Abstract

This document specifies requirements for chemical and physical properties, and minimum performance requirements of low expansion foams suitable for surface application to water-miscible liquids. Requirements are also specified for marking.
IMPORTANT - The fire performance is tested using acetone and isopropanol as the fuel, which also forms the basis for the performance classification. However, there are a large number of water-miscible liquids which have more or less different properties to acetone and isopropanol. It has been shown by tests using other fuels that the performance of various foams can differ considerably. Examples of such fuel is Methyl Ethyl Ketone (MEK). It is therefore essential that the user checks for any unfavourable or unacceptable loss of efficiency when the foam is used against fires in any other water-miscible fuels than acetone and isopropanol respectively. The fire test conditions and procedure given in Clause M.2 can be used in order to achieve results comparative with acetone and isopropanol respectively and related requirements.
IMPORTANT - Other fuel depths and methods of application than those specified in Clause M.2 can cause considerable loss of efficiency. It is important that these matters are carefully considered by the user when assessing the suitability for particular applications.
WARNING - Any type approval according to this document is invalidated by any change in composition of the approved product.
NOTE 1   Some concentrates conforming to this document can also conform to other parts of the EN 1568 series and therefore can also be suitable for application as medium and/or high expansion foams.
NOTE 2   For national deviations, see Annex T.

Status
Not Published
Publication Date
25-Apr-2027
Current Stage
4599 - Dispatch of FV draft to CMC - Finalization for Vote
Start Date
23-Nov-2026
Due Date
23-Nov-2026
Completion Date
23-Nov-2026

Buy Documents

FprEN 1568-4:2026 is a CEN draft European standard for low expansion foam concentrates used for surface application to water-miscible liquids. It specifies the chemical and physical properties, minimum fire performance, marking, and test methods used to judge whether a foam concentrate is suitable for this duty. Manufacturers, test laboratories, system designers, and buyers use it to compare products and document conformity.

What does FprEN 1568-4:2026 specify?

FprEN 1568-4:2026 covers low expansion foam concentrates for surface application to water-miscible liquids, and it sets both product properties and performance requirements. The performance classification is based on fire tests using acetone and isopropanol, so the standard is a benchmark for those fuels and not a guarantee of identical behavior on every other water-miscible liquid.

The document is organized into clauses 1 to 16 and a set of annexes that support sampling, test methods, fire testing, quality checking, marking, and user information. It also includes a warning that any type approval is invalidated if the composition of the approved product changes.

AnnexWhat it covers
AGrades of foam concentrate
BSampling of foam concentrates
CDetermination of percentage sediment
DFreezing point determination
EDetermination of viscosity for pseudo-plastic foam concentrates
FTemperature conditioning of foam concentrates
GDetermination of surface tension
HStability/separation test of foam concentrate
IDetermination of expansion and drainage time
JDetermination of test fire performance
KOccupational health and ecotoxicological testing
LDescription of a radiation measurement method
MSmall-scale fire test
NAnnual foam quality check
ODetermination of foam expansion sensitivity
PExample of a technical information sheet
QA-Deviations

What are the key requirements of FprEN 1568-4:2026?

Clause 4 to Clause 16 combine product acceptance limits, fire test results, information duties, and marking rules. In practice, this is the part that tells a manufacturer what to prove and tells a buyer or laboratory what to check.

  • Representative sampling is the starting point. Annex B requires samples to be delivered in completely filled, sealable containers and taken so they represent the stored foam concentrate. That matters because every later result depends on the sample matching the product in the tank or container.

  • Sediment is tightly limited, before and after ageing. Clause 4 requires sediment to pass a 180 μm sieve and sets separate limits for fresh and aged samples, with ageing carried out under Annex C. This is a storage-stability check, so it helps spot contamination, breakdown, or settling that could affect proportioning and performance.

  • Freezing point and viscosity must fit the claimed use conditions. Clause 5 sends freezing point testing to Annex D, and Clause 6 requires viscosity checks over the claimed temperature range. Newtonian foam concentrates use EN ISO 3104, while pseudo-plastic foam concentrates use Annex E. For users, this affects whether the concentrate will pump, proportion, and flow correctly in the coldest conditions claimed by the supplier.

  • pH and surface tension are controlled as part of the basic chemistry. Clause 7 limits pH to a defined range, and Clause 8 checks the surface tension of foam solutions made from top and bottom half-samples after temperature conditioning. This is a practical way to see whether storage has altered the concentrate enough to change foam formation.

  • Storage stability is checked by conditioning and visual separation tests. Clause 9 requires the concentrate not to separate, stratify, or precipitate into distinct layers when tested in Annex H. It also adds special checks on solid deposits for synthetic foams and protein foams. That matters because a product can look acceptable in the container but still lose function after heat or cold exposure.

  • Expansion and drainage performance are checked before and after conditioning. Clause 10 uses Annex I to measure foam expansion and 25 % and 50 % drainage times, with simulated fresh water and, if claimed, simulated sea water. After temperature conditioning, top and bottom half-samples must stay close to each other and close to the unconditioned result. This tells the user whether the foam will still make stable foam after storage.

  • Fire performance is based on standard fuels and a defined fire test. Clause 11 uses acetone and isopropanol in the large-scale test of Annex J, with fresh water and, where claimed, sea water. The standard assigns extinguishing performance classes and burn-back resistance levels. In practice, this is the central proof that the concentrate can control and resist re-ignition on water-miscible liquid fires under the test conditions.

  • The document also covers documentation, ongoing checks, and packaging information. Clause 12 requires occupational health and ecotoxicological information from Annex K. Clause 13 recommends an annual foam quality check using Annex N, Clause 14 adds an expansion performance comparison test for F3-AR foams and for products claimed for fixed firefighting systems, Clause 15 points to a technical information sheet, and Clause 16 sets the container marking content. For buyers and operators, these clauses support traceability, safe use, and periodic verification of stored stock.

What terms does FprEN 1568-4:2026 define?

  • foam concentrate - the liquid product that is diluted with water to produce foam solution.
  • foam solution - the homogeneous mixture of foam concentrate and water at the manufacturer’s specified proportion.
  • premix - a foam solution prepared in a batch by adding a measured amount of foam concentrate to water in storage.
  • expansion (E) - the ratio of foam volume to the volume of foam solution used to make it.
  • low expansion foam - foam with an expansion ratio below 20.
  • pseudo-plastic foam concentrates - concentrates whose viscosity decreases as shear rate increases.
  • gentle application - application of foam indirectly to the fuel surface from a backboard.

Who uses FprEN 1568-4:2026?

FprEN 1568-4:2026 is used by foam concentrate manufacturers, accredited test laboratories, and organizations that specify or buy fire-fighting foam for water-miscible liquid hazards. It is also used by designers and operators of fixed firefighting systems, especially where foam performance must be documented against a defined test method.

In practice, manufacturers use it to formulate, test, label, and describe a concentrate. Laboratories use it for sampling, physical testing, fire testing, and annual quality checks. Buyers, quality managers, and system owners use it to compare product declarations, storage limits, sea water suitability, and the performance class claimed for a product.

What changed in FprEN 1568-4:2026 from the previous edition?

FprEN 1568-4:2026 is intended to supersede EN 1568-4:2018. The foreword states these technical changes relative to that edition:

  • determination of solid deposits for synthetic foams and protein foams was clarified;
  • an optional annual foam quality check was introduced;
  • temperature and wind speed measurements for the performance fire test were clarified;
  • stainless steel was added as an optional material for the small-scale fire tray;
  • a foam expansion performance test was introduced;
  • some test procedures were clarified.

Which standards are used with FprEN 1568-4:2026?

StandardWhat it contributes
EN 13565 (all parts)Context for fixed firefighting systems and the expansion comparison test in Clause 14
EN ISO 2811-1Density by pycnometer for the annual quality check
EN ISO 3104Viscosity of Newtonian foam concentrates
EN ISO 3219-2:2021Rotational rheometry basis for pseudo-plastic viscosity testing
EN ISO 3675Alternative density method for the annual quality check
EN ISO 11348-2Luminescent bacteria ecotoxicity method
EN ISO 23753-1Activated sludge-related test method named for ecotoxicological information
ISO 304Surface tension measurement by ring or plate method
ISO 3310-1Metal wire test sieve requirements for the 180 μm sieve
OECD 201, 202, 203, 301, 404, 405, 420Ecotoxicological and toxicological test methods named for Annex K
EN ISO/IEC 17025Competence basis for accredited testing laboratories noted in the foreword
EN 1568-1, EN 1568-2, EN 1568-3Companion parts in the EN 1568 series for other foam concentrate applications

What does the FprEN 1568-4:2026 document contain?

The document contains detailed test procedures, apparatus descriptions, formulas, and figures for checking foam concentrate behavior in the laboratory and in fire tests. Annexes C, D, E, G, H, I, J, M, and O give the practical methods for sediment, freezing point, viscosity, surface tension, stability, expansion/drainage, large-scale fire performance, small-scale fire performance, and expansion sensitivity.

It also contains a radiation measurement method for objective fire test recording, an annual quality check program with multiple analytical checks, and a worked example of the type of information expected in a manufacturer’s technical information sheet. Clause 16 and Annex P support product marking and user-facing documentation, while Annex Q records national A-deviations.

Relations

Effective Date
19-Jan-2023

Buy Documents

Get Certified

Connect with accredited certification bodies for this standard

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Kmetijski inštitut Slovenije

Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

FprEN 1568-4:2026 is a draft published by the European Committee for Standardization (CEN). Its full title is "Fire extinguishing media - Foam concentrates - Part 4: Specification for low expansion foam concentrates for surface application to water-miscible liquids". This standard covers: This document specifies requirements for chemical and physical properties, and minimum performance requirements of low expansion foams suitable for surface application to water-miscible liquids. Requirements are also specified for marking. IMPORTANT - The fire performance is tested using acetone and isopropanol as the fuel, which also forms the basis for the performance classification. However, there are a large number of water-miscible liquids which have more or less different properties to acetone and isopropanol. It has been shown by tests using other fuels that the performance of various foams can differ considerably. Examples of such fuel is Methyl Ethyl Ketone (MEK). It is therefore essential that the user checks for any unfavourable or unacceptable loss of efficiency when the foam is used against fires in any other water-miscible fuels than acetone and isopropanol respectively. The fire test conditions and procedure given in Clause M.2 can be used in order to achieve results comparative with acetone and isopropanol respectively and related requirements. IMPORTANT - Other fuel depths and methods of application than those specified in Clause M.2 can cause considerable loss of efficiency. It is important that these matters are carefully considered by the user when assessing the suitability for particular applications. WARNING - Any type approval according to this document is invalidated by any change in composition of the approved product. NOTE 1 Some concentrates conforming to this document can also conform to other parts of the EN 1568 series and therefore can also be suitable for application as medium and/or high expansion foams. NOTE 2 For national deviations, see Annex T.

This document specifies requirements for chemical and physical properties, and minimum performance requirements of low expansion foams suitable for surface application to water-miscible liquids. Requirements are also specified for marking. IMPORTANT - The fire performance is tested using acetone and isopropanol as the fuel, which also forms the basis for the performance classification. However, there are a large number of water-miscible liquids which have more or less different properties to acetone and isopropanol. It has been shown by tests using other fuels that the performance of various foams can differ considerably. Examples of such fuel is Methyl Ethyl Ketone (MEK). It is therefore essential that the user checks for any unfavourable or unacceptable loss of efficiency when the foam is used against fires in any other water-miscible fuels than acetone and isopropanol respectively. The fire test conditions and procedure given in Clause M.2 can be used in order to achieve results comparative with acetone and isopropanol respectively and related requirements. IMPORTANT - Other fuel depths and methods of application than those specified in Clause M.2 can cause considerable loss of efficiency. It is important that these matters are carefully considered by the user when assessing the suitability for particular applications. WARNING - Any type approval according to this document is invalidated by any change in composition of the approved product. NOTE 1 Some concentrates conforming to this document can also conform to other parts of the EN 1568 series and therefore can also be suitable for application as medium and/or high expansion foams. NOTE 2 For national deviations, see Annex T.

FprEN 1568-4:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.10 - Fire-fighting. The ICS classification helps identify the subject area and facilitates finding related standards.

FprEN 1568-4:2026 has the following relationships with other standards: It is inter standard links to EN 1568-4:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

FprEN 1568-4:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 25 %/50 % drainage time
  • 3.2 expansion (E)
  • 3.3 low expansion foam
  • 3.4 medium expansion foam
  • 3.5 high expansion foam
  • 3.6 fire-fighting foam
  • 3.7 foam concentrate
  • 3.8 foam solution
  • 3.9 premix
  • 3.10 sediment
  • 3.11 Newtonian foam concentrates
  • 3.12 pseudo-plastic foam concentrates
  • 3.13 surface tension
  • 3.14 freezing point
  • 3.15 designation
  • 3.16 demineralized water
  • 3.17 qualified personnel
  • 3.17 gentle application
  • 4 Sediment in the foam concentrate
  • 4.1 Sediment before ageing
  • 4.2 Sediment after ageing
  • 5 Freezing point
  • 6 Viscosity of the foam concentrate
  • 6.1 Test temperatures
  • 6.2 Newtonian foam concentrates
  • 6.3 Pseudo-plastic foam concentrates
  • 8 Surface tension of the foam solution
  • 9 Stability/separation test of foam concentrate
  • 10 Determination of expansion and drainage time
  • 10.1 Before temperature conditioning
  • 10.2 After temperature conditioning
  • 11 Test fire performance
  • 12 Occupation health and ecotoxicological information
  • 13 Annual foam quality check
  • 13.1 General
  • 13.2 Principles
  • 13.3 Types of analysis
  • 14 Expansion performance comparison test
  • 15 Technical information sheet
  • 16 Container marking
  • Annex A
  • Annex B
  • Annex C
  • Annex D
  • Annex E
  • Annex F
  • Annex G
  • Annex H
  • Annex I
  • Annex J
  • Annex K
  • Annex L
  • Annex M
  • 1 Burn-back pot
  • 5 Venturi tube (see Figure M.7)
  • 2 Knurled
  • Annex N
  • Annex O
  • 11 T-piece 21 O-ring
  • 1 Mounting bracket (example)
  • Annex P
  • Annex Q
  • 2 September 1982 from the Danish Ministry of Labour
  • Bibliography

Introduction

As fire-fighting foams are chemical agents or chemical preparations, Commission Directive 2006/60/CE and Regulations (EC) No 1272/2008 (CLP) and No 1907/2006 (REACH) apply and need to be taken into account.

Classes of fire are defined in EN 2 as follows:

 Class A: fires involving solid materials, usually of an organic nature, in which combustion normally takes place with the formation of glowing embers;  Class B: fires involving liquids or liquefiable solids;  Class C: fires involving gases;  Class D: fires involving metals;  Class F: fires involving cooking media (vegetable or animal oils and fats) in cooking appliances. Fire-fighting foams are widely used to control and extinguish Class B fires and to inhibit re-ignition. These foams can also be used for prevention of ignition of flammable liquids and, in certain conditions, to extinguish Class A fires.

Foams can be used in combination with other extinguishing media, particularly gaseous media and powders, which are the subject of other European Standards (see the European foreword). These specifications have been designed to ensure that fire extinguishing media have the minimum useful fire fighting capability. The user should ensure that the foam concentrates are used accurately at the concentration recommended by the manufacturer. Fire performances indicated by this standard cannot replicate practical fire situations.

Foam concentrates of different types and manufacture should not be mixed. Some combinations of extinguishing powder and foam can lead to unacceptable loss of efficiency, caused by unfavourable interaction of the chosen media when applied simultaneously or successively to the fire. It is extremely important that the foam concentrate after dilution with water to the recommended concentration does not in normal usage present a significant toxic hazard to life in relation to the environment. Commission Directive 2006/60/CE and Regulations (EC) No 1272/2008 (CLP) and No 1907/2006 (REACH) apply when considering the testing of ecotoxicological properties and safety in the work environment.

A special quality characteristic is the type test conducted by an independent testing laboratory accredited to EN ISO/IEC 17025.

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E)

1 Scope

This document specifies requirements for chemical and physical properties, and minimum performance requirements of low expansion foams suitable for surface application to water-miscible liquids. Requirements are also specified for marking.

IMPORTANT — The fire performance is tested using acetone and isopropanol as the fuel, which also forms the basis for the performance classification. However, there are a large number of water-miscible liquids which have more or less different properties to acetone and isopropanol. It has been shown by tests using other fuels that the performance of various foams can differ considerably. Examples of such fuel is Methyl Ethyl Ketone (MEK). It is therefore essential that the user checks for any unfavourable or unacceptable loss of efficiency when the foam is used against fires in any other water-miscible fuels than acetone and isopropanol respectively. The fire test conditions and procedure given in Clause J.2 can be used in order to achieve results comparative with acetone and isopropanol respectively and related requirements.

It is also essential for the user to note that other fuel depths and methods of application than those specified in Clause J.2 can cause considerable loss of efficiency and these matters should be carefully considered by the user when assessing the suitability for particular applications. WARNING — Any type approval according to this standard is invalidated by any change in composition of the approved product.

NOTE Some concentrates conforming to this document can also conform to other parts and therefore can also be suitable for application as medium and/or high expansion foams.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 13565 (all parts), Fixed firefighting systems — Foam systems EN ISO 2811-1, Paints and varnishes - Determination of density - Part 1: Pycnometer method (ISO 2811-1) EN ISO 3104, Petroleum products - Transparent and opaque liquids - Determination of kinematic viscosity and calculation of dynamic viscosity (ISO 3104) EN ISO 3219-2:2021, Rheology - Part 2: General principles of rotational and oscillatory rheometry (ISO 3219-2:2021) EN ISO 3675, Crude petroleum and liquid petroleum products - Laboratory determination of density - Hydrometer method (ISO 3675) EN ISO 11348-2, Water quality - Determination of the inhibitory effect of water samples on the light emission of Vibrio fischeri (Luminescent bacteria test) - Part 2: Method using liquid-dried bacteria (ISO 11348-2) EN ISO 23753-1, Soil quality - Determination of dehydrogenases activity in soils - Part 1: Method using triphenyltetrazolium chloride (TTC) (ISO 23753-1:2019) ISO 304, Surface active agents — Determination of surface tension by drawing up liquid films ISO 3310-1, Test sieves — Technical requirements and testing — Part 1: Test sieves of metal wire cloth

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E) OECD 201, Test No. 201: Freshwater Alga and Cyanobacteria, Growth Inhibition Test OECD 202, Test No. 202: Daphnia sp. Acute Immobilisation Test OECD 203, Test No. 203: Fish, Acute Toxicity Test OECD 301, Test No. 301: Ready Biodegradability OECD 404, Test No. 404: Acute Dermal Irritation/Corrosion OECD 405, Test No. 405: Acute Eye Irritation/Corrosion OECD 420, Test No. 420: Acute Oral Toxicity – Fixed Dose Procedure

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:

 IEC Electropedia: available at https://www.electropedia.org/  ISO Online browsing platform: available at https://www.iso.org/obp

3.1 25 %/50 % drainage time

time taken for 25 %/50 % of the volume of the original foam solution to drain out of the generated foam

3.2 expansion (E)

expansion value expansion ratio ratio of the volume of foam to the volume of the foam solution from which it was made

3.3 low expansion foam

foam which has an expansion ratio less than 20

3.4 medium expansion foam

foam which has an expansion ratio greater than or equal to 20 but less than 200

3.5 high expansion foam

foam which has an expansion ratio greater than or equal to 200

3.6 fire-fighting foam

aggregate of air-filled bubbles formed from a foam solution used for fire fighting

3.7 foam concentrate

liquid which is diluted with water to produce foam solution Note 1 to entry: Annex A gives information on grades of foam concentrate.

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E)

3.8 foam solution

homogeneous mixture of foam concentrate and water in the proportions as specified by the foam concentrate manufacturer

3.9 premix

foam solution prepared in a batch process by introducing a measured amount of foam concentrate into a given amount of water in a storage

3.10 sediment

insoluble particles in the foam concentrate

3.11 Newtonian foam concentrates

foam concentrates which have a viscosity which is independent of the shear rate

3.12 pseudo-plastic foam concentrates

foam concentrates which have a viscosity which decreases with increasing shear rate

3.13 surface tension

tension within the interface between a liquid and air

3.14 freezing point

temperature at which the first ingredient of a mixture starts to solidify or freeze out

3.15 designation

identifying name name that corresponds to a chemical formulation and a specific production process Note 1 to entry: The designation guarantees consistency of the characteristics, performance and conditions of use of the foam concentrate.

3.16 demineralized water

−1 water conforming to EN ISO 3696 (Grade 3), or having a surface tension greater than 70 mN⋅m and a −1 conductivity of ≤ 5 μS⋅cm Note 1 to entry: Surface tension tested in accordance with Clause G.2.

3.17 qualified personnel

designated individual, suitably trained, competent through knowledge and practical experience and with the necessary instruction to enable the tests and examinations to be carried out

3.17 gentle application

application (of foam from the test nozzle) indirectly to the surface of the fuel from a backboard

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E) Note 1 to entry: This definition of gentle application relates to the fire test procedures used in EN 1568-3 and EN 1568-4. In practice fire-fighting systems foam can also be applied gently by fixed foam pourers or by indirect application via a tank wall or other surface.

4 Sediment in the foam concentrate

4.1 Sediment before ageing

Any sediment in the foam concentrate sampled in accordance with Annex B, but not aged in accordance with Clause C.1, shall be dispersible through a 180 μm sieve, and the percentage volume of sediment shall be not more than 0,25 % when tested in accordance with Annex C.

4.2 Sediment after ageing

Any sediment in the foam concentrate sampled in accordance with Annex B, and aged in accordance with Clause C.1, shall be dispersible through a 180 μm sieve and the percentage volume of sediment shall be not more than 1,0 % when tested in accordance with Annex C.

5 Freezing point

The freezing point of the foam concentrate sampled in accordance with Annex B shall be determined in accordance with Annex D.

6 Viscosity of the foam concentrate

6.1 Test temperatures

The viscosity of the foam concentrate shall be measured from 20 °C up to and including the lowest temperature for use claimed by the manufacturer in steps of 10 °C. Use a fresh sample for each temperature.

6.2 Newtonian foam concentrates

The viscosity of the foam concentrate shall be determined in accordance with EN ISO 3104. If the viscosity 2 –1 is > 200 mm s , the container shall be marked in accordance with Clause 14, item j).

6.3 Pseudo-plastic foam concentrates

The viscosity of the foam concentrate shall be determined in accordance with Annex E. If the viscosity at −1 the lowest temperature for use is greater than or equal to 120 mPa·s at 375 s , the container shall be marked in accordance with Clause 14, item k).

7 pH of the foam concentrate The pH of the foam concentrate sampled in accordance with Annex B shall be not less than 6,0 and not more than 9,5 at (20 ± 1) °C.

8 Surface tension of the foam solution

The surface tension (determined in accordance with Clause G.2) of the foam solutions prepared using top and bottom half-samples (see Clause F.4) of the foam concentrate sampled in accordance with Annex B and conditioned in accordance with Annex F shall be not less than 0,95 times and not more than 1,05 times the surface tension of the foam solution prepared using the sampled foam concentrate.

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E)

9 Stability/separation test of foam concentrate

The foam concentrate shall not separate, stratify or precipitate as indicated by two or more distinct layers when tested in accordance with Annex H.

The amount of solid deposits of the aged sample determined according to Annex C at 20 °C in synthetic foams shall not increase from the fresh sample.

The amount of solid deposits of the aged sample determined according to Annex C at 20 °C in protein foams shall not increase by more than 4 times the amount obtained from the fresh sample, and shall not exceed a volume fraction of 1 % in total.

10 Determination of expansion and drainage time

10.1 Before temperature conditioning

The foam produced from the foam solution prepared from the foam concentrate sampled in accordance with Annex B, at the supplier’s recommended concentration with simulated fresh water in accordance with Clause I.4, shall be tested in accordance with Annex I and give an expansion according to 3.3. If appropriate, a further sample of the same concentration made with the simulated sea water in accordance with Clause I.4 shall also be tested.

10.2 After temperature conditioning

The foams produced from the solutions prepared with simulated fresh water by using top and bottom half-samples (see Clause F.4) of foam concentrate sampled in accordance with Annex B at the supplier’s recommended concentration, when tested in accordance with Annex I, shall have the following:

a) expansions which do not differ from each other or from the value obtained according to 10.1 using simulated fresh water (i.e. before temperature conditioning) by more than 20 % of the value obtained according to 10.1 using simulated fresh water; and b) 25 % drainage times which do not differ from each other or from the value obtained according to 10.1 using simulated fresh water (i.e. before temperature conditioning) by more than 20 % of the value obtained according to 10.1 using simulated fresh water.

If appropriate, the tests shall be repeated using top and bottom half-samples (see Clause F.4) of foam concentrate, sampled in accordance with Annex B at the supplier’s recommended concentration, using foam solutions prepared with the simulated sea water in accordance with Clause I.4. These foam solutions shall have the following:

c) expansions which do not differ from each other or from the value obtained according to 10.1 using the simulated sea water (i.e. before temperature conditioning) by more than 20 % of the value obtained according to 10.1 using the simulated sea water in accordance with Clause I.4; and d) 25 % drainage times which do not differ from each other or from the value obtained according to 10.1 using the simulated sea water (i.e. before temperature conditioning) by more than 20 % of the value obtained according to 10.1 using the simulated sea water in accordance with Clause I.4. NOTE Expansion is dependent on the foam concentrate and the equipment used to make the foam.

11 Test fire performance

The foam produced from the foam solutions prepared using the foam concentrate sampled in accordance with Annex B at the supplier's recommended concentration with simulated fresh water in accordance

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E) with Clause I.4, and if appropriate at the same concentration with the simulated sea water in accordance with Clause I.4, shall have an extinguishing performance class and burn-back resistance level as specified in Table 1 when tested in accordance with Clause J.2 and Clause J.3. NOTE 1 The values obtained with sea water can differ from those obtained with simulated fresh water. NOTE 2 Annex M describes a small-scale fire test which can be suitable for quality control purposes. NOTE 3 The lack of homogeneity of the premix can influence the firefighting performance of the foam generated from it.

Table 1 — Extinguishing performance classes and burn-back resistance levels Extinguishing 25 % Burn-back Extinction time not 25 % Burn-back performance class resistance level more than time not less than min min A 3 15 I B 3 10 C 3 5 A 5 15 II B 5 10 C 5 5

12 Occupation health and ecotoxicological information

The manufacturer shall provide information as specified in Annex K. If the data for the ecotoxicological report was generated by a third party, this data may be added to the test report or may added as a reference. If the data for the ecotoxicological report was generated by mathematical means (or as a reference) it shall be added to the test report. If the toxicological/ecotoxicological data were generated by application of mathematical methodologies in accordance with Annex K the corresponding report shall be added to the report confirming conformity with this document.

If the toxicological/ecotoxicological data were generated by an independent third party the data may be added to the report confirming conformity to this document either as a report or as a reference to the report-ID given by the third party.

13 Annual foam quality check

13.1 General

Firefighting foam concentrates are recommended to be checked annually for their quality, indicating their functionality. The test program described in 13.2 is considered to be a collection of analytical methods which in its entirety is suitable to detect degradation or a declining function of a foam concentrate. The outcome of the annual foam quality check described in 13.2 is intended to be used to qualify or disqualify a foam concentrate for its further usability. Therefore, the quality of testing and evaluation of test data is a special quality characteristic of the body executing the foam quality check.

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E)

13.2 Principles

13.2.1 The sample of the foam concentrate(s) shall be collected in such a way, that the sample is

representative of the stored volume.

13.2.2 A full declaration of the foam product’s identity, hazards associated with it [see section 2 of the most recent material safety data sheet (MSDS)], as well as information on PFAS content, proportioning rate, age, storage condition and possible contaminations shall be given.

13.2.3 For foam concentrates which can be used as low, medium and high expansion foam the desired

testing expansion shall be specified as well as the water quality (simulated fresh or sea water) to be used. 13.2.4 Packing and labelling of foam concentrate samples is subject to European regulation on packaging and labelling of chemical mixtures (Regulation (EC) No 1272/2008, CLP, e.g. Article 35). 13.2.5 The equipment for testing shall be calibrated and maintained in full function. 13.2.6 The foam concentrate sample should be processed as it was received. If stratification, sedimentation or other inhomogeneities are visible, that sample shall not be homogenised prior to testing. Instead, the sample may be considered as a fail.

13.2.7 A comprehensive test report with all tested results should be provided. The report may include evaluation of the obtained results and further recommendations. If this is the case, this shall be indicated as an evaluation of the data based on the experience and knowledge of the body executing the foam quality test.

13.2.8 The test data shall be compared with the technical data of the respective foam concentrate given by the manufacturer.

13.3 Types of analysis

Table 2 indicates the type of analysis that should be run for a given type of foam concentrate. Annex N gives test descriptions and requirements.

Table 2 — Types of analysis AR non-AR medium high expansion expansion application application Visual examination X X X X Density at (20 ± 1) °C X X X X pH-value at (20 ± 1) °C X X X X Sediment at (20 ± 1) °C X X X X Viscosity at (20 ± 1) °C X X X X Refractive index at (20 ± 1) °C X X X X 25 %-drainage, low expansion X X — — foam 25 %-drainage, medium — — X — expansion foam

oSIST prEN 1568-4:2025 prEN 1568-4:2025 (E) AR non-AR medium high expansion expansion application application 25 %-drainage, high expansion — — — X foam expansion, low expansion foam X X — — expansion, medium expansion — — X — foam expansion, high expansion — — — X foam Resistance to isopropanol X — — —

14 Expansion performance comparison test

The extinguishing performance of foams is influenced by the foam expansion ratio. For foams of the type F3-AR (fire extinguishing performance class I and class II) fire extinguishing tests shall be performed according to Annex O, Table O.1 a) and b), to determine the degree of the performance impact caused by changing the expansion ratio.

...