EN 17415-2:2021
(Main)District cooling pipes - Bonded single pipe systems for directly buried cold water networks - Part 2: Factory made fitting assemblies of steel or plastic service pipe, polyurethane thermal insulation and a casing of polyethylene
District cooling pipes - Bonded single pipe systems for directly buried cold water networks - Part 2: Factory made fitting assemblies of steel or plastic service pipe, polyurethane thermal insulation and a casing of polyethylene
This document specifies requirements, design and test methods for factory made thermally insulated bonded fitting assemblies for directly buried district cooling distribution systems, comprising a service fitting from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene.
The fitting assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers.
This document covers the following fitting assemblies: bend, tee, reducer, cap and anchor.
This document applies only to insulated fitting assemblies, for continuous operation with water at various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE An expected service life of 50 years presupposes that treated water is used.
Fernkälterohre - Einrohr-Verbundsysteme für direkt erdverlegte Fernkältenetze - Teil 2: Werkmäßig gefertigte Formstückbaueinheiten, bestehend aus Stahl- oder Kunststoff-Mediumrohr, einer Wärmedämmung aus Polyurethan und einer Ummantelung aus Polyethylen
Dieses Dokument legt die Anforderungen, Auslegung und Prüfverfahren für werkmäßig gefertigte, wärmegedämmte Formstückbaueinheiten für direkt erdverlegte Fernkältenetzwerke fest, die aus einem Mediumrohr von DN 15 bis DN 1200, einer Polyurethan-Hartschaumstoffdämmung und einem Polyethylenmantel bestehen.
Die Formstückbaueinheit kann darüber hinaus die folgenden zusätzlichen Bauteile umfassen: Messdrähte, Abstandhalter und Diffusionsbarrieren.
Dieses Dokument behandelt folgende Formstückbaueinheiten: Bogen, T Stück, Reduzierstück, Kappe und Festpunktelement.
Dieses Dokument ist nur anzuwenden für gedämmte Formstückbaueinheiten, für den Dauerbetrieb mit Wasser bei verschiedenen Temperaturen (1 °C bis 30 °C) und einem Betriebsdruck von höchstens 25 bar.
Die Auslegung basiert auf einer erwarteten Lebensdauer von mindestens 50 Jahren bei Dauerbetrieb.
ANMERKUNG Bei der erwarteten Lebensdauer von 50 Jahren wird die Verwendung von aufbereitetem Wasser vorausgesetzt.
Réseaux d’eau glacée - Systèmes bloqués de tuyaux pour les réseaux d'eau glacée enterrés directement - Partie 2 : Assemblages de raccords manufacturés pour tubes de service en acier ou en plastique, isolation thermique en polyuréthane et tube de protection en polyéthylène
Le présent document spécifie les exigences, la conception et les méthodes d’essai pour des assemblages manufacturés de raccords bloqués préisolés thermiquement pour les réseaux de distribution d’eau glacée urbains enterrés directement, constitués d’un raccord de DN 15 à DN 1200, d’une isolation en mousse de polyuréthane rigide et d’un tube de protection en polyéthylène.
Le raccord préisolé peut également comprendre les éléments supplémentaires suivants : des câbles de mesure, des entretoises et les barrières anti diffusion.
Le présent document couvre les raccords préisolés suivants : coude, té, réducteur, bouchon, compensateur à usage unique et pièce d’ancrage.
Le présent document ne concerne que les assemblages de raccords préisolés, destinés à un usage continu avec de l’eau à diverses températures (de 1 °C à 30 °C) et à une pression de service maximale de 25 bar.
La conception est fondée sur une durée utile prévue en fonctionnement continu d’au moins 50 ans.
NOTE Une durée utile prévue de 50 ans présuppose l'utilisation d'eau traitée.
Cevi za daljinsko hlajenje - Spojeni enocevni sistemi za neposredno vkopana hladnovodna omrežja - 2. del: Tovarniško izdelana armatura iz jeklene ali plastične delovne cevi, poliuretanske toplotne izolacije in polietilenskega plašča
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-november-2021
Cevi za daljinsko hlajenje - Spojeni enocevni sistemi za neposredno vkopana
hladnovodna omrežja - 2. del: Tovarniško izdelana armatura iz jeklene ali plastične
delovne cevi, poliuretanske toplotne izolacije in polietilenskega plašča
District cooling pipes - Bonded single pipe systems for directly buried cold water
networks - Part 2: Factory made fitting assemblies of steel or plastic service pipe,
polyurethane thermal insulation and a casing of polyethylene
Fernkühlungsrohre - Werkmäßig gedämmte Verbundmantelrohrsysteme für direkt
erdverlegte Fernkältenetze - Teil 2: Werkmäßig gedämmte Verbund-Formstücke
bestehend aus Stahl-oder Plastik-Mediumrohr, Polyurethan-Wärmedämmung und
Außenmantel aus Polyethylen
Réseaux d’eau glacée - Systèmes bloqués de tuyaux pour les réseaux d'eau glacée
enterrés directement - Partie 2 : Assemblages de raccords manufacturés pour tubes de
service en acier ou en plastique, isolation thermique en polyuréthane et tube de
protection en polyéthylène
Ta slovenski standard je istoveten z: EN 17415-2:2021
ICS:
23.040.99 Drugi sestavni deli za Other pipeline components
cevovode
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 17415-2
EUROPEAN STANDARD
NORME EUROPÉENNE
September 2021
EUROPÄISCHE NORM
ICS 23.040.99
English Version
District cooling pipes - Bonded single pipe systems for
directly buried cold water networks - Part 2: Factory made
fitting assemblies of steel or plastic service pipe,
polyurethane thermal insulation and a casing of
polyethylene
Réseaux d'eau glacée - Systèmes bloqués de tuyaux Fernkälterohre - Einzelrohr-Verbundsysteme für
pour les réseaux d'eau glacée enterrés directement - direkt erdverlegte Fernkältenetze - Teil 2: Werkmäßig
Partie 2 : Assemblages de raccords manufacturés pour gefertigte Verbundformstücke, bestehend aus Stahl-
tubes de service en acier ou en plastique, isolation oder Kunststoff-Mediumrohr, einer Wärmedämmung
thermique en polyuréthane et tube de protection en aus Polyurethan und einer Ummantelung aus
polyéthylène Polyethylen
This European Standard was approved by CEN on 18 July 2021.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17415-2:2021 E
worldwide for CEN national Members.
Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 7
4 Requirements . 7
4.1 General requirements . 7
4.2 Service pipe parts . 7
4.3 Casing . 15
4.4 Polyurethane (PUR) foam thermal insulation . 15
4.5 Fitting assemblies . 15
4.6 Surveillance system . 19
5 Test methods . 19
5.1 General . 19
5.2 Test specimens . 20
5.3 Steel service pipe parts . 20
5.4 Plastics service pipe fittings . 21
5.5 Casing . 22
5.6 Polyurethane (PUR) foam thermal insulation . 22
5.7 Fitting assemblies . 22
5.8 Surveillance system . 23
6 Marking . 23
6.1 General . 23
6.2 Service pipe . 23
6.3 Casing . 24
6.4 Fitting assembly . 24
Annex A (informative) Guidelines for inspection and testing . 25
Annex B (informative) Procedures for casing welding . 29
Annex C (informative) Waste treatment and recycling . 33
Bibliography . 34
European foreword
This document (EN 17415-2:2021) has been prepared by Technical Committee CEN/TC 107 “Prefabricated
district heating and district cooling pipe system”, the secretariat of which is held by DS.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by March 2022, and conflicting national standards shall be withdrawn
at the latest by March 2022.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national standards body. A
complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North Macedonia,
Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
Introduction
Factory made bonded single pipe systems for directly buried district cooling networks are of common
technical usage. In order to ensure quality including product-related service life, to ensure safety in use,
economical energy usage and to facilitate comparability in the market, CEN/TC 107 decided to set up
standards for these products.
This document is one of a series of standards which form several parts of EN 17415, District cooling pipes –
Bonded single pipe systems for directly buried cold water networks:
— Part 1: Factory made pipe assembly of steel or plastic service pipe, polyurethane thermal insulation and a
casing of polyethylene;
— Part 2: Factory made fitting assemblies of steel or plastic service pipe, polyurethane thermal insulation and
a casing of polyethylene (this document);
— Part 3: Factory made steel valve assembly for steel or plastic service pipe, polyurethane thermal insulation
and a casing of polyethylene.
The other standards from CEN/TC 107 covering this subject are:
— EN 17414-1, District cooling pipes — Factory made flexible pipe systems — Part 1: Classification, general
requirements and test methods;
— EN 17414-2, District cooling pipes — Factory made flexible pipe systems — Part 2: Bonded system with
plastic service pipes; requirements and test methods;
— EN 17414-3, District cooling pipes — Factory made flexible pipe systems — Part 3: Non bonded system
with plastic service pipes; requirements and test methods;
— EN XXXXX-1 , District cooling pipes — Design and installation of thermal insulated bonded single and twin
pipe systems for directly buried cold water networks — Part 1: Design;
, District cooling pipes — Design and installation of thermal insulated bonded single and twin
— EN XXXXX-2
pipe systems for directly buried cold water networks — Part 2: Installation;
— EN 489-1, District heating pipes — Bonded single and twin pipe systems for buried hot water networks —
Part 1: Joint casing assemblies and thermal insulation for hot water networks in accordance with
EN 13941-1;
— EN 14419, District heating pipes — Bonded single and twin pipe systems for directly buried hot water
networks — Surveillance systems.
Waste management and recycling of materials is dealt with in Annex C.
Under development.
1 Scope
This document specifies requirements, design and test methods for factory made thermally insulated
bonded fitting assemblies for directly buried district cooling distribution systems, comprising a service
fitting from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene.
The fitting assembly can also include the following additional elements: measuring wires, spacers and
diffusion barriers.
This document covers the following fitting assemblies: bend, tee, reducer, cap and anchor.
This document applies only to insulated fitting assemblies, for continuous operation with water at various
temperatures (1 to 30) °C and a maximum operation pressure of 25 bar.
The design is based on an expected service life with continuous operation of a minimum 50 years.
NOTE An expected service life of 50 years presupposes that treated water is used.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 10204, Metallic products - Types of inspection documents
EN 10253-2, Butt-welding pipe fittings - Part 2: Non alloy and ferritic alloy steels with specific inspection
requirements
EN 12201-2, Plastics piping systems for water supply, and for drainage and sewerage under pressure —
Polyethylene (PE) — Part 2: Pipes
EN 12201-3, Plastics piping systems for water supply, and for drainage and sewerage under pressure —
Polyethylene (PE) — Part 3: Fittings
EN 12201-5, Plastics piping systems for water supply, and for drainage and sewerage under pressure -
Polyethylene (PE) - Part 5: Fitness for purpose of the system
EN 12814-1, Testing of welded joints of thermoplastics semi-finished products - Part 1: Bend test
EN 13018, Non-destructive testing - Visual testing - General principles
EN 13067, Plastics welding personnel - Qualification of welders - Thermoplastics welded assembli
...