SIST EN 671-1:2001
(Main)Fixed firefighting systems - Hose systems - Part 1: Hose reels with semi-rigid hose
Fixed firefighting systems - Hose systems - Part 1: Hose reels with semi-rigid hose
This European Standard specifies requirements and methods of test for the construction and performance of fire hose reel systems with semi-rigid hose for installation in buildings and other construction works, permanently connected to a water supply, for use by the occupants.
Its requirements may apply in general for other applications, for example in marine applications or in aggressive environments, but additional requirements may be necessary in such cases.
This standard is applicable to both manual and automatic fire hose reels for installation with and without cabinets.
For convenience of application in conformity testing, the normative annexes of this standard are arranged so that annex A gives the sequence of testing for conformity assessment and annexes B, C, D, E and F are in the correct sequence for testing.
NOTE All pressures are gauge pressures and are expressed in megapascals. 1 MPa = 10 bar.
Ortfeste Löschanlagen - Wandhydranten - Teil 1: Schlauchhaspeln mit formstabilem Schlauch
Diese Europäische Norm legt Anforderungen und Prüfverfahren für Bauart und Ausführung von Schlauchhaspeln mit formstabilem Schlauch zum Einbau in Gebäuden oder anderen baulichen Anlagen fest, die fest mit der Wasserzufuhr verbunden und zum Gebrauch durch jede Person geeignet sind.Die Anforderungen dieser Norm dürfen in der Regel auch für andere Anwendungen zu Grunde gelgt werden, z.B. im Schiffbau oder bei aggressivem Umfeld, in diesen Fällen können jedoch zusätzliche Anforderungen notwendig sein.
Diese Norm gilt für Schlauchhaspeln sowohl mit handbetätigten als auch automatischen Ventilen jeweils zum Einbau mit oder ohne Schrank. Im Sinne der Zweckmäßigkeit für die Anwendung bei Konformitätsprüfungen sind die normativen Anhänge dieser Norm so angelegt, dass Anhang A die Reihenfolge der Konformitätsprüfungen angibt, während die Anhänge B, C, D, E und F die Prüfungen in der exakten Reihenfolge ihrer Durchführung enthalten.
Anmerkung: Alle DrÜcke sind Manometerdrücke und werden in Megapascal angegeben; 1 MPa = 10 bar.
Installations fixes de lutte contre l'incendie - Systemes équipés de tuyaux - Partie 1: Robinets d'incendie armés équipés de tuyaux semi-rigides
1 Domaine d'application
La présente Norme européenne prescrit les exigences et méthodes d'essais de fabrication et de performances des robinets d'incendie armés équipés de tuyaux semi-rigides, destinés a etre installés dans des immeubles et autres bâtiments industriels, raccordés en permanence a une alimentation en eau, pour etre utilisés par les occupants.
Ses exigences peuvent concerner d'autres cas, par exemple les applications en atmospheres marines ou corrosives ; dans ces cas, des exigences supplémentaires peuvent s'avérer nécessaires.
La présente norme s'applique aux robinets d'incendie armés, manuels ou automatiques, destinés a etre installés ou non dans des armoires.
Pour la bonne conformité aux essais, les annexes normatives de cette norme sont aménagées de telle sorte que l'annexe A donne les méthodes d'évaluation de la conformité et les annexes B, C, D, E et F mentionnent les essais dans l'ordre indiqué par cette annexe A.
NOTE Toutes les pressions sont des pressions manométriques exprimées en mégapascals : 1 MPa = 10 bar.
Vgrajeni gasilni sistemi - Cevni sistemi - 1. del: Cevni koluti s poltogo cevjo
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 671-1:2001
01-oktober-2001
1DGRPHãþD
SIST EN 671-1:1997
Vgrajeni gasilni sistemi - Cevni sistemi - 1. del: Cevni koluti s poltogo cevjo
Fixed firefighting systems - Hose systems - Part 1: Hose reels with semi-rigid hose
Ortfeste Löschanlagen - Wandhydranten - Teil 1: Schlauchhaspeln mit formstabilem
Schlauch
Installations fixes de lutte contre l'incendie - Systemes équipés de tuyaux - Partie 1:
Robinets d'incendie armés équipés de tuyaux semi-rigides
Ta slovenski standard je istoveten z: EN 671-1:2001
ICS:
13.220.10 Gašenje požara Fire-fighting
23.040.70 Gumene cevi in armature Hoses and hose assemblies
SIST EN 671-1:2001 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 671-1:2001
---------------------- Page: 2 ----------------------
SIST EN 671-1:2001
EUROPEAN STANDARD
EN 671-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2001
ICS 13.220.20 Supersedes EN 671-1:1994
English version
Fixed firefighting systems - Hose systems - Part 1: Hose reels
with semi-rigid hose
Installations fixes de lutte contre l'incendie - Systèmes Ortfeste Löschanlagen - Wandhydranten - Teil 1:
équipés de tuyaux - Partie 1: Robinets d'incendie armés Schlauchhaspeln mit formstabilem Schlauch
équipés de tuyaux semi-rigides
This European Standard was approved by CEN on 1 March 2001.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2001 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 671-1:2001 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 671-1:2001
Page 2
EN 671-1:2001
Contents
Foreword.3
Introduction .4
1 Scope .4
2 Normative references.4
3 Terms and definitions .5
4 Reel .5
5 Hose .6
6 Shut-off nozzle.6
7 Inlet stop valve.7
8 Cabinets.8
9 Materials .8
10 Hydraulic properties.9
11 Colour, symbols, marking and instructions .11
12 Evaluation of conformity.11
Annex A (normative) Schedule for initial type testing.13
Annex B (normative) Test method for resistance to external corrosion.14
Annex C (normative) Ageing test for plastics materials .15
Annex D (normative) Test method for resistance to corrosion of waterways .16
Annex E (normative) Test methods for nozzle.17
Annex F (normative) Test method for physical endurance .20
Annex ZA (informative) Clauses of this European Standard addressing the provisions of EU
Construction Products Directive.23
Bibliography .27
---------------------- Page: 4 ----------------------
SIST EN 671-1:2001
Page 3
EN 671-1:2001
Foreword
This European Standard has been prepared by Technical Committee CEN/TC 191 "Fixed firefighting system", the
secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by October 2001, and conflicting national standards shall be withdrawn at the latest
by January 2003.
This European Standard replaces EN 671-1:1994.
EN 671 has the general title “Fixed firefighting systems – Hose systems” and is in three parts;
Part 1: Hose reels with semi-rigid hose
Part 2: Hose systems with lay-flat hose
Part 3: Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose
This European Standard has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association and supports the essential requirements of EU Directive 89/106/EEC.
For relationship with EU Directives, see informative Annex ZA, which is an integral part of this Standard.
Annexes A, B, C, D, E and F are normative.
This European Standard includes a bibliography.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,
France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden,
Switzerland and the United Kingdom.
---------------------- Page: 5 ----------------------
SIST EN 671-1:2001
Page 4
EN 671-1:2001
Introduction
Fire hose systems in proper condition provide a very effective firefighting facility with a continuous supply of water
available immediately.
The requirements of this standard have been framed to ensure that hose reels can be operated efficiently by one
person and that such systems will have a long service life and will not need excessive maintenance.
1 Scope
This European Standard specifies requirements and methods of test for the construction and performance of fire
hose reel systems with semi-rigid hose for installation in buildings and other construction works, permanently
connected to a water supply, for use by the occupants.
Its requirements may apply in general for other applications, for example in marine applications or in aggressive
environments, but additional requirements may be necessary in such cases.
This standard is applicable to both manual and automatic fire hose reels for installation with and without cabinets.
For convenience of application in conformity testing, the normative annexes of this standard are arranged so that
annex A gives the sequence of testing for conformity assessment and annexes B, C, D, E and F are in the correct
sequence for testing.
NOTE All pressures are gauge pressures and are expressed in megapascals. 1 MPa = 10 bar.
2 Normative references
This European Standard incorporates by dated or undated references, provisions from other publications. These
normative references are cited at the appropriate places in the text and the publications are listed hereafter. For
dated references, subsequent amendments to or revisions of any of these publications apply to this European
Standard only when incorporated in it by amendment of revision. For undated references the latest edition of the
publication referred to applies (including amendments).
EN 671-3, Fixed firefighting systems - Hose systems – Part 3: Maintenance of hose reels with semi-rigid hose and
hose systems with lay-flat hose.
EN 694:2001, Fire-fighting hoses – Semi-rigid hoses for fixed systems.
EN ISO 4892-2:1999, Plastics – Methods of exposure to laboratory light sources – Part 2: Xenon-arc sources (ISO
4892-2:1994).
ISO 9227:1990, Corrosion tests in artificial atmospheres; salt spray tests.
---------------------- Page: 6 ----------------------
SIST EN 671-1:2001
Page 5
EN 671-1:2001
3 Terms and definitions
For the purposes of this European Standard, the following terms and definitions apply:
3.1
manual fire hose reel; manual hose reel
firefighting appliance consisting of a reel with water supplied through the centre, manual inlet stop valve adjacent to
the reel, semi-rigid hose, shut-off nozzle and, where required, a hose guide
3.2
automatic fire hose reel; automatic hose reel
firefighting appliance consisting essentially of a reel with water supplied through the centre, automatic inlet stop
valve, semi-rigid hose, shut-off nozzle and, where required, a hose guide
3.3
reel and valve subassembly
that part of a fire hose reel assembly consisting of a reel, automatic inlet stop valve (if fitted) and the connection to
the reel, but excluding semi-rigid hose, shut-off nozzle and connectors or couplings
3.4
fixed fire hose reel; fixed hose reel
hose reel capable only of rotating in one plane with a hose guide adjacent to the reel
3.5
swinging fire hose reel; swinging hose reel
hose reel capable of rotating and swinging in more than one plane and mounted on one of the following:
- swinging arm; or
- swinging pipe; or
- swinging door
3.6
shut-off nozzle
component, at the end of the hose, used to direct and control the discharge of water
4 Reel
4.1 The reel shall rotate around a spindle.
4.2 The reel shall consist of two wheels with a maximum diameter not more than 800 mm, and inside segments or
drum with a minimum diameter not less than 200 mm for 19 mm and 25 mm hose and a minimum diameter not less
than 280 mm for 33 mm hose.
4.3 Hose reels shall show no visible leakage after rotation when tested in accordance with F.2.
o
4.4 Swinging hose reels shall be able to swing to minimum 170 and show no visible leakage or damage when
tested in accordance with F.3.
4.5 The forces to unwind the hose in any horizontal direction shall not exceed the appropriate values given in
Table 1, when the hose reel is tested in accordance with F.4.
4.6 Rotation of the reel shall stop within one turn when the hose reel is tested in accordance with F.5.
4.7 No deformation which may harm the function of the reel shall occur on the reel itself, or of the hose fittings at
the reel inlet and outlet when the hose reel is tested in accordance with F.6.
---------------------- Page: 7 ----------------------
SIST EN 671-1:2001
Page 6
EN 671-1:2001
Table 1 - Forces to unwind the hose
Hose diameter, mm Maximum initial force Maximum initial force at Maximum force at any
without hose guide, N any point with hose point to pull out the
guide, N entire hose, N
19 70 150 250
25 70 200 300
33 100 300 350
5Hose
5.1 General
The hose shall be semi-rigid and conform to EN 694:2001.
5.2 Hose bore
The nominal bore of the hose shall be one of the following:
— 19 mm; or
— 25 mm; or
— 33 mm
5.3 Maximum length
The length of the hose shall be in one piece and shall not exceed 30 m.
6 Shut-off nozzle
6.1 General
The hose shall terminate in a shut-off nozzle, which shall give the following control settings:
a) shut, and
b) spray; and/or
c) jet
NOTE When both spray and jet are provided it is recommended that the sequence should be as above with the
spray setting between the shut setting and the jet setting.
Any spray discharge shall be in the form of either a sheet spray or a conical spray.
6.2 Resistance to impact
The nozzle shall not break or show any visible leakage when tested in accordance with E.1.
---------------------- Page: 8 ----------------------
SIST EN 671-1:2001
Page 7
EN 671-1:2001
6.3 Operating torque
The torque necessary to operate the nozzle to each control setting at maximum working pressure shall not exceed
the appropriate value given in Table 2 when determined after testing in accordance with E.2.
Table 2 — Maximum operating torque of nozzle control according to hose diameter
Control setting Maximum operating torque in Nm
19 mm and 25 mm hose 33 mm hose
Operating 4 7
Spray 4 7
Jet 4 7
Flowrate control 4 7
6.4 Marking of control conditions
6.4.1 Rotary operated nozzles shall be marked to show the direction of closing and opening.
6.4.2 Lever operated nozzles shall be marked to show the settings for
a) shut; and
b) spray; and/or jet
7 Inlet stop valve
7.1 General
A stop valve shall be fitted to the hose reel.
NOTE It is normally appropriate for valve connections and valve combinations to comply with national standards of
the country in which the equipment is to be installed.
7.2 Manual inlet stop valve
NOTE 1 It is recommended that an interlocking device be fitted so that the nozzle cannot be withdrawn unless the
water supply is first turned on by opening of the manual stop valve.
NOTE 2 The valve may be of screwdown-type or quick-opening type. In selecting the type of stop valve to be
used, the effect of water hammer should be considered.
7.2.1 The valve shall be closed by turning the handle or handwheel in a clockwise direction.
7.2.2 The direction of opening shall be marked.
7.2.3 Screwdown valves shall be fully open after maximum 3½ turns of the handwheel.
---------------------- Page: 9 ----------------------
SIST EN 671-1:2001
Page 8
EN 671-1:2001
7.3 Automatic inlet stop valve
An automatic inlet stop valve shall be fully opened by not more than 3 complete revolutions of the reel. No visible
leakage shall occur when tested in accordance with F.2.
NOTE To assist ease of maintenance for hose reels fitted with automatic valves, consideration should be given to
water supply isolation valves.
8 Cabinets
8.1 General
Cabinets shall be fitted with a door and may be fitted with a lock. Lockable cabinets shall be provided with an
emergency opening device, which may be protected only by transparent frangible material. To provide access for
inspection and maintenance, the cabinet shall be unlockable with a key.
If the emergency opening device is protected by a frangible glass front this shall be of the type which when broken
does not leave jagged or sharp edges, which might cause injury when the emergency opening is operated.
Cabinets shall be free of sharp edges, which might damage the equipment or cause injury.
Cabinets may also be used to contain other firefighting equipment, provided that the cabinet is of sufficient size and
o
the equipment does not interfere with the prompt use of the hose reel. Cabinet doors shall open to minimum 170
to allow the hose to be run out freely in any direction. For service in some climatic conditions it may be necessary
to provide the cabinet with suitable ventilating openings.
8.2 Cabinets for manual hose reels with screwdown type valves
The screwdown valve shall be positioned in such a way that there is at least 35 mm free space around the external
diameter of the handwheel, when the valve is in any position from fully open to fully closed.
9 Materials
NOTE 1 Where fire hose reels are connected to a public domestic water supply, the appropriate authority may
specify materials which are, or are not, acceptable to the authority.
NOTE 2 The advice of the hose reel supplier should be requested in cases of special corrosion risk.
9.1 Resistance to external corrosion
Any metal parts shall provide adequate protection when coated parts are tested in accordance with B.1 and
uncoated parts are tested in accordance with B.2.
9.2 Plastics materials
9.2.1 Components subjected to pressure
After the ageing test in accordance with Annex C;
- components shall show no leakage when tested at the maximum working pressure in accordance with F.7,
- centre parts shall also meet the requirements of 4.7 when tested in accordance with F.6.2,
- nozzles shall also meet the requirements of 6.2 when tested in accordance with E.1.
9.2.2 Components not subjected to pressure
After the ageing test in accordance with Annex C, all components, excluding any marking plates, shall meet the
requirements of 4.7 when tested in accordance with F.6.1.
---------------------- Page: 10 ----------------------
SIST EN 671-1:2001
Page 9
EN 671-1:2001
9.3 Resistance to corrosion of waterways
There shall be no significant corrosion defects and the mechanical operation of all working parts shall be
unimpaired when waterways are tested in accordance with Annex D.
10 Hydraulic properties
10.1 Resistance to internal pressure
Hose reels shall not leak when tested to the appropriate test pressure given in Table 3, in accordance with F.7.
10.2 Strength
Hose reels shall not burst at less than the appropriate minimum burst pressure given in Table 3 when tested
without the hose in accordance with F.8.
Table 3 - Working, test and minimum burst pressure for hose reels
Nominal diameter Working pressure, MPa Test pressure, MPa Minimum burst pressure, MPa
of hose, mm
19 1,2 1,8 3,0
25 1,2 1,8 3,0
33 0,7 1,05 1,75
---------------------- Page: 11 ----------------------
SIST EN 671-1:2001
Page 10
EN 671-1:2001
10.3 Minimum flow rate
The flow rates in jet and spray settings shall be not less than the appropriate values given in Table 4 when the
hose reel is tested in accordance with E.4.1.
Table 4 - Minimum flow rates and minimum k-coefficient according to pressure
Nozzle diameter or equivalent Minimum flow rate Q l/min K-coefficient
diameter, mm (see note)
P = 0,2 MPa P = 0,4 MPa P = 0,6 MPa
4 12 18229
518 26 31 13
624 34 41 17
7 31 44 53 22
839 56 68 28
946 66 80 33
10 59 84 102 42
12 90 128 156 64
NOTE Flowrate Q at a pressure P is related to the equation Q = K 10P , where Q is in litres/minute and P
is in megapascals.
10.4 Effective throw range
The effective throw ranges of the discharges at a pressure of 0,2 MPa when determined in accordance with E.4.2
shall not be less than as follows:
- jet discharge 10 m;
- sheet spray discharge 6 m;
- conical spray discharge 3 m
as appropriate.
10.5 Spray discharge
Nozzles with a spray setting shall give a spray angle when determined in accordance with E.3 as follows:
- sheet spray 90° + 5°;
- conical spray not less than 45°.
---------------------- Page: 12 ----------------------
SIST EN 671-1:2001
Page 11
EN 671-1:2001
11 Colour, symbols, marking and instructions
11.1 Colour
The colour of the reel wheels shall be red except where regulatory requirements permit the use of other colours.
NOTE A suitable red colour is specified in ISO 3864 - Safety colours and safety signs.
11.2 Identification symbol
The hose reel and hose reel cabinet shall be marked with the symbol according to Council Directive 92/58/EEC.
NOTE The symbol may have a luminescent surface.
11.3 Marking
The reel shall be marked with the following information:
a) supplier’s name or trade mark, or both;
b) number of this European Standard;
c) year of manufacture;
d) maximum working pressure;
e) length and bore of hose;
f) nozzle equivalent diameter (marked on the nozzle).
11.4 Instruction for use
Fire hose reel assemblies shall be provided with full operational instructions for display on or adjacent to the hose
reel.
11.5 Installation and maintenance instructions
The supplier shall make available an installation manual specific for the hose reel.
Maintenance procedures shall be as specified
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.