Standard Test Method for Fire Tests of Penetration Firestop Systems

SIGNIFICANCE AND USE
This test method is used to determine the performance of a firestop system with respect to exposure to a standard time-temperature fire test and a hose stream test. The performance of a firestop system is dependent upon the specific assembly of materials tested including the number, type, and size of penetrations and the floors or walls in which it is installed.
Two ratings shall be established for each firestop system. An F rating shall be based upon flame occurrence on the unexposed surface, while the T rating shall be based upon the temperature rise as well as flame occurrence on the unexposed side of the firestop system. These ratings, together with detailed performance data such as the location of through-openings and temperatures of penetrating items are intended to be one factor in assessing performance of firestop systems.
SCOPE
1.1 This test method is applicable to firestop systems of various materials and construction. Firestop systems are intended for use in openings in fire-resistive walls and floors that are evaluated in accordance with Test Methods E119.
1.2 Tests conducted in conformance with this test method record firestop system performance during the test exposure; but such tests shall not be construed to determine suitability of the firestop system for use after test exposure.
1.3 This test method also measures the resistance of firestop systems to an external force stimulated by a hose stream. However, this test method shall not be construed as determining the performance of the firestop system during actual fire conditions when subjected to forces such as failure of cable support systems and falling debris.
1.4 The intent of this test method is to develop data to assist others in determining the suitability of the firestops for use where fire resistance is required.
1.5 This test method does not apply to membrane penetrations of a floor-ceiling assembly or roof-ceiling assembly that are tested as part of the assembly in accordance with Test Methods E119.
1.6 This test method does not apply to membrane penetrations of load-bearing walls.
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.8 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of materials, products, or assemblies under actual fire conditions.  
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.  
1.10 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered requirements of the standard.

General Information

Status
Historical
Publication Date
31-Mar-2011
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E814-11a - Standard Test Method for Fire Tests of Penetration Firestop Systems
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E814-11a - Standard Test Method for Fire Tests of Penetration Firestop Systems
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E814 − 11a AnAmerican National Standard
Standard Test Method for
1
Fire Tests of Penetration Firestop Systems
This standard is issued under the fixed designation E814; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
INTRODUCTION
Characteristically fire spreads from one building compartment to another by the collapse of a
barrier, or by openings through which flames or hot gases may pass, or by transfer of sufficient heat
to ignite combustibles beyond the barrier. Test Methods E119 describe the method to be used to
measure the fire-resistive performance of these barriers.
However, various techniques of providing for the distribution of services within a structure
sometimes require that openings be made in fire-resistive walls and floors to allow the passage of such
penetrating items as cables, conduits, pipes, trays, and ducts through to the adjacent compartment.
Fire-stop material is installed into these openings to resist the spread of fire.
The performance of through-penetration firestops should be measured and specified according to a
common standard that describes the method of fire exposure and rating criteria.
1. Scope 1.6 This test method does not apply to membrane penetra-
tions of load-bearing walls.
1.1 This test method is applicable to firestop systems of
various materials and construction. Firestop systems are in- 1.7 The values stated in inch-pound units are to be regarded
tended for use in openings in fire-resistive walls and floors that as standard. The values given in parentheses are mathematical
are evaluated in accordance with Test Methods E119. conversions to SI units that are provided for information only
and are not considered standard.
1.2 Tests conducted in conformance with this test method
record firestop system performance during the test exposure; 1.8 This standard is used to measure and describe the
but such tests shall not be construed to determine suitability of response of materials, products, or assemblies to heat and
the firestop system for use after test exposure. flame under controlled conditions, but does not by itself
incorporate all factors required for fire-hazard or fire-risk
1.3 This test method also measures the resistance of firestop
assessment of materials, products, or assemblies under actual
systems to an external force stimulated by a hose stream.
fire conditions.
However, this test method shall not be construed as determin-
1.9 This standard does not purport to address all of the
ing the performance of the firestop system during actual fire
safety concerns, if any, associated with its use. It is the
conditions when subjected to forces such as failure of cable
responsibility of the user of this standard to establish appro-
support systems and falling debris.
priate safety and health practices and determine the applica-
1.4 The intent of this test method is to develop data to assist
bility of regulatory limitations prior to use.
others in determining the suitability of the firestops for use
1.10 Thetextofthisstandardreferencesnotesandfootnotes
where fire resistance is required.
which provide explanatory material. These notes and footnotes
1.5 This test method does not apply to membrane penetra-
(excluding those in tables and figures) shall not be considered
tions of a floor-ceiling assembly or roof-ceiling assembly that
requirements of the standard.
are tested as part of the assembly in accordance with Test
Methods E119.
2. Referenced Documents
2
2.1 ASTM Standards:
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire
Standards and is the direct responsibility of Subcommittee E05.11 on Fire
2
Resistance. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved April 1, 2011. Published April 2011. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1981. Last previous edition approved in 2011 as E814 – 11. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/E0814-11A. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E814 − 11a
E119 Test Methods for Fire Tests of Building Construction time-temperature fire test and a hose stream test. The perfor-
and Materials mance of a firestop system is dependent upon the specific
E176 Terminology of Fire Standards assembly of materials tested including the number, t
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:E814–11 Designation:E814–11a
Standard Test Method for
1
Fire Tests of Penetration Firestop Systems
This standard is issued under the fixed designation E814; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
INTRODUCTION
Characteristically fire spreads from one building compartment to another by the collapse of a
barrier, or by openings through which flames or hot gases may pass, or by transfer of sufficient heat
to ignite combustibles beyond the barrier. Test Methods E119 describe the method to be used to
measure the fire-resistive performance of these barriers.
However, various techniques of providing for the distribution of services within a structure
sometimes require that openings be made in fire-resistive walls and floors to allow the passage of such
penetrating items as cables, conduits, pipes, trays, and ducts through to the adjacent compartment.
Fire-stop material is installed into these openings to resist the spread of fire.
The performance of through-penetration firestops should be measured and specified according to a
common standard that describes the method of fire exposure and rating criteria.
1. Scope
1.1 This test method is applicable to firestop systems of various materials and construction. Firestop systems are intended for
use in openings in fire-resistive walls and floors that are evaluated in accordance with Test Methods E119.
1.2 Tests conducted in conformance with this test method record firestop system performance during the test exposure; but such
tests shall not be construed to determine suitability of the firestop system for use after test exposure.
1.3 This test method also measures the resistance of firestop systems to an external force stimulated by a hose stream. However,
this test method shall not be construed as determining the performance of the firestop system during actual fire conditions when
subjected to forces such as failure of cable support systems and falling debris.
1.4 The intent of this test method is to develop data to assist others in determining the suitability of the firestops for use where
fire resistance is required.
1.5 This test method does not apply to membrane penetrations of a floor-ceiling assembly or roof-ceiling assembly that are
tested as part of the assembly in accordance with Test Methods E119.
1.6 This test method does not apply to membrane penetrations of load-bearing walls.
1.7 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.8 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of materials,
products, or assemblies under actual fire conditions.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.10 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered requirements of the standard.
2. Referenced Documents
2
2.1 ASTM Standards:
1
This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved Jan.April 1, 2011. Published FebruaryApril 2011. Originally approved in 1981. Last previous edition approved in 20102011 as E814 – 101. DOI:
10.1520/E0814-11A.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ------
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.