EN 16211:2024
(Main)Ventilation for buildings - Measurement of air flow rates on site - Methods
Ventilation for buildings - Measurement of air flow rates on site - Methods
This document specifies methods for the measurement of air flow rates on site. It provides a description of the air flow rate measurement methods and how measurements are performed within the margins of stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight duct, uniform velocity profile) to achieve the stipulated measurement uncertainties.
The methods for measuring the air flow rate inside ducts do not apply to:
- ducts that are not circular or rectangular (e.g. oblong ducts);
- flexible ducts.
Lüftung von Gebäuden - Luftvolumenstrommessung in Lüftungssystemen - Verfahren
Dieses Dokument legt Verfahren für die Messung von Luftvolumenströmen vor Ort fest. Es enthält eine Beschreibung der Verfahren für die Messung von Luftvolumenströmen und wie Messungen innerhalb der für das Verfahren vorgeschriebenen Toleranzen durchgeführt werden. Es enthält die notwendigen Messbedingungen (z. B. Länge der geraden Luftleitung, gleichmäßiges Geschwindigkeitsprofil) zur Erreichung der vorgegebenen Messunsicherheiten.
Die Verfahren zur Messung des Luftvolumenstroms in Luftleitungen sind nicht anwendbar für:
Luftleitungen, die nicht kreisförmig oder rechteckig sind (z B. ovale Luftleitungen);
flexible Luftleitungen.
Ventilation des bâtiments - Mesurages des débits d'air sur site - Méthodes
Le présent document spécifie des méthodes pour le mesurage des débits d’air sur site. Il fournit une description des méthodes de mesurage de débit d’air et indique la façon dont les mesurages sont réalisés dans les marges d’incertitude de la méthode stipulée. Il donne les conditions de mesure nécessaires (par exemple, longueur de conduit droit, profil de vitesse uniforme) pour atteindre les incertitudes de mesure stipulées.
Les méthodes de mesure du débit d’air dans les conduits ne s’appliquent pas:
- aux conduits qui ne sont pas circulaires ou rectangulaires (par exemple, conduits oblongs);
- aux conduits flexibles.
Prezračevanje stavb - Meritve pretoka zraka v sistemu prezračevanja - Metode
Ta dokument določa metode za merjenje pretoka zraka v sistemu prezračevanja. Opisuje metode za merjenje pretoka zraka in način izvajanja meritev znotraj mejnih vrednosti negotovosti predpisane metode. Navaja tudi merilne pogoje (npr. dolžina ravne cevi in enoten hitrostni profil), potrebne za doseganje predpisanih merilnih negotovosti.
Metode za merjenje pretoka zraka v zračnih kanalih se ne uporablja za:
– kanale, ki niso krožne in pravokotne oblike (npr. podolgovati kanali);
– gibke kanale.
General Information
Relations
Overview
EN 16211:2024 / EN 16211:2024 specifies accepted methods for the on‑site measurement of air flow rates in ventilation systems for buildings. It describes measurement techniques, required instrumentation and the measurement conditions (for example straight duct length and uniform velocity profile) needed to achieve the stipulated method uncertainties. The standard consolidates previously separate methods (including methods from EN 12599:2012) and clarifies uncertainty evaluation and maximum permissible measurement errors (MPME).
Key technical topics and requirements
- Scope and exclusions
- Applies to air flow rate measurements inside ducts and at terminal devices.
- Does not apply to ducts that are not circular or rectangular (e.g. oblong ducts) or to flexible ducts.
- Measurement methods covered
- Multi‑point cross‑section measurements (with and without specified measurement‑plane criteria).
- Fixed devices and in‑system sensors (ID3, ST1, ET1).
- Tight bag method at supply ATDs (ST2).
- Flow hood measurements for grilles and terminal devices (ST3, ET2).
- Tracer gas method (informative Annex A) and point measurements using anemometers or thermal anemometers (informative).
- Instrumentation and parameters
- Requirements for instruments: anemometers, Pitot‑static tubes, differential pressure manometers, thermometers, and barometers.
- Treatment of influencing parameters: hydraulic diameter, flow disturbances, air density, conversion from dynamic pressure to velocity, and corrections/conversions of measured flow.
- Measurement uncertainty
- Annex B provides guidance on uncertainty evaluation (type B, combined and expanded uncertainties) and examples.
- Measurement device requirements are expressed in terms of MPME (maximum permissible measurement error).
Practical applications and users
Who uses EN 16211:
- HVAC designers, commissioning engineers and balancing contractors
- Test laboratories and field measurement technicians
- Building inspectors, energy assessors and compliance officers
- Manufacturers of air terminal devices and ventilation components
Typical applications:
- Commissioning and performance verification of ventilation systems
- Routine inspection, testing and balancing (TAB) of ducted systems
- Troubleshooting airflow imbalances and system tuning
- Demonstrating compliance with building codes, indoor air quality and energy performance requirements
Related standards
- EN 12792 - Symbols, terminology and graphical symbols for ventilation systems (referenced normative).
- EN 14277 - Air terminal devices - measurement by calibrated sensors in or near ATD/plenum boxes (referenced).
- EN 12599:2012 methods were incorporated into this edition.
Keywords: ventilation for buildings, measurement of air flow rates on site, EN 16211, air flow measurement methods, flow hood, Pitot tube, anemometer, measurement uncertainty, HVAC commissioning.
Frequently Asked Questions
EN 16211:2024 is a standard published by the European Committee for Standardization (CEN). Its full title is "Ventilation for buildings - Measurement of air flow rates on site - Methods". This standard covers: This document specifies methods for the measurement of air flow rates on site. It provides a description of the air flow rate measurement methods and how measurements are performed within the margins of stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight duct, uniform velocity profile) to achieve the stipulated measurement uncertainties. The methods for measuring the air flow rate inside ducts do not apply to: - ducts that are not circular or rectangular (e.g. oblong ducts); - flexible ducts.
This document specifies methods for the measurement of air flow rates on site. It provides a description of the air flow rate measurement methods and how measurements are performed within the margins of stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight duct, uniform velocity profile) to achieve the stipulated measurement uncertainties. The methods for measuring the air flow rate inside ducts do not apply to: - ducts that are not circular or rectangular (e.g. oblong ducts); - flexible ducts.
EN 16211:2024 is classified under the following ICS (International Classification for Standards) categories: 17.120.10 - Flow in closed conduits; 91.140.30 - Ventilation and air-conditioning systems. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 16211:2024 has the following relationships with other standards: It is inter standard links to EN 16211:2015. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase EN 16211:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.
Standards Content (Sample)
SLOVENSKI STANDARD
01-januar-2025
Nadomešča:
SIST EN 16211:2015
Prezračevanje stavb - Meritve pretoka zraka v sistemu prezračevanja - Metode
Ventilation for buildings - Measurement of air flow rates on site - Methods
Lüftung von Gebäuden - Luftvolumenstrommessung vor Ort - Verfahren
Ventilation des bâtiments - Mesurages des débits d'air sur site - Méthodes
Ta slovenski standard je istoveten z: EN 16211:2024
ICS:
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 16211
EUROPEAN STANDARD
NORME EUROPÉENNE
November 2024
EUROPÄISCHE NORM
ICS 17.120.10; 91.140.30 Supersedes EN 16211:2015
English Version
Ventilation for buildings - Measurement of air flow rates
on site - Methods
Ventilation des bâtiments - Mesurages des débits d'air Lüftung von Gebäuden - Luftvolumenstrommessung in
sur site - Méthodes Lüftungssystemen - Verfahren
This European Standard was approved by CEN on 30 September 2024.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 16211:2024 E
worldwide for CEN national Members.
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Symbols and abbreviated terms . 7
5 Expression of air flow rate and parameters of influence . 10
5.1 Hydraulic diameter . 10
5.2 Flow disturbances . 11
5.3 Stability of the air flow rate . 11
5.4 Air density . 11
5.5 Conversion of dynamic pressure into air velocity . 11
5.6 Correction and conversion of measured air flow rate . 12
5.6.1 General . 12
5.6.2 Correction of the air flow rate . 12
5.6.3 Conversion of the air flow rate . 13
6 Measuring instruments requirements . 14
6.1 General . 14
6.2 Air flow rate measuring instruments . 14
6.3 Differential pressure measuring instruments (manometers) . 14
6.4 Air velocity measuring instruments . 14
6.4.1 General . 14
6.4.2 Anemometers . 14
6.4.3 Pitot static tubes . 14
6.5 Temperature measuring instruments (thermometers) . 15
6.6 Atmospheric pressure measuring instruments (barometers) . 15
7 Methods for measurement of air flow rates . 16
7.1 Overview of described methods . 16
7.2 Multi‐point measurement in the duct cross‐section – with measurement plane
criteria (ID1) . 17
7.2.1 Principle . 17
7.2.2 Apparatus . 17
7.2.3 Measurement procedure . 18
7.2.4 Expression of results . 23
7.3 Multipoint measurement in the duct cross‐section – without measurement plane
criteria (ID2) . 25
7.3.1 Principle . 25
7.3.2 Apparatus . 25
7.3.3 Measurement procedure . 26
7.3.4 Expression of results . 32
7.4 Fixed devices for air flow rate measurement (ID3, ST1 and ET1) . 37
7.4.1 Principle . 37
7.4.2 Apparatus . 38
7.4.3 Measurement procedure . 38
7.4.4 Expression of results . 38
7.5 Air flow rate measurement with tight bag at supply ATDs (ST2) . 39
7.5.1 Principle . 39
7.5.2 Apparatus . 40
7.5.3 Measurement procedure . 40
7.5.4 Expression of results . 40
7.6 Air flow rate measurement with flow hood (ST3 and ET2) . 40
7.6.1 Principle . 40
7.6.2 Apparatus . 41
7.6.3 Measurement procedure . 43
7.6.4 Expression of results . 44
Annex A (informative) Additional methods . 45
A.1 Tracer gas measurement (ID4) . 45
A.1.1 Principle . 45
A.1.2 Apparatus . 45
A.1.3 Measurement procedure – Conditions for homogeneous mixing of tracer gas . 46
A.1.4 Expression of result – Calculation of air flow rate . 47
A.2 Measurement using anemometer at air intake (IN1) or air exhaust (EX1) . 48
A.2.1 Principle . 48
A.2.2 Apparatus . 48
A.2.3 Measurement procedure . 48
A.2.4 Expression of results . 49
A.3 Point measurements using thermal anemometers on rectangular intake (IN2) and
extract (ET3) grilles on walls . 49
A.3.1 Principle . 49
A.3.2 Measurement instruments/Apparatus . 50
A.3.3 Measurement procedure . 50
A.3.4 Standard measurement uncertainty . 52
Annex B (informative) Measurement uncertainty . 53
B.1 Uncertainty of the result of a measurement . 53
B.2 Type B evaluation of standard uncertainty . 53
B.3 Combined standard uncertainty . 55
B.4 Expanded uncertainty . 55
B.5 Examples . 56
Bibliography . 61
European foreword
This document (EN 16211:2024) has been prepared by Technical Committee CEN/TC 156 “Ventilation
for buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by May 2025, and conflicting national standards shall be
withdrawn at the latest by May 2025.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 16211:2015.
In addition to a number of editorial revisions, the main changes compared with EN 16211:2015 are as
follows:
— the whole document has been rearranged;
— the method described previously in EN 12599:2012 to measure air (volume) flow rate in ductwork
has been included;
— the tracer gas method has been moved in Annex A (informative);
— two new methods to measure air flow rate at exhaust and intake grille have been added in Annex A
(informative);
— parts dealing with uncertainty have been replaced by Annex B (informative);
— requirements on measuring devices are now expressed in MPME (maximum permissible
measurement error).
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
Measurement of the air (volume) flow rate in a ventilation system is of general interest that is not related
to a specific operation or stage (e.g. installation, inspection, commissioning or handover). It was therefore
agreed to take advantage of the simultaneous revision of EN 16211:2015 and EN 12599:2012 to address
this subject in a single document (EN 16211:2024) rather than scattering or repeating it in various
documents.
In this document, all types of measurements are air (volume) flow rate. For the sake of readability, the
term "air (volume) flow rate" is replaced in the text by the contracted term "air flow rate".
1 Scope
This document specifies methods for the measurement of air flow rates on site. It provides a description
of the air flow rate measurement methods and how measurements are performed within the margins of
stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight
duct, uniform velocity profile) to achieve the stipulated measurement uncertainties.
The methods for measuring the air flow rate inside ducts do not apply to:
— ducts that are not circular or rectangular (e.g. oblong ducts);
— flexible ducts.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12792, Ventilation for buildings — Symbols, terminology and graphical symbols
EN 14277, Ventilation for buildings — Air terminal devices — Method for airflow measurement by
calibrated sensors in or close to ATD/plenum boxes
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp/
3.1
measuring interval
set of values of quantities of the same kind that can be measured by a given measuring instrument or
measuring system with specified instrumental measurement uncertainty, under defined conditions
Note 1 to entry: In some fields, the term is “measuring range” or “measurement range”.
[SOURCE: JCGM 200:2012, 4.7, modified – Note 2 has not been reproduced.]
3.2
maximum permissible measurement error
extreme value of measurement error, with respect to a known reference quantity value, permitted by
specifications or regulations for a given measurement, measuring instrument or measuring system
Note 1 to entry: More information on the calculation of the measurement uncertainty based on the maximum
permissible measurement error is given in Annex B.
[SOURCE: JCGM 200:2012, 4.26, modified – The accepted terms “maximum permissible error” and “limit
of error” have been removed, NOTE 1 and NOTE 2 have been removed, a Note 1 to entry has been added.]
3.3
standard uncertainty
measurement uncertainty expressed as a standard deviation
Note 1 to entry: More information on the use of standard uncertainty in measurement uncertainty is given in
Annex B.
[SOURCE: JCGM 200:2012, 2.30, modified – The preferred term and the first accepted term have been
removed and a Note 1 to entry has been added.]
3.4
calibration
operation that, under specified conditions, in a first step, establishes a relation between the quantity
values with measurement uncertainties provided by measurement standards and corresponding
indications with associated measurement uncertainties and, in a second step, uses this information to
establish a relation for obtaining a measurement result from an indication
[SOURCE: JCGM 200:2012, 2.39, modified — NOTE 1 and NOTE 2 have been removed.]
3.5
correction
compensation for an estimated systematic effect
[SOURCE: JCGM 200:2012, 2.53, modified — NOTE 1 and NOTE 2 have been removed.]
3.6
hypothetical
obtained by making hypothesis on the existing conditions
3.7
dynamic pressure
velocity pressure
pressure equivalent of the kinetic energy of the fluid at a point
3.8
static pressure
pressure exerted, in a moving fluid, on an element moving at the same velocity as the fluid
3.9
total pressure
sum of static pressure (3.8) and dynamic pressure (3.7) at any point of a fluid
4 Symbols and abbreviated terms
For the purposes of this document, the symbols given in Table 1 and the abbreviated terms given in
Table 2 apply.
Table 1 — Symbols
Symbol Description Unit
a, b, c, d, e, f Dimensions of length mm
a/D Relative distance —
h
2 2
A Cross-section area m , mm
2 2
A Effective cross-section area of the probe m , mm
g
3 3
C Initial tracer gas concentration cm /m
i
3 3
C Tracer gas concentration in the sampling cross-section cm /m
s
D Diameter mm
D Hydraulic diameter mm
h
D Diameter of the centroidal ring of the annulus mm
i
D Probe diameter mm
so
e Device’s flow exponent given by the manufacturer (usually 0,5) —
H Height of the duct mm
i Ordinal number —
I Irregularity of the velocity profile %
k Characteristic of the fixed device depending on its setting —
(k-factor)
K Coverage factor —
K Correction factor (for method IN2 and EX2) —
k Correction factor for density —
k Correction factor for duct shape —
L Length of head of the pitot static tube mm
L Mixing length for the tracer gas mm
L Smaller dimension of a rectangular duct cross section mm
L Larger dimension of a rectangular duct cross section mm
n Number —
n Number of measuring points along the smaller dimension —
L1
n Number of measuring points along the larger dimension —
L2
p Atmospheric pressure Pa
atm
p Atmospheric pressure in actual conditions Pa
atm,act
p Atmospheric pressure in device hypothetical condition Pa
atm,hyp
p Atmospheric pressure in standardized conditions (101 325 Pa) Pa
atm,std
p Dynamic pressure Pa
d
p Static pressure Pa
s
Symbol Description Unit
p Total pressure Pa
t
P Perimeter of the cross-section m, mm
3 3
q Air flow rate m /s, m /h, l/s
3 3
q Tracer gas flow rate m /s, m /h, l/s
s
3 3
q Tracer gas flow rate at duct temperature m /s, m /h, l/s
sϑduct
3 3
q Tracer gas flow rate at rotameter temperature m /s, m /h, l/s
sϑtracer
3 3
qv,act Actual air flow rate (in actual conditions) m /s, m /h, l/s
3 3
q Hypothetical air flow rate assuming device default conditions m /s, m /h, l/s
v,hyp
3 3
q Measured air flow rate m /s, m /h, l/s
v,m
3 3
q Standardized air flow rate (in standard conditions) m /s, m /h, l/s
v,std
t Time s
T Air temperature in actual conditions K
act
T Air temperature in device default condition K
hyp
T Air temperature in standardized conditions (293,15 K) K
std
u Standard uncertainty —
u Combined standard uncertainty —
c
U Expanded uncertainty —
v Air velocity m/s
v Actual air velocity m/s
act
v Air velocity reading m/s
g
v Air velocity for measuring point k m/s
k
v Average air velocity m/s
m
v Maximum of the arithmetic mean of velocities in a quarter of the m/s
max
cross-section or at a radius
v Minimum of the arithmetic mean of velocities in a quarter of the m/s
min
cross-section or at a radius
v Air velocity for a given quarter m/s
q
v Air velocity for a given radius m/s
r
V Volume of the measuring bag m
W Width of the duct mm
x Distance from the duct wall mm
i
y Distance from the duct wall mm
i
Δl Tolerance for the probe location mm
Δp Measured pressure difference Pa
θ Air temperature in actual conditions (= T − 273,15) °C
act act
Symbol Description Unit
ρ Air density kg/m
ρ Air density in actual conditions kg/m
act
ρ Air density in device default condition kg/m
hyp
ρ Air density in standardized conditions kg/m
std
ρ Air density at the temperature inside the duct kg/m
ϑduct
ρ Air density at the temperature of tracer gas kg/m
ϑtracer
ϑ Temperature of air °C
ϑ Temperature inside the duct °C
duct
ϑ Temperature of tracer gas °C
tracer
Table 2 — Abbreviated terms
Abreviated terms Description
ATD Air terminal devices
MPME Maximum permissible measurement error
RH Relative humidity of the air
5 Expression of air flow rate and parameters of influence
5.1 Hydraulic diameter
The hydraulic diameter, D , is the diameter of a circular duct which causes the same pressure drop, at
h
equal air velocity and equal roughness factor, than the considered duct and is defined by Formula (1).
A
D 4⋅ (1)
h
P
where
A is the area of the cross-section, in mm ;
P is the perimeter of the cross-section, in mm.
For a rectangular duct, Formula (1) becomes Formula (2).
LL⋅
D 2⋅ (2)
h
LL+
( )
where
L is the smaller dimension of the rectangular duct, in mm;
L is the larger dimension of the rectangular duct, in mm.
=
=
For a circular duct, Formula (1) becomes Formula (3).
D = D (3)
h
5.2 Flow disturbances
Within an air flow, disturbances result in irregular velocity profiles. Irregular velocity profile can induce
additional measurement errors and complicate the measurement. Away from any disturbance the
velocity profile gets more and more regular. For some methods, requirements are set regarding the
position of the measurement device from flow disturbances.
NOTE Flow seldom has a symmetrical appearance except after long straight sections. The symmetry is often
disturbed by varying resistance, for example after a bend, an area decrease or an area increase. The velocity profile
also becomes disturbed by singularities such as damper and branch as well as before and after a fan.
5.3 Stability of the air flow rate
Measurement methods described in this document are based on the assumption that the air flow rate
does not change during the measurement time.
NOTE Variation of the air flow rate increases the measurement uncertainty.
5.4 Air density
The density of dry air, ρ, varies with atmospheric pressure and temperature in accordance with
Formula (4).
p
273,15
atm
ρ=1,293⋅⋅
(4)
101 325 273,15+ϑ
where
p is the atmospheric pressure, in Pa;
atm
ϑ is the temperature of the air, in °C.
The relative humidity of the air (RH) has very little influence on the density of air at room temperature.
The density of air at 20 °C and 101 325 Pa which is saturated with water vapour is only approximately
1 % less than equivalent dry air.
If the static pressure of the ventilation system is above about 2 000 Pa, the influence of the static pressure
on air density should be considered and the calculation is then performed using Formula (5).
pp+
273,15
atm s
ρ=1,293⋅⋅ (5)
101 325 273,15+ϑ
where
p is the static pressure in the ductwork, in Pa.
s
5.5 Conversion of dynamic pressure into air velocity
Dynamic pressure within an air flow can be measured with a Pitot static tube connected to a manometer
(see Figure 1 in 6.4.3).
Air velocity can be calculated from dynamic pressure using Formula (6).
2p
d
v = (6)
act
ρ
act
where
v is the actual air velocity (in prevailing conditions);
act
p is the dynamic pressure;
d
ρ is the air density (in prevailing conditions).
act
5.6 Correction and conversion of measured air flow rate
5.6.1 General
By nature, air flow rate measurements on site are done in actual conditions (i.e. conditions existing in a
particular place and at a particular time).
The actual conditions refer to the place where measurements are made. For measurements in ducts,
atmospheric pressure may be measured outside the duct for practical reasons. In this case, the static
pressure in the duct should be added to the atmospheric pressure for calculation purpose. When the static
pressure in the duct is below 2 000 Pa in absolute value it may be neglected.
However, depending on their settings, some measuring systems may:
— give uncorrected air flow rate, q , by making the hypothesis that the air is at the device default
v,hyp
condition (e.g. 1,204 kg/m corresponding to 293,15 K and 101 325 Pa). This hypothetical air flow
rate is neither the actual air flow rate nor the standardized air flow rate and corrections given in 5.6.2
shall be done;
— automatically calculate or convert quantity values into different than actual conditions (e.g. standard
conditions). In this case, conversion to actual conditions, as given in 5.6.3, shall be done.
In any case, the technical data sheet should be consulted to find out to which conditions (actual, standard,
etc.) the indicated quantity values correspond and how to correct or convert them into actual conditions.
5.6.2 Correction of the air flow rate
The formula to convert hypothetical air flow rate into actual air flow rate (air flow rate occurring in actual
conditions) depends on the measuring device used.
To obtain the actual air flow rate, the user shall refer to manufacturer specifications to determine
whether:
— the correction is done automatically, in this case no further corrections shall be done, the read value
is equal to the actual value; or
— the correction shall be done by the user.
If formulae to perform the correction are available in the manufacturer specifications they should be
used.
If the correction is not done automatically and no correction’s formula is available on manufacturer
specifications the following corrections should be used:
— When the air flow rate varies with the inverse of the square root of the air density (e.g. for Pitot static
tubes or fixed measuring device with exponent (reference of the measurement method ID3X)),
Formula (7) shall be used.
ρ pp
T θ + 273,15
hyp atm,hyp atm,hyp
act act
q =q ⋅=q =q (7)
v,act v,hyp v,hyp v,hyp
ρ p T p T
act atm,act hyp atm,act hyp
— When the air flow rate varies with the inverse of the air density (e.g. for hot-wire anemometers)
Formula (8) shall be used.
ρ pp
T θ + 273,15
hyp atm,hyp atm,hyp
act act
q = q ⋅= q = q (8)
v,act v,hyp v,hyp v,hyp
ρ p T p T
act atm,act hyp atm,act hyp
where
q is the hypothetical air flow rate assuming device default conditions;
v,hyp
q is the actual air flow rate (in actual conditions);
v,act
ρ is the air density in device default condition;
hyp
ρact is the air density in actual conditions;
p is the atmospheric pressure in device default condition;
atm,hyp
p is the atmospheric pressure in actual conditions;
atm,act
T is the air temperature in device default condition, in K;
hyp
T is the air temperature in actual conditions, in K;
act
θ is the air temperature in actual conditions, in °C.
act
NOTE The multiplier of qv,hyp is sometimes termed “k1”.
— For vane anemometers no corrections are needed for temperature and atmospheric pressure (air
density). In this case, the hypothetical air flow rate is equal to the actual air flow rate.
5.6.3 Conversion of the air flow rate
Standardized air flow rate (air flow rate converted to standardized conditions) can be converted into
actual air flow rate (air flow rate occurring in actual conditions) using Formula (9).
pp
ρθT + 273,15
atm,std atm,std
std act act
q = q ⋅ = q = q (9)
v,act v,std v,std v,std
ρ p T p T
act atm,act std atm,act std
Conversely, actual air flow rate can be converted into standardized air flow rate using Formula (10).
pp
ρ T T
atm,act atm,act
act std std
qq= ⋅ = q = q (10)
v,std v,act v,act v,act
ρθpT p + 273,15
std atm,std act atm,std act
where
q is the standardized air flow rate (in standard conditions);
v,std
q is the actual air flow rate (in actual conditions);
v,act
ρ is the air density in standardized conditions;
std
ρ is the air density in actual conditions;
act
p is the atmospheric pressure in standardized conditions (101 325 Pa), in Pa;
atm,std
p is the atmospheric pressure in actual conditions, in Pa;
atm,act
T is the air temperature in standardized conditions (293,15 K), in K;
std
T is the air temperature in actual conditions, in K;
act
θ is the air temperature in actual conditions, in °C.
act
6 Measuring instruments requirements
6.1 General
The present clause provides good practices values for maximum permissible measurement error (MPME)
of measuring instruments. For estimating the overall uncertainty of the measurement see Annex B and
be consistent with the purpose of the test.
In order to reduce measuring uncertainty, instruments with a mean value calculation function (e.g.
according to EN 13182) should be used.
EXAMPLE Instruments can calculate the mean value from 15 readings with 0,1 s apart.
6.2 Air flow rate measuring instruments
The MPME of an air flow rate measuring instrument, that provides air flow rate directly (such as flow
hood), should be lower or equal to 3,6 m /h + 5 % of the measured value for the measuring interval that
includes the measured quantity value.
6.3 Differential pressure measuring instruments (manometers)
The MPME of manometers should be lower or equal to 0,4 Pa + 3 % of the measured value, for the
measuring interval that includes the measured quantity value.
Manometers should be zeroed before each sequence of measurement according to manufacturer
instructions.
6.4 Air velocity measuring instruments
6.4.1 General
Air velocity is usually measured by anemometers or by Pitot static tubes.
The MPME of air velocity measuring instrument shall be lower or equal to 0,1 m/s + 5 % of the measured
value, for the measuring interval that includes the measured quantity value.
For in duct measurements, the projected area of the device obstructing the duct passage area should not
exceed 1/10th of the duct cross-section area.
Directional probes shall be oriented into the direction of the flow.
6.4.2 Anemometers
Anemometers, e.g. hot-wire anemometers or vane anemometers, provide a direct measurement of air
velocity values.
The MPME of the instrument shall be consistent with the MPME given in 6.4.1.
Hot wire anemometers usually show a better accuracy at low velocities, vane anemometers are less
temperature dependent and show a better accuracy at higher velocities. The velocity where there is a
transition between the two types of instruments is usually within range 1 m/s to 3 m/s, this information
is given in the manufacturer instructions.
6.4.3 Pitot static tubes
Pitot static tubes are described in EN ISO 16911-1 and ISO 3966. The principle of measurement with a
Pitot static tube is given in Figure 1.
Pitot static tubes are used with a manometer complying with 6.3 to measure the dynamic or the static
pressure within the duct. From the dynamic pressure measurement, air velocity can be calculated as
described in 5.5.
The derived MPME of the air velocity shall be consistent with the MPME of the air velocity measurement
devices given in 6.4.1 and this shall be checked using Formula (11).
MPME p ≤ 0,,1⋅⋅ρρv+ 0 05⋅⋅ v (11)
( )
d
where
MPME(p ) is the maximum permissible measurement error at the measured dynamic pressure.
d
In general, Pitot static tubes are best to measure velocity from 2 m/s and above if the MPME of the
manometer is consistent with 6.3.
Key
1 connection for static pressure p total pressure
t
2 connection for total pressure p dynamic pressure
d
l length of head ps static pressure
D diameter of tube
Figure 1 — Measurement principle of Pitot static tube
Some measuring instruments display directly velocity or air flow rate while they are measuring dynamic
pressure.
6.5 Temperature measuring instruments (thermometers)
Thermometers shall have a MPME of ±1 °C for the measuring interval that includes the measured quantity
value.
The duration of measurement should be consistent with the response time of the thermometer.
6.6 Atmospheric pressure measuring instruments (barometers)
Barometers shall have a MPME of ±500 Pa for the measuring interval that includes the measured quantity
value.
7 Methods for measurement of air flow rates
7.1 Overview of described methods
The methods described in this document are summarized in Table 3.
The following abbreviations are used in Table 3 and also in the document:
— ID: In duct;
— ST: Supply terminal;
— ET: Extract terminal;
— EX: Exhaust;
— IN: Intake.
Table 3 — Summary of the methods described in this document
Measurement location designation Clause(s)/
Measurement In duct At At At fan At At intake subclause(s)
method supply extract exhaust vent of this
vent document
Multi-point ID1XX 7.2
measurement in the
duct cross-section –
with measurement
plane criteria
Multipoint ID2XX 7.3
measurement in the
duct cross-section –
without measurement
plane criteria
Fixed devices for air ID3X ST1X ET1X ID31 7.4
flow rate
measurement
Measurement with ST2 7.5
tight bag
Measurement with ST3X ET2X 7.6
flow hood
Measurement with ID4 Annex A
tracer gas (informative)
Measurement at EX1 IN1 Annex A
intake vents or (informative)
exhaust vents
Point measurements ET3 IN2 Annex A
using hot wire (informative)
anemometer at
rectangular grilles
To determine the measurement conditions of the ventilation system the air temperature and atmospheric
pressure should be measured. For in duct measurement, the static pressure in the duct (at measurement
plane) should be measured.
Additional information, such as wind speed and outdoor temperature, might also be of interest for
uncertainty evaluation.
7.2 Multi‐point measurement in the duct cross‐section – with measurement plane
criteria (ID1)
7.2.1 Principle
Method ID1 involves the air flow rate being calculated from a series of air velocities determined by
measurements in the duct cross-section. The determination of velocity is carried out using a Pitot static
tube or an anemometer.
The air flow rate is then calculated by multiplying the average air velocity with the duct area and
correction factors (given in 5.6).
Table 4 gives method numbers according to the kind of ductwork and the kind of measurement device,
together with the standard method uncertainty.
Table 4 — Methods ID1 for measurement of air flow rates
Method/measurement device/kind of Method Standard method
a
ductwork number uncertainty
Multi-point measurement in the duct cross- ID1
section – with measurement plane criteria
Pressure measurements using a Pitot static tube ID11
a) Circular cross-section ID111 4 % (case A)
6 % (case B)
b) Rectangular cross-section ID112 4 %
Velocity measurement using a hot-wire ID12
anemometer or a mechanical anemometer
a) Circular cross-section ID121 4 % (case A)
6 % (case B)
b) Rectangular cross-section ID122 4 %
a
See Annex B for more information on standard uncertainty.
Random method uncertainties can arise, e.g. as a result of oblique velocity profile in the measurement
cross-section and oblique setting of the probe. The standard method uncertainty with a coverage
probability of approximately 68 % is given in Table 4.
7.2.2 Apparatus
For all methods, the equipment that shall be used is:
— a thermometer;
— a barometer;
and for:
— ID11 a manometer with Pitot static tube;
— ID12 an anemometer.
In both cases, the Pitot static tube or the anemometer shall include an indication of:
— insertion length;
— the orientation of the probe (to be aligned with the flow direction).
7.2.3 Measurement procedure
7.2.3.1 Preparations to be made at the site of measurement
7.2.3.1.1 Selection of the plane of measurement
The flow profile has a distorted appearance after certain disturbances to the flow, e.g. section change,
bends or dampers. If measurement takes place directly after a flow disturbance, there is a risk of low
accuracy.
The plane of measurement is accepted if it meets the following criteria:
— duct sections are free from disturbances for a distance, both before and after the plane of
measurement: see Table 5 for values;
— the highest dynamic pressure (ID11) in the measurement plane:
— is located more than 0,1 D from all duct walls;
h
— is less than twice the dynamic pressure in the centre;
— the highest velocity (ID12) in the measurement plane:
— is located more than 0,1 D from all duct walls;
h
— is less than 1,4 times the velocity in the centre;
— the likeliness of backflow in the cross-section is small.
If these three criteria are not met, a new plane of measurement shall be selected and tested.
To determine if there is a risk of backflow in the cross-section, insert the anemometer in the duct in the
measuring plane and sweep slowly to determine maximum value location. If negative or close to zero
values are noticed, there is a high possibility of backflow.
For rectangular ductwork, the “centre” is the intersection of diagonals.
NOTE A Pitot static tube can normally not detect velocities below approximatively 0,5 m/s and a hot-wire
anemometer is not able to detect the direction of the flow.
Table 5 — Necessary length of straight sections before and after the plane of measurement
Location of the straight section Length of the duct straight section
Circular Rectangular
Before plane of measurement a ≥ 5 ⋅ D a ≥ 6 ⋅ D
h
After plane of measurement a ≥ 2 ⋅ D a ≥ 2 ⋅ D
h
150 mm minimum from duct 50 mm minimum from duct
connections connections
7.2.3.1.2 Preparation
a) Select the location of the plane of measurement according to 7.2.3.1.1, taking into consideration the
required straight sections.
b) Remove the external insulation at the point of measurement.
c) Drill holes in the duct so that measurements can be made along lines in a cross-section:
1) the cross-section shall be perpendicular to the axis of the duct;
2) for circular ducts, the two lines shall be perpendicular to each other:
i) case A (preferred one, lower uncertainty): one of the lines of points is placed in the same
plane as the axis of the duct and the centre of the bent upstream the duct;
ii) case B (higher uncertainty): two perpendicular lines in the cross-section other than those of
case A are used (e.g. in case of access restriction).
The uncertainty is higher in case B. The reasons for the increase of uncertainty in case B are that the flow
profil
...
Die Norm EN 16211:2024 bietet einen umfassenden Rahmen für die Messung von Luftstromraten vor Ort in Gebäuden. Ihr Hauptziel ist es, präzise Methoden zu definieren, die innerhalb festgelegter Unsicherheitsgrenzen für die Luftstrommessung angewendet werden können. Dies stärkt die Qualität und Zuverlässigkeit von Messungen, die für die Bewertung der Belüftungseffizienz von Gebäuden entscheidend sind. Eine der Stärken dieser Norm ist die detaillierte Beschreibung der erforderlichen Bedingungen für die Messung, einschließlich der Länge des geraden Kanals und der Notwendigkeit eines einheitlichen Geschwindigkeitsprofils, um die geforderte Messgenauigkeit zu gewährleisten. Diese Klarheit hilft Fachleuten im Bereich Gebäude- und Raumlufttechnikin, konsistente und nachvollziehbare Ergebnisse zu erzielen. Die Norm konzentriert sich auch auf die spezifischen Anforderungen an die Messmethoden und schließt ausdrücklich Ducts aus, die nicht kreisförmig oder rechteckig sind, sowie flexible Kanäle. Dies ist ein wesentlicher Punkt, der sicherstellt, dass die Messmethoden effektiv und anwendbar sind, und vermeidet Verwirrung in der praktischen Anwendung. Insgesamt ist die EN 16211:2024 von großer Relevanz für Ingenieure und Fachleute im Bereich der Gebäudetechnik. Sie fördert nicht nur die Genauigkeit von Luftstrommessungen, sondern verbessert auch das Verständnis für die Belüftungseffizienz in verschiedenen Gebäudetypen. Die präzisen Vorgaben helfen, die Leistung von Heizungs-, Lüftungs- und Klimaanlagen zu optimieren und tragen somit zur Schaffung gesünderer und energieeffizienterer Innenräume bei.
SIST EN 16211:2025 표준은 건물의 환기를 위한 현장 공기 흐름 속도 측정 방법을 규정하는 문서로, 이 표준의 범위와 강점, 그리고 관련성을 살펴보면 다음과 같습니다. 이 표준은 공기 흐름 속도 측정에 대한 명확한 방법론을 제공하며, 현장에서의 측정을 수행할 때 지켜야 할 조건을 정의합니다. 특히, 공기 흐름 속도 측정 방법의 불확실성 기준을 명시하여 정확한 측정 결과를 얻기 위한 필수 조건을 제시하고 있습니다. 이러한 조건에는 직선 덕트의 길이 및 균일한 속도 프로파일과 같은 요소가 포함되어 있습니다. 본 표준은 공기 흐름 속도를 측정하기 위한 방법이 중요하게 다루어지는 실무적인 응용 분야에서 강력한 지침을 제공합니다. 특히, 동관이나 직사각형 이외의 형상(예: 장방형 덕트)이나 유연 덕트에 대해서는 해당 방법이 적용되지 않음을 분명히 하여, 사용자들이 올바른 도구와 방법을 선택하도록 돕고 있습니다. SIST EN 16211:2025 표준은 환기 시스템의 효율성을 높이기 위해 필수적인 정보와 절차를 포함하고 있으며, 이는 건축물의 공기질 개선과 에너지 효율성 향상에 기여하는 데 중요한 역할을 합니다. 따라서 이 표준은 건축 공학 및 환경공학 분야에서 공기 흐름 측정의 신뢰성을 유지하기 위한 필수적인 기준으로 자리잡고 있습니다. 결론적으로, SIST EN 16211:2025는 효과적인 공기 흐름 속도 측정 방법을 통해 건물 환기의 중요성을 강조하며, 이를 통해 건강하고 쾌적한 실내 환경을 조성하는 데 기여하는 매우 중요한 표준으로 평가됩니다.
La norme EN 16211:2024 spécifie les méthodes de mesure des débits d'air sur site, un aspect essentiel pour garantir la qualité de l'air dans les bâtiments. Son champ d'application est clairement défini, ce qui permet aux professionnels de comprendre les conditions de mesure nécessaires et les incertitudes pouvant affecter les résultats. L'un des points forts de cette norme est qu'elle offre une description détaillée des méthodes de mesure, ainsi que des conditions requises, comme la longueur des conduits droits et le profil de vitesse uniforme, afin d'obtenir des incertitudes de mesure acceptables. L'inclusion d'exigences spécifiques sur les types de conduits, comme l'exclusion des conduits oblongs et flexibles, renforce la clarté et la pertinence de la norme EN 16211:2024. Cela permet d'éviter des erreurs potentielles lors de l'application de ces méthodes dans des situations non conformes. La norme est donc particulièrement pertinente pour les techniciens et les ingénieurs qui doivent réaliser des mesures précises des débits d'air, garantissant ainsi que les systèmes de ventilation répondent aux exigences de performance et de sécurité. En résumé, la norme EN 16211:2024 est un outil indispensable pour ceux qui interviennent dans le domaine de la ventilation des bâtiments, en leur fournissant des méthodes claires et fiables pour la mesure des débits d'air sur site, tout en établissant des paramètres importants pour la précision de ces mesures.
EN 16211:2024は、建物の換気に関する重要な標準であり、現場での空気流量の測定方法を明確に定義しています。この文書は、空気流量測定の手法及び測定を行う際の不確実性の範囲内での実施方法について詳細に説明しています。特に、測定を円滑に行うための必要な測定条件(例えば、直管の長さや均一な速度プロファイル)についても明記されており、信頼性の高い測定結果を得るための基準が示されています。 この基準の強みは、その具体性と適用可能性にあります。特に、測定方法が明確に定義されているため、実務者は一貫した手法を用いて、正確な空気流量の測定を行うことができます。また、適用外とされるダクトのタイプ(円形や矩形でないダクトや柔軟なダクト)を明示することで、適切な測定条件下での使用を促進し、誤った測定を防ぐ役割も果たしています。 また、EN 16211:2024は、換気システムの設計や管理に携わる専門家にとって、業務の質を向上させるための重要なリソースとなります。現場での空気流量の測定は、エネルギー効率や室内空気質の向上に直結するため、その正確性と信頼性が求められるのです。この標準に基づく測定は、建物の換気性能を適切に評価し、持続可能な建物設計の実現に寄与することが期待されます。 総じて、EN 16211:2024の重要性は、標準化された空気流量測定方法を提供することで、現場での測定精度を向上させ、建物の換気システムの最適化を実現する点にあります。
The EN 16211:2024 standard serves a vital role in the field of building ventilation by outlining comprehensive methods for the measurement of air flow rates on site. Its defined scope emphasizes the importance of precise measurement techniques critical for ensuring the efficiency and effectiveness of ventilation systems in buildings. One of the strengths of this standard is its systematic approach to specifying the necessary conditions for accurate air flow rate measurements. By detailing required parameters such as the length of straight duct and the need for a uniform velocity profile, the standard empowers practitioners to achieve stipulated measurement uncertainties. This focus on rigor in measurement conditions enhances the reliability of data gathered, leading to better-informed decisions regarding building ventilation systems. Furthermore, the standard clearly delineates the applicability of its methods, explicitly noting that techniques for measuring air flow rates are not intended for ducts that do not conform to standard configurations, such as oblong or flexible ducts. This specification streamlines the measurement process for professionals, ensuring that the focus remains on standard duct shapes that can be effectively measured. The relevance of EN 16211:2024 cannot be overstated, as effective ventilation is paramount in maintaining indoor air quality and comfort within buildings. By providing a standardized framework for measurement practices, it supports professionals in achieving compliance with health and safety regulations while optimizing ventilation performance. This document ensures that the methods employed are not only aligned with best practices but also contribute to energy efficiency and sustainability goals inherent to modern building designs. In summary, the EN 16211:2024 standard is an invaluable resource for professionals engaged in building ventilation, delivering clarity, precision, and robust methodology for on-site air flow rate measurement.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...