Standard Specification for Segmental Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD

SCOPE
1.1 This specification covers precast reinforced concrete box sections comprised of separate segments that once properly field assembled make the final structure. These structures are intended to be used for the construction of culverts and for the conveyance of storm water, industrial wastes and sewage.
Note 1: This specification is primarily a manufacturing and purchasing specification. However, box culverts manufactured to this standard are intended to meet the design requirements of the AASHTO LRFD Bridge Design Specifications, and as such, design guidance is included in Appendix X1.
Note 2: The successful performance of this product depends upon the proper selection of the box section, bedding, backfill, and care that the installation conforms to the construction specifications. The purchaser of the precast reinforced concrete box sections specified herein is cautioned that proper correlation of the loading conditions and the field requirements with the box section specified, and provision for inspection at the construction site, are required.  
1.2 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.

General Information

Status
Historical
Publication Date
31-Oct-2014
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1786-14 - Standard Specification for Segmental Precast Reinforced Concrete Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD
English language
11 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1786 −14
StandardSpecification for
Segmental Precast Reinforced Concrete Box Sections for
Culverts, Storm Drains, and Sewers Designed According to
1
AASHTO LRFD
This standard is issued under the fixed designation C1786; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope C260 Specification for Air-Entraining Admixtures for Con-
crete
1.1 This specification covers precast reinforced concrete
C309 Specification for Liquid Membrane-Forming Com-
box sections comprised of separate segments that once prop-
pounds for Curing Concrete
erly field assembled make the final structure. These structures
C494/C494M Specification for Chemical Admixtures for
are intended to be used for the construction of culverts and for
Concrete
the conveyance of storm water, industrial wastes and sewage.
C497 Test Methods for Concrete Pipe, Manhole Sections, or
NOTE 1—This specification is primarily a manufacturing and purchas-
Tile
ing specification. However, box culverts manufactured to this standard are
C595 Specification for Blended Hydraulic Cements
intended to meet the design requirements of the AASHTO LRFD Bridge
C618 Specification for Coal Fly Ash and Raw or Calcined
Design Specifications, and as such, design guidance is included in
Natural Pozzolan for Use in Concrete
Appendix X1.
NOTE 2—The successful performance of this product depends upon the
C822 Terminology Relating to Concrete Pipe and Related
proper selection of the box section, bedding, backfill, and care that the
Products
installation conforms to the construction specifications. The purchaser of
C989 Specification for Slag Cement for Use in Concrete and
the precast reinforced concrete box sections specified herein is cautioned
Mortars
thatpropercorrelationoftheloadingconditionsandthefieldrequirements
C1116 Specification for Fiber-Reinforced Concrete and
with the box section specified, and provision for inspection at the
construction site, are required.
Shotcrete
3
1.2 The values stated in inch-pound units are to be regarded
2.2 AASHTO Standards:
as standard. No other units of measurement are included in this
AASHTO LRFD Bridge Design Specifications
standard.
AASHTO LRFD Bridge Construction Specifications
4
2.3 ACI Standards:
2. Referenced Documents
ACI 318 Building Code Requirements for Structural Con-
2
2.1 ASTM Standards:
crete
A615/A615M SpecificationforDeformedandPlainCarbon-
Steel Bars for Concrete Reinforcement
3. Terminology
A706/A706M Specification for Deformed and Plain Low-
3.1 Definitions of Terms Specific to This Standard:
Alloy Steel Bars for Concrete Reinforcement
3.1.1 box section—the completed box culvert unit with all
A1064/A1064M Specification for Carbon-Steel Wire and
segments adjoined (see Fig. 1 for configuration options).
Welded Wire Reinforcement, Plain and Deformed, for
Concrete
3.1.2 box segment—the individual piece (top slab, bottom
C33 Specification for Concrete Aggregates
slab, or three-sided structure) that gets adjoined to other pieces
C150 Specification for Portland Cement
to complete the final box section
3.2 Definitions—Fordefinitionsoftermsrelatingtoconcrete
box culvert sections not found above, see Terminology C822.
1
This test method is under the jurisdiction of ASTM Committee C13 on
Concrete Pipe and is the direct responsibility of Subcommittee C13.07 on
Acceptance Specifications and Precast Concrete Box Sections.
Current edition approved Nov. 1, 2014. Published December 2014. DOI:
3
10.1520/C1786–14. Available from American Association of State Highway and Transportation
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM http://www.transportation.org.
4
Standards volume information, refer to the standard’s Document Summary page on Available fromAmerican Concrete Institute (ACI), P.O. Box 9094, Farmington
the ASTM website. Hills, MI 48333-9094, http://www.concrete.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1786−14
FIG. 1Segment Configuration Options
2

---------------------- Page: 2 ----------------------
C1786−14
4. Basis of Acceptance mentmeetingtheyieldstrengthsdesignatedinthedesignofthe
box culvert, but the yield strength shall not be less than 60 ksi.
4.1 Acceptability of the box sections produced in accor-
5.6 Synthetic Fibers—Collated fibrillated virgin polypropyl-
dance with this standard shall be determined by the result
...