Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods

IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating.
This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions.
[1] Numbers in square brackets refer to the Bibliography.

Parafoudres basse tension - Partie 361: Transformateurs d’isolement contre les surtensions (SIT) connectés aux réseaux de distribution basse tension - Exigences et méthodes d’essai

IEC 61643-361: 2026 s’applique aux transformateurs d’isolement contre les surtensions (SIT) destinés à atténuer les surtensions et à être connectés à des circuits d’alimentation 50/60 Hz et à des équipements d’une tension assignée allant jusqu’à 1 000 V en valeur efficace. Le présent document couvre les performances en matière de surtension et d’atténuation des SIT dont la tension de tenue aux chocs atteint au moins 30 kV, et fournit des méthodes normalisées d’essai et d’évaluation.
Le présent document couvre les paramètres liés aux surtensions, mais ne traite pas des essais et paramètres types des transformateurs couverts par la série IEC 61558 [13][1]. Le présent document ne couvre pas non plus le fonctionnement d’un SIT dans des conditions de surtension due à la foudre en mode différentiel.
[1] Les chiffres entre crochets renvoient à la Bibliographie.

General Information

Status
Published
Publication Date
27-Apr-2026
Drafting Committee
JWG 5 - TC 37/SC 37B/JWG 5
Current Stage
PPUB - Publication issued
Start Date
28-Apr-2026
Completion Date
22-May-2026

Overview

IEC 61643-361:2026, published by the International Electrotechnical Commission (IEC), specifies requirements and test methods for surge isolation transformers (SITs) used in low-voltage power distribution systems. This international standard focuses on SITs intended for surge mitigation, supporting safe connection to 50/60 Hz power circuits and equipment rated up to 1,000 V RMS. It emphasizes surge-related performance-particularly impulse withstand voltage (minimum 30 kV)-and presents standardized methods for rating and testing SITs.

Surge isolation transformers are essential components for electrical protection, as they greatly attenuate transient overvoltages and support the resilience of electrical infrastructures against lightning or switching surges. This standard is vital for manufacturers, electrical designers, and end users seeking reliable surge protection in low-voltage networks.

Key Topics

  • Scope and Applicability

    • Applies to SITs for power circuits up to 1,000 V RMS and 50/60 Hz operation
    • Focuses on SITs with impulse withstand voltage of at least 30 kV
    • Excludes general transformer tests covered by IEC 61558 and differential mode lightning surge operation
  • Surge Isolation Transformer (SIT) Performance

    • Details electrical insulation requirements between primary and secondary windings
    • Specifies the need for enhanced insulation and the use of an electric screen (ES) to attenuate common-mode surges
    • Describes how SITs are used alongside surge protective devices (SPDs)
  • Testing and Evaluation

    • Insulation resistance testing (minimum 100 MΩ at DC 500 V)
    • Power frequency withstand voltage testing (typically 10 kV or higher for SITs with 30 kV impulse rating)
    • Impulse withstand voltage tests using 1,2/50 µs voltage waveforms to ensure robust surge performance
  • Environmental and Installation Conditions

    • Covers acceptable temperature (−25 °C to 40 °C), humidity (5% to 95%), and altitude (≤1,000 m) operating ranges
    • Notes requirements for extended ranges based on agreement between manufacturer and user
    • Discusses the impact of environmental factors like altitude on insulation breakdown

Applications

SITs specified in IEC 61643-361:2026 are used in a wide array of practical settings where surge protection is critical:

  • Industrial and Commercial Buildings

    • For protecting sensitive equipment from transient overvoltages in low-voltage distribution systems
    • Forming integral parts of lightning protection zones by isolating critical loads
    • Used in combination with SPDs to enhance overall surge suppression
  • Telecommunication and Data Centers

    • Safeguarding mission-critical communication infrastructure from common-mode surges
    • Ensuring high reliability and continuity of service
  • Infrastructure Installations

    • Power supply systems in smart grids, transportation, and renewable energy installations
    • Protecting devices and facilities where exposure to lightning-induced surges is likely
  • Standardization and Product Certification

    • Provides a uniform basis for type testing, specification, and compliance verification of SITs
    • Facilitates consistent international procurement and quality assurance

Related Standards

IEC 61643-361:2026 aligns with and references several key international standards, including:

  • IEC 61643 Series: General framework for low-voltage surge protective devices, including SITs and SPDs
  • IEC 61558 Series: General safety requirements for transformers (not specific to surge performance)
  • IEC 60068-1: Environmental testing fundamentals
  • IEC 60664-1: Principles of insulation coordination for equipment within low-voltage systems
  • IEC 61643-12: Selection and application principles for SPDs
  • IEC 62305-4: Lightning protection for electrical and electronic systems in structures

By adhering to IEC 61643-361:2026, manufacturers and system designers can ensure high-performance surge isolation and test compliance in demanding electrical environments. This standard supports improved operational safety, equipment reliability, and effective surge management in modern low-voltage power systems.

Buy Documents

Standard

IEC 61643-361:2026 - Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods

ISBN:978-2-8327-1224-5
Release Date:28-Apr-2026
English language (18 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 61643-361:2026 - Parafoudres basse tension - Partie 361: Transformateurs d’isolement contre les surtensions (SIT) connectés aux réseaux de distribution basse tension - Exigences et méthodes d’essai

ISBN:978-2-8327-1224-5
Release Date:28-Apr-2026
French language (19 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC 61643-361:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Low-voltage surge protective devices - Part 361: Surge isolation transformers (SITs) connected to low-voltage distribution system – Requirements and test methods". This standard covers: IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating. This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions. [1] Numbers in square brackets refer to the Bibliography.

IEC 61643-361:2026 applies to surge isolation transformers (SITs) dedicated to surge mitigation and for connection to 50/60 Hz power circuits and equipment rated up to 1 000 V RMS. This document covers the surge and mitigation performance of SITs with an impulse withstand voltage performance of at least 30 kV, and provides standard methods for testing and rating. This document covers surge-related parameters but does not address typical transformer tests and parameters covered by the IEC 61558 series [13][1]. This document also does not cover SIT operation under differential mode lightning surge conditions. [1] Numbers in square brackets refer to the Bibliography.

IEC 61643-361:2026 is classified under the following ICS (International Classification for Standards) categories: 29.180 - Transformers. Reactors. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61643-361:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


IEC 61643-361 ®
Edition 1.0 2026-04
INTERNATIONAL
STANDARD
Low-voltage surge protective devices -
Part 361: Surge isolation transformers (SITs) connected to low-voltage
distribution system - Requirements and test methods
ICS 29.180  ISBN 978-2-8327-1224-5

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or
by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either
IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC copyright
or have an enquiry about obtaining additional rights to this publication, please contact the address below or your local
IEC member National Committee for further information.

IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.

IEC publications search - IEC Products & Services Portal - products.iec.ch
webstore.iec.ch/advsearchform Discover our powerful search engine and read freely all the
The advanced search enables to find IEC publications by a
publications previews, graphical symbols and the glossary.
variety of criteria (reference number, text, technical With a subscription you will always have access to up to date
committee, …). It also gives information on projects, content tailored to your needs.
replaced and withdrawn publications.

Electropedia - www.electropedia.org
IEC Just Published - webstore.iec.ch/justpublished The world's leading online dictionary on electrotechnology,
Stay up to date on all new IEC publications. Just Published containing more than 22 500 terminological entries in English
details all new publications released. Available online and and French, with equivalent terms in 25 additional languages.
once a month by email. Also known as the International Electrotechnical Vocabulary
(IEV) online.
IEC Customer Service Centre - webstore.iec.ch/csc
If you wish to give us your feedback on this publication or
need further assistance, please contact the Customer
Service Centre: sales@iec.ch.
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
1 Scope . 6
2 Normative references . 6
3 Terms, definitions and symbols . 6
3.1 Terms and definitions . 6
3.2 Symbols . 8
3.3 Abbreviated terms and acronyms . 9
4 Service condition . 9
4.1 Temperature range . 9
4.2 Humidity range . 9
4.3 Altitude and air pressure . 9
5 SIT surge condition . 10
5.1 General . 10
5.2 SITs surge mitigation . 10
6 Electrical requirements . 11
6.1 General . 11
6.2 Insulation resistance . 11
6.3 Power frequency withstand voltage . 11
6.4 Impulse withstand voltage . 12
7 Type tests . 12
7.1 General . 12
7.2 Test condition . 12
7.3 Sample preparation. 12
7.4 Insulation resistance . 13
7.5 Power frequency withstand voltage . 13
7.6 Impulse withstand voltage . 14
Annex A (informative) 1,2/50 impulse . 17
Bibliography . 18

Figure 1 – Symbol of SIT for single phase low-voltage power system (single-line
diagram) . 8
Figure 2 – Symbol of SIT for single phase low-voltage power system (multi-line
diagram) . 8
Figure 3 – SITs under common mode surge condition . 11
Figure 4 – Sample preparation . 13
Figure 5 – Test circuit of insulation resistance . 13
Figure 6 – Power frequency withstand voltage test circuit . 14
Figure 7 – Construction of pass/fail template from the 1,2/50 open-circuit waveform . 15
Figure 8 – Pass/fail template and test waveforms . 15
Figure 9 – Impulse withstand voltage test circuit . 16
Figure A.1 – 1,2/50 time periods and voltage amplitudes . 17

Table 1 – List of abbreviations and acronyms used in this standard . 9
Table 2 – Conditions used for test . 12
Table A.1 – 1,2/50 voltage impulse generator parameters . 17

INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
Low-voltage surge protective devices -
Part 361: Surge isolation transformers (SITs) connected
to low-voltage distribution system - Requirements and test methods

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
IEC 61643-361 has been prepared by subcommittee 37B: Components for low-voltage surge
protection, of IEC technical committee 37: Surge arresters. It is an International Standard.
The text of this International Standard is based on the following documents:
Draft Report on voting
37B/267/FDIS 37B/270/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
A list of all parts in the IEC 61643 series, published under the general title Low-voltage surge
protective devices, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
– reconfirmed,
– withdrawn, or
– revised.
INTRODUCTION
This part of IEC 61643 covers surge isolation transformers (SITs) whose rated impulse
withstands voltage coordinates with the expected surge environment of the installation location.
This type of surge protective component (SPC) isolates and attenuates transient voltage in
conjunction with current diverting components (or SPDs).
SITs are a product with specific enhanced insulation layers between the primary and secondary
windings and an electric screen (ES) inserted between primary and secondary windings. With
these ES and specific enhanced insulation layers, the surge that appears between the primary
winding and earth (common-mode) is greatly attenuated and appears between the secondary
winding and earth. SITs are products with a particularly improved impulse withstand voltage
compared to ordinary isolating transformers.
It is essential that SITs are protected by an appropriate SPD at their primary side, to avoid any
damage to the SIT itself. SITs are intended to be used in surge protection to establish lightning
protection zones.
1 Scope
This part of IEC 61643 applies to surge isolation transformers (SITs) dedicated to surge
mitigation and for connection to 50/60 Hz power circuits and equipment rated up to
1 000 V RMS. This document covers the surge and mitigation performance of SITs with an
impulse withstand voltage performance of at least 30 kV, and provides standard methods for
testing and rating.
This document covers surge-related parameters but does not address typical transformer tests
and parameters covered by the IEC 61558 series [13] . This document also does not cover SIT
operation under differential mode lightning surge conditions.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60068-1, Environmental testing - Part 1: General and guidance
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
– IEC Electropedia: available at https://www.electropedia.org/
– ISO Online browsing platform: available at https://www.iso.org/obp
3.1.1
surge isolation transformer for power
SIT
isolation transformer which has high impulse withstand voltage with/without electric screen
between input and output windings
Note 1 to entry: SITs for power systems require electric screen.
[SOURCE: IEC 61643-351:2016 [8], 3.1.1, modified – the alternative without electric screen has
been removed.]
3.1.2
electric screen
electric shield (US)
screen of conductive material intended to reduce the penetration of an electric field into a given
region
[SOURCE: IEC 60050-151:2001 [9], 151-13-10]
___________
Numbers in square brackets refer to the Bibliography.
3.1.3
clearance
shortest distance in air between two conductive parts
[SOURCE: IEC 60664-1:2020 [10], 3.1.4]
3.1.4
creepage distance
shortest distance along the surface of a solid insulating material between two conductive parts
[SOURCE: IEC 60050-151:2001 [9], 151-15-50]
3.1.5
impulse withstand voltage
highest peak value of impulse voltage of specified form and polarity which does not cause
breakdown of insulation under specified conditions
[SOURCE: IEC 60664-1:2020 [10], 3.1.15]
3.1.6
electric insulation
part of an electrotechnical product which separates the conducting parts at different electrical
potentials during operation or insulates such parts from the surroundings
[SOURCE: IEC 60664-1:2020 [10], 3.1.28]
3.1.7
insulation resistance
resistance under specified condition between two conductive elements separated by insulation
materials
[SOURCE: IEC 60050-151:2001 [9], 151-15-43]
3.1.8
power frequency withstand voltage
RMS value of sinusoidal power frequency voltage that the insulation of the given equipment can
withstand during tests made under specified conditions and for a specified duration
[SOURCE: IEC 60050-614:2016 [11], 614-03-22]
3.1.9
electric breakdown
failure of insulation under electric stress when the discharge completely bridges the insulation,
thus reducing the voltage between the electrodes almost to zero
[SOURCE: IEC 60664-1:2020 [10], 3.1.44]
3.1.10
virtual front time
T
virtual parameter defined as 1/0,6 times the interval T between the
AB
instants when the impulse is 30 % and 90 % of the peak value on the test voltage curve
SEE: Figure A.1.
[SOURCE: IEC 60060-1:2025 [1], 3.8.18, modified – “virtual” has been added to the term, the
note and figure have been deleted and a reference to Figure A.1 added.]
3.1.11
virtual origin
O
...


IEC 61643-361 ®
Edition 1.0 2026-04
NORME
INTERNATIONALE
Parafoudres basse tension -
Partie 361: Transformateurs d’isolement contre les surtensions (SIT) connectés
aux réseaux de distribution basse tension - Exigences et méthodes d’essai
ICS 29.180  ISBN 978-2-8327-1224-5

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.

IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.

Recherche de publications IEC -  IEC Products & Services Portal - products.iec.ch
webstore.iec.ch/advsearchform Découvrez notre puissant moteur de recherche et consultez
La recherche avancée permet de trouver des publications gratuitement tous les aperçus des publications, symboles
IEC en utilisant différents critères (numéro de référence, graphiques et le glossaire. Avec un abonnement, vous aurez
texte, comité d’études, …). Elle donne aussi des toujours accès à un contenu à jour adapté à vos besoins.
informations sur les projets et les publications remplacées
ou retirées. Electropedia - www.electropedia.org
Le premier dictionnaire d'électrotechnologie en ligne au
IEC Just Published - webstore.iec.ch/justpublished monde, avec plus de 22 500 articles terminologiques en
Restez informé sur les nouvelles publications IEC. Just anglais et en français, ainsi que les termes équivalents
Published détaille les nouvelles publications parues. dans 25 langues additionnelles. Egalement appelé
Disponible en ligne et une fois par mois par email. Vocabulaire Electrotechnique International (IEV) en ligne.

Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-
nous: sales@iec.ch.
SOMMAIRE
AVANT-PROPOS . 3
INTRODUCTION . 5
1 Domaine d’application . 6
2 Références normatives . 6
3 Termes, définitions et symboles . 6
3.1 Termes et définitions. 6
3.2 Symboles . 8
3.3 Abréviations et acronymes . 9
4 Conditions de service . 9
4.1 Plage de températures . 9
4.2 Plage de taux d’humidité . 9
4.3 Altitude et pression atmosphérique . 10
5 Condition de surtension d'un SIT . 10
5.1 Généralités . 10
5.2 Atténuation des surtensions dans un SIT . 11
6 Exigences électriques . 12
6.1 Généralités . 12
6.2 Résistance d'isolement. 12
6.3 Tension de tenue à fréquence industrielle . 12
6.4 Tension de tenue aux chocs . 12
7 Essais de type . 13
7.1 Généralités . 13
7.2 Conditions d'essai . 13
7.3 Préparation de l'échantillon. 13
7.4 Résistance d'isolement. 13
7.5 Tension de tenue à fréquence industrielle . 14
7.6 Tension de tenue aux chocs . 15
Annexe A (informative) Tension de choc 1,2/50 . 18
Bibliographie . 19

Figure 1 – Symbole du SIT pour un réseau d’alimentation monophasé basse tension
(schéma unifilaire) . 9
Figure 2 – Symbole du SIT pour un réseau d’alimentation monophasé basse tension
(schéma multifilaire) . 9
Figure 3 – SIT en condition de surtension en mode commun . 11
Figure 4 – Préparation de l'échantillon . 13
Figure 5 – Circuit d'essai de la résistance d'isolement . 14
Figure 6 – Circuit d’essai de tension de tenue à fréquence industrielle . 15
Figure 7 – Construction du modèle de réussite/échec à partir de la forme d’onde en
circuit ouvert 1,2/50 . 16
Figure 8 – Modèle de réussite/échec et formes d'onde d'essai . 16
Figure 9 – Circuit d’essai de tension de tenue aux chocs . 17
Figure A.1 – Périodes de temps et amplitudes de tension 1,2/50 . 18

Tableau 1 – Liste des abréviations et des acronymes utilisés dans la présente norme . 9
Tableau 2 – Conditions utilisées pour l’essai . 13
Tableau A.1 – Paramètres du générateur de tension de choc 1,2/50 . 18

COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
Parafoudres basse tension -
Partie 361: Transformateurs d'isolement contre les surtensions (SIT)
connectés aux réseaux de distribution basse tension -
Exigences et méthodes d’essai
AVANT-PROPOS
1) La Commission Électrotechnique Internationale (IEC) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de l’IEC). L’IEC a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. À cet effet, l’IEC – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de l’IEC"). Leur élaboration est confiée à des comités d'études, aux
travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec l’IEC, participent également aux
travaux. L’IEC collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de l’IEC concernant les questions techniques représentent, dans la mesure du
possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de l’IEC intéressés
sont représentés dans chaque comité d’études.
3) Les Publications de l’IEC se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de l’IEC. Tous les efforts raisonnables sont entrepris afin que l’IEC
s'assure de l'exactitude du contenu technique de ses publications; l’IEC ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de l’IEC s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de l’IEC dans leurs publications nationales
et régionales. Toutes divergences entre toutes Publications de l’IEC et toutes publications nationales ou
régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) L’IEC elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de l’IEC. L’IEC n'est responsable d'aucun des services effectués par les organismes de certification
indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à l’IEC, à ses administrateurs, employés, auxiliaires ou mandataires,
y compris ses experts particuliers et les membres de ses comités d'études et des Comités nationaux de l’IEC,
pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre dommage de quelque
nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais de justice) et les dépenses
découlant de la publication ou de l'utilisation de cette Publication de l’IEC ou de toute autre Publication de l’IEC,
ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L'IEC attire l'attention sur le fait que la mise en application du présent document peut entraîner l'utilisation d'un
ou de plusieurs brevets. L'IEC ne prend pas position quant à la preuve, à la validité et à l'applicabilité de tout
droit de brevet revendiqué à cet égard. À la date de publication du présent document, l'IEC n'a pas reçu
notification qu'un ou plusieurs brevets pouvaient être nécessaires à sa mise en application. Toutefois, il y a lieu
d'avertir les responsables de la mise en application du présent document que des informations plus récentes
sont susceptibles de figurer dans la base de données de brevets, disponible à l'adresse https://patents.iec.ch.
L'IEC ne saurait être tenue pour responsable de ne pas avoir identifié de tels droits de brevets.
L’IEC 61643-361 a été établie par le sous-comité 37B: Composants pour parafoudres basse
tension, du comité d'études 37 de l'IEC: Parafoudres. Il s'agit d'une Norme internationale.
Le texte de cette Norme internationale est issu des documents suivants:
Projet Rapport de vote
37B/267/FDIS 37B/270/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à son approbation.
La langue employée pour l'élaboration de cette Norme internationale est l'anglais.
Ce document a été rédigé selon les Directives ISO/IEC, Partie 2, il a été développé selon les
Directives ISO/IEC, Partie 1 et les Directives ISO/IEC, Supplément IEC, disponibles sous
www.iec.ch/members_experts/refdocs. Les principaux types de documents développés par
l'IEC sont décrits plus en détail sous www.iec.ch/publications.
Une liste de toutes les parties de la série IEC 61643, publiées sous le titre général Parafoudres
basse tension, se trouve sur le site web de l’IEC.
Le comité a décidé que le contenu de ce document ne sera pas modifié avant la date de stabilité
indiquée sur le site web de l'IEC sous webstore.iec.ch dans les données relatives au document
recherché. À cette date, le document sera
– reconduit,
– supprimé, ou
– révisé.
INTRODUCTION
La présente partie de l'IEC 61643 couvre les transformateurs d’isolement contre les surtensions
(SIT, surge isolation transformers) dont la tension assignée de tenue aux chocs correspond à
l’environnement de surtension prévu pour le lieu de l’installation. Ce type de composant de
protection contre les surtensions (SPC, surge protective component) isole et atténue les
tensions transitoires en conjonction avec des composants de dérivation du courant (ou des
parafoudres).
Les SIT sont des produits comportant des couches d’isolation renforcées spécifiques entre les
enroulements primaire et secondaire et un écran électrique (ES, electric screen) inséré entre
les enroulements primaire et secondaire. Avec cet ES et ces couches d’isolation renforcées
spécifiques, la surtension qui apparaît entre l’enroulement primaire et la terre (mode commun)
est fortement atténuée et apparaît entre l’enroulement secondaire et la terre. Les SIT sont des
produits avec une tension de tenue aux chocs particulièrement améliorée par rapport aux
transformateurs d'isolement ordinaires.
Pour éviter qu’ils ne soient endommagés, il est essentiel que les SIT soient protégés par un
parafoudre approprié sur leur côté primaire. Les SIT sont destinés à être utilisés dans la
protection contre les surtensions afin d’établir des zones de protection contre la foudre.

1 Domaine d’application
La présente partie de l’IEC 61643 s’applique aux transformateurs d’isolement contre les
surtensions (SIT) destinés à atténuer les surtensions et à être connectés à des circuits
d’alimentation 50/60 Hz et à des équipements d’une tension assignée allant jusqu’à 1 000 V en
valeur efficace. Le présent document couvre les performances en matière de surtension et
d’atténuation des SIT dont la tension de tenue aux chocs atteint au moins 30 kV, et fournit des
méthodes normalisées d’essai et d’évaluation.
Le présent document couvre les paramètres liés aux surtensions, mais ne traite pas des essais
et paramètres types des transformateurs couverts par la série IEC 61558 [13] . Le présent
document ne couvre pas non plus le fonctionnement d’un SIT dans des conditions de surtension
due à la foudre en mode différentiel.
2 Références normatives
Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie
de leur contenu, des exigences du présent document. Pour les références datées, seule
l'édition citée s'applique. Pour les références non datées, la dernière édition du document de
référence s'applique (y compris les éventuels amendements).
IEC 60068-1, Essais d’environnement - Partie 1: Généralités et lignes directrices
3 Termes, définitions et symboles
3.1 Termes et définitions
Pour les besoins du présent document, les termes et définitions suivants s’appliquent.
L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées
en normalisation, consultables aux adresses suivantes:
– IEC Electropedia: disponible à l'adresse https://www.electropedia.org/
– ISO Online browsing platform: disponible à l'adresse https://www.iso.org/obp
3.1.1
transformateur d'isolement contre les surtensions pour l'alimentation
SIT
transformateur d'isolement ayant une tension élevée de tenue aux chocs avec/sans écran
électrique entre les enroulements d'entrée et de sortie
Note 1 à l'article: Les SIT pour les réseaux d'alimentation exigent un écran électrique.
Note 2 à l'article: L’abréviation "SIT" est dérivée du terme anglais développé correspondant "surge isolation
transformer".
[SOURCE: IEC 61643-351:2016 [8], 3.1.1, modifié – l'alternative sans écran électrique a été
supprimée.]
___________
Les chiffres entre crochets renvoient à la Bibliographie.
3.1.2
écran électrique
écran en matériau conducteur destiné à réduire la pénétration d'un champ électrique dans une
région déterminée
[SOURCE: IEC 60050-151:2001 [9], 151-13-10]
3.1.3
distance d’isolement
plus petite distance dans l’air entre deux parties conductrices
[SOURCE: IEC 60664-1:2020 [10], 3.1.4]
3.1.4
ligne de fuite
distance la plus courte, le long de la surface d'un isolant solide, entre deux parties conductrices
[SOURCE: IEC 60050-151:2001 [9], 151-15-50]
3.1.5
tension de tenue aux chocs
valeur de crête la plus élevée d'une tension de choc, de forme et de polarité spécifiées, qui ne
provoque pas de claquage dans des conditions d'essai spécifiées
[SOURCE: IEC 60664-1:2020 [10], 3.1.15]
3.1.6
isolant électrique
partie d'un produit électrotechnique qui sépare les pièces conductrices portées à des potentiels
différents au cours du fonctionnement ou isole ces pièces de l’environnement
[SOURCE: IEC 60664-1:2020 [10], 3.1.28]
3.1.7
résistance d'isolement
résistance, mesurée dans des conditions spécifiées, entre deux éléments conducteurs séparés
par des isolants
[SOURCE: IEC 60050-151:2001 [9], 151-15-43]
3.1.8
tension de tenue à fréquence industrielle
valeur efficace de la tension sinusoïdale à fréquence industrielle que l’isolation du matériel
considéré peut supporter lors d’essais faits dans des conditions spécifiées et pendant une
durée spécifiée
[SOURCE: IEC 60050-614:2016 [11], 614-03-22]
3.1.9
claquage électrique
défaillance de l'isolation en cas de contrainte électrique lorsque la décharge court-circuite
complètement l'isolation, réduisant pratiquement à zéro la tension entre les électrodes
[SOURCE: IEC 60664-1:2020 [10], 3.1.44]
3.1.10
durée conventionnelle du front
T
paramètre virtuel défini comme étant égal à 1/0,6 fois l'intervalle de
temps T entre les instants où la tension atteint 30 % et 90 % de la valeur de crête sur la
AB
courbe de la tension d'essai
VOIR: Figure A.1.
[SOURCE: IEC 60060-1:2025 [1], 3.8.18, modifié – le mot "conventionnelle" a été ajouté au
terme, la note et la figure ont été supprimées et une référence à la Figure A.1 a été ajoutée.]
3.1.11
origine virtuelle
O
, celui qui
instant qui précède d'une durée de 0,3 T
correspond au point A sur la courbe de la tension d'essai
VOIR: Figure A.1.
[SOURCE: IEC 60060-1:2025 [1], 3.8.19, modifié – les Notes 1 et 2 ont été supprimées et une
référence à la Figure A.1 a été ajoutée.]
3.1.12
durée conventionnelle jusqu'à mi-valeur
T
intervalle de temps entre l'instant de l'origine virtuelle O et l'instant où la tension ou le courant
a diminué jusqu'à atteindre la moitié de sa valeur de crête
VOIR: Figure A.1.
3.1.13
énoncé de la forme d’un choc
)
combinaison de deux valeurs, la première représentant la durée conventionnelle du front (T
et la seconde la durée convent
...

Questions, Comments and Discussion