Standard Specification for Track-Resistant Crosslinked Polyethylene Insulation for Wire and Cable, 90 °C Operation

ABSTRACT
This specification covers track-resistant black crosslinked polyethylene insulation for conducting wires and cables operating continuously at a specified conductor temperature. The insulation is suitable for use for power transmission in overhead spaced-line service that is exposed to sunlight and other atmospheric environments. The prescribed tests cannot be performed unless the insulation is formed around a conductor, but these are done solely to determine the insulation properties and not to test the conductor or completed cable. Each test sample should be subjected to an ac or dc voltage withstand test at voltages that are based on the nominal thickness of the insulation and should comply with the required values for aging, heat distortion, cold blend, U-bend discharge, track resistance, tensile strength, elongation at rupture, track resistance, and surface resistivity.
SCOPE
1.1 This specification covers a track-resistant crosslinked polyethylene insulation, the base polymer which consists substantially of polyethylene or its copolymers. This insulation shall be carbon black pigmented, or colored and suitably protected to enable UV stability.  
1.2 This type of insulation is considered suitable for use on wire or cable that will be used for continuous operation at conductor temperatures up to 90 °C.  
1.3 This insulation is suitable for use on wire or in cable used for power transmission in overhead spaced-line service, installed at temperatures above −25° and exposed to sunlight and other atmospheric environments between −55 and +90 °C.  
1.4 In many instances, the insulation cannot be tested unless it has been formed around a conductor. Therefore, tests done on insulated wire in this standard are solely to determine the relevant property of the insulation and not to test the conductor or completed cable.  
1.5 Whenever two sets of values are presented, in different units, the values in the first set are to be regarded as standard. The values given in parentheses are mathematical conversions that are provided for information only and are not considered standard.  
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
31-Jul-2020
Current Stage
Ref Project

Buy Standard

Technical specification
ASTM D3555-20e1 - Standard Specification for Track-Resistant Crosslinked Polyethylene Insulation for Wire and Cable, 90 °C Operation
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
´1
Designation:D3555 −20
Standard Specification for
Track-Resistant Crosslinked Polyethylene Insulation for
1
Wire and Cable, 90 °C Operation
This standard is issued under the fixed designation D3555; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—Editorially corrected Table 1 and 4.1 in October 2020.
1. Scope* 2. Referenced Documents
2
1.1 This specification covers a track-resistant crosslinked 2.1 ASTM Standards:
polyethylene insulation, the base polymer which consists D470Test Methods for Crosslinked Insulations and Jackets
substantiallyofpolyethyleneoritscopolymers.Thisinsulation for Wire and Cable
shall be carbon black pigmented, or colored and suitably D1711Terminology Relating to Electrical Insulation
protected to enable UV stability. D2132Test Method for Dust-and-Fog Tracking and Erosion
Resistance of Electrical Insulating Materials
1.2 This type of insulation is considered suitable for use on
D2765Test Methods for Determination of Gel Content and
wire or cable that will be used for continuous operation at
Swell Ratio of Crosslinked Ethylene Plastics
conductor temperatures up to 90 °C.
2.2 ICEA Standard:
1.3 This insulation is suitable for use on wire or in cable
ICEAT-28-562Test Method for Measurement of Hot Creep
3
used for power transmission in overhead spaced-line service,
of Polymeric Insulations
installed at temperatures above −25° and exposed to sunlight
and other atmospheric environments between −55 and +90 °C. 3. Terminology
1.4 Inmanyinstances,theinsulationcannotbetestedunless 3.1 Definitions:
ithasbeenformedaroundaconductor.Therefore,testsdoneon 3.1.1 Fordefinitionsoftermsusedinthisspecification,refer
insulated wire in this standard are solely to determine the to Terminology D1711.
relevantpropertyoftheinsulationandnottotesttheconductor 3.2 Definitions of Terms Specific to This Standard:
or completed cable. 3.2.1 aging, (act of), n—exposure of materials to air at a
temperature of 121 °C for 168 h.
1.5 Whenever two sets of values are presented, in different
units, the values in the first set are to be regarded as standard.
4. Physical Properties
The values given in parentheses are mathematical conversions
4.1 When tested for physical and aging requirements, heat
that are provided for information only and are not considered
distortion,coldbend,U-benddischarge,surfaceresistivity,and
standard.
track resistance in accordance with Test Methods D470, the
1.6 This international standard was developed in accor-
track-resistant crosslinked polyethylene insulation shall meet
dance with internationally recognized principles on standard-
therequirementsspecifiedinTable1.Theinsulationistomeet
ization established in the Decision on Principles for the
the requirements for percent hot creep and hot set specified in
Development of International Standards, Guides and Recom-
Table 1. The test is to be performed in accordance with ICEA
mendations issued by the World Trade Organization Technical
T-28-562. Only in case of dispute, the solvent extraction (gel
Barriers to Trade (TBT) Committee.
contentandswellratio)testinTestMethodsD2765istobethe
1 2
This specification is under the jurisdiction of ASTM Committee D09 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Electrical and Electronic Insulating Materials and is the direct responsibility of contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Subcommittee D09.07 on Electrical Insulating Materials. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved Aug. 1, 2020. Published September 2020. Originally the ASTM website.
3
approved in 1977. Last previous edition approved in 2018 as D3555–07(2018). Available from The Insulated Cable Engineers Association, Inc. (ICEA), P.O.
DOI: 10.1520/D3555-20E01. Box 1568, Carrollton, GA 30112, http://www.icea.net.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
´1
D3555−20
TABLE 1 Physical Requirements for Track-Resistant Crosslinked
Polyethylene Insulation†
Physical requirements (unaged):
Tensile strength, min, psi (MPa) 1800 (12.4)
Elongation at rupture, min, % 250
Physical requirements
(after aging in an air oven at 121±1°Cfor 168 h):
Tensile strength, min, % of unaged value 75
...

Questions, Comments and Discussion