essential requirements of EU Directive(s).
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway,
Portugal, Spain, Sweden, Switzerland and the United Kingdom.
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this standard.
It forms one Part of EN 12259, covering components for automatic sprinkler systems and is included in a
series of European Standards planned to cover:
a) automatic sprinkler systems (EN 12259 & 12845)
b) Gaseous extinguishing systems (EN 12094 )
1)
c) powder systems (EN 12416)
d) explosion protection systems (EN 26 184)
e) foam systems (EN13565)
f) hydrant and hose reel systems (EN 671)
g) smoke and heat control systems (EN 12101)
h) water spray systems
EN 12259 has the general title “Fixed fire fighting systems - Components for sprinkler and water spray
systems” and will subdivided as follows:
Part 1: Sprinklers.
Part 2: Wet alarm valve assemblies
Part 3: Dry alarm valve assemblies
Part 4: Water motor alarms.
Part 5: Water flow detectors.
Part 6: Pipe couplings.
In preparation
Page 3
Part 7: Pipe hangers.
Part 8: Pressure switches.
Part 9: Deluge alarm valve assemblies.
Part 10 Multiple controls.
Part 11 Medium and high velocity water sprayers.
Part 12 Sprinkler pump sets.
Page 4
a) Radial clearance = R - R b) Diametrical clearance = D - D
2 1 2 1
c) Total axial clearance = l - l ; clearance,
2 1
-
l l
Dimension
A =
Key
1 valve body
2 pin
3 bushings
4 sealing assembly
Figure 1 - Clearances
Page 5
8 Evaluation of conformity
8.1 General
The compliance of a wet alarm valve assembly with the requirements of this standard shall be
demonstrated by:
- initial type testing
- factory production control by the manufacturer.
8.2 Initial type testing
Initial type testing shall be performed on first application of this standard. Tests previously performed in
accordance with the provisions of this standard (same product, same characteristic, test method, sampling
method and system of attestation of conformity) may be taken into account. In addition, initial type testing
shall be performed at the beginning of the production of a product type or at the beginning of a new
method of production (where these may affect the stated properties).
All characteristics given in clause 4, and where appropriate clause 5, shall be subject to initial type testing.
8.3 Factory production control (FPC)
The supplier shall establish, document and maintain an FPC system to ensure that the products placed on
the market conform with the stated performance characteristics.
The FPC system shall consist of procedures, regular inspections and tests and/or assessments and the
use of the results to control raw and other incoming materials or components, equipment, the production
process and the product. It shall be sufficiently detailed to ensure that the conformity of the product is
apparent, ensuring detection of irregularities at the earliest possible stage.
An FPC system conforming with the requirements of the relevant part(s) of EN ISO 9000, and made
specific to the requirements of this standard, shall be considered to satisfy the above requirements.
The results of inspections, tests or assessments requiring action shall be recorded, as shall any action
taken. The
...